Technical Datasheet 1SBC101407D0201 25/03/11 AF16-30-10-.. / AF16Z-30-10-.. 3-pole Contactors AC / DC Operated - with Screw Terminals AF16(Z) contactors are used for controlling power circuits up to 690 V AC and 220 V DC. They are mainly used for controlling 3-phase motors, non-inductive or slightly inductive loads. -- AF..(Z) contactors include an electronic coil interface providing reduced pull-in and holding consumption, particularly for AC control circuits -- Only four coils are needed to cover control voltages between 24...500 V 50/60 Hz or 20...500 V DC. AF..(Z) offer extended operating limits and are suitable worldwide for different control voltages. e.g.: the coil 100...250 V 50/60 Hz - DC is suitable for Europe (230 V 50 Hz) and for North America (120 V 60 Hz and 208 V 60 Hz). AF..(Z) contactors can manage large control voltage variations -- AF..Z contactors equipped with a 24...60 V 50/60 Hz - 20...60 V DC coil allow direct control by 24 V DC 500 mA PLC-output -- AF..Z contactors withstand short voltage dips and voltage sags (SEMI F47-0706 compliance) -- AF..(Z) contactors have built-in surge protection and do not require additional surge suppressors. 7.5 kW 10 hp 3D CAD outline drawings available on Control Product 3D portal Ordering Details IEC Rated power 400 V AC-3 kW UL/CSA Control voltage 3-phase Uc min. ... Uc max. motor rating 480 V hp Main Auxiliary Type contacts contacts fitted Order code EAN Weight Pack(ing) 1 piece kg V 50/60 Hz V DC 3-pole Contactors 7.5 10 24...60 48...130 100...250 250...500 20...60 48...130 100...250 250...500 3 3 3 3 0 0 0 0 1 1 1 1 0 0 0 0 AF16-30-10-11 AF16-30-10-12 AF16-30-10-13 AF16-30-10-14 1SBL 177 001 R1110 1SBL 177 001 R1210 1SBL 177 001 R1310 1SBL 177 001 R1410 3471523110618 3471523110625 3471523110632 3471523110649 0.270 0.270 0.270 0.310 Note: AF16-30-10-11 not suitable for a direct control by PLC-output. AF16-30-10-11 available in some countries: please consult your ABB representative. 3-pole Contactors - Low Consumption 7.5 10 24...60 48...130 100...250 12...20 20...60 48...130 100...250 3 3 3 3 0 0 0 0 1 1 1 1 0 0 0 0 AF16Z-30-10-20 AF16Z-30-10-21 AF16Z-30-10-22 AF16Z-30-10-23 1SBL 176 001 R2010 1SBL 176 001 R2110 1SBL 176 001 R2210 1SBL 176 001 R2310 3471523113800 3471523113817 3471523113824 3471523113831 0.310 0.310 0.310 0.310 Note: Only AF..Z contactors with DC control voltage 12...20 V DC need to respect the connection polarities indicated close to the coil terminals: A1+ for the positive pole and A2- for the negative pole Certifications and Approvals CE cULus CCC GOST C-Tick ABB | Technical Datasheet 1SBC101407D0201 1 Main Pole - Utilization Characteristics according to IEC Standards Rated operational voltage Ue max. Rated frequency limits Conventional free-air thermal current Ith IEC 60947-1 / 60947-4-1 and EN 60947-1 / 60947-4-1 690 V 25 ... 400 Hz acc. to IEC 60947-4-1, open contactors, 40 C 35 A 6 mm with conductor cross-sectional area AC-1 Utilization category for air temperature close to contactor Ie / AC-1 rated operational current Ue max. 690 V, 50/60 Hz 40 C 60 C 70 C with conductor cross-sectional area AC-3 Utilization category for air temperature close to contactor 60 C 30 A 30 A 26 A 6 mm (for 1500 r.p.m., 50 Hz or 1800 r.p.m., 60 Hz, 3-phase motors) Ie / AC-3 max. rated operational current 3-phase motors M 3 AC-3 rated operational power M 3 1500 r.p.m. 50 Hz 1800 r.p.m. 60 Hz 3-phase motors 220-230-240 V 380-400 V 415 V 440 V 500 V 690 V 220-230-240 V 380-400 V 415 V 440 V 500 V 690 V Rated making capacity AC-3 Rated breaking capacity AC-3 AC-8a Utilization category 18 A 18 A 18 A 18 A 15 A 10.5 A 4 kW 7.5 kW 9 kW 9 kW 9 kW 9 kW 10 x Ie AC-3 acc. to IEC 60947-4-1 8 x Ie AC-3 acc. to IEC 60947-4-1 (without thermal overload relay - Ue 400 V - 40 C) 22 A 11 kW Ie / AC-8a rated operational current AC-8a rated operational power Short-circuit protection for contactors without thermal O/L relay - Motor protection excluded Ue 500 V AC - gG type fuse Rated short-time withstand current Icw at 40 C ambient temperature, in free air from a cold state Maximum breaking capacity cos = 0.45 Heat dissipation per pole Max. electrical switching frequency 2 Technical Datasheet 1SBC101407D0201 | ABB 1s 10 s 30 s 1 min 15 min at 440 V at 690 V Ie / AC-1 Ie / AC-3 AC-1 AC-3 AC-2, AC-4 32 A 300 A 150 A 80 A 60 A 35 A 250 A 106 A 1.2 W 0.35 W 600 cycles/h 1200 cycles/h 300 cycles/h Built-in Auxiliary Contacts according to IEC 690 V 16 A 25 ... 400 Hz Rated operational voltage Ue max. Conventional free air thermal current Ith - 40 C Rated frequency limits Rated operational current Ie / AC-15 acc. to IEC 60947-5-1 24-127 V 50/60 Hz 220-240 V 50/60 Hz 400-440 V 50/60 Hz 500 V 50/60 Hz 690 V 50/60 Hz Making capacity AC-15 Breaking capacity AC-15 Rated operational current Ie / DC-13 24 V DC 48 V DC 72 V DC 110 V DC 125 V DC 220 V DC 250 V DC 400 V DC 500 V DC 600 V DC acc. to IEC 60947-5-1 Short-circuit protection gG type fuse Rated short-time withstand current Icw for 1.0 s for 0.1 s Minimum switching capacity with failure rate acc. to IEC 60947-5-4 Non-overlapping time between N.O. and N.C. contacts Heat dissipation per pole at 6 A Max. electrical switching frequency AC-15 DC-13 6A 4A 3A 2A 2A 10 x Ie AC-15 acc. to IEC 60947-5-1 10 x Ie AC-15 acc. to IEC 60947-5-1 6 A / 144 W 2.8 A / 134 W 1 A / 72 W 0.55 A / 60 W 0.55 A / 69 W 0.27 A / 60 W 0.27 A / 68 W 0.15 A / 60 W 0.13 A / 65 W 0.1 A / 60 W 10 A 100 A 140 A 12 V / 3 mA 10 -7 2 ms 0.1 W 1200 cycles/h 900 cycles/h Main Pole - Utilization Characteristics according to UL / NEMA / CSA Standards Rated operational voltage Ue max. NEMA size NEMA continuous amp rating NEMA maximum H.P. ratings 1-phase, 60 Hz NEMA maximum H.P. ratings 3-phase, 60 Hz UL General use rating 600 V AC With conductor cross-sectional area 80 V DC - 1-pole With conductor cross-sectional area UL maximum 1-phase motor rating Amp-rating Motor power UL maximum 3-phase motor rating Amp-rating Motor power (for 1500 r.p.m., 50 Hz or 1800 r.p.m., 60 Hz 3-phase motors) UL 508, CSA C22.2 N14 600 V thermal current 115 V AC 230 V AC 200 V AC 230 V AC 460 V AC 575 V AC 30 A AWG 10 30 A AWG 10 120 V AC 240 V AC 120 V AC 240 V AC 200-208 V AC 220-240 V AC 440-480 V AC 550-600 V AC 200-208 V AC 220-240 V AC 440-480 V AC 550-600 V AC 20 A 17 A 1-1/2 hp 3 hp 17.5 A 15.2 A 14 A 17 A 5 hp 5 hp 10 hp 15 hp Short-circuit protection for contactors without thermal O/L relay - Motor protection excluded Fuse rating Fuse type, 600 V Max. electrical switching frequency for general use for motor use 60 A NTD 600 cycles/h 1200 cycles/h ABB | Technical Datasheet 1SBC101407D0201 3 Built-in Auxiliary Contacts according to UL / CSA 600 V AC, 600 V DC A600, Q600 10 A 7200 VA 720 VA 2.5 A 69 VA Max. rated operational voltage Ue max. Pilot duty AC thermal rated current AC maximum volt-ampere making AC maximum volt-ampere breaking DC thermal rated current DC maximum volt-ampere making-breaking General Technical Data Rated insulation voltage Ui 690 V 600 V 6 kV Devices complying with IEC 60947-1 / EN 60947-1 - Environment A acc. to IEC 60947-4-1 acc. to UL /CSA Rated impulse withstand voltage Uimp. Electromagnetic compatibility Ambient air temperature close to contactor Operation fitted with thermal overload relay without thermal overload relay Storage Climatic withstand Operating altitude Mechanical durability Number of operating cycles Max. switching frequency Shock withstand -25 ... +60 C -40 ... +70 C -60 ... +80 C Category B according to IEC 60947-1 Annex Q 3000 m 10 millions operating cycles 3600 cycles/h acc. IEC 60068-2-27 and EN 60068-2-27 Mounting position 1 Closed or open position C1 A A B1 Shock direction A B1 B2 C1 C2 B2 C2 Vibration withstand acc. to IEC 60068-2-6 1/2 sinusoidal shock for 11 ms: no change in contact position 30 g 25 g Closed position / 5 g Open position 15 g 25 g 25 g 5 ... 300 Hz 4 g Closed position / 2 g Open position Magnet System Characteristics Coil operating limits AC supply at 60 C 0.85 x Uc min ... 1.1 x Uc max at 70 C 0.85 x Uc min ... Uc max DC supply at 60 C 0.85 x Uc min ... 1.1 x Uc max at 70 C (AF) 0.85 x Uc min ... Uc max - (AF..Z) 0.85 x Uc min ... 1.1 x Uc max 24 ... 500 V AC (AF) 50 VA - (AF..Z) 16 VA (AF) 2.2 VA / 2 W - (AF..Z) 1.7 VA / 1.5 W 12 ... 500 V DC (AF) 50 W - (AF..Z) 12 ... 16 W (AF) 2 W - (AF..Z) 1.7 W (AF..Z) 500 mA 24 V DC 60 % Uc min (AF..Z) conditions of use on request (AF..Z) 22 ms average for Uc = 24 ... 250 V 50/60Hz acc. to IEC 60947-4-1 AC control voltage 50/60 Hz Rated control circuit voltage Uc Average pull-in value Coil consumption DC control voltage Rated control circuit voltage Uc Average pull-in value Coil consumption Average holding value Average holding value PLC-Output control Drop-out voltage in % of Uc min. Voltage sag immunity according to SEMI F47-0706 Dips withstand (level 0% according to IEC 61000-4-11) -20 C +60 C Operating time N.O. contact closing 40 ... 95 ms between coil energization and: N.C. contact opening 38 ... 90 ms N.O. contact opening 11 ... 95 ms between coil de-energization and: N.C. contact closing 13 ... 98 ms 4 Technical Datasheet 1SBC101407D0201 | ABB Mounting Characteristics Mounting positions Pos. 2 +30 -30 Pos. 4 Pos. 3 Pos. 1 Pos. 1 30 Pos. 5 Max. N.C. built-in and add-on N.C. auxiliary contacts: see accessory fitting details for a 3-pole contactor AF09 ... AF38 The contactors can be assembled side by side. Mounting distances Fixing on rail according to IEC 60715, EN 60715 by screws (not supplied) 35 x 7.5 mm or 35 x 15 mm 2 x M4 screws placed diagonally Connecting Characteristics Main terminals Screw terminals with cable clamp Connecting capacity (min. ... max.) Main conductors (poles) Rigid solid ( 4 mm) stranded ( 6 mm) Flexible with non insulated ferrule Flexible with insulated ferrule L 6 Bars or lugs Capacity according to UL/CSA Stripping length Auxiliary conductors (built-in auxiliary terminals + coil terminals) Rigid solid Flexible with non insulated ferrule Flexible with insulated ferrule L 6 Bars or lugs Capacity according to UL/CSA Stripping length Degree of protection 1x 2x 1x 2x 1x 2x L< 1 or 2 x 1 ... 6 mm 1 ... 6 mm 0.75 ... 6 mm 0.75 ... 6 mm 0.75 ... 4 mm 0.75 ... 2.5 mm 9.6 mm AWG 16 ... 10 10 mm 1x 2x 1 ... 2.5 mm 1 ... 2.5 mm 1x 2x 1x 2x L< 0.75 ... 2.5 mm 0.75 ... 2.5 mm 0.75 ... 2.5 mm 0.75 ... 1.5 mm 8 mm 1 or 2 x AWG 18 ... 14 10 mm acc. to IEC 60947-1 / EN 60947-1 and IEC 60529 / EN 60529 Main terminals Coil terminals Built-in auxiliary terminals Screw terminals Main terminals Coil terminals Built-in auxiliary terminals Screwdriver type Tightening torque Main pole terminals Coil terminals Built-in auxiliary terminals IP20 IP20 IP20 (delivered in open position, screws of unused terminals must be tightened) M3.5 M3.5 M3.5 Flat O 5.5 / Pozidriv 2 1.5 Nm / 13 lb.in 1.2 Nm / 11 lb.in 1.2 Nm / 11 lb.in ABB | Technical Datasheet 1SBC101407D0201 5 Accessory Fitting Details for a 3-pole Contactor Many configurations of accessories are possible depending on whether these are front-mounted or side-mounted. Main poles Front-mounted accessories Built-in auxiliary contacts Side-mounted accessories Auxiliary contact blocks Electrical and mechanical interlock set Auxiliary contact blocks (between 2 contactors) 1-pole CA4 Left side 1-pole CC4 2-pole CAT4-11 4-pole CA4 Right side 2-pole CAL4-11 VEM4 Max. N.C. built-in and add-on N.C. auxiliary contacts: 4 N.C. max. on positions 1, 2, 3, 4 and 3 N.C. max. on positions 1 30, 5 3 0 1 0 4 max. or 1 or 1 - + 1 - 2 max. or 1 - - + 1 + 1 3 max. - - + 1 + 1 or 1 Overview of main accessories (other accessories available) VEM4 mechanical and electrical interlock set including: - VM4 mechanical interlock unit including 2 fixing clips - VE4 electrical interlock block with A2-A2 connection AF contactor (without top mounted coil terminal block) AF contactor Fixing clips A2 A2 AF contactor ssories cks ght side 2-pole CAT4-11 VM4 1-pole CA4, CC4 4-pole CA4 2-pole CAL4-11 1-pole CA4, CC4 VE4 2-pole CAL4-11 1-pole CA4, CC4 TF42 EF.. TF42 EF.. 6 Technical Datasheet 1SBC101407D0201 | ABB Main Accessories Ordering Details Description Auxiliary contacts Type Order code EAN Pack(ing) Weight piece kg Front-mounted instantaneous auxiliary contact blocks (1 pce) 0 1 - - CA4-01 1SBN 010 110 R1001 3471523130029 1 0.014 1 0 - - CA4-10 1SBN 010 110 R1010 3471523130005 1 0.014 0 1 - - CA4-01-T 1SBN 010 110 T1001 3471523130395 10 0.014 1 0 - - CA4-10-T 1SBN 010 110 T1010 3471523130371 10 0.014 - - 0 1 CC4-01 1SBN 010 111 R1001 3471523130432 1 0.014 - - 1 0 CC4-10 1SBN 010 111 R1010 3471523130425 1 0.014 Side-mounted instantaneous auxiliary 1 1 contact blocks - - CAL4-11 1SBN 010 120 R1011 3471523130043 1 0.040 1 1 - - CAL4-11-T 1SBN 010 120 T1011 3471523130418 10 0.040 0 4 - - CA4-04M 1SBN 010 140 R1104 3471523130197 1 0.055 1 3 - - CA4-13M 1SBN 010 140 R1113 3471523130180 1 0.055 2 2 - - CA4-22M 1SBN 010 140 R1122 3471523130166 1 0.055 3 1 - - CA4-31M 1SBN 010 140 R1131 3471523130173 1 0.055 Front-mounted instantaneous auxiliary contact and A1/A2 coil terminal blocks Mechanical interlock unit 1 1 - - CAT4-11M 1SBN 010 151 R1111 3471523130074 1 0.040 VM4 1SBN 030 105 T1000 3471523130609 10 0.005 Mechanical and electrical interlock set 1 1 VEM4 1SBN 030 111 R1000 3471523130616 1 0.035 BB4 1SBN 110 120 W1000 3471523130722 50 0.002 BEA16-4 1SBN 081 306 T1000 3471523130739 10 0.025 Connection sets for reversing contactors BER16-4 1SBN 081 311 R1000 3471523130777 1 0.045 Additional coil terminal block Additional coil terminal block LDC4 1SBN 070 156 T1000 3471523130678 10 0.010 Protective covers Protective covers BX4 1SBN 110 108 T1000 3471523130708 10 0.006 BX4-CA 1SBN 110 109 W1000 3471523130715 50 0.001 BA4 1SNA 235 156 R2700 3472592351568 16 0.011 HTP500-BA4 1SNA 235 712 R2400 3472592357126 1 0.220 SPRC 1 3472593600108 1 0.290 Additional auxiliary contact blocks Front-mounted auxiliary contact blocks with N.O. leading contact and N.C. lagging contact Front-mounted instantaneous auxiliary contact blocks Interlocks Fixing clips Connection accessories Connecting links with manual motor for starting starters Function markers Function markers - - 1SNA 360 010 R1500 Note: - CAT4: not fittable on AF..Z contactors with DC control voltage 12...20VDC. - VM4: includes 2 fixing clips (BB4) to maintain together both contactors. - VEM4: includes a VM4 mechanical interlock unit with 2 fixing clips (BB4), a VE4 electrical interlock block and A2-A2 connection. VE4 block must be used with its A2-A2 connection to respect the electrical connection diagram. VEM4 not fittable on AF..Z contactors with DC control voltage 12...20 V DC. ABB | Technical Datasheet 1SBC101407D0201 7 Terminal Marking and Positioning Standard devices without addition of auxiliary contacts A1 A2 1L1 3L2 5L3 A1 1L1 3L2 5L3 13 NO A2 2T1 4T2 6T3 NO 14 13 NO AF16-30-10-.. / AF16Z-30-10-.. NO 2T1 4T2 6T3 14 A1 A2 AF16-30-10-.. / AF16Z-30-10-.. Dimensions mm, inches 5.5 0.22" 10 0.39" 35 1.38" 2x o 4.2 0.17" M4 8-32 UNC 2x M4 8-32 UNC 70 2.76" 5.5 0.22" o 4.2 0.17" 60 2.36" 35 mm EN/IEC 60715 35 mm EN/IEC 60715 6 0.24" 80 3.15" 6 0.24" 80 3.15" 35 1.38" 5.5 0.22" 10 0.39" 5 0.20" 5 0.20" 71 2.80" 5.5 0.22" 70602.76" 2.36" 77 3.03" 71 2.80" 45 1.77" 5 0.20" 77 3.03" 45 1.77" 5 0.20" AF16 AF16 110.5 4.35" 71 2.80" 45 1.77" 77 3.03" 10 0.39" 12 0.47" 71 2.80" 45 1.77" 80 3.15" 5.5 0.22" 35 mm EN/IEC 60715 6 0.24" 5.5 0.22" 43 1.69" 80 3.15" 35 mm EN/IEC 60715 6 0.24" 5.5 0.22" 5.5 0.22" 10 0.39" AF16 + CA4, CC4 1-pole auxiliary contact block AF16 + CAL4-11 2-pole auxiliary contact block 102.5 4.04" 110.5 4.35" 71 2.80" 10 0.39" 45 1.77" 5.5 0.22" AF16 + CA4 4-pole auxiliary contact block 102.5 4.04" 102.5 4.04" 60 2.36" 60 2.36" 43 1.69" 43 1.69" 35 mm EN/IEC 60715 35 mm EN/IEC 60715 91.5 3.60" 5.5 0.22" 5.5 0.22" 2x 2x M4 8-32 M4UNC 8-32 UNC 5 0.20" 80 3.15" 80 3.15" 5 0.20" 70 2.76" 10 0.39" 10 0.39" 70 2.76" 71 2.80" 71 2.80" 5.5 0.22" 5.5 0.22" 91.5 3.60" 5.5 0.22" AF16 + CAT4 2-pole auxiliary contact and coil terminal block 90 3.54" 90 3.54" o 4.2 0.17" o 4.2 0.17" 5 0.20"5 0.20" AF16 + VEM4 mechanical and electrical interlock set Note: contactor lateral distance to grounded component 2 mm 0.08" min. 8 10 0.39" 5.5 0.22" 35 mm EN/IEC 60715 80 3.15" 43 1.69" 80 3.15" 35 mm EN/IEC 60715 6 0.24" 5.5 0.22" Technical Datasheet 1SBC101407D0201 | ABB AF16 + VEM4 mechanical and electrical interlock set 43 1.69" 71 2.80" 45 1.77" You can find the address of your local sales organisation on the ABB home page http://www.abb.com/contacts -> Low Voltage products Note We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB does not accept any responsibility whatsoever for potential errors or possible lack of information in this document. We reserve all rights in this document and in the subject matter and illustrations contained therein. Any reproduction, disclosure to third parties or utilization of its contents - in whole or in parts - is forbidden without prior written consent of ABB. Copyright(c) 2011 ABB All rights reserved www.abb.com/lowvoltage Technical Datasheet 1SBC101407D0201 ABB France Low Voltage Products Division 10, rue Ampere Z.I. - B.P. 114 F-69685 Chassieu cedex / France (25/03/11) Contact us