A-414
ZWS
(*1) Operating period at peak output current is less than 10 sec.
(Average output power and current is less than maximum output
power and current)
(*2) At 100/200VAC, Ta=25℃ and maximum output power.
(*3) For cases where conformance to various safety specs (UL, CSA,
EN) are required, to be described as 100-240VAC (50/60Hz).
(*4) Not applicable for the in-rush current to noise filter for less than
0.2ms.
(*5) Please refer to Fig. A for measurement of line & load regulation
and ripple voltage.
(Measure with JEITA RC-9131 probe.)
(*6) 85 - 265VAC, constant load.
(*7) No load-maximum load, constant input voltage.
(*8) Constant current limit with automatic recovery.
Not operate at overload or dead short condition for more than 30
seconds.
(*9) OVP circuit will shut down output, manual reset. (Line recycle)
(*10) At 100/200VAC nominal output voltage and maximum output cur-
rent.
(*11) Measured by the each measuring method of UL, CSA, EN and
DENAN (at 60Hz).
(*12) At standard mounting.
- Load (%) is percent of maximum output power or maximum
output current, whichever is greater.
- For other mountings, refer to derating curve.
- When forced air cooling, refer to derating curve.
(*13) As for DENAN, built to meet at 100VAC.
ZWS50AF
ITEMS/UNITSMODEL ZWS50AF-3 ZWS50AF-5 ZWS50AF-12 ZWS50AF-15 ZWS50AF-24
Input
Voltage Range (*3) V AC85 - 265 or DC120 - 370
Frequency (*3) Hz 47-63
Power Factor (100/200VAC)(typ) (*2)
0.99 / 0.95
Efficiency (typ) (*2) %67 75 78 79 81
Current (100/200VAC)(typ) (*2) A 0.6 / 0.3 0.8 / 0.4
Inrush Current (100/200VAC)(typ) (*4)
A 14 / 28 at Ta=25℃, cold start
Leakage Current (*11) mA 0.5 MAX, 0.1 (typ) at 100VAC / 0.16 (typ) at 230VAC
Output
Nominal Voltage V 3.3 5 12 15 24
Maximum Current A 10 10 4.3 3.5 2.1
Maximum Peak Current (*1) A -5.2 4.2 2.6
Maximum Power W 33 50 51.6 52.5 50.4
Maximum Peak Power (*1) W -62.4 63 62.4
Maximum Line Regulation (*5)(*6) mV 20 20 48 60 96
Maximum Load Regulation (*5)(*7) mV 40 40 96 120 150
Temperature Coefficient Less than 0.02%/℃
Maximum Ripple & Noise (0<Ta<60℃) (*5)
mVp-p
120 120 150
Maximum Ripple & Noise (-10<Ta<0℃) (*5)
mVp-p
160 160 180
Hold-up Time (typ) (*10) ms 20
Voltage Adjustable Range VDC 2.97 - 3.63 4.5 - 5.5 10.8 - 13.2 13.5 - 16.5 21.6 - 26.4
Function
Over Current Protection (*8) A >10.5 >10.5 >5.4 >4.4 >2.7
Over Voltage Protection (*9) VDC 3.79 - 4.95 5.75 - 7.00 13.8 - 16.2 17.3 - 20.3 27.6 - 32.4
Remote ON/OFF Control Possible
Parallel Operation -
Series Operation Possible
Environment
Operating Temperature (*12) ℃-10 to 60
Convection : -10 to 50: 100%, +60: 70%
Storage Temperature ℃-30 to +85
Operating Humidity %RH 30 - 90 (No dewdrop)
Storage Humidity %RH 10 - 95 (No dewdrop)
Vibration At no operating, 10-55Hz (sweep for 1min)
19.6m/s² constant, X, Y, Z 1hour each.
Shock (In package) Less than 196.1m/s²
Cooling Convection cooling
Isolation Withstand Voltage Input - FG : 2kVAC (20mA), Input - Output : 3kVAC (20mA)
Output - FG : 500VAC (100mA) for 1min
Isolation Resistance More than 100MΩ at 25℃ and 70%RH Output - FG : 500VDC
Standards
Safety Standards (*13) Approved by UL60950-1, CSA C22.2 No.60950-1, EN60950-1, EN50178. Built to meet DENAN.
PFHC Built to meet EN61000-3-2
EMI Built to meet EN55011/EN55022-B, FCC-ClassB, VCCI-B.
Immunity Built to meet EN61000-4-2, -3, -4, -5, -6 , -8, -11
Mechanical
Weight (typ) g 210
Size (W x H x D) mm 55 x 26 x 195 ( Refer to outline drawing )
●
Recommended EMC Filter
RSEL-2002W
Please refer to "TDK-Lambda
EMC Filters" catalog.
ZWS50AF Specifications
ZWS50AF
・All specifications are subject to change without notice.
CN51
Measurement point for
Vo,Line/Load Regulation. Measurement point
for Vripple
L:150mmAWG#18
C1:Elec.Cap 100uF
C2:Film Cap 0.1uF
Bandwidth of scope:100MHz
L
C1 C2
+V
-V
Fig.A