2 Fluke Corporation Fluke 360 AC Leakage Current Clamp Meter
Special Features
IEC 61010 and EMC Conformance
IEC 61010 safety features including a tactile barrier and
special jaw design provide the user with confidence
when making measurements in hazardous voltage areas.
Conformance to EMC standards ensures high reliability
through reduced susceptibility to electromagnetic interference.
The Fluke 360 also meets the latest safety standard
VDE0404-4 and the new VDE0702 requirements.
High Accuracy
Advanced jaw design means that the Fluke 360 accuracy
is little affected by external magnetic fields even at low
currents. Typical external current rejection is 200,000:1.
General Specification
Method of detection Mean value
Display Digital display: 3200 counts
Bar-graph display: 32 segments, LCD
Measurement cycle 2 times/second (Digital display), 12 times/second (Bar-graph display)
Range switching Auto-range
Ambient temperature and humidity 0 °C to 50 °C, 80 % RH or less (no condensation)
Temperature coefficient 0.05 % of range/°C or less (within the ranges of 0 °C to 18 °C and
28 °C to 50 °C for measurement of 0-50 A)
Influence of external magnetic field 0.0005 % typical 1 (on current value of adjacent cable)
Influence of conductor position Within accuracy
Circuit voltage ≤ 300 Vrms
Safety standard EN 61010-1, EN 61010-2-032. 300 V CAT II, Pollution Degree 2
Withstanding voltage 3.7 kV ac for one minute
Battery type 1 x 3 V Lithium battery (button cell) CR2032
Battery life Approx. 90 hours (when continuously used)
Auto power-off Approx. 10 minutes
Diameter of measurable conductor 40 mm max.
Weight 200 g (441 lb)
Dimension 176 mm x 70 mm x 25 mm (6.9 in x 2.8 in x 1 in)
Operating altitude 2000 m (6,562 ft)
Electrical Specification
Specifications at 23 ± 5 °C. 80 % RH max
Accuracy: ± (% rdg + dgt) = ± (% readout + value of least significant digit)
AC Current Measurement
Measuring range Resolution Accuracy Max Permissible current
3 mA 0.001 mA 1 % + 5
60 A rms
30 mA 0.01 mA
30 A 0.01 A 1 % + 5 (0~50 A)
5 % + 5 (50~60 A)
60 A 0.1 A
Mean value detection and rms-value calibration.
Accuracy specified at 50/60 Hz
Frequency range 15 Hz to 150 Hz
Fluke. Keeping your world
up and running.™
Fluke Corporation
PO Box 9090, Everett, WA USA 98206
Fluke Europe B.V.
PO Box 1186, 5602 BD
Eindhoven, The Netherlands
For more information call:
In the U.S.A. (800) 443-5853 or
Fax (425) 446-5116
In Europe/M-East/Africa +31 (0) 40 2675 200 or
Fax +31 (0) 40 2675 222
In Canada (800)-36-FLUKE or
Fax (905) 890-6866
From other countries +1 (425) 446-5500 or
Fax +1 (425) 446-5116
Web access: http://www.fluke.com
©2006 Fluke Corporation. All rights reserved.
Specifications subject to change without notice.
Printed in U.S.A. 12/2006 2791021 D-EN-N Rev A