CP1L
7
Performance Specifications
●CP1L CPU Unit (EM/EL Type)
Type CP1L-EM40 (40 points) CP1L-EM30 (30 points) CP1L-EL20 (20 points)
Item Models CP1L-EM40D@-@CP1L-EM30D@-@CP1L-EL20D@-@
Control method Stored program method
I/O control method Cyclic scan with immediate refreshing
Program language Ladder diagram
Function blocks Maximum number of function block definitions: 128 Maximum number of instances: 256
Languages usable in function block definitions: Ladder diagrams, structured text (ST)
Instruction length 1 to 7 steps per instruction
Instructions Approx. 500 (function codes: 3 digits)
Instruction execution time Basic instructions: 0.55 μs min. Special instructions: 4.1 μs min.
Common processing time 0.4ms
Program capacity 10K steps 5K steps
FB program memory 10K steps
Number of tasks 288 (32 cyclic tasks and 256 interrupt tasks)
Scheduled interrupt tasks 1 (interrupt task No. 2, fixed)
Input interrupt tasks 6 (interrupt task No. 140 to 145, fixed)
(High-speed counter interrupts and interrupt tasks specified by external interrupts can also be executed.)
Maximum subroutine number 256
Maximum jump number 256
I/O areas
Input Area 1,600 bits (100 words) CIO 0 to CIO 99
Built-in Input Area 24 bits: CIO 0.00 to CIO 0.11 and
CIO 1.00 to CIO 1.11
18 bits: CIO 0.00 to CIO 0.11 and
CIO 1.00 to CIO 1.05 12 bits: CIO 0.00 to CIO 0.11
Output Area 1,600 bits (100 words) CIO 100 to CIO 199
Built-in Output
Area
16 bits: CIO 100.00 to CIO 100.07
and CIO 101.00 to CIO 101.07
12 bits: CIO 100.00 to CIO 100.07
and CIO 101.00 to CIO 101.03 8 bits: CIO 100.00 to CIO 100.07
1:1 Link Area 256 bits (16 words): CIO 3000.00 to CIO 3015.15 (CIO 3000 to CIO 3015)
Serial PLC Link Area 1,440 bits (90 words): CIO 3100.00 to CIO 3189.15 (CIO 3100 to CIO 3189)
Work bits
4,800 bits (300 words): CIO 1200.00 to CIO 1499.15 (words CIO 1200 to CIO 1499)
6,400 bits (400 words): CIO 1500.00 to CIO 1899.15 (words CIO 1500 to CIO 1899)
15,360 bits (960 words): CIO 2000.00 to CIO 2959.15 (words CIO 2000 to CIO 2959)
9,600 bits (600 words): CIO 3200.00 to CIO 3799.15 (words CIO 3200 to CIO 3799)
37,504 bits (2,344 words): CIO 3800.00 to CIO 6143.15 (words CIO 3800 to CIO 6143)
TR Area 16 bits: TR0 to TR15
Holding Area 8,192 bits (512 words): H0.00 to H511.15 (H0 to H511)
AR Area Read-only (Write-prohibited): 7168 bits (448 words): A0.00 to A447.15 (A0 to A447)
Read/Write: 8192 bits (512 words): A448.00 to A959.15 (A448 to A959)
Timers 4,096 timer numbers: T0 to T4095
Counters 4,096 counter numbers: C0 to C4095
DM Area 32 Kwords: D0 to D32767 10 Kwords: D0 to D9999, D32000
to D32767
Data Register Area 16 registers (16 bits): DR0 to DR15
Index Register Area 16 registers (32 bits): IR0 to IR15
Task Flag Area 32 flags (32 bits): TK0000 to TK0031
Trace Memory 4,000 words (500 samples for the trace data maximum of 31 bits and 6 words.)
Memory Cassette A special Memory Cassette (CP1W-ME05M) can be mounted.
Note: Can be used for program backups and auto-booting.
Clock function Supported. Accuracy (monthly deviation): -4.5 min to -0.5 min (ambient temperature: 55°C),
-2.0 min to +2.0 min (ambient temperature: 25°C), -2.5 min to +1.5 min (ambient temperature: 0°C)
Communications functions
Built-in Ethernet Port (Connecting Support Software, Message Communications, Socket Service)
A maximum of two Serial Communications Option Boards can be
mounted.
A maximum of one Serial
Communications Option Board can
be mounted.
Memory backup
Flash memory: User programs, parameters (such as the PLC Setup), comment data, and the entire DM Area
can be saved to flash memory as initial values.
Battery backup: The Holding Area, DM Area, and counter values (flags, PV) are backed up by a battery.
Battery service life Service life expectancy is 5 years at 25°C, less at higher temperatures. (From 0.75 to 5 years depending on
model, power supply rate, and ambient temperature.)
Built-in input terminals 40 (24 inputs, 16 outputs) 30 (18 inputs, 12 outputs) 20 (12 inputs, 8 outputs)
Number of connectable Expansion Units and
Expansion I/O Units CP-series Expansion Unit and Expansion I/O Units: 3 max. CP-series Expansion Units and
Expansion I/O Units: 1 max.
Max. number of I/O points 160 (40 built in + 40 per Expansion
(I/O) Unit x 3 Units)
150 (30 built in + 40 per Expansion
(I/O) Unit x 3 Units)
60 (20 built in + 40 per Expansion
(I/O) Unit x 1 Unit)
Interrupt inputs 6 inputs (Response time: 0.3 ms)
Interrupt inputs counter mode 6 inputs (Response frequency: 5 kHz max. for all interrupt inputs), 16 bits Up or down counters
Quick-response inputs 6 points (Min. input pulse width: 50 μs max.)
Scheduled interrupts 1
High-speed counters
4 inputs/2 axes (24 VDC)
Differential phases (4x), 50 kHz
Single-phase (pulse plus direction, up/down, increment), 100 kHz
Value range: 32 bits, Linear mode or ring mode
Interrupts: Target value comparison or range comparison