Surge Protection Module
LED Lighting Surge Protection Module > LSP05G Europe Version
© 2016 Littelfuse, Inc.
Specifications are subject to change without notice.
Revised: 05/24/16
LSP05G European Version Series Device Ratings & Specifications
Part Number Parallel/
Series
Operating
Voltage
(VAC)
MCOV/UC1
(VAC)
Maximum
Discharge
Current2
Imax (A)
Nominal
Discharge
Current3
In (A)
M LV 4
(V)
UP5
(V)
Safety Compliance
IEC/
EN61643-116
Luminaire
Class UL1449
LSP05G240PX3333 P240 275 10,000 5,000
L-N:970
L-G:1410
N-G:1410
L-N:1100
L-G:1600
N-G:1600
IX
LSP05G240PX3316 P240 275 10,000 5,000
L-N:970
L-G:1410
N-G:1410
L-N:1100
L-G:1600
N-G:1600
II X
LSP05G240SX3333 S240 275 10,000 5,000
L-N:970
L-G:1410
N-G:1410
L-N:1100
L-G:1600
N-G:1600
X I X
LSP05G240SX3316 S240 275 10,000 5,000
L-N:970
L-G:1410
N-G:1410
L-N:1100
L-G:1600
N-G:1600
X II X
LSP05G277PX3333 P277 320 10,000 5,000
L-N:1130
L-G:1410
N-G:1410
L-N:1200
L-G:1600
N-G:1600
IX
LSP05G277PX3316 P277 320 10,000 5,000
L-N:1130
L-G:1410
N-G:1410
L-N:1200
L-G:1600
N-G:1600
II X
LSP05G277SX3333 S 277 320 10,000 5,000
L-N:1130
L-G:1410
N-G:1410
L-N:1200
L-G:1600
N-G:1600
X I X
LSP05G277SX3316 S 277 320 10,000 5,000
L-N:1130
L-G:1410
N-G:1410
L-N:1200
L-G:1600
N-G:1600
X II X
Glossary:
1. MCOV/UC: Maximum Continuous Operating Voltage - maximum r.m.s. voltage that could be continuously applied to the SPD.
2. Maximum Discharge Current Imax (A): The maximum discharge current is a measure of the SPDs maximum capability; single impulse of discharge current uses the 8/20µs
current waveform.
3. Nominal Discharge Current In (A): The nominal discharge current is a measure of the SPDs endurance capability; 15 impulses of discharge current uses the 8/20µs current waveform.
4. MLV: UL1449 Measured limiting voltage; the highest value of residual voltage measurements during the application of impulses of 8/20µs nominal discharge current (In);
an average voltage value of 15 impulses
5. Up: IEC 61643-11 Voltage protection level; the highest value of residual voltage measurements during the application of impulses of 8/20µs nominal discharge current (In);
a rounding voltage value of maximum measurement.
6. Series module used in parallel connection for indication circuit connection.
7. LSP05G240S & LSP05G277S are certified by DEKRA with below IEC 61643-11 specifications.
LSP05G240S Specification Parameter Value Unit Condition
Temporary overvoltage TOV UT337 V LV system fault 255 V x 1.32 at tT = 5 s, TN power grid
Temporary overvoltage TOV UT442 V LV system fault 255 V x 1.732 at tT = 120 min, TN power grid
Power grids TN
Backup fuse 16 A max., gG fuse
End of life indication yes Optical, light ON: SPD is functional
Light OFF: SPD has reached end-of-life
Max earth leakage current at Uc 50 µA Max. rms, to GND
Notes:
• It is normal practice to disconnect components that intentionally breakdown between Line and Protective Earth, otherwise the apparent leakage current measured by the Hi-Pot tester
may incorrectly be judged a “failure.”
• Maximum Discharge Current Imax (A): The maximum discharge current is a measure of the SPDs maximum capability; single impulse of discharge current uses the 8/20µs current
waveform. All Devices pass maximum discharge current with possible, safe opening of thermal disconnect.
LSP05G277S Specification Parameter Value Unit Condition
Temporary overvoltage TOV UT403 V LV system fault 305 V x 1.32 at tT = 5 s, TN power grid
Temporary overvoltage TOV UT529 V LV system fault 305 V x 1.732 at tT = 120 min, TN power grid
Power grids TN
Backup fuse 20 A max., gG fuse
End of life indication yes Optical, light ON: SPD is functional
Light OFF: SPD has reached end-of-life
LSP05G240S LSP05G277S
Ic 8/20 µS Differential mode U2 Common mode U1/U2 Ic 8/20 µS Differential mode U2 Common mode U1/U2
5kA 970V 1600V/1410V 5kA 1130V 1600V/1410V
LSP05G Protection Levels Up