Connecting Capacity Main Circuit: Screw Clamp / Flexible 1x 0.2 ... 6 mm²
Screw Clamp / Flexible 2x 0.2 ... 2.5 mm²
Screw Clamp / Rigid 1x 0.2 ... 6 mm²
Screw Clamp / Rigid 2x 0.2 ... 2.5 mm²
Screw Clamp / With Insulated Ferrrule 1x 0.22 ... 4 mm²
Screw Clamp / Without Insulated Ferrule 1x 0.22 ... 4 mm²
Screw Clamp / With Twin Ferrule 2x 0.22 ... 2.5 mm²
Gauge Type: A4-B3
Rated Current (I ): Main Circuit 40 A
Rated Short-time Withstand
Current (I ):
for 1 s 720 A
Rated Voltage (U ): 800 V
Rated Impulse Withstand Voltage
(U ):
8000 V
Dielectric Test Voltage: 2000 V
Pollution Degree: 3
Power Loss: 2.6 W
Degree of Protection: acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP20
Insulation Material: Polyamide
Mounting on DIN Rail: TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
Wire Stripping Length: 10.0 mm
Recommended Screw Driver: 4 mm
Technical UL/CSA
Maximum Operating Voltage
UL/CSA:
Main Circuit 300 V
Connecting Capacity Main Circuit
UL/CSA:
Screw Clamp / Flexible 1x 24 ... 10 AWG
Screw Clamp / Flexible 2x 24 ... 14 AWG
Screw Clamp / Rigid 1x 24 ... 10 AWG
Screw Clamp / Rigid 2x 24 ... 14 AWG
Screw Clamp / With Insulated Ferrrule 1x 24 ... 12 AWG
Screw Clamp / Without Insulated Ferrule 1x 24 ... 12 AWG
Screw Clamp / With Twin Ferrule 2x 24 ... 14 AWG
Connecting Capacity UL/CSA: Stranded 10 AWG
Flammability According to UL94: V0
Short-Circuit Current Rating
(SCCR):
100 kA
Environmental
Ambient Air Temperature: Operation -55 ... +110 °C
Storage -55 ... +110 °C