Product data sheet
Characteristics
TVS1HWA10X
Surge protection device, Surgelogic, HWA,
100kA, 120/240 VAC, 1 phase, 3 wire, NEMA 4X
Main
Product Surge protection device
Range Surgelogic
Device Short Name HWA
Complementary
Surge Current 100kA per phase
Voltage Rating 120/240 V AC
Number of Phases 1 phase
Wiring Configuration 3-wire
Connection Wire phase and neutral AWG 10 copper
Wire ground AWG 10 copper
Wire dry contacts AWG 22 copper
MCOV 150V
Nominal Discharge Current 20kA
Max Number of Poles 1
SCCR 200kA
Local Signalling Status LED green per phase normal operation
Status LED red per phase fault
Alarm fault
Mounting Location Back of enclosure
Device Mounting Surface
Flush fixing kit
Height 4.80in (122mm)
Width 8.62in (219mm)
Depth 3.11in (79mm)
Cable length 33.6in (853.44mm)
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
8-Nov-2020