Carling Technologies, Inc.
60 Johnson Avenue, Plainville, CT 06062
Email: sales@carlingtech.com
Application Support: team2@carlingtech.com
Phone: 860.793.9281 Fax: 860.793.9231
www.carlingtech.com
N-Series
N-Series
CIRCUIT BREAKER
Carling Technologies’ high-performance N-Series hydraulic-magnetic circuit breaker is ideally suited for the rigors
and conned spaces of telecom and datacom power distribution units and rack systems. Its innovative, low prole
design features easily accessible load and line terminals and sliding barriers for effortless installation.
With the integration of an optional current transformer, the N-Series is capable of sensing current down to a level
of 1%. This optional capability provides precise current monitoring and reporting required for back billing of the
actual power consumed by datacenter storage and routing devices. This feature also facilitates load adjustments and
maximizes efciency.
A patent pending, ush-rocker actuator and push-to-reset guard offer additional protection against accidental switching.
1-2 poles; ratings: 1-30 amps up to 240 VAC, 277 VAC, 120/240 VAC; 22,000 Amps Max Interrupting Capacity; UL
489 Compliant Sliding Terminal Barriers; EN60947-2 Certied
Product Highlights:
240 VAC, 277 VAC, 120/240 VAC
UL 489 Compliant Sliding Terminal Barriers
22,000 Amps Max Interrupting Capacity
1 – 30 Amps Current Rating
Optional Current Transformer
EN60947-2 Certied
Typical Applications:
Telecom/Datacom
- PDU’s
- Data Servers
- Data Storage
IGS
Resources:
Download 3D CAD Files
IGS STP
Watch Product Video
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
2 |N-Series Circuit Breaker - Design Features
TERMINAL
Allows for easy hook-up of wires
on both sides of the breaker
LOAD “ LINE “
CURRENT TRANSFORMER
Remote current sensing via
molex connector
UPPER ARC RUNNER
Optional, for 277 VAC
rated breakers
GRIDS (5x)
Arc deionizing splitter plates that
increase arc voltage for quick
interrupt
LOWER ARC RUNNER
Motivates arc o of the
stationary contact
SLIDING TERMINAL BARRIERS
N-Series
DESIGN FEATURES
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
| 3
N-Series Circuit Breaker - General Specications
Electrical
Current Metering Integrated current transformer.
Measurement range: 1-30 Amps.
Voltage output: 10mV per Amp
according to the formula below:
2(Amp)≤I≤30(Amp)
V = 0.01× I ± 2%
(with current metering codes 1 or 2)
V = 0.01× I ±1%
(with current metering codes 3 or 4)
%85.0
10
10
10
10
I
V
I
V
I
V
Where V=CT output in volts
V10=CT output in volts with
I=I10=10 (A); I=primary current in
amperage (50/60 Hz). Phase shift
between primary current and CT
output is 0.25±0.25°. Maximum
crest factor of primary current is 1.73.
R1 shall be integrated in the breaker.
R2 and R3 are provided by end user
and external to the breaker.
Connection: below Load Terminal.
2-pin connector, Molex 35362-0250.
Mating Connector housing – Molex
PN35507-0200.
(Current metering is available on AC
rated devices only)
I ~
(FROM 1 - 30 AMPS)
R3=14Ω±Y%
V=0.01 X (I)
V
R2=14Ω±Y%
R1=28Ω±Y%
I : 1400 CT
Note: Whencurrentmeteringcodeis1or2;Ytoequal1.0
Whencurrentmeteringcodeis3or4;Ytoequal0.1
Dielectric Strength UL, CSA-1960V 50/60 Hz for one
minute between all electrically
isolated terminals. Comply
with the 8mm spacing and 3750V
50/60 Hz dielectric requirements
from hazardous voltage to operator
accessible surfaces and between
main circuits of adjacent poles per
Publications EN 60950 and VDE 0805
Impedance See next page
Insulation Resistance Minimum of 100 Megohms @ 500VDC
Overload 50 operations @ 600% of rated current
for AC rated devices
Interrupt Capacity See table A
Environmental
Environmental MIL-PRF-55629 and MIL-STD-202G
Operating Temperature -40°C to +85°C
Vibration Withstands 0.06” excursion
from 10-55 Hz and 10Gs 55-500 Hz
at rated current per MIL-PRF-55629
and MIL-STD-202G, Method 204D,
Test Condition A. Instantaneous and
ultra-short curves tested at 90% of
rated current
Shock Withstands 50 Gs, 6 ms saw tooth
while carrying rated current per
MIL-PRF-55629 and MIL-STD-202G,
Method 213B, test condition “I”.
Instantaneous and ultra short curves
tested at 90% of rated current
Thermal Shock MIL-PRF-55629 and MIL-STD-202G,
Method 107G, Condition A (5-cycles
at -55ºC to +25ºC to +85ºC to +25ºC)
Moisture Resistance MIL-PRF-55629 and MIL-STD-202G,
Method 106G, i.e., Ten 24-hour
cycles at +25°C to +65°C, 80-98% RH
Salt Spray Method 101, Condition A (90-95%
RH @ 5% NaCl Solution, 96hrs)
Mechanical
Endurance 10,000 “On-Off” operations @ 6 per
minute; with rated current & voltage
Trip Free Trips on overload even when
actuator is forcibly held in the “On”
position
Trip Indication The operating actuator moves
positively to the “Off” position
when an overload causes the
breaker to trip
Agency Approvals
UL489, cUL, TUV EN60947-2
Physical
Number of Poles 1 - 2 poles
Termination Wire ready and touch proof wire
clamp (See Figure 1). Accepts up
to (2) #10 AWG wires per terminal.
Designed for use with solid,
strandedandexiblestranded
wires, with or without ferrule or pin
terminals. Also accepts straight fork
andangedforkterminals.
Termination Torque 15-20 in-lbs (Line & Load terminals)
Termination Barrier Integral sliding barrier to comply
with spacing requirements
(Seegure1)
Mounting Threaded Insert: #6-32 UNC-2B, or
M3X0.5-6H B ISO
Insert Termination Torque 7-9 in-lbs
Actuator Rocker, with or without guard
(Seegures1,2,and4)
InternalCircuitCong. Series Trip
Materials Housing - Glass Filled Polyester
Rocker – Nylon
Line/Load Terminals - Copper Alloy;
Bright Acid Tin Plated
Weight ~107 grams (~3.76 ounces) per pole
Standard Color Housing – Black
Rocker - Several
(See ordering scheme for colors)
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
4 |
*Manufacturer reserves the right to change product specification without prior notice.
N-Series Circuit Breaker - General Specications
Electrical Tables
Table A: Voltage and Current Ratings
N-SERIES TABLE A: ELECTRICAL RATINGS
VOLTAGE CURRENT
AMPS
NUMBER
OF POLES
INTERRUPT CAPACITY AMPS
UL 489 EN609472
1-20 A 21-30 A 1-20 A 21-30 A
Icu Ics Icu Ics
120/240 VAC 1 - 30 2 22000 5000 10000 5000 10000 5000
240 VAC 1 - 20 1 10000 N/A 10000 5000 5000 5000
277 VAC 1 - 20 110000 N/A N/A N/A
Electrical: Impedance / Resistance
30
30
30
30
CURRENT
(AMPS)
TOLERANCE
(%)
0.10 - 5.0 +/- 15
5.1 - 30.0 +/- 25
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
| 5
N-Series Circuit Breaker - Ordering Scheme
1
Series
2
Actuator
3
Poles
5
Current
Metering
6
Frequency
& Delay
7
Current Rating
8
Terminal
9
Actuator
Color &
Legend
10
Mounting
11
Rating
12
Agency
Approval
4
Circuit
N 1 B 1 11 0 2 D G24 620
1 SERIES
N N-Series Circuit Breaker
2 ACTUATOR
1 Single Color Low Prole Rocker, Vertical Legend
2 Single Color Low Prole Rocker, Horizontal Legend
3 Single Color Push To Reset Low Prole Rocker, Vertical Legend
4 Single Color Push To Reset Low Prole Rocker, Horizontal Legend
8 TERMINAL
1 Screw Terminal
3 POLES
1 One 2 Two
4 CIRCUIT
B Series Trip (current)
5 CURRENT METERING
0 Without Current Transformer
1 1 Integrated Current Transformer, +/- 2%, 1 per unit
2 Integrated Current Transformer, +/- 2%, 1 per pole
3 2,6 Integrated Current Transformer, +/- 1%, 1 per unit
4 6 Integrated Current Transformer, +/- 1%, 1 per pole
6 FREQUENCY & DELAY
21 50/60 Hz Ultra Short
22 50/60 Hz Short
24 50/60 Hz Medium
26 50/60 Hz Long
42 50/60 Hz Short, HI-Inrush
44 50/60 Hz Medium, Hi-Inrush
46 50/60 Hz Long, Hi-Inrush
7 CURRENT RATING (AMPERES)
CODE AMPERES
410 1.00
512 1.25
415 1.50
517 1.75
420 2.00
522 2.25
425 2.50
527 2.75
430 3.00
435 3.50
440 4.00
445 4.50
450 5.00
455 5.50
460 6.00
465 6.50
470 7.00
475 7.50
480 8.00
485 8.50
490 9.00
495 9.50
610 10.00
710 10.50
611 11.00
711 11.50
612 12.00
712 12.50
613 13.00
614 14.00
615 15.00
616 16.00
617 17.00
618 18.00
620 20.00
622 22.00
624 24.00
625 25.00
630 30.00
11 APPLICATION RATING
C 120/240 VAC (2 Pole only)
D 2 240 VAC
F 3 277 VAC
12 AGENCY APPROVAL
A Without Approvals
G UL 489 Listed
U 4 TUV Certied, IEC 60947-2
3 5 UL 489 Listed, TUV Certied
Notes:
1 On multi pole units one current transformer is supplied on the actuator pole
2 Available up to 20 amps
3 Voltage rating F only available as a 1 pole device at 20 amps maximum
4 TUV approval requires dual (I-O, ON-OFF) markings
5 Approval Code “3” requires Dual (I-O, ON-OFF) markings on rocker.
6 +/-1% tolerance only available when used with +/-0.1% tolerance external
burden resistor.
10 MOUNTING
1 6-32 x .195 inches Threaded Inserts
2 ISO M3 x 5 mm Threaded Inserts
9 ACTUATOR COLOR & LEGEND
Actuator Color I-O ON-OFF Dual Legend Color
White A B 1 Black
Black C D 2 White
Red F G 3 White
Green H J 4 White
Blue K L 5 White
Yellow M N 6 Black
Gray P Q 7 Black
Orange R S 8 Black
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
6 |N-Series Circuit Breaker - Dimensional Specications
INSERT 6-32 or M3 x .195
[4.95] DEEP
0.750 [19.05]
MAXIMUM
LINE
Figure 1. N-Series 1-Pole Construction
LOAD
DETAIL A
0.105 [2.67]
SEE
DETAIL A
1.76 [44.70]
0.185 [4.70]
TERMINAL BARRIER SHOWN
IN OPEN POSITION
TERMINAL BARRIER SHOWN
IN CLOSED POSITION
0.187 [4.75]
1.356
[34.44]
3.675
[93.34]
3.915 ± 0.015
[99.44 ± 0.38]
0.187
[4.74]
1.135
[28.83]
0.490
[12.45]
1.400
[35.56]
0.603
[15.33]
2X
WIRE INSERTION POINT
INTERGRATED
MOLEX CONNECTOR
CURRENT METERING
SUPPLIED ON ACTUATOR
POLE OR EVERY POLE
OFF
O
ON
I
37.0˚
PUSH TO RESET ACTUATOR
Notes:
1 All dimensions are in inches [millimeters].
2 Tolerance ±.020 [.51] unless otherwise specied.
Dimensional Specifications: in. [mm]
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
| 7
N-Series Circuit Breaker - Dimensional Specications
Figure 3. Panel Cutout Details
1 POLE 2 POLE
TERMINAL BARRIER SHOWN
IN OPEN POSITION
1.500 [38.10]
MAXIMUM
2.962
[75.23]
TYP
#8-32 SCREW TOUCH PROOF
WIRE CLAMP TERMINAL
0.75
[19.05]
0.75
[19.05]
0.75
[19.05]
0.156
[3.96]
TYP
1.38
[35.05]
1.73
[43.94]
0.175
[4.45]
TYP
Figure 2. N-Series 2-Pole Construction
Notes:
1 All dimensions are in inches [millimeters].
2 Tolerance ±.020 [.51] unless otherwise specied.
Dimensional Specifications: in. [mm]
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
8 |Notes
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
| 9
Sales Representatives, Distributors & Company Prole
Authorized Sales Representatives and Distributors
About Carling
Founded in 1920, Carling Technologies is a leading manufacturer of electrical and electronic switches
and assemblies, circuit breakers, electronic controls, power distribution units, and multiplexed power
distribution systems. With four ISO registered manufacturing facilities and technical sales oces worldwide,
Carling Technologies Sales, Service and Engineering teams do much more than manufacture electrical
components, they engineer powerful solutions! To learn more about Carling please visit
www.carlingtech.com/company-prole.
To view all of Carling’s environmental, quality, health & safety certications please visit
www.carlingtech.com/environmental-certications
Click on a region of the map below to nd your local representatives and distributors or visit
www.carlingtech.com/ndarep.
EUROPE
MIDDLE
EAST
SOUTH
AMERICA
ASIA-PACIFIC
OCEANIA
AFRICA
MEXICO
USA
CANADA
Worldwide Headquarters
Carling Technologies, Inc.
60 Johnson Avenue, Plainville, CT 06062
Phone: 860.793.9281 Fax: 860.793.9231
Email: sales@carlingtech.com
Northern Region Sales Oce: nrsm@carlingtech.com
Southeast Region Sales Oce: sersm@carlingtech.com
Midwest Region Sales Oce: mrsm@carlingtech.com
West Region Sales Oce: wrsm@carlingtech.com
Latin America Sales Oce: larsm@carlingtech.com
Asia-Pacific Headquarters
Carling Technologies, Asia-Pacic Ltd.,
Suite 1607, 16/F Tower 2, The Gateway,
Harbour City, 25 Canton Road,
Tsimshatsui, Kowloon, Hong Kong
Phone: Int + 852-2737-2277 Fax: Int + 852-2736-9332
Email: sales@carlingtech.com.hk
Shenzhen, China: shenzhen@carlingtech.com
Shanghai, China: shanghai@carlingtech.com
Pune, India: india@carlingtech.com
Kaohsiung, Taiwan: taiwan@carlingtech.com
Yokohama, Japan: japan@carlingtech.com
Europe | Middle East | Africa Headquarters
Carling Technologies LTD
4 Airport Business Park, Exeter Airport,
Clyst Honiton, Exeter, Devon, EX5 2UL, UK
Phone: Int + 44 1392.364422 Fax: Int + 44 1392.364477
Email: ltd.sales@carlingtech.com
Germany: gmbh@carlingtech.com
France: sas@carlingtech.com
www.carlingtech.com REV_03_2017
Mouser Electronics
Authorized Distributor
Click to View Pricing, Inventory, Delivery & Lifecycle Information:
Carling Technologies:
N22-B1-24-610-121-C3 N11-B0-24-610-121-D3 N32-B2-44-620-122-D3 N11-B1-44-620-122-D3 N41-B1-24-615-
121-F3