060816/6
LEM www.lem.com
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice. Page 1/2
AC Current transducer AKR-C420L
Transducer for the electronic measurement AC waveforms current,
with galvanic isolation between the primary (High power) and the
secondary circuits (Electronic circuit). Jumper selectable ranges and
True RMS 4-20mA current output.
Electrical data
Primary Nominal CurrentAnalogue Output Signal1) Type RoHS
IPN (A.t.RMS) IOUT (mA) Date Code
2,5 4-20 AKR 5 C420L JULY 2006
10,20,50 4-20 AKR 50 C420L planned
100,150,200 4-20 AKR 200 C420L JULY 2006
Vc Supply voltage (Loop powered) 24 V DC
RLLoad resistance see power supply diagram
VbRated voltage (CAT III, PD2) 150 VAC
VdRMS Isolation voltage test, 50 Hz, 1mn 3 kV AC
fFrequency bandwith 20-100 Hz
Accuracy - Dynamic performance data
XAccuracy @ IPN, TA=25°C ± 1 %
trResponse time @ 90% of IPN < 600 mS
General data
TAAmbient operating temperature (0-95% RH) -20 ..+ 50 °C
TSAmbient storage temperature -20 ..+ 85 °C
mMass 90 g
Safety IEC 61010-1
EMC EN 61326
Note:1) For 4-20mA output model, no saturation output up to 23 mA.
Selecting the transducer
VFD (Variable Frequency Drive) and SCR (Semi Conductor Rectifier) output
waveforms are rough approximations of a sine wave. There are numerous spikes
and dips in each cycle. AKR transducers use a mathematical algorithm called
“True RMS,” which integrates the actual waveform over time. True RMS is the only
way to accurately measure distorted AC waveforms. Select AKR transducers for
nonlinear loads or in “noisy” power environments.
IPN = 2..200A
Features
• VFD and SCR waveforms current
measurement
• True RMS responding
• 4-20 mA Current output
• Loop powered transducers
• Panel mounting
• Accurate
• Jumper selectable ranges
Advantages
• Large aperture
• High isolation between primary and
secondary circuits
• Easy to mount
Applications
• VFD Controlled Loads:
VFD output indicates how the motor
and attached load are operating.
• SCR Controlled Loads:
Acurate measurement of phase
angle fired or burst fired (time
proportioned) SCRs.
• Switching Power Supplies and
Electronic Ballasts:
True RMS sensing is the most
accurate way to measure power
supply or ballast input power.
Options on request
• DIN mounting