PRODUCT-DETAILS CM-PAS.31P CM-PAS.31P Three-phase monitoring relay 2c/o, 0,0.1-30s, L1-L2-L3=3x160-300VAC General Information Extended Product Type Product ID EAN Catalog Description Long Description CM-PAS.31P 1SVR740774R1300 4016779851978 CM-PAS.31P Three-phase monitoring relay 2c/o, 0,0.1-30s, L1-L2-L3=3x160-300VAC The CM-PAS.31P relay is from the CM three-phase monitors range. This relay operates with a rated control supply voltage / three-phase measuring voltage of 160-300 V AC and has a 2 c/o output with contacts rated at 250 V / 4 A. The CM-PAS.31P monitors the phase parameters phase failure, phase sequence and phase unbalance. An ONdelay is adjustable over a range of instantaneous to 30 s (0, 0.1-30 s). A sealable transparent cover for protection against unauthorized changes is available as accessory. The device offers maintenance free Easy Connect Technology with push-in terminals. Ordering Minimum Order Quantity Customs Tariff Number 1 piece 85364900 Popular Downloads Data Sheet, Technical Information Instructions and Manuals 2CDC112180D0201 1SVC730510M0000 CM-PAS.31P 2 Dimensions Product Net Width 22.5 mm Product Net Depth / Length 103.7 mm Product Net Height 85.6 mm Product Net Weight 0.124 kg Technical Function Standards Phase failure detection Phase sequence monitoring Phase unbalance detection CAN/CSA C22.2 No.14 EN 50581 IEC/EN 60255-27 IEC/EN 61000-6-2 IEC/EN 61000-6-3 UL 508 Measuring Range (L-L) 160 ... 300 V AC Rated Control Supply Voltage (U s ) (L-L) 160 ... 300 V AC Rated Frequency (f) Output Time Range Terminal Type Supply Circuit 50/60 Hz 2 c/o (SPDT) contacts 200 ms start-up delay 0 s or 0.1 ... 30 s tripping delay (ON) Screwless Terminals Rated Operational Current AC-12 (I e ) (230 V) 4 A Rated Operational Current AC-15 (I e ) (230 V) 3 A Rated Operational Current DC-12 (I e ) (24 V) 4 A Rated Operational Current DC-13 (I e ) (24 V) 2 A Minimum Switching Capacity 24 V 10 mA Rated Insulation Voltage (U i ) Input Circuit / Output Circuit 600 V Output Circuit 1 / Output Circuit 2 300 V Rated Impulse Withstand Voltage (U imp ) Input Circuit 6 kV Output Circuit 4 kV Degree of Protection Overvoltage Category Pollution Degree Short-Circuit Protective Devices Electrical Durability Housing IP50 Terminals IP20 III 3 Output Circuit NC - F Type Fuses 6 A Output Circuit NO - F Type Fuses 10 A AC-12 100000 cycle Mechanical Durability 30000000 cycle Connecting Capacity Flexible with Ferrule 2x 0.5 ... 1.5 mm Flexible with Insulated Ferrule 2x 0.5 ... 1.5 mm Flexible 2x 0.5 ... 1.5 mm Rigid 2x 0.5 ... 1.5 mm Wire Stripping Length Mounting Position Mounting on DIN Rail 8 mm Any TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 Environmental Ambient Air Operation -20 ... +50 C CM-PAS.31P 3 Temperature Storage -40 ... +85 C RoHS Status Following EU Directive 2011/65/EU Technical UL/CSA Maximum Operating Voltage UL/CSA Contact Rating UL/CSA Connecting Capacity UL/CSA Output Circuit 300 V AC B300 Flexible 2x 18-16 AWG Rigid 2x 20-16 AWG Certificates and Declarations (Document Number) CCC Certificate cULus Certificate Declaration of Conformity - CE DNV GL Certificate EAC Certificate Environmental Information CCC_2009010303326655 cULus508_20120829-E140448 1SVD981014-0002 DNV_GL_TAA000017D EAC_RU_C-DE.ME77.B.03424 1SAA981020-2401 Instructions and Manuals 1SVC730510M0000 RMRS Certificate RMRS_1740020250 RoHS Information 1SVD981014-0002 Container Information Package Level 1 Units 1 piece Package Level 1 Width 97 mm Package Level 1 Height 109 mm Package Level 1 Depth / Length 30 mm Package Level 1 Gross Weight Package Level 1 EAN 0.149 kg 4016779851978 Classifications Object Classification Code B ETIM 4 EC001441 - Phase monitoring relay ETIM 5 EC001441 - Phase monitoring relay ETIM 6 EC001441 - Phase monitoring relay ETIM 7 EC001441 - Phase monitoring relay eClass 7.0 27371803 UNSPSC 39121536 E-Number (Sweden) 3860598 Categories CM-PAS.31P Low Voltage Products and Systems Control Products Electronic Relays and Controls Three Phase Monitors 4