©June 2011 Littelfusewww.littelfuse.com
POWR-GARD® Fuse Datasheet
UL Class RK5
2
CLASS RK5 CURRENT-LIMITING EFFECTS
SHORT CIRCUIT CURRENT*
APPARENT RMS SYMMETRICAL CURRENT FOR VARIOUS FUSE RATINGS
15 A 30 A 60 A 100 A 200 A 400 A 600 A
5,000 800 1,100 2,100 3,200 5,000 5,000 5,000
10,000 1,100 1,600 2,900 4,300 7,3 00 10,000 10,000
15,000 1,300 1,900 3,400 5,000 8,600 13,700 15,000
20,000 1,400 2,200 3,800 5,600 9,500 15,500 19,000
25,000 1,500 2,500 4,100 6,100 10,300 16,700 21,500
30,000 1,600 2,700 4,500 6,500 11,000 17,700 23,500
35,000 1,700 2,900 4,700 6,800 11,600 18,600 25,200
40,000 1,800 3,100 5,000 7,2 00 12,100 19,400 26,600
50,000 1,900 3,400 5,400 7,80 0 13,100 20,800 29,500
60,000 2,000 3,600 5,800 8,300 13,900 22,000 30,600
80,000 2,200 4,000 6,300 9,100 15,400 24,000 33,200
100,000 2,300 4,200 6,800 9,800 16,700 25,500 35,100
150,000 2,600 4,500 7,700 11,200 19,300 28,100 38,000
200,000 2,800 4,600 8,400 12,400 21,400 30,000 39,600
Current-Limiting Effects of IDSR (600 V) Fuses