General-purpose Relay MY New model 1
General-purpose Relay
MY New model
Versatile and Function-filled Miniature Power
Relay for Sequence Control and Power
Switching Applications
Models with lockable test buttons now available.
Many variations possible through a selection of operation indi-
cators (mechanical and LED indicators), lockable test button,
built-in diode and CR (surge suppression), bifurcated contacts,
etc.
Arc barrier standard on 4-pole Relays.
Dielectric strength: 2,000 VAC (coil to contact)
Environment-friendly cadmium-free contacts.
Safety standard approvals obtained.
Wide range of Sockets (PY, PYF Series) and optional parts are
available.
Max. Switching Current: 2-pole: 10 A, 4-pole: 5 A
Provided with nameplate.
LR
Ordering Information
Relays
Standard Coil Polarity
Reverse Coil Polarity
Note: When ordering, add the rated coil voltage and “(s)” to the model number. Rated coil voltages are given in the coil ratings table.
Type Contact form Plug-in socket/Solder terminals Without LED indicator
Standard with LED indicator With LED indicator and
lockable test button
Standard DPDT MY2N MY2IN MY2
4PDT MY4N MY4IN MY4
4PDT (bifurcated) MY4ZN MY4ZIN MY4Z
With built-in diode
(DC only)
DPDT MY2N-D2 MY2IN-D2 ---
4PDT MY4N-D2 MY4IN-D2 ---
4PDT (bifurcated) MY4ZN-D2 MY4ZIN-D2 ---
With built-in CR
(220/240 VAC, 110/120 VAC
only)
DPDT MY2N-CR MY2IN-CR ---
4PDT MY4N-CR MY4IN-CR ---
4PDT (bifurcated) MY4ZN-CR MY4ZIN-CR ---
Type Contact form Plug-in socket/Solder terminals
With LED indicator With LED indicator and
lockable test button
Standard (DC only) DPDT MY2N1 MY2IN1
4PDT MY4N1 MY4IN1
4PDT (bifurcated) MY4ZN1 MY4ZIN1
With built-in diode
(DC only)
DPDT MY2N1-D2 MY2IN1-D2
4PDT MY4N1-D2 MY4IN1-D2
4PDT (bifurcated) MY4ZN1-D2 MY4ZIN1-D2
Example: MY2 6VAC (S)
Rated coil voltage
New model
2General-purpose Relay MY New model
Accessories (Order Separately)
Sockets
Socket Hold-down Clip Pairing
Mounting Plates for Sockets
Note: PYP-18 and PYP-36 can be cut into any desired length in accordance with the number of Sockets.
Track and Accessories
Specifications
Coil Ratings
Note: 1. The rated current and coil resistance are measured at a coil temperature of 23°C with tolerances of +15%/–20% for rated currents and
±15% for DC coil resistance.
2. Performance characteristic data are measured at a coil temperature of 23°C.
3. AC coil resistance and impedance are provided as reference values (at 60 Hz).
4. Power consumption drop was measured for the above data. When driving transistors, check leakage current and connect a bleeder re-
sistor if required.
5. Rated voltage denoted by “*” will be manufactured upon request. Ask your OMRON representative.
Poles Front-mounting
Socket (DIN-track/
screw mounting)
Back-mounting Socket
Solder terminals Wire-wrap terminals PCB terminals
Without clip With clip Without clip With clip
2 PYF08A-E
PYF08A-N
PY08 PY08-Y1 PY08QN
PY08QN2
PY08QN-Y1
PY08QN2-Y1
PY08-02
4 PYF14A-E
PYF14A-N
PY14 PY14-Y1 PY14QN
PY14QN2
PY14QN-Y1
PY14QN2-Y1
PY14-02
Relay type Poles Front-connecting Socket (DIN-track/
screw mounting)
Back-connecting Socket
Solder/Wire-wrap terminals PCB terminals
Socket Clip Socket Clip Socket Clip
Without 2-pole test
button
2 PYF08A-E
PYF08A-N
PYC-A1 PY08(QN) PYC-P
PYC-P2
PY08-02 PYC-P
PYC-P2
4 PYF14A-E
PYF14A-N
PY14(QN) PY14-02
2-pole test button 2 PYF08A-E
PYF08A-N
PYC-E1 PY08(QN) PYC-P2 PY08-02 PYC-P2
Socket model For 1 Socket For 18 Sockets For 36 Sockets
PY08, PY08QN(2), PY14, PY14QN(2) PYP-1 PYP-18 PYP-36
Supporting Track (length = 500 mm) PFP-50N
Supporting Track (length = 1,000 mm) PFP-100N, PFP-100N2
End Plate PFP-M
Spacer PFP-S
Rated voltage Rated current Coil
resistance
Coil inductance
(reference value)
Must
operate
voltage
Must
release
voltage
Max.
voltage
Power
consumption
(approx.)
50 Hz 60 Hz Arm. OFF Arm. ON % of rated voltage
AC 6 V* 214.1 mA 183 mA 12.2 0.04 H 0.08 H 80% max. 30% min. 110% 1.0 to 1.2 VA
(60 Hz)
12 V 106.5 mA 91 mA 46 0.17 H 0.33 H
24 V 53.8 mA 46 mA 180 0.69 H 1.30 H
48/50 V* 24.7/
25.7 mA
21.1/
22.0 mA
788 3.22 H 5.66 H
110/120 V 9.9/10.8 mA 8.4/9.2 mA 4,430 19.20 H 32.1 H 0.9 to 1.1 VA
(60 Hz)
220/240 V 4.8/5.3 mA 4.2/4.6 mA 18,790 83.50 H 136.4 H
DC 6 V* 151 mA 39.8 0.17 H 0.33 H 10% min. 0.9 W
12 V 75 mA 160 0.73 H 1.37 H
24 V 37.7 mA 636 3.20 H 5.72 H
48 V* 18.8 mA 2,560 10.60 H 21.0 H
100/110 V 9.0/9.9 mA 11,100 45.60 H 86.2 H
General-purpose Relay MY New model 3
Contact Ratings
Note: Don’t exceed the carry current of a Socket in use. Please see page 9.
Characteristics
Note: The values given above are initial values.
Endurance Characteristics
Item 2-pole 4-pole 4-pole (bifurcated)
Resistive load
(cosφ = 1)
Inductive load
(cosφ = 0.4, L/R = 7 ms)
Resistive load
(cosφ = 1)
Inductive load
(cosφ = 0.4, L/R = 7 ms)
Resistive load
(cosφ = 1)
Inductive load
(cosφ = 0.4, L/R = 7 ms)
Rated load 5A, 250 VAC
5A, 30 VDC
2A, 250 VAC
2 A, 30 VDC
3 A, 250 VAC
3 A, 30 VDC
0.8 A, 250 VAC
1.5 A, 30 VDC
3 A, 250 VAC
3 A, 30 VDC
0.8 A, 250 VAC
1.5 A, 30 VDC
Carry current 10 A (see note) 5 A (see note)
Max. switching
voltage
250 VAC
125 VDC
250 VAC
125 VDC
Max. switching
current
10 A 5 A
Max. switching
power
2,500 VA
300 W
1,250 VA
300 W
1,250 VA
150 W
500 VA
150 W
1,250 VA
150 W
500 VA
150 W
Failure rate
(reference value)
5 VDC, 1 mA 1 VDC, 1 mA 1 VDC, 100 µA
Item All Relays
Contact resistance 100 m max.
Operate time 20 ms max.
Release time 20 ms max.
Max. operating frequency Mechanical: 18,000 operations/hr
Electrical: 1,800 operations/hr (under rated load)
Insulation resistance 1,000 M min. (at 500 VDC)
Dielectric strength 2,000 VAC, 50/60 Hz for 1.0 min (1,000 VAC between contacts of same polarity)
Vibration resistance Destruction: 10 to 55 to 10 Hz, 0.5 mm single amplitude (1.0 mm double amplitude)
Malfunction: 10 to 55 to 10 Hz, 0.5 mm single amplitude (1.0 mm double amplitude)
Shock resistance Destruction: 1,000 m/s2
Malfunction: 200 m/s2
Endurance See the following table.
Ambient temperature Operating: –55°C to 70°C (with no icing)
Ambient humidity Operating: 5% to 85%
Weight Approx. 35 g
Pole Mechanical life (at 18,000 operations/hr) Electrical life
(at 1,800 operations/hr under rated load)
2-pole AC:50,000,000 operations min.
DC:100,000,000 operations min.
500,000 operations min.
4-pole 200,000 operations min.
4-pole (bifurcated) 20,000,000 operations min. 100,000 operations min.
4General-purpose Relay MY New model
Approved Standards
VDE Recognitions (File No. 112467UG, IEC 255, VDE 0435)
UL508 Recognitions (File No. 41515)
CSA C22.2 No. 14 Listings (File No. LR31928)
IMQ (File No. EN013 to 016)
LR Recognitions (File No. 98/10014)
SEV Listings (File No. 99.5 50902.01)
No. of poles Coil ratings Contact ratings Operations
2 6, 12, 24, 48/50, 100/110
110/120, 200/220,
220/240 VAC
6, 12, 24, 48, 100/110,
125 VDC
10 A, 250 VAC (cosφ=1)
10 A, 30 VDC (L/R=0 ms)
10 x 103
4 5 A, 250 VAC (cosφ=1)
5 A, 30 VDC (L/R=0 ms)
100 x 103
MY4Z AC; 50 x 103
No. of poles Coil ratings Contact ratings Operations
2 6 to 240 VAC
6 to 125 VDC
10 A, 30 VDC (General purpose)
10 A, 250 VAC (General purpose)
6 x 103
4 5 A, 250 VAC (General purpose)
5 A, 30 VDC (General purpose)
No. of poles Coil ratings Contact ratings Operations
2 6 to 240 VAC
6 to 125 VDC
10 A, 30 VDC
10 A, 250 VAC
6 x 103
4 5 A, 250 VAC (Same polarity)
5 A, 30 VDC (Same polarity)
No. of poles Coil ratings Contact ratings Operations
2 6, 12, 24, 48/50, 100/110
110/120, 200/220,
220/240 VAC
6, 12, 24, 48, 100/110,
125 VDC
10 A, 30 VDC
10 A, 250 VAC
10 x 103
4 5 A, 250 VAC
5 A, 30 VDC
100 x 103
MY4Z AC; 50 x 103
No. of poles Coil ratings Contact ratings Operations
2 6 to 240 VAC
6 to 125 VDC
10 A, 250 VAC (Resistive)
2 A, 250 VAC (PF0.4)
10 A, 30 VDC (Resistive)
2 A, 30 VDC (L/R=7 ms)
50 x 103
4 5 A, 250 VAC (Resistive)
0.8 A, 250 VAC (PF0.4)
5 A, 30 VDC (Resistive)
1.5 A, 30 VDC (L/R=7 ms)
50 x 103
No. of poles Coil ratings Contact ratings Operations
2 6 to 240 VAC
6 to 125 VDC
10 A, 250 VAC
10 A, 30 VDC 10 x 103
4 5 A, 250 VAC
5 A, 30 VDC 100 x 103
MY4Z AC; 50 x 103
General-purpose Relay MY New model 5
Engineering Data
Maximum Switching Power
Endurance
MY2 MY4, MY4Z
Switching current (A)
AC resistive load
DC resistive load
AC resistive load
DC resistive load
Switching current (A)
Switching voltage (V) Switching voltage (V)
AC inductive load
(cosφ=0.4)
DC inductive load
(L/R=7 ms)
AC inductive load
(cosφ=0.4)
DC inductive load
(L/R=7 ms)
10000
5000
3000
1000
500
300
100
50
30
10
10000
5000
3000
1000
500
300
100
50
30
10
MY2 (Resistive Loads) MY2 (Inductive Loads)
Endurance (x10 operations)
3
Switching current (A)
250 VAC
30 VDC 30 VDC
250 VAC
Endurance (x10 operations)
3
Switchin
g
current
(
A
)
30 VDC
250 VAC
250 VAC
30 VDC
10000
5000
3000
1000
500
300
100
50
30
10
10000
5000
3000
1000
500
300
100
50
30
10
MY4 (Resistive Loads) MY4 (Inductive Loads)
Endurance (x10 operations)
3
Switching current (A)
250 VAC
30 VDC
30 VDC
250 VAC
Endurance (x10 operations)
3
Switchin
g
current
(
A
)
30 VDC
250 VAC
250 VAC
30 VDC
6General-purpose Relay MY New model
10000
5000
3000
1000
500
300
100
50
30
10
10000
5000
3000
1000
500
300
100
50
30
10
MY4Z (Resistive Loads) MY4Z (Inductive Loads)
Endurance (x10 operations)
3
Switching Current (A)
250 VAC
30 VDC
250 VAC
30 VDC
250 VAC
250 VAC
30 VDC
30 VDC
Endurance (x10 operations)
3
Switching Current (A)
General-purpose Relay MY New model 7
Dimensions
Note: All units are in millimeters unless otherwise indicated.
2-Pole Models
4-Pole Models
Models with Test Button
0.5
6.4
MY2N
21.5 max.
36 max.
28 max.
2.6
Eight, 1.2 dia. × 2.2 long holes
0.5
21.5 max.
36 max. 6.4
MY4N
28 max.
2.6
Eight, 1.2 dia. × 2.2 long holes
36 max.
MY2IN
8
14.2
5
80.5 6.3
2.6
Eight, 1.2 dia. × 2.2 long holes
21.5 max.
28 max.
MY4IN
36 max.
<1.417>
Fourteen, 1.2 dia. × 2.2 long holes
0.5
80.5 6.3
5
6.4
14.2
8
2.6
21.5 max.
28 max.
8General-purpose Relay MY New model
Terminal Arrangement/Internal Connections (Bottom View)
Note: The DC models have polarity.
1
5
9
13
4
8
12
14
1
5
9
13
4
8
12
14
1
5
9
13
4
8
12
14
1
5
9
13
4
8
12
14
1
5
9
13
4
8
12
14
1
5
9
13
4
8
12
14
1
5
9
13
4
8
12
14
1
5
9
13
4
8
12
14
2
6
10
3
7
11
1
5
9
4
8
12
2
6
10
3
7
11
1
5
4
8
2
6
3
7
1
5
4
8
2
6
3
7
1
5
9
4
8
12
2
6
10
3
7
11
1
5
4
8
2
6
3
7
1
5
4
8
2
6
3
7
13 14 13 14 13 14
13 14 13 14 13 14
MY2 MY2N/MY2IN
(AC Models)
MY2N/MY2IN
(DC Models)
MY2N-D2/MY2IN-D2
(DC Models Only)
MY2N-CR/MY2IN-CR
(AC Models Only)
MY2N1/MY2IN1
(DC Models Only)
MY2N1-D2/MY2IN1-D2
(DC Models Only)
MY4(Z) MY4(Z)N/MY4(Z)IN
(AC Models)
MY4(Z)N/MY4(Z)IN
(DC Models)
MY4(Z)N-D/MY4(Z)IN-D2
(DC Models Only)
MY4(Z)N-CR/MY4(Z)IN-CR
(AC Models Only)
MY4(Z)N1/MY4(Z)IN1
(DC Models Only)
MY4(Z)N1-D2/MY4(Z)IN1-D2
(DC Models Only)
+− +−
−+ −+
+− +−
−+ −+
General-purpose Relay MY New model 9
Socket for MY
Track-mounted (DIN Track) Socket
Conforms to VDE 0106, Part 100
Snap into position along continuous sections of any mount-
ing track.
Facilitates sheet metal design by standardized mounting di-
mensions.
Design with sufficient dielectric separation between termi-
nals eliminates the need of any insulating sheet.
Safety Standards for Sockets
Back-connecting Sockets
Specifications
Note: 1. The values given above are initial values.
2. The values for insulation resistance were measured at 500 V at the same place as the dielectric strength.
3. The maximum operating ambient temperature for the PYF08A-N and PYF14A-N is 55°C.
4. When using the PYF08A-N or PYF14A-N at an operating ambient temperature exceeding 40°C, reduce the current to 60%.
5. The MY2(S) can be used at 70°C with a carry current of 7 A.
Model Standards File No.
PYF08A-E, PYF08A-N
PYF14A-E, PYF14A-N
UL508 E87929
CSA22.2 LR31928
Item Pole Model Carry current Dielectric withstand
voltage
Insulation resistance
(see note 2)
Screwless Clamp
Terminal Socket
2 PYF08S 10 A 2,000 VAC, 1 min Less than 1,000 M
4 PYF14S 5 A
Track-mounted
Socket
2 PYF08A-E 7 A 2,000 VAC, 1 min 1,000 M min.
PYF08A-N (see note 3) 7 A (see note 4)
4 PYF14A-E 5 A
PYF14A-N (see note 3) 5 A (see note 4)
Back-connecting
Socket
2 PY08(-Y1) 7 A 1,500 VAC, 1 min 100 M min.
PY08QN(-Y1)
PY08-02
4 PY14(-Y1) 3 A
PY14QN(-Y1)
PY14-02
10 General-purpose Relay MY New model
Dimensions
Note: All units are in millimeters unless otherwise indicated.
Socket Dimensions Terminal arrangement/
Internal connections
(top view)
Mounting holes
---
PYF08S
(5.3)
85 max.
38.2 max.
36.5 max.
23.2 max.
PYF08A-E
31 max.
23 max.
72 max.
Two, 4.2 x 5
mounting
holes
Eight, M3 x 8
sems screws
(TOP VIEW)
Two, M3, M4, or 4.5-dia. holes
Note: Track mounting is also
possible. Refer to page
12 for supporting tracks.
PYF08A-N
4
42
8
44
1
12
5
14
41
12
A2
14
11
9
A1
13
A2
14
PYF-08A-N 73
22 max.
67 max.
30 max.
4
42
1
85
12 9
14 14 13
44
12
14
41 11
A2 A2 A1
18.7
3.0 dia.
3.5 dia. or M3
Note: Track mounting is also
possible. Refer to page
12 for supporting tracks.
General-purpose Relay MY New model 11
---
Socket Dimensions Terminal arrangement/
Internal connections
(top view)
Mounting holes
PYF14S
36.5 max.
31 max.
85 max.
PYF14A-E
31 max.
29.5 max.
72 max.
Two, 4.2 x 5
mounting
holes Fourteen, M3 x 8
sems screws
(TOP VIEW)
Two, M3, M4, or 4.5-dia. holes
Note: Track mounting is also
possible. Refer to page
12 for su
pp
ortin
g
tracks.
PYF14A-N
4
42
3
32
2
22
1
12
8
44
7
34
6
24
5
14
41
12
31
11
21
10
11
9
A1
13
A2
14
A2
14
PYF-14A-N
73
30 max.
67 max.
29.5 max.
4 3 2 1
8 7 6 5
12 11 10 9
14 14 13
42 32 22 12
44 34 24 14
41 31 21 11
A2 A2 A1
26
Two, 4.5 dia. or M4
Note: Track mounting is also
possible. Refer to page
12 for supporting tracks.
12 General-purpose Relay MY New model
Note: Use a panel with plate thickness of 1 to 2 mm for mounting the Sockets.
Socket Dimensions Terminal arrangement/
Internal connections
(bottom view)
Mounting holes
PY08/PY08-Y1 (See note) Eight, 3 x 1.2 elliptical holes
25.5 max.
29.5 max.
24 max.
42 max.
Note: The PY08-Y1 includes sections indicated by
dotted lines.
20 max.
PY08QN/
PY08QN-Y1
(See note) 29.5 max.
22 max.
24 max.
41.5 max.
42 max.
Note: The PY08QN-Y1 includes sections
indicated b
y
dotted lines.
PY08-02
16.5 max.
22 max.
25.5 max.
29.5 max.
Eight, 1.3-dia.
holes
PY14/PY14-Y1
(See note) Fourteen, 3 x 1.2 elliptical holes
25.5 max.
29.5 max.
24 max.
42 max.
Note: The PY14-Y1 includes sections indicated by
dotted lines.
20 max.
PY14QN/
PY14QN-Y1 (See note)
29.5 max.
22 max.
24 max.
41.5 max.
42 max.
Note: The PY14QN-Y1 includes sections
indicated b
y
dotted lines.
PY14-02
16.5 max.
22 max.
25.5 max.
29.5 max.
Fourteen, 1.3-dia.
holes
General-purpose Relay MY New model 13
Hold-down Clips
Mounting Plates for Back-connecting Sockets
4.5
1.2
36.3
4.5
36.3
5.75 4.25
4.5±0.1
5
3.3
38.5
10
28
PYC-P PYC-P2
29 max.
PYC-A1
(2 pcs per set)
PYC-E1
(2 pcs per set)
PYP-1 PYP-36
PYP-18
t=1.6
Two, 3.4-dia. holes
72 elliptical holes
72 elliptical holes
14 General-purpose Relay MY New model
Tracks and Accessories
Supporting Tracks
PFP-50N/PFP-100N
PFP-100N2
End Plate
PFP-M
Spacer
PFP-S
4.5
15 25 25
10 25
1000 (500) *
25
10 15 (5) 1
35±0.3
7.3±0.15
27±0.15
Note: The figure in the parentheses is for PFP-50N.
29.2
1.5
27 24
16
1
4.5
15 25 25
10 25
1000
25
10 15
35±0.3
50
11.5
10
10
6.2
1.8
1
35.5 35.3
1.8
1.3
4.8
M4 x 8 pan head screw
M4 spring washer
5
16
12
44.3
16.5
34.8
General-purpose Relay MY New model 15
Precautions
Refer to General Precautions on page 11 of the General-purpose Relays and Power Relays Group Catalog (X034).
Connections
Do not reverse polarity when connecting DC-operated Relays with
built-in diodes or indicators or high-sensitivity DC-operated Relays.
Mounting
Whenever possible, mount Relays so that it is not subject to vibra-
tion or shock in the same direction as that of contact movement.
16
In the interest of product improvement, specifications are subject to change without notice.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
Cat. No. J111-E1-03
OMRON RELAY & DEVICES Corporation
General Purpose Relay Division
Marketing & Product Engineering Department
1110 Sugi, Yamaga-City,
Kumamoto, 861-0596 Japan
Tel: (81)968-44-4160/Fax: (81)968-44-4107 Printed in Japan
2007.3
OMRON Corporation
Industrial Automation Company
http://www.ia.omron.com/ (c)Copyright OMRON Corporation 2007 All Rights Reserved.
In the interest of product improvement, specifications are subject to change without notice.
Read and Understand This Catalog
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or
comments.
Warranty and Limitations of Liability
WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if
specified) from date of sale by OMRON.
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR
FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS
DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER
WARRANTIES, EXPRESS OR IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS, OR COMMERCIAL
LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR
STRICT LIABILITY.
In no event shall responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS
OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT
SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's
application or use of the product.
At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the
products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product,
machine, system, or other application or use.
The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible
uses of the products, nor is it intended to imply that the uses listed may be suitable for the products:
• Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this catalog.
• Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles, safety
equipment, and installations subject to separate industry or government regulations.
• Systems, machines, and equipment that could present a risk to life or property.
Please know and observe all prohibitions of use applicable to the products.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE
SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCT IS PROPERLY RATED AND
INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
Disclaimers
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons.
It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made.
However, some specifications of the product may be changed without any notice. When in doubt, special model numbers may be assigned to fix
or establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual
specifications of purchased product.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.
ERRORS AND OMISSIONS
The information in this catalog has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical,
typographical, or proofreading errors, or omissions.
PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent
the result of OMRON’s test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON
Warranty and Limitations of Liability.
PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof.
COPYRIGHT AND COPY PERMISSION
This catalog shall not be copied for sales or promotions without permission.
This catalog is protected by copyright and is intended solely for use in conjunction with the product. Please notify us before copying or reproducing this
catalog in any manner, for any other purpose. If copying or transmitting this catalog to another, please copy or transmit it in its entirety.
Cat. No. J111-E1-03