N-Series Circuit Breaker - General Specications
Electrical
Current Metering Integrated current transformer.
Measurement range: 1-30 Amps.
Voltage output: 10mV per Amp
according to the formula below:
2(Amp)≤I≤30(Amp)
V = 0.01× I ± 2%
(with current metering codes 1 or 2)
V = 0.01× I ±1%
(with current metering codes 3 or 4)
%85.0
10
10
10
10
I
V
I
V
I
V
Where V=CT output in volts
V10=CT output in volts with
I=I10=10 (A); I=primary current in
amperage (50/60 Hz). Phase shift
between primary current and CT
output is 0.25±0.25°. Maximum
crest factor of primary current is 1.73.
R1 shall be integrated in the breaker.
R2 and R3 are provided by end user
and external to the breaker.
Connection: below Load Terminal.
2-pin connector, Molex 35362-0250.
Mating Connector housing – Molex
PN35507-0200.
(Current metering is available on AC
rated devices only)
I ~
(FROM 1 - 30 AMPS)
R3=14Ω±Y%
V=0.01 X (I)
V
R2=14Ω±Y%
R1=28Ω±Y%
I : 1400 CT
Note: Whencurrentmeteringcodeis1or2;Ytoequal1.0
Whencurrentmeteringcodeis3or4;Ytoequal0.1
Dielectric Strength UL, CSA-1960V 50/60 Hz for one
minute between all electrically
isolated terminals. Comply
with the 8mm spacing and 3750V
50/60 Hz dielectric requirements
from hazardous voltage to operator
accessible surfaces and between
main circuits of adjacent poles per
Publications EN 60950 and VDE 0805
Impedance See next page
Insulation Resistance Minimum of 100 Megohms @ 500VDC
Overload 50 operations @ 600% of rated current
for AC rated devices
Interrupt Capacity See table A
Environmental
Environmental MIL-PRF-55629 and MIL-STD-202G
Operating Temperature -40°C to +85°C
Vibration Withstands 0.06” excursion
from 10-55 Hz and 10Gs 55-500 Hz
at rated current per MIL-PRF-55629
and MIL-STD-202G, Method 204D,
Test Condition A. Instantaneous and
ultra-short curves tested at 90% of
rated current
Shock Withstands 50 Gs, 6 ms saw tooth
while carrying rated current per
MIL-PRF-55629 and MIL-STD-202G,
Method 213B, test condition “I”.
Instantaneous and ultra short curves
tested at 90% of rated current
Thermal Shock MIL-PRF-55629 and MIL-STD-202G,
Method 107G, Condition A (5-cycles
at -55ºC to +25ºC to +85ºC to +25ºC)
Moisture Resistance MIL-PRF-55629 and MIL-STD-202G,
Method 106G, i.e., Ten 24-hour
cycles at +25°C to +65°C, 80-98% RH
Salt Spray Method 101, Condition A (90-95%
RH @ 5% NaCl Solution, 96hrs)
Mechanical
Endurance 10,000 “On-Off” operations @ 6 per
minute; with rated current & voltage
Trip Free Trips on overload even when
actuator is forcibly held in the “On”
position
Trip Indication The operating actuator moves
positively to the “Off” position
when an overload causes the
breaker to trip
Agency Approvals
UL489, cUL, TUV EN60947-2
Physical
Number of Poles 1 - 2 poles
Termination Wire ready and touch proof wire
clamp (See Figure 1). Accepts up
to (2) #10 AWG wires per terminal.
Designed for use with solid,
strandedandexiblestranded
wires, with or without ferrule or pin
terminals. Also accepts straight fork
andangedforkterminals.
Termination Torque 15-20 in-lbs (Line & Load terminals)
Termination Barrier Integral sliding barrier to comply
with spacing requirements
(Seegure1)
Mounting Threaded Insert: #6-32 UNC-2B, or
M3X0.5-6H B ISO
Insert Termination Torque 7-9 in-lbs
Actuator Rocker, with or without guard
(Seegures1,2,and4)
InternalCircuitCong. Series Trip
Materials Housing - Glass Filled Polyester
Rocker – Nylon
Line/Load Terminals - Copper Alloy;
Bright Acid Tin Plated
Weight ~107 grams (~3.76 ounces) per pole
Standard Color Housing – Black
Rocker - Several
(See ordering scheme for colors)