The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
Aug 28, 2015
1
Product data sheet
Characteristics
TMC4TI2
cartridge M241 - 2 temperature inputs
Main
Commercial Status Commercialised
Range of product Modicon M241
Product or component
type
Analogue input cartridge
Product compatibility Modicon M241C
Analogue input number 2
Complementary
Analogue input type Temperature probe, input range: - 200...600 °C (Pt 1000)
Temperature probe, input range: - 200...850 °C (Pt 100)
Temperature probe, input range: - 60...180 °C (Ni 100/Ni 1000)
Thermocouple, input range: - 200...800 °C for thermocouple E
Thermocouple, input range: - 200...1300 °C for thermocouple N
Thermocouple, input range: - 200...400 °C for thermocouple T
Thermocouple, input range: 0...1820 °C for thermocouple B
Thermocouple, input range: 0...1760 °C for thermocouple S
Thermocouple, input range: 0...1760 °C for thermocouple R
Thermocouple, input range: - 200...1300 °C for thermocouple K
Thermocouple, input range: - 200...1000 °C for thermocouple J
Analogue input resolution 14 bits
Permissible continuous overload 6 V
Input impedance >= 1 MOhm
LSB value 0.1 °C
Sampling duration 100 ms
Absolute accuracy error +/- 0.5 % of full scale (Pt 100/Pt 1000, Ni 100/ Ni 1000)
+/- 0.1 % of full scale for thermocouple B, input range: 400...1280 °C
+/- 0.2 % of full scale for thermocouple B, input range: 250...400 °C
+/- 0.2 % of full scale for thermocouple N
+/- 0.2 % of full scale for thermocouple E
+/- 0.2 % of full scale for thermocouple T
+/- 0.2 % of full scale for thermocouple S
+/- 0.2 % of full scale for thermocouple R
+/- 0.2 % of full scale for thermocouple K
+/- 0.2 % of full scale for thermocouple J
Temperature drift +/- 0.008 %FS/°C
Repeat accuracy +/- 0.1 %FS
Non-linearity +/- 0.05 %FS
Cross talk 80 dB
Type of cable Twisted shielded pairs cable
Power consumption in W 2 W at 24 V DC
Electrical connection 1 spring terminal block (pitch 3.81 mm) 1.5 mm² 1 for outputs and supply
Cable length <= 30 m twisted shielded pairs cable (input)
Insulation Non-insulated between inputs
Between input and internal logic 500 V DC
Supply voltage limits 20.4...28.8 V
2
Local signalling 1 LED green PWR
Height 1.97 in (50 mm)
Depth 0.83 in (21 mm)
Width 1.34 in (34 mm)
Product weight 0.12 lb(US) (0.055 kg)
Environment
Immunity to microbreaks 10 ms