Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
May 14, 2018
1
Product data sheet
Characteristics
LC1D50F7
CONTACTOR 600VAC 50AMP IEC +OPTIONS
Product availability : Stock - Normally stocked in distribution facility
Price* : 324.00 USD
Main
Range of product TeSys D
Range TeSys
Product or component type Contactor
Device short name LC1D
Contactor application Motor control
Resistive load
Utilisation category AC-1
AC-2
AC-3
AC-4
Control circuit type AC 50/60 Hz
Poles description 3P
Pole contact composition 3 NO
[Ie] rated operational current 50 A (<= 140 °F (60 °C)) at <= 440 V AC AC-3 power circuit
80 A (<= 140 °F (60 °C)) at <= 440 V AC AC-1 power circuit
Motor power kW 22 kW at 380...400 V AC 50/60 Hz AC-3
25 kW at 415 V AC 50/60 Hz AC-3
30 kW at 440 V AC 50/60 Hz AC-3
30 kW at 500 V AC 50/60 Hz AC-3
33 kW at 660...690 V AC 50/60 Hz AC-3
15 kW at 220...230 V AC 50/60 Hz AC-3
11 kW at 400 V AC 50/60 Hz AC-4
30 kW at 1000 V AC 50/60 Hz AC-3
Motor power hp 15 hp at 200/208 V AC 60 Hz 3P motors conforming to CSA
15 hp at 200/208 V AC 60 Hz 3P motors conforming to UL
15 hp at 230/240 V AC 60 Hz 3P motors conforming to CSA
15 hp at 230/240 V AC 60 Hz 3P motors conforming to UL
3 hp at 115 V AC 60 Hz 1P motors conforming to CSA
3 hp at 115 V AC 60 Hz 1P motors conforming to UL
40 hp at 460/480 V AC 60 Hz 3P motors conforming to CSA
40 hp at 460/480 V AC 60 Hz 3P motors conforming to UL
40 hp at 575/600 V AC 60 Hz 3P motors conforming to CSA
40 hp at 575/600 V AC 60 Hz 3P motors conforming to UL
7.5 hp at 230/240 V AC 60 Hz 1P motors conforming to CSA
2
7.5 hp at 230/240 V AC 60 Hz 1P motors conforming to UL
[Uc] control circuit voltage 110 V AC 50/60 Hz
Connections - terminals Control circuit: screw clamp terminal 1 cable 0...0.01 in² (1...4 mm²) - cable stiffness: solid - without
cable end
Control circuit: screw clamp terminal 2 cable 0...0.01 in² (1...4 mm²) - cable stiffness: solid - without
cable end
Power circuit: screw clamp terminal 1 cable 0...0.05 in² (1...35 mm²) - cable stiffness: solid - without
cable end
Power circuit: screw clamp terminal 2 cable 0...0.04 in² (1...25 mm²) - cable stiffness: solid - without
cable end
Power circuit: screw clamp terminal 1 cable 0...0.05 in² (1...35 mm²) - cable stiffness: flexible - without
cable end
Control circuit: screw clamp terminal 1 cable 0...0.01 in² (1...4 mm²) - cable stiffness: flexible - with
cable end
Control circuit: screw clamp terminal 2 cable 0...0 in² (1...2.5 mm²) - cable stiffness: flexible - without
cable end
Control circuit: screw clamp terminal 2 cable 0...0.01 in² (1...4 mm²) - cable stiffness: flexible - with
cable end
Power circuit: screw clamp terminal 2 cable 0...0.04 in² (1...25 mm²) - cable stiffness: flexible - with
cable end
Power circuit: screw clamp terminal 2 cable 0...0.05 in² (1...35 mm²) - cable stiffness: flexible - without
cable end
Power circuit : screw terminals
Complementary
Coil technology Without built-in bidirectional peak limiting diode suppressor
Protective cover With
Auxiliary contacts type Type mechanically linked (1 NO + 1 NC) conforming to IEC 60947-5-1
Type mirror contact (1 NC) conforming to IEC 60947-4-1
Auxiliary contact composition 1 NO + 1 NC
Control circuit voltage limits 0.3...0.6 Uc at 140 °F (60 °C) drop-out 50/60 Hz
0.8...1.1 Uc at 140 °F (60 °C) operational 50 Hz
0.85...1.1 Uc at 140 °F (60 °C) operational 60 Hz
[Ui] rated insulation voltage 600 V control circuit certifications CSA
600 V control circuit certifications UL
600 V power circuit certifications CSA
600 V power circuit certifications UL
690 V control circuit conforming to IEC 60947-1
690 V power circuit conforming to IEC 60947-1
[Uimp] rated impulse withstand voltage 8 kV IEC 60947
Overvoltage category III
Mounting support Plate
Rail
Flame retardance V1 conforming to UL 94
Tightening torque Power circuit: 44.25 lbf.in (5 N.m) - on screw clamp terminal - with screwdriver flat Ø 6 mm
Control circuit: 10.62 lbf.in (1.2 N.m) - on screw clamp terminal - with screwdriver Philips No 2
Control circuit: 10.62 lbf.in (1.2 N.m) - on screw clamp terminal - with screwdriver flat Ø 6 mm
Power circuit: 44.25 lbf.in (5 N.m) - on screw clamp terminal - with screwdriver flat Ø 8 mm
System Voltage <= 690 V AC 25...400 Hz power circuit
[Ith] conventional free air thermal
current
10 A at <= 140 °F (60 °C) control circuit
80 A at <= 140 °F (60 °C) power circuit
Irms rated making capacity 140 A AC for control circuit conforming to IEC 60947-5-1
900 A at 440 V power circuit conforming to IEC 60947
Rated breaking capacity 900 A at 440 V power circuit conforming to IEC 60947
Associated fuse rating 10 A gG control circuit conforming to IEC 60947-5-1
100 A gG at <= 690 V coordination type 1 power circuit
100 A gG at <= 690 V coordination type 2 power circuit
Power dissipation per pole 3.7 W AC-3
9.6 W AC-1
Inrush power in VA 140 VA at 68 °F (20 °C) (cos φ 0.75)
160 VA at 68 °F (20 °C) (cos φ 0.75)
Hold-in power consumption in VA 13 VA at 68 °F (20 °C) (cos φ 0.3) 60 Hz
15 VA at 68 °F (20 °C) (cos φ 0.3) 50 Hz
Operating time 12...26 ms closing
4...19 ms opening
3
Safety reliability level B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Mechanical durability 6000000 cycles
Operating rate 3600 cyc/h at <= 140 °F (60 °C)
Minimum switching current 5 mA control circuit
Minimum switching voltage 17 V control circuit
Non-overlap time 1.5 ms on de-energisation between NC and NO contacts
1.5 ms on energisation between NC and NO contacts
Insulation resistance > 10 MOhm control circuit
Height 5 in (127 mm)
Width 2.95 in (75 mm)
Depth 4.69 in (119 mm)
Product weight 3.09 lb(US) (1.4 kg)
Compatibility code LC1D
Environment
Standards EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 508
CSA C22.2 No 14
Product certifications BV
CCC
CSA
DNV
GL
GOST
LROS (Lloyds register of shipping)
RINA
UL
IP degree of protection IP2x conforming to IEC 60529
IP2x conforming to VDE 0106
Ambient air temperature for operation 23...140 °F (-5...60 °C)
Ambient air temperature for storage -76...176 °F (-60...80 °C)
Permissible ambient air temperature
around the device
-40...158 °F (-40...70 °C) at Uc
Operating altitude 9842.52 ft (3000 m) without derating in temperature
Fire resistance 1562 °F (850 °C) conforming to IEC 60695-2-1
Shock resistance 10 gn contactor opened
15 gn contactor closed
Vibration resistance 2 gn 5...300 Hz contactor opened
4 gn 5...300 Hz contactor closed
Heat dissipation 4...5 W at 50/60 Hz for control circuit
Ordering and shipping details
Category 22345 - CTR,D-LINE,OPEN,NONREV-NEW
Discount Schedule I12
GTIN 00785901421399
Nbr. of units in pkg. 1
Package weight(Lbs) 3.1699999999999999
Returnability Y
Country of origin CZ
Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant - since 0001 - Schneider Electric declaration of conformity
4
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Available
Contractual warranty
Warranty period 18 months