SENSATATECHNOLOGIES
529PleasantStreet
Attleboro,MA02703-0964USA
1-508-236-3287(Main)
1-508-236-1598(Fax)
http://airpax.sensata.com
http://www.sensata.com
ImportantNotice:SensataTechnologies(Sensata)reserves
therighttomakechangestoordiscontinueanyproductor
serviceidentiedinthispublicationwithoutnotice.Sensata
advises its customers to obtain the latest version of the
relevant information to verify, before placing any orders,
that the information being relied upon is current. Sensata
assumes no responsibility for infringement of patents or
rights of others based on Sensata applications assistance
or product specications since Sensata does not possess
fullaccessconcerningtheuseorapplicationofcustomers’
products. Sensata also assumes no responsibility for
customers’productdesigns.
245–500–6010 Printed In U.S.A., August, 2009
5. TOP TEMPERATURE IN °F
°F °C °F °C °F °C
Temperature Setting 35°Fto200°F 1.6°Cto93°C 201°Fto300°F 94°Cto149°C 301°Fto325°F 150°Cto163°C
Standard Tolerance ±5°F ±2.8°C ±8°F ±4.4°C ±10°F ±5.6°C
Nominal Differential 15°F 8.3°C 25°F 13.8°C 30°F 16.7°C
NOTES:
· Select any temperature in the range of 35°F to 325°F. Standard choices fall on the 5°F increments, for example 35°F, 40°F, 45°F, 50°F... up to 320°F or 325°F
· Specify the °F temperature in the part numbering scheme as a three digit code without the ‘°F’ in the part number. For example, for 90°F, put in code ‘090’
6. TOP TEMPERATURE TOLERANCE
CODE A B C X Z
± °F ±5°F ±8°F ±10°F Maximum CustomertoSpecify
± °C ±2.8°C ±4.4°C ±5.6°C Maximum CustomertoSpecify
NOTES:
· The standard tolerance for the top temperature is based on the temperature range the top temperature falls in, please refer to “5. Top Temperature in °F” chart,
and select the appropriate code for a standard top temperature tolerance.
7. BOTTOM TEMPERATURE IN °F
“BottomTemperaturein°F”equalsthe“TopTemperaturein°F”minusthe“NominalDifferentialin°Fforthattemperature”.
Example1:50°F–15°F=35°FExample2:250°F–25°F=225°FExample3:310°F–30°F=280°F
NOTES:
· Specify the °F temperature in the part numbering scheme as a three digit code without the ‘°F’ in the part number (example 90°F, put in the code as ‘090’)
8. BOTTOM TEMPERATURE TOLERANCE
CODE A B C Y Z
± °F ±5°F ±8°F ±10°F Minimum CustomertoSpecify
± °C ±2.8°C ±4.4°C ±5.6°C Minimum CustomertoSpecify
NOTES:
· The typical standard bottom temperature tolerance is a ‘Y’ = minimum trip, which indicates the “reset” trip occurs at or above the lower temperature set point.
· The other standard tolerances are based on the temperature range the bottom temperature is in. The most convenient solution is to use either the ‘Y’ minimum
reset code or choose the same tolerance code selection used in “6. Top Temperature Tolerance Code”.