DUO series Manual Motor Starters
Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
02/5
02
Quick reference guide
32AF types and ratings
Note: * 1 Adjustable thermal-magnetic trip type only Available Not available
* 2When the breaking duty is once “0” in JEM 1195, the breaking capacity is 50kA.
Replace the
mark
in the type number
by current range
codes.
Standard breaking capacity High breaking capacity
Adjustable thermal-magnetic trip type BM3RSB-
BM3RHB-
Instantaneous trip type BM3RHBK-
KK01-317 AF01-42
Number of poles 3 3
Handle type Rocker Rotary
Rated current In (A) 0.16 to 32
Rated operational voltage Ue (V) 200 to 690
Rated frequency (Hz) 50/60
Rated insulation voltage Ui (V) 690
Rated impulse withstand voltage Uimp (kV) 6
Utilization IEC 60947-2 Circuit breaker Cat. A
category IEC 60947-4-1 Motor starter AC-3
Trip class IEC 60947-4-1 *110
Instantaneous trip characteristic 13 ln max.
Power loss (total of 3-pole) 7W: In=0.16 to 25A 8.5W: In=32A
Mechanical durability (operations) 100,000: In=0.16 to 25A 70,000: In=32A
Electrical durability (operations) 100,000: In=0.16 to 25A 70,000: In=32A
Max. operations per hour (motor start-up) 25
Phase-loss protection Provided
Tripping state indication Provided
Test trip function Provided
Rated breaking Adjustable current range 240V 415V 460V 500V 690V 240V 415V 460V 500V 690V
capacity (kA) Code Ie: Min.–Max. 230V 400V 440V 600V 230V 400V 440V 600V
IEC 60947-2 (A) Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics
P16 0.1–0.16 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
P25 0.16–0.25 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
P40 0.25–0.4 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
P63 0.4–0.63 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
001 0.63–1.100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
1P6 1–1.6 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
2P5 1.6–2.5 100 100 100 100 100 100 100 100 3 2 100 100 100 100 100 100 100 100 8 6
004 2.5–4.100 100 100 100 100 100 100 100 3 2 100 100 100 100 100 100 100 100 8 6
6P3 4–6.3 100 100 100 100 50 38 50 38 3 2 100 100 100 100 100 100 100 100 6 5
010 6.3–10 .100 100 100 100 15 11 10 8 3 2 100 100 100 100 50 38 50 38 6 5
013 9–13 .100 100 50 38 10 8 6 5 3 2 100 100 100 100 50 38 42 32 6 5
016 11–16 .100 100 25 19 10 8 6 5 3 2 100 100 50 38 35*227 10 8 4 3
020 14–20 .50 38 25 19 10 8 6 5 3 2 100 100 50 38 35*227 10 8 4 3
025 19–25 .50 38 25 19 10 8 6 5 3 2 100 100 50 38 35*227 10 8 4 3
032 24–32 .50 38 25 19 10 8 6 5 3 2 100 100 50 38 35*227 10 8 4 3
040 28–40 .–––––––––
050 35–50 .–––––––––
063 45–63 .–––––––––
Dimensions (mm) W H D4590 66 45 90 79
Mass (g) 350 370
Optional Auxiliary contact block
accessory Alarm contact block
Auxiliary and alarm contact block
Short-circuit alarm contact block
Shunt trip device
Undervoltage trip device
External operating handle
Standard IEC 60947-1, 60947-2, 60947-4-1, UL 508, CSA C22.2 No.14, TÜV
DUO series Manual Motor Starters
02/6
Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
Quick reference guide
63AF types and ratings
Replace the
mark
in the type number
by current range
codes.
Note: * 1 Adjustable thermal-magnetic trip type only Available Not available
* 2When the breaking duty is once “0” in JEM 1195, the breaking capacity is 50kA.
Standard breaking capacity High breaking capacity
Adjustable thermal-magnetic trip type BM3VSB-
BM3VHB-
Instantaneous trip type BM3VHBK-
AF01-47 AF01-43
Number of poles 3 3
Handle type Rotary Rotary
Rated current In (A) 10 to 63
Rated operational voltage Ue (V) 200 to 690
Rated frequency (Hz) 50/60
Rated insulation voltage Ui (V) 1000
Rated impulse withstand voltage Uimp (kV) 8
Utilization IEC 60947-2 Circuit breaker Cat. A
category IEC 60947-4-1 Motor starter AC-3
Trip class IEC 60947-4-1 *110
Instantaneous trip characteristic 13 ln max.
Power loss (total of 3-pole ) 11W: In=10 to 32A 15W: In=40 to 50A 17W: In=63A
Mechanical durability (operations) 50,000
Electrical durability (operations) 25,000
Max. operations per hour (motor start-up) 25
Phase-loss protection Provided
Tripping state indication Provided
Test trip function Provided
Rated breaking Adjustable current range 240V 415V 460V 500V 690V 240V 415V 460V 500V 690V
capacity (kA) Code Ie: Min.–Max. 230V 400V 440V 600V 230V 400V 440V 600V
IEC 60947-2 (A) Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics
P16 0.1–0.16
P25 0.16–0.25
P40 0.25–0.4
P63 0.4–0.63
001 0.63–1.––––––––––
1P6 1–1.6
2P5 1.6–2.5
004 2.5–4.–––––––––
6P3 4–6.3
010 6.3–10 .100 100 100 100 15 12 10 8 4 3 100 100 100 100 50 38 50 38 6 5
013 9–13 .100 100 50 38 10 8 6 5 4 3 100 100 100 100 50 38 42 32 6 5
016 11–16 .100 100 25 19 10 8 6 5 4 3 100 100 50 38 50 38 12 9 5 4
020 14–20 .50 38 25 19 10 8 6 5 4 3 100 100 50 38 50 38 12 9 5 4
025 19–25 .50 38 25 19 10 8 6 5 4 3 100 100 50 38 35*227 12 9 5 4
032 24–32 .50 38 25 19 10 8 6 5 4 3 100 100 50 38 35*227 10 8 5 4
040 28–40 .50 38 25 19 10 8 6 5 4 3 100 100 50 38 35*227 10 8 5 4
050 35–50 .50 38 25 19 10 8 6 5 4 3 100 100 50 38 35*227 10 8 5 4
063 45–63 .50 38 25 19 10 8 6 5 4 3 100 100 50 38 35*227 10 8 5 4
Dimensions (mm) W H D55110 96
Mass (g) 780
Optional Auxiliary contact block
accessory Alarm contact block
Auxiliary and alarm contact block
Short-circuit alarm contact block
Shunt trip device
Undervoltage trip device
External operating handle
Standard IEC 60947-1, 60947-2, 60947-4-1, UL 508, CSA C22.2 No.14, TÜV
DUO series Manual Motor Starters
Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
02/7
02
Quick reference guide
32AF types and ratings, with ring terminal connection
Note: * 1 Adjustable thermal-magnetic trip type only Available Not available
* 2When the breaking duty is once “0” in JEM 1195, the breaking capacity is 50kA.
Replace the
mark
in the type number
by current range
codes.
Standard breaking capacity High breaking capacity
Adjustable thermal-magnetic trip type BM3RSR-
BM3RHR-
Instantaneous trip type BM3RHRK-
KKD05-197 KKD05-198
Number of poles 3 3
Handle type Rocker Rotary
Rated current In (A) 0.16 to 32
Rated operational voltage Ue (V) 200 to 690
Rated frequency (Hz) 50/60
Rated insulation voltage Ui (V) 690
Rated impulse withstand voltage Uimp (kV) 6
Utilization IEC 60947-2 Circuit breaker Cat. A
category IEC 60947-4-1 Motor starter AC-3
Trip class IEC 60947-4-1 *110
Instantaneous trip characteristic 13 ln max.
Power loss (total of 3-pole) 7W: In=0.16 to 25A 8.5W: In=32A
Mechanical durability (operations) 100,000: In=0.16 to 25A 70,000: In=32A
Electrical durability (operations) 100,000: In=0.16 to 25A 70,000: In=32A
Max. operations per hour (motor start-up) 25
Phase-loss protection Provided
Tripping state indication Provided
Test trip function Provided
Rated breaking Adjustable current range 240V 415V 460V 500V 690V 240V 415V 460V 500V 690V
capacity (kA) Code Ie: Min.–Max. 230V 400V 440V 600V 230V 400V 440V 600V
IEC 60947-2 (A) Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics
P16 0.1–0.16 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
P25 0.16–0.25 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
P40 0.25–0.4 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
P63 0.4–0.63 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
001 0.63–1.100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
1P6 1–1.6 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
2P5 1.6–2.5 100 100 100 100 100 100 100 100 3 2 100 100 100 100 100 100 100 100 8 6
004 2.5–4.100 100 100 100 100 100 100 100 3 2 100 100 100 100 100 100 100 100 8 6
6P3 4–6.3 100 100 100 100 50 38 50 38 3 2 100 100 100 100 100 100 100 100 6 5
010 6.3–10 .100 100 100 100 15 11 10 8 3 2 100 100 100 100 50 38 50 38 6 5
013 9–13 .100 100 50 38 10 8 6 5 3 2 100 100 100 100 50 38 42 32 6 5
016 11–16 .100 100 25 19 10 8 6 5 3 2 100 100 50 38 35*227 10 8 4 3
020 14–20 .50 38 25 19 10 8 6 5 3 2 100 100 50 38 35*227 10 8 4 3
025 19–25 .50 38 25 19 10 8 6 5 3 2 100 100 50 38 35*227 10 8 4 3
032 24–32 .50 38 25 19 10 8 6 5 3 2 100 100 50 38 35*227 10 8 4 3
040 28–40 .–––––––––
050 35–50 .–––––––––
063 45–63 .–––––––––
Dimensions (mm) W H D4590 66 45 90 79
Mass (g) 350 370
Optional Auxiliary contact block
accessory Alarm contact block
Auxiliary and alarm contact block
Short-circuit alarm contact block
Shunt trip device
Undervoltage trip device
External operating handle
Standard IEC 60947-1, 60947-2, 60947-4-1, UL 508, CSA C22.2 No.14, TÜV
DUO series Manual Motor Starters
02/8
Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
Adjustable thermal-magnetic trip types
Max. motor capacity and full-load current Rated Thermal Instantaneous Rated breaking Type
3-phase *1current *2current trip current capacity Icu (kA)
200-240V AC 380-440V AC In (A) setting range (A)
(kW) (A) (kW) (A) Ie (A) 240V AC 415V AC 440V AC
––0.02 0.1 0.16 0.1–0.16 2.1 100 100 100 BM3RSB-P16
0.03 0.24 0.06 0.21 0.25 0.16–0.25 3.3 100 100 100 BM3RSB-P25
0.06 0.37 0.1 0.34 0.4 0.25–0.4 5.2 100 100 100 BM3RSB-P40
0.06 0.37 0.12 0.41 0.63 0.4–0.63 8.2 100 100 100 BM3RSB-P63
0.1 0.68 0.2 0.65 1 0.63–1.13 100 100 100 BM3RSB-001
0.2 1.3 0.4 1.15 1.6 1–1.6 20.8 100 100 100 BM3RSB-1P6
0.4 2.3 0.75 1.8 2.5 1.6–2.5 32.5 100 100 100 BM3RSB-2P5
0.75 3.6 1.5 3.1 4 2.5–4.52 100 100 100 BM3RSB-004
1.5 6.1 2.2 4.6 6.3 4–6.3 81.9 100 100 50 BM3RSB-6P3
2.2 9.2 3.7 7.5 10 6.3–10 .130 100 100 15 BM3RSB-010
2.2 9.2 5.5 11.5 13 9–13 .169 100 50 10 BM3RSB-013
3.7 15 7.5 14.5 16 11–16 .208 100 25 10 BM3RSB-016
3.7 15 7.5 14.5 20 14–20 .260 50 25 10 BM3RSB-020
5.5 22.5 11 21 25 19–25 .325 50 25 10 BM3RSB-025
7.5 29 15 27.5 32 24–32 .416 50 25 10 BM3RSB-032
Types and ratings
32AF standard breaking capacity, rocker handle types
Adjustable thermal-magnetic trip types
Features
•A wide rated operational current range of up to 32A for the
45mm wide and 63A for the 55mm wide starters.
ON/OFF and trip indications ensure instant status
recognition.
Suitable for 3-phase motors up to 30kW at 440V AC, AC-3.
Accessories like auxiliary contact blocks, shunt trip devices,
and undervoltage trip devices have been standardized for
the 45mm and 55mm wide frame sizes of the BM3R and
BM3V.
Enclosures and external operating handles are available as
optional accessories.
Standards
IEC 60947-1, 60947-2, 60947-4-1, UL 508,
CSA C22.2 No.14, TÜV, CCC
Notes: *1Motor full-load currents are based on FUJI’s standard type totally-enclosed induction motors.
*2Max. thermal current setting value
BM3VHB
AF01-43
BM3RHB
AF01-42
BM3RSB
KK01-317
32AF high breaking capacity, rotary handle types
Max. motor capacity and full-load current Rated Thermal Instantaneous Rated breaking Type
3-phase *1current *2current trip current capacity Icu (kA)
200-240V AC 380-440V AC In (A) setting range (A)
(kW) (A) (kW) (A) Ie (A) 240V AC 415V AC 440V AC
––0.02 0.1 0.16 0.1–0.16 2.1 100 100 100 BM3RHB-P16
0.03 0.24 0.06 0.21 0.25 0.16–0.25 3.3 100 100 100 BM3RHB-P25
0.06 0.37 0.1 0.34 0.4 0.25–0.4 5.2 100 100 100 BM3RHB-P40
0.06 0.37 0.12 0.41 0.63 0.4–0.63 8.2 100 100 100 BM3RHB-P63
0.1 0.68 0.2 0.65 1 0.63–1.13 100 100 100 BM3RHB-001
0.2 1.3 0.4 1.15 1.6 1–1.6 20.8 100 100 100 BM3RHB-1P6
0.4 2.3 0.75 1.8 2.5 1.6–2.5 32.5 100 100 100 BM3RHB-2P5
0.75 3.6 1.5 3.1 4 2.5–4.52 100 100 100 BM3RHB-004
1.5 6.1 2.2 4.6 6.3 4–6.3 81.9 100 100 100 BM3RHB-6P3
2.2 9.2 3.7 7.5 10 6.3–10 .130 100 100 50 BM3RHB-010
2.2 9.2 5.5 11.5 13 9–13 .169 100 100 50 BM3RHB-013
3.7 15 7.5 14.5 16 11–16 .208 100 50 35 BM3RHB-016
3.7 15 7.5 14.5 20 14–20 .260 100 50 35 BM3RHB-020
5.5 22.5 11 21 25 19–25 .325 100 50 35 BM3RHB-025
7.5 29 15 27.5 32 24–32 .416 100 50 35 BM3RHB-032
DUO series Manual Motor Starters
Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
02/9
02
Adjustable thermal-magnetic trip types
63AF standard breaking capacity, rotary handle types
63AF high breaking capacity, rotary handle types
Notes: *1Motor full-load currents are based on FUJI’s standard type totally-enclosed induction motors.
*2Max. thermal current setting value
BM3VHB - 063 (CCC)
Basic type
Frame size Rated current
Operating characteristic
R: 32AF 45mm wide
V: 63AF 55mm wide B: Adjustable thermal-magnetic trip
BK: Instantaneous trip
R: Adjustable thermal-magnetic trip, ring terminal
RK: Instantaneous trip, ring terminal
Breaking capacity
S: Standard breaking capacity
H: High breaking capacity
Ordering information
Specify the following:
1. Type number
2. Accessories if required
Type number nomenclature
CCC approved
Max. motor capacity and full-load current Rated Thermal Instantaneous Rated breaking Type
3-phase *1current *2current trip current capacity Icu (kA)
200-240V AC 380-440V AC In (A) setting range (A)
(kW) (A) (kW) (A) Ie (A) 240V AC 415V AC 440V AC
2.2 9.2 3.7 7.5 10 6.3–10 130 100 100 15 BM3VSB-010
2.2 9.2 5.5 11.5 13 9–13 169 100 50 10 BM3VSB-013
3.7 15 7.5 14.5 16 11–16 208 100 25 10 BM3VSB-016
3.7 15 7.5 14.5 20 14–20 260 50 25 10 BM3VSB-020
5.5 22.5 11 21 25 19–25 325 50 25 10 BM3VSB-025
7.5 29 15 27.5 32 24–32 416 50 25 10 BM3VSB-032
7.5 29 18.5 34 40 28–40 520 50 25 10 BM3VSB-040
11 42 22 39 50 35–50 650 50 25 10 BM3VSB-050
15 55 30 54 63 45–63 819 50 25 10 BM3VSB-063
Max. motor capacity and full-load current Rated Thermal Instantaneous Rated breaking Type
3-phase *1current *2current trip current capacity Icu (kA)
200-240V AC 380-440V AC In (A) setting range (A)
(kW) (A) (kW) (A) Ie (A) 240V AC 415V AC 440V AC
2.2 9.2 3.7 7.5 10 6.3–10 130 100 100 50 BM3VHB-010
2.2 9.2 5.5 11.5 13 9–13 169 100 100 50 BM3VHB-013
3.7 15 7.5 14.5 16 11–16 208 100 50 50 BM3VHB-016
3.7 15 7.5 14.5 20 14–20 260 100 50 50 BM3VHB-020
5.5 22.5 11 21 25 19–25 325 100 50 35 BM3VHB-025
7.5 29 15 27.5 32 24–32 416 100 50 35 BM3VHB-032
7.5 29 18.5 34 40 28–40 520 100 50 35 BM3VHB-040
11 42 22 39 50 35–50 650 100 50 35 BM3VHB-050
15 55 30 54 63 45–63 819 100 50 35 BM3VHB-063
DUO series Manual Motor Starters
02/10
Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
Instantaneous trip types
Max. motor capacity and full-load current Rated current Instantaneous trip Rated breaking Type
3-phase * In (A) current (A) capacity Icu (kA)
200-240V AC 380-440V AC
(kW) (A) (kW) (A) 240V AC 415V AC 440V AC
2.2 9.2 3.7 7.5 10 130 100 100 50 BM3VHBK-010
2.2 9.2 5.5 11.5 13 169 100 100 50 BM3VHBK-013
3.7 15 7.5 14.5 16 208 100 50 50 BM3VHBK-016
3.7 15 7.5 14.5 20 260 100 50 50 BM3VHBK-020
5.5 22.5 11 21 25 325 100 50 35 BM3VHBK-025
7.5 29 15 27.5 32 416 100 50 35 BM3VHBK-032
7.5 29 18.5 34 40 520 100 50 35 BM3VHBK-040
11 42 22 39 50 650 100 50 35 BM3VHBK-050
15 55 30 54 63 819 100 50 35 BM3VHBK-063
Notes: *1Motor full-load currents are based on FUJI’s standard type totally-enclosed induction motors.
Select appropriate thermal overload relay for starter.
Instantaneous trip types
Features
Instantaneous trip type for short-circuit or overcurrent
protection of three-phase motors up to 63A (240V AC, 15kW,
or 440V AC, 30kW).
No overload protection function. Allows motor circuit
protection in combination with appropriate thermal overload
relay depending on the thermal characteristics of the motor
winding and the start-up time of the motor.
•Two modules, 45mm or 55mm wide, cover current ratings
from 0.1 to 63A.
RHBK: 45mm wide, rated current of 0.1 to 32A
VHBK: 55mm wide, rated current of 6.3 to 63A
Rotary handle
•Versatile accessories
Internal and external auxiliary contact blocks, alarm contact block
Short-circuit alarm contact block
Shunt trip device
Undervoltage trip device
BM3VHBKBM3RHBK
63AF high breaking capacity, rotary handle type
Standards
IEC 60947-1, 60947-2, 60947-4-1, UL 508
CSA C22.2 No.14, TÜV, CCC
Types and ratings
32AF high breaking capacity, rotary handle type
AF01-46 AF01-45
Max. motor capacity and full-load current Rated current Instantaneous trip Rated breaking Type
3-phase * In (A) current (A) capacity Icu (kA)
200-240V AC 380-440V AC
(kW) (A) (kW) (A) 240V AC 415V AC 440V AC
–– 0.02 0.1 0.16 2.1 100 100 100 BM3RHBK-P16
0.03 0.24 0.06 0.21 0.25 3.3 100 100 100 BM3RHBK-P25
0.06 0.37 0.1 0.34 0.4 5.2 100 100 100 BM3RHBK-P40
0.06 0.37 0.12 0.41 0.63 8.2 100 100 100 BM3RHBK-P63
0.1 0.68 0.2 0.65 1 13 100 100 100 BM3RHBK-001
0.2 1.3 0.4 1.15 1.6 20.8 100 100 100 BM3RHBK-1P6
0.4 2.3 0.75 1.8 2.5 32.5 100 100 100 BM3RHBK-2P5
0.75 3.6 1.5 3.1 4 52 100 100 100 BM3RHBK-004
1.5 6.1 2.2 4.6 6.3 81.9 100 100 100 BM3RHBK-6P3
2.2 9.2 3.7 7.5 10 130 100 100 50 BM3RHBK-010
2.2 9.2 5.5 11.5 13 169 100 100 50 BM3RHBK-013
3.7 15 7.5 14.5 16 208 100 50 35 BM3RHBK-016
3.7 15 7.5 14.5 20 260 100 50 35 BM3RHBK-020
5.5 22.5 11 21 25 325 100 50 35 BM3RHBK-025
7.5 29 15 27.5 32 416 100 50 35 BM3RHBK-032
Notes: *Motor full-load currents are based on FUJI’s standard type totally-enclosed induction motors.
Select appropriate thermal overload relay for starter.
DUO series Manual Motor Starters
Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
02/11
02
Ring terminal connection types
Adjustable thermal-magnetic trip types
Max. motor capacity and full-load current Rated Thermal Instantaneous Rated breaking Type
3-phase *1current *2current trip current capacity Icu (kA)
200-240V AC 380-440V AC In (A) setting range (A)
(kW) (A) (kW) (A) Ie (A) 240V AC 415V AC 440V AC
––0.02 0.1 0.16 0.1–0.16 2.1 100 100 100 BM3RSR-P16
0.03 0.24 0.06 0.21 0.25 0.16–0.25 3.3 100 100 100 BM3RSR-P25
0.06 0.37 0.1 0.34 0.4 0.25–0.4 5.2 100 100 100 BM3RSR-P40
0.06 0.37 0.12 0.41 0.63 0.4–0.63 8.2 100 100 100 BM3RSR-P63
0.1 0.68 0.2 0.65 1 0.63–1.13 100 100 100 BM3RSR-001
0.2 1.3 0.4 1.15 1.6 1–1.6 20.8 100 100 100 BM3RSR-1P6
0.4 2.3 0.75 1.8 2.5 1.6–2.5 32.5 100 100 100 BM3RSR-2P5
0.75 3.6 1.5 3.1 4 2.5–4.52 100 100 100 BM3RSR-004
1.5 6.1 2.2 4.6 6.3 4–6.3 81.9 100 100 50 BM3RSR-6P3
2.2 9.2 3.7 7.5 10 6.3–10 .130 100 100 15 BM3RSR-010
2.2 9.2 5.5 11.5 13 9–13 .169 100 50 10 BM3RSR-013
3.7 15 7.5 14.5 16 11–16 .208 100 25 10 BM3RSR-016
3.7 15 7.5 15 20 14–20 .260 50 25 10 BM3RSR-020
5.5 22.5 11 21 25 19–25 .325 50 25 10 BM3RSR-025
7.5 29 15 27.5 32 24–32 .416 50 25 10 BM3RSR-032
Types and ratings
32AF standard breaking capacity, rocker handle types
Ring terminal connection types
Adjustable thermal-magnetic trip types
Features
•Similar to FUJI MCCBs, the new type allows easy mounting
and removal of the terminal cover, and up to two ring crimp
terminals can be connected from the upper terminal part.
Straight wiring connection is also possible in addition to ring
terminal connection.
The BM3RSR (0.16 to 32A rocker handle types) and
BM3RHR (0.16 to 32A rotary handle types) are available.
All optional accessories for standard manual motor starters
can be mounted.
The series conforms to IEC, UL and JIS standards, as do the
standard manual motor starters.
•Crimp terminal insulation and a long terminal cover
conforming to UL508 type E and F standards are available.
(Purchased separately.)
Notes: *1Motor full-load currents are based on FUJI’s standard type totally-enclosed induction motors.
*2Max. thermal current setting value
BM3RSR
KK04-055
32AF high breaking capacity, rotary handle types
Max. motor capacity and full-load current Rated Thermal Instantaneous Rated breaking Type
3-phase *1current *2current trip current capacity Icu (kA)
200-240V AC 380-440V AC In (A) setting range (A)
(kW) (A) (kW) (A) Ie (A) 240V AC 415V AC 440V AC
––0.02 0.1 0.16 0.1–0.16 2.1 100 100 100 BM3RHR-P16
0.03 0.24 0.06 0.21 0.25 0.16–0.25 3.3 100 100 100 BM3RHR-P25
0.06 0.37 0.1 0.34 0.4 0.25–0.4 5.2 100 100 100 BM3RHR-P40
0.06 0.37 0.12 0.41 0.63 0.4–0.63 8.2 100 100 100 BM3RHR-P63
0.1 0.68 0.2 0.65 1 0.63–1.13 100 100 100 BM3RHR-001
0.2 1.3 0.4 1.15 1.6 1–1.6 20.8 100 100 100 BM3RHR-1P6
0.4 2.3 0.75 1.8 2.5 1.6–2.5 32.5 100 100 100 BM3RHR-2P5
0.75 3.6 1.5 3.1 4 2.5–4.52 100 100 100 BM3RHR-004
1.5 6.1 2.2 4.6 6.3 4–6.3 81.9 100 100 100 BM3RHR-6P3
2.2 9.2 3.7 7.5 10 6.3–10 .130 100 100 50 BM3RHR-010
2.2 9.2 5.5 11.5 13 9–13 .169 100 100 50 BM3RHR-013
3.7 15 7.5 14.5 16 11–16 .208 100 50 35 BM3RHR-016
3.7 15 7.5 14.5 20 14–20 .260 100 50 35 BM3RHR-020
5.5 22.5 11 21 25 19–25 .325 100 50 35 BM3RHR-025
7.5 29 15 27.5 32 24–32 .416 100 50 35 BM3RHR-032
Notes: *1Motor full-load currents are based on FUJI’s standard type totally-enclosed induction motors.
*2Max. thermal current setting value
DUO series Manual Motor Starters
02/12
Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
Ring terminal connection types
Instantaneous trip types
32AF high breaking capacity, rotary handle type
Max. motor capacity and full-load current Rated current *2Instantaneous trip Rated breaking Type
3-phase *1In (A) current (A) capacity Icu (kA)
200-240V AC 380-440V AC
(kW) (A) (kW) (A) 240V AC 415V AC 440V AC
–– 0.02 0.1 0.16 2.1 100 100 100 BM3RHRK-P16
0.03 0.24 0.06 0.21 0.25 3.3 100 100 100 BM3RHRK-P25
0.06 0.37 0.1 0.34 0.4 5.2 100 100 100 BM3RHRK-P40
0.06 0.37 0.12 0.41 0.63 8.2 100 100 100 BM3RHRK-P63
0.1 0.68 0.2 0.65 1 13 100 100 100 BM3RHRK-001
0.2 1.3 0.4 1.15 1.6 20.8 100 100 100 BM3RHRK-1P6
0.4 2.3 0.75 1.8 2.5 32.5 100 100 100 BM3RHRK-2P5
0.75 3.6 1.5 3.1 4 52 100 100 100 BM3RHRK-004
1.5 6.1 2.2 4.6 6.3 81.9 100 100 100 BM3RHRK-6P3
2.2 9.2 3.7 7.5 10 130 100 100 50 BM3RHRK-010
2.2 9.2 5.5 11.5 13 169 100 100 50 BM3RHRK-013
3.7 15 7.5 14.5 16 208 100 50 35 BM3RHRK-016
3.7 15 7.5 14.5 20 260 100 50 35 BM3RHRK-020
5.5 22.5 11 21 25 325 100 50 35 BM3RHRK-025
7.5 29 15 27.5 32 416 100 50 35 BM3RHRK-032
Notes: *1Motor full-load currents are based on FUJI’s standard type totally-enclosed induction motors.
*2Max. thermal current setting value
Wirings
Wire size Ring crimp terminal Terminal screw Tightening torque
(mm2)max. width (mm) (N·m)
Line side 1 to 8 11 (R1.25-4 to R8-4) M4 2
Load side 1 to 8 11 (R1.25-4 to R8-4) M4 2