2
7.5 hp at 230/240 V AC 60 Hz 1P motors conforming to UL
[Uc] control circuit voltage 110 V AC 50/60 Hz
Connections - terminals Control circuit: screw clamp terminal 1 cable 0...0.01 in² (1...4 mm²) - cable stiffness: solid - without
cable end
Control circuit: screw clamp terminal 2 cable 0...0.01 in² (1...4 mm²) - cable stiffness: solid - without
cable end
Power circuit: screw clamp terminal 1 cable 0...0.05 in² (1...35 mm²) - cable stiffness: solid - without
cable end
Power circuit: screw clamp terminal 2 cable 0...0.04 in² (1...25 mm²) - cable stiffness: solid - without
cable end
Power circuit: screw clamp terminal 1 cable 0...0.05 in² (1...35 mm²) - cable stiffness: flexible - without
cable end
Control circuit: screw clamp terminal 1 cable 0...0.01 in² (1...4 mm²) - cable stiffness: flexible - with
cable end
Control circuit: screw clamp terminal 2 cable 0...0 in² (1...2.5 mm²) - cable stiffness: flexible - without
cable end
Control circuit: screw clamp terminal 2 cable 0...0.01 in² (1...4 mm²) - cable stiffness: flexible - with
cable end
Power circuit: screw clamp terminal 2 cable 0...0.04 in² (1...25 mm²) - cable stiffness: flexible - with
cable end
Power circuit: screw clamp terminal 2 cable 0...0.05 in² (1...35 mm²) - cable stiffness: flexible - without
cable end
Power circuit : screw terminals
Complementary
Coil technology Without built-in bidirectional peak limiting diode suppressor
Protective cover With
Auxiliary contacts type Type mechanically linked (1 NO + 1 NC) conforming to IEC 60947-5-1
Type mirror contact (1 NC) conforming to IEC 60947-4-1
Auxiliary contact composition 1 NO + 1 NC
Control circuit voltage limits 0.3...0.6 Uc at 140 °F (60 °C) drop-out 50/60 Hz
0.8...1.1 Uc at 140 °F (60 °C) operational 50 Hz
0.85...1.1 Uc at 140 °F (60 °C) operational 60 Hz
[Ui] rated insulation voltage 600 V control circuit certifications CSA
600 V control circuit certifications UL
600 V power circuit certifications CSA
600 V power circuit certifications UL
690 V control circuit conforming to IEC 60947-1
690 V power circuit conforming to IEC 60947-1
[Uimp] rated impulse withstand voltage 8 kV IEC 60947
Overvoltage category III
Mounting support Plate
Rail
Flame retardance V1 conforming to UL 94
Tightening torque Power circuit: 44.25 lbf.in (5 N.m) - on screw clamp terminal - with screwdriver flat Ø 6 mm
Control circuit: 10.62 lbf.in (1.2 N.m) - on screw clamp terminal - with screwdriver Philips No 2
Control circuit: 10.62 lbf.in (1.2 N.m) - on screw clamp terminal - with screwdriver flat Ø 6 mm
Power circuit: 44.25 lbf.in (5 N.m) - on screw clamp terminal - with screwdriver flat Ø 8 mm
System Voltage <= 690 V AC 25...400 Hz power circuit
[Ith] conventional free air thermal
current
10 A at <= 140 °F (60 °C) control circuit
80 A at <= 140 °F (60 °C) power circuit
Irms rated making capacity 140 A AC for control circuit conforming to IEC 60947-5-1
900 A at 440 V power circuit conforming to IEC 60947
Rated breaking capacity 900 A at 440 V power circuit conforming to IEC 60947
Associated fuse rating 10 A gG control circuit conforming to IEC 60947-5-1
100 A gG at <= 690 V coordination type 1 power circuit
100 A gG at <= 690 V coordination type 2 power circuit
Power dissipation per pole 3.7 W AC-3
9.6 W AC-1
Inrush power in VA 140 VA at 68 °F (20 °C) (cos φ 0.75)
160 VA at 68 °F (20 °C) (cos φ 0.75)
Hold-in power consumption in VA 13 VA at 68 °F (20 °C) (cos φ 0.3) 60 Hz
15 VA at 68 °F (20 °C) (cos φ 0.3) 50 Hz
Operating time 12...26 ms closing
4...19 ms opening