Type Number
Product Name Type No. Quantity
Web Server Unit FC4A-SX5ES1E 1
PLC Communication Cable FC4A-KC3C 1
35mm DIN Rail (aluminium, 1m) BAA1000PN10 10
Mounting Clip BNL6PN10 10
Manual FC9Y-B919 1
General Specifications
Rated Power Voltage 24V DC
Allowable Voltage Range 20.4 to 26.4V DC
Current Draw 70 mA
Allowable Momentary
Power Interruption 10 ms maximum
Dielectric Strength 500V AC, 1 minute
Insulation Resistance 10MΩ minimum (500V DC megger)
Noise Resistance DC power terminal: 1.0 kV, 50 ns to 1 µs
Ethernet cable: 0.5 kV, 50 ns to 1 µs (coupling clamp)
Inrush Current 4A maximum
Operating Temperature 0 to 55˚C
Storage Temperature –40 to +70˚C (no freezing)
Relative Humidity 10 to 95% (no condensation)
Pollution Degree 2 (IEC 60664-1)
Corrosion Immunity Free from corrosive gases
Degree of Protection IP20 (IEC60529)
Vibration Resistance
When mounted on a DIN rail:
5 to 9 Hz amplitude 3.5 mm
9 to 150 Hz accelaration 9.8 m/s2 (1G)
2 hours in each of 3 axes
Shock Resistance 147 m/s2 (15G), 11 ms duration
3 shocks each in 3 axes
Weight (approx.) 150g
IDEC CORPORATION (USA)
1175 Elko Drive, Sunnyvale, CA 94089-2209, USA
Tel: +1-408-747-0550 / (800) 262-IDEC (4332)
Fax: +1-408-744-9055 / (800) 635-6246
E-mail: opencontact@idec.com
IDEC CANADA LIMITED
Unit 22-151, Brunel Road Mississauga, Ontario, L4Z 1X3, Canada
Tel: +1-905-890-8561, Toll Free: (888) 317-4332, Fax: +1-905-890-8562
E-mail: sales@ca.idec.com
IDEC ELECTRONICS LIMITED
Unit 2, Beechwood, Chineham Business Park, Basingstoke, Hampshire
RG24 8WA, UK
Tel: +44-1256-321000, Fax: +44-1256-327755
E-mail: sales@uk.idec.com
IDEC ELEKTROTECHNIK GmbH
Wendenstrasse 331, D-20537 Hamburg, Germany
Tel: +49-40-25 30 54 10, Fax: +49-40-25 30 54 24
E-mail: service@idec.de
IDEC AUSTRALIA PTY. LTD.
2/3 Macro Court, Rowville, Victoria 3178, Australia
Tel: +61-3-9763-3244, Toll Free: 1800-68-4332, Fax: +61-3-9763-3255
E-mail: sales@au.idec.com
7-31, Nishi-Miyahara 1-Chome, Yodogawa-ku, Osaka 532-8550, Japan
Tel: +81-6-6398-2571, Fax: +81-6-6392-9731
E-mail: products@idec.co.jp
Specifications and other descriptions in this catalog are subject to change without notice.
Cat. No. EP1086-0 JANUARY 2006 12DNP PRINTED IN JAPAN
IDEC IZUMI ASIA PTE. LTD.
No. 31, Tannery Lane #05-01, Dragon Land Building, Singapore 347788
Tel: +65-6746-1155, Fax: +65-6844-5995
E-mail: info@sg.idec.com
IDEC IZUMI (H.K.) CO., LTD.
Unit 1505-07, DCH Commercial Centre No. 25, Westlands Road,
Quarry Bay, Hong Kong
Tel: +852-2803-8989, Fax: +852-2565-0171
E-mail: info@hk.idec.com
IDEC (SHANGHAI) CORPORATION
Room 608-609, 6F, Gangtai Plaza, No. 700, Yan'an East Road,
Shanghai 200030, China
Tel: +86-21-5353-1000, Fax: +86-21-5353-1263
E-mail: idec@cn.idec.com
IDEC TAIWAN CORPORATION
8F, No. 79, Hsin Tai Wu Road, Sec. 1, Hsi-Chih, Taipei County, Taiwan
Tel: +886-2-2698-3929, Fax: +886-2-2698-3931
E-mail: service@idectwn.com.tw
www.idec.com
Interface Specifications
Communication RS232C <=> Ethernet conversion function
Ethernet
Specifications
Electrical characteristics: Complies with IEEE802.3
Transmission speed: 10BASE-T/100BASE-TX
(Not CE compliant)
Communication protocol: IP/ICMP/ARP
Ethernet protocol: TCP/SMTP/HTTP/Telnet
No. of TCP connections: 1
Serial I/F
Specifications
Electrical characteristics: EIA RS232C
Transmission speed: 9600 to 115200 bps
Synchronization: Asynchronous
Communication protocol: Full duplex
Transmission control: RTS/CTS, XON/OFF, None
Connection
Method
Ethernet interface: RJ45
Serial interface: Mini DIN 8-pin connector
Cable Type No.: FC4A-KC3C
Major Functions
Remote maintenance: Uploading, downloading and
monitoring using WindLDR via
Ethernet
Web server: Configure the web server unit using
Internet Explorer etc. Reading and writing
PLC operands using Java applet.
Web file area: 512 Kbyte
Compliant browser: Internet Explorer 6.0
Netscape Navigator 7.2
Ethernet user communication:
User communication using Ethernet
Message transmission:
Registered outgoing message
32 message types
3 characters max.
2 email addresses
64 address characters max.
45.0
80.0
2.1
45.0
35.0
70.0
80.0
70.0
∗
∗5.6mm when the clamp is pulled out
Dimensions
PLC Connector
To MicroSmart To Web Server Unit
Pin No.
1
2
3
4
5
6
7
8
Cover
Pin No.
1
2
3
4
5
6
7
8
Cover
Port 1
NC
NC
NC
CMSW
SG
NC
Name
DSR
CTS
SD
RD
RTS
NC
GND
DTR
Shield
Port 2
RS
ER
DR
SG
SG
NC
SD
RD
SG
Connector for
MicroSmart
Connector for
Web Server Unit
Option
Utility CD: Configuration file, PLC operand monitor
sample programs, sample program
configuration instructions, instruction manual
Connectable Devices
Programmable Controllers
IDEC FC5A MicroSmart (available soon)
IDEC FC4A MicroSmart
IDEC FC3A OpenNet Controller
Operator Interface
(RS232C communication with PLC through Ethernet)
IDEC HG2F
IDEC HG2S
•
•
Ethernet is a registered trademark of Xerox Corporation.•
Mounting Hole Layout
for Direct Mounting
•
(Type No. FC4A-KC3C, Cable Length: 100 mm)
Cable Dimensions •
Connector Pinout •
Cable Connection Diagram •
M4 mounting screw
(12 mm or 15 mm)
Web Server Unit