PHOENIX CONTACT Inc., USA Page 1 / 6
http://www.phoenixcon.com Oct 8, 2010
Extract from the online
catalog
TRIO-PS/ 3AC/24DC/40
Order No.: 2866404
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2866404
DIN rail power supply unit, primary-switched mode, 3-phase, output:
24 V DC / 40 A
Commercial data
GTIN (EAN) 4046356046688
sales group H001
Pack 1 pcs.
Customs tariff 85044081
Weight/Piece 3.34 KG
Catalog page information Page 573 (IF-2009)
Product notes
WEEE/RoHS-compliant since:
10/17/2006
http://
www.download.phoenixcontact.com
Please note that the data given
here has been taken from the
online catalog. For comprehensive
information and data, please refer
to the user documentation. The
General Terms and Conditions of
Use apply to Internet downloads.
Product description
TRIO POWER is the DIN-rail-mountable power supply unit with basic functions. With an output voltage of 12VDC,
24VDC and 48VDC and 1- and 3-phase versions with 60 W or 960 W, it is particularly suited for use in series
production in mechanical engineering. The wide-range input and international certification package allows worldwide
implementation.
The high MTBF of 500,000 h stands for high supply reliability. The devices can be connected in parallel to increase the
capacity and redundancy.
TRIO-PS/ 3AC/24DC/40 Order No.: 2866404
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2866404
PHOENIX CONTACT Inc., USA Page 2 / 6
http://www.phoenixcon.com Oct 8, 2010
The clear LED signaling and the device connection with double terminal block for plus and minus for fast potential
distribution are further advantages of this device series. A third terminal block simplifies the grounding on the secondary
side. All power supply units are idle proof and short-circuit proof and provide a regulated and adjustable output voltage.
Technical data
Input data
Nominal input voltage 3x 400 V AC ... 500 V AC
AC input voltage range 3 x 320 V AC ... 575 V AC
AC frequency range 45 Hz ... 65 Hz
Current consumption Approx. 3x 2 A (400 V AC)
3x 1.6 A (480 V AC)
Inrush surge current < 20 A
Power failure bypass > 16 ms (400 V AC)
> 20 ms (480 V AC)
Permissible backup fuse B10
B16
Required backup fuse (device and line protection) (externally via 3 10 A or 16 A circuit breakers, characteristic B)
Power factor (cos phi) 0.76
Type of protection Transient surge protection
Protective circuit/component Varistor
Output data
Nominal output voltage 24 V DC ±1%
Setting range of the output voltage 22.5 V DC ... 29.5 V DC (> 24 V constant capacity)
Output current 40 A (-25°C ... 55°C)
Derating +55°C to +70°C: 2.5% per Kelvin
55 °C ... 70 °C (2.5%/K)
Connection in parallel Yes, for redundancy and increased capacity
Connection in series Yes
Max. capacitive load Unlimited
Current limitation Approx. 48 A
Control deviation < 1 % (change in load, static 10% ... 90%)
< 2 % (change in load, dynamic 10% ... 90%)
< 0.1 % (change in input voltage ±10%)
Residual ripple < 20 mVPP
Peak switching voltages nominal load < 40 mVPP
Maximum power dissipation idling 16 W
TRIO-PS/ 3AC/24DC/40 Order No.: 2866404
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2866404
PHOENIX CONTACT Inc., USA Page 3 / 6
http://www.phoenixcon.com Oct 8, 2010
Power loss nominal load max. 91 W
General data
Width 139 mm
Height 130 mm
Depth 190 mm
Net weight 2.9 kg
Operating voltage display LED green
Efficiency > 91.5 % (at 400 V AC and nominal values)
Insulation voltage input/output 4 kV AC (type test)
2 kV AC (routine test)
Degree of protection IP20
Class of protection I, with PE connection
MTBF > 500 000 h in acc. with IEC 61709 (SN 29500)
Ambient temperature (operation) -25 °C ... 70 °C (> 55° C derating)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Max. permissible relative humidity (operation) 95 % (at 25 °C, no condensation)
Mounting position Horizontal DIN rail NS 35, EN 60715
Assembly instructions Can be aligned: Horizontal 0 cm, vertical 5 cm
Electromagnetic compatibility Conformance with EMC directive 2004/108/EC
Noise immunity EN 61000-6-2:2005
Low Voltage Directive Conformance with LV directive 2006/95/EC
Standard – Electrical equipment of machines EN 60204
Standard - Safety of transformers EN 61558-2-17
Standard - Electrical safety EN 60950/VDE 0805 (SELV)
EN 61558-2-17
Standard – Electronic equipment for use in
electrical power installations and their assembly
into electrical power installations
EN 50178/VDE 0160 (PELV)
Standard – Safety extra-low voltage EN 60950 (SELV)
EN 60204 (PELV)
Standard - Safe isolation DIN VDE 0100-410
DIN VDE 0106-1010
Standard – Protection against electric shock DIN 57100-410
Standard – Protection against shock currents,
basic requirements for protective separation in
electrical equipment
DIN VDE 0106-101
TRIO-PS/ 3AC/24DC/40 Order No.: 2866404
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2866404
PHOENIX CONTACT Inc., USA Page 4 / 6
http://www.phoenixcon.com Oct 8, 2010
Standard – Limitation of mains harmonic currents EN 61000-3-2
UL approvals UL/C-UL listed UL 508
UL/C-UL Recognized UL 60950
Surge voltage category III
Connection data, input
Type of connection Screw connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 6 mm²
Conductor cross section stranded min. 0.2 mm²
Conductor cross section stranded max. 4 mm²
Conductor cross section AWG/kcmil min. 22
Conductor cross section AWG/kcmil max 10
Stripping length 8 mm
Screw thread M3
Connection data, output
Type of connection Screw connection
Conductor cross section solid min. 0.5 mm²
Conductor cross section solid max. 16 mm²
Conductor cross section stranded min. 0.5 mm²
Conductor cross section stranded max. 10 mm²
Conductor cross section AWG/kcmil min. 8
Conductor cross section AWG/kcmil max 6
Stripping length 10 mm
Signaling
Status display "DC OK" LED green
Note on status display UOUT > 21.5 V: LED lights up
Certificates / Approvals
Certification CUL, CUL Listed, UL, UL Listed
TRIO-PS/ 3AC/24DC/40 Order No.: 2866404
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2866404
PHOENIX CONTACT Inc., USA Page 5 / 6
http://www.phoenixcon.com Oct 8, 2010
Accessories
Item Designation Description
General
2938235 UWA 182/52 Universal wall adapter
Diagrams/Drawings
Block diagram
Dimensioned drawing
TRIO-PS/ 3AC/24DC/40 Order No.: 2866404
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2866404
PHOENIX CONTACT Inc., USA Page 6 / 6
http://www.phoenixcon.com Oct 8, 2010
Address
PHOENIX CONTACT Inc., USA
586 Fulling Mill Road
Middletown, PA 17057,USA
Phone (800) 888-7388
Fax (717) 944-1625
http://www.phoenixcon.com
© 2010 Phoenix Contact
Technical modifications reserved;