Characteristics
TMC4TI2
cartridge M241 - 2 temperature inputs
Main
Commercial Status Commercialised
Range of product Modicon M241
Product or component
type
Analogue input cartridge
Product compatibility Modicon M241C
Analogue input number 2
Complementary
Analogue input type Temperature probe, input range: - 200...600 °C (Pt 1000)
Temperature probe, input range: - 200...850 °C (Pt 100)
Temperature probe, input range: - 60...180 °C (Ni 100/Ni 1000)
Thermocouple, input range: - 200...800 °C for thermocouple E
Thermocouple, input range: - 200...1300 °C for thermocouple N
Thermocouple, input range: - 200...400 °C for thermocouple T
Thermocouple, input range: 0...1820 °C for thermocouple B
Thermocouple, input range: 0...1760 °C for thermocouple S
Thermocouple, input range: 0...1760 °C for thermocouple R
Thermocouple, input range: - 200...1300 °C for thermocouple K
Thermocouple, input range: - 200...1000 °C for thermocouple J
Analogue input resolution 14 bits
Permissible continuous overload 6 V
Input impedance >= 1 MOhm
LSB value 0.1 °C
Sampling duration 100 ms
Absolute accuracy error +/- 0.5 % of full scale (Pt 100/Pt 1000, Ni 100/ Ni 1000)
+/- 0.1 % of full scale for thermocouple B, input range: 400...1280 °C
+/- 0.2 % of full scale for thermocouple B, input range: 250...400 °C
+/- 0.2 % of full scale for thermocouple N
+/- 0.2 % of full scale for thermocouple E
+/- 0.2 % of full scale for thermocouple T
+/- 0.2 % of full scale for thermocouple S
+/- 0.2 % of full scale for thermocouple R
+/- 0.2 % of full scale for thermocouple K
+/- 0.2 % of full scale for thermocouple J
Temperature drift +/- 0.008 %FS/°C
Repeat accuracy +/- 0.1 %FS
Non-linearity +/- 0.05 %FS
Cross talk 80 dB
Type of cable Twisted shielded pairs cable
Power consumption in W 2 W at 24 V DC
Electrical connection 1 spring terminal block (pitch 3.81 mm) 1.5 mm² 1 for outputs and supply
Cable length <= 30 m twisted shielded pairs cable (input)
Insulation Non-insulated between inputs
Between input and internal logic 500 V DC
Supply voltage limits 20.4...28.8 V