Surge Protective Devices
OVRT23N40320PTSU
Product data sheet
Electrical Characteristics
Protection mode LL-LN-LG-NG
Number of poles / Type of current 4 / AC
Type / Test class UL 1449 3rd Ed. - Type 4 for Type 2 apps
IEC 61 643-1 2nd Ed. - T2 / II
Nominal voltage (Un) (L-N / L-L) [V] 277 +/- 15% ; 480 +/- 15%
Frequency [Hz] 50-60
Maximum continuous operating voltage (Uc) (L-N / L-L) [V] 320 / 640
Voltage protection level (Ures) 3 kA (L-N / N-G / L-G) [kV] 1.0/0.4/1.0
Voltage protection level (Ures) 5 kA (L-N / N-G / L-G) [kV] 1.1/0.6/1.1
Voltage protection level (Ures) 10 kA (L-N / N-G / L-G) [kV] 1.2/0.7/1.2
Voltage protection rating (VPR - UL 3rd Ed.)
(L-N / N-G / L-G) [kV] 1.0/1.2/1.1
Nominal discharge current (In @ 8/20) [kA] 20
Maximum discharge current (Imax @ 8/20) [kA] 40
Follow current interrupt rating (Ifi) (L-N / N-G) [A] None / 100
Response time [ns] < 25
Operating current (Ic) [mA] < 0.1
Short circuit withstand current (Isccr) [kA] 200
Integrated thermal disconnector Yes
State indicator Yes
Safety reserve No
Remote indicator Yes
Disconnector Circuit breaker B or C curve [A] ≤ 125
Disconnector J class fuse [A] ≤ 100
Mechanical Characteristics
Wire range - Solid wire [AWG] 4-14
Wire range - Stranded wire [AWG] 6-14
Stripping length [In] 0.5
Tightening torque [in-lbs] 24.5
Degree of protection NEMA 1
Remote indicator
Type of contact 1 NO / 1 NC
Minimum load 12 VDC / 10 mA
Maximum load 250 VAC / 1 A
Connection cross section [AWG] 16
Miscellaneous Characteristics
Operating temperature / Storing temperature [°C] -40 to +80 / -40 to +80
Maximum altitude [M/ft] 2000 / 6562
Weight [g/lb] 120/0.25
Color of housing / Fire resistance according to UL94 Gray RAL 7035 / V0
Reference standards UL1449 3rd Ed; IEC 61 643-1; cURus
Replacement Cartridges
Phase OVRT240-320CU
Neutral OVRT270-NCU