https://www.phoenixcontact.com/us/produkte/2859699
05.12.2012Page2/5
Type 2 surge protection connector-VAL-CP-N/PE-350-
ST-2859699
Technical data
Standards
Direction of action N-PE
Protective circuit
IEC category II
IEC category T2
EN type T2
Nominal voltage UN240 V AC
Arrester rated voltage UC264 V AC
Arrester rated voltage UC (N-PE) 264 V AC
UT (TOV-proof) 1200 V AC (200 ms / N-PE)
Nominal frequency fN50 Hz
Nominal frequency fN60 Hz
Ground conductor current IPE ≤ 1 µA
Standby power consumption PC≤ 0.26 mVA
Max. discharge surge current Imax (8/20) µs 40 kA
Max. discharge surge current Imax (8/20) µs maximum (N-PE) 40 kA
Nominal discharge surge current In (8/20) µs 20 kA
Nominal discharge surge current In (8/20) µs (N-PE) 20 kA
Impulse operate voltage at 6 kV (1.2/50)µs ≤ 1.5 kV
Impulse operate voltage at 6 kV (1.2/50)µs (N-PE) ≤ 1.5 kV
Protection level Up≤ 1.5 kV
Protection level UP (N-PE) ≤ 1.5 kV
Residual voltage ≤ 0.5 kV (at In)
Residual voltage ≤ 0.3 kV (at 10 kA)
Residual voltage ≤ 0.25 kV (at 5 kA)
Residual voltage ≤ 0.2 kV (at 3 kA)
Clamping voltage ringwave ≤ 1.5 kV (category C3 20 kV/10 kA)
Clamping voltage ringwave ≤ 1.3 kV (category C2 10 kV/5 kA)
Clamping voltage ringwave ≤ 1.2 kV (category B3/C1 6 kV/3 kA)
Response time ≤ 100 ns
Response time (N-PE) ≤ 100 ns
Short-circuit resistance IP with max. backup fuse (effective) 25 kA
Follow current quenching capacity If 100 A
Connection, protective circuit
Connection type IN FLASHTRAB/VALVETRAB plug-in system
Connection type OUT FLASHTRAB/VALVETRAB plug-in system
Standards
Standards/regulations IEC 61643-1 2005
Standards/regulations DIN EN 61643-11 2002
Standards/regulations DIN EN 61643-11/A11 2007