www.tracopower.com Page 1 of 6
Industrial Power Supplies TIB 080 Series, 80 Watt
Slim profile, for DIN-rail mounting
Alternative side-mounting
for flat panels
High power factor by active power
correction
Very high efficiency up to 90%
Back power immunity
150% peak current for 4 sec.
Operating temperature range:
–40°C to +70°C max.
Adjustable output voltage
DC–OK indicator
Short circuit and overload protection
This generation of DIN-rail power supplies combines the most efficient circuit
topology with optimized cost/performance ratio for industrial environments and
for electrical control cabinets.
They have a very high efficiency of up to 90.0% which allows a very slim package
design. The output voltage is adjustable from –2% to +17%. The case offers the
potentially useful feature to fix the DIN-rail clip to the side wall for the mounting
inside flat panels. Over a period of minimum 4 seconds they can operate with a
boost power of 150%. The boost power facilitates the activation of stepper mo-
tors, solenoids or actuators. The units operate with a high power factor by active
power factor correction which also keeps the input inrush current low. The TIB
series are also available with higher nominal power of 120, 240 or 480 Watt
(+50% boost power). They come with the safety standard approvals for IEC/EN
60950-1, UL 60950-1 and UL 508.
Order Code Output Power
(max.)
Output Voltage
nom. (adjustable)
Output Current
(max.)
Efficiency
(typ.)
TIB 080-112 80 W 12 VDC (11.8–15.0) 6.7 A 88.0 %
TIB 080-124 80 W 24 VDC (23.5–28.0) 3.4 A 90.0 %
TIB 080-148 80 W 48 VDC (47.0–56.0) 1.7 A 90.0 %
Models
UL508
CB
Scheme
UL60950-1
Other output power of same series:
www.tracopower.com/overview/tib
www.tracopower.com Page 2 of 6
TIB 080 Series, 80 Watt
All specifications valid at nominal input voltage, full load and +25°C after warm-up time unless otherwise stated.
Input Specifications
Input voltage – nominal ranges 100 – 240 VAC
– effective ranges 85 – 264 VAC
(below 90 VAC a derating of 3%/V is required)
Input voltage frequency 45 – 65 Hz
Standby power cunsumption 0.9/1.45 W (115 / 23 0 VA C )
Power Factor Correction (PFC) 0.48/0.48 (115 / 2 3 0 VAC )
Harmonic limits – acc. EN 61000-3-2 class A
Inrush current 15/30 A max. (115 / 230 VA C )
Output Specifications
Output voltage adjustment 1) 12 Vout models: 11.8 – 15.0 V
24 Vout models: 23.5 – 28.0 V
48 Vout models: 47.0 – 56.0 V
Regulation – Input variation 0.1 % max.
– Load variation (10–90 %) 0.5 % max.
Temperature coefficient 0.02 %/K
Hold-up time 20/160 ms min. (115 / 23 0 VA C )
Start-up time 2 s max.
Ripple and Noise (20MHz bandwidth) 12 & 24 Vout models: 100 mVp-p max.
48 Vout models: 200 mVp-p max.
Output overvoltage protection (OVP) 2) 12 Vout models: 16 – 19 V
24 Vout models: 32 – 35 V
48 Vout models: 56 – 60 V
Power back immunity 3) < OVP level
Operation – Nominal operation 100 % of Iout nom.
– Peak power operation 105 – 150 % of Iout nom.
– Constant current (cc) > 155 % of Iout nom.
Duty cycle 4) – Threshold > 105 %
(for peak and cc mode) – CC or peak opeartion timer 4 s max. (switch off)
– normal operation / off period 6 s typ. (automatic restart after switch off or
peak and cc operation timer reset)
Short circuit Switch off after 4s delay, automatic restart
DC OK signal – Threshold for Vout 12 Vout models: on: > 10.9 V typ., off: < 10.7 V typ.
24 Vout models: on: > 22.5 V typ., off: < 21.5 V typ.
48 Vout models: on: > 45 V typ., off: < 43 V typ.
– DC ON relay contact closed, 1 A max., < 100 mOhm
(also indicated by green LEDs: front and side)
– DC OFF relay contact open, 30 V max.
1) Output voltage can be adjusted as indicated. However, output power has to be maintained at nominal value. This means the output
nominal current has to be reduced in accordance with the increase of output voltage.
2) In case of an internal error a second voltage regulation loop keeps the output voltage at a save level, the power supply turns off and
restarts after typ. 6 seconds.
3) When external voltage is supplied above set output voltage and below OVP threshold, the power supply will function normally without
switch off or destruction, even if external voltage is applied continuously.
4) In case of overload or short circuit, the unit switches the output voltage off after 4 seconds and tries to restart every typ. 6 seconds.
www.tracopower.com Page 3 of 6
TIB 080 Series, 80 Watt
General Specifications
Operating temperature range –40°C to +70°C max.
Derating 2 %/K above +60°C
Cooling convection cooling, no internal fan
Overtemperature protection switch off at overtemperature
Humidity (non condensing) 5–95 % rel. H max.
Altitude during operation 2000 m max.
Isolation Voltage – Input/Ouput 4250 VDC
– Input/Chassis 1500 VDC
– Ouput/Chassis 750 VDC
Creepage Clearance – Input/Ouput 8 mm
– Input/Chassis 4 mm
– Output/Chassis 1.5 mm
MTBF (acc. to IEC 61709 at 25°C) > 1‘950‘000 h
Safety standards – Information technology equipment
IEC/EN 60950-1, UL 60950-1
CSA 22.2 No 60950-1-03
– Safety low voltage switchgear and controlgear UL 508
– Certification documents www.tracopower.com/overview/tib
Electromagnetic compatibility (EMC), Emissions EN 61000-6-3, EN 61204-3
– Conducted emission input EN 55032, EN 55011 class B
– Radiated RI emission EN 55032, EN 55011 class B
Electromagnetic compatibility (EMC), Immunity EN 61000-6-2, EN 61204-3
– Railway applications signalling apparatus EN 50121-4
– Railway applications rolling stock apparatus EN 50121-3-2
– Electrostatic discharge (ESD) IEC/EN 61000-4-2 4 kV/8 kV criteria A
– Radiated RF field immunity IEC/EN 61000-4-3 10 V/m criteria A
– Electrical fast transient / burst immunity IEC/EN 61000-4-4 2 kV criteria B
– Surge immunity IEC/EN 61000-4-5 1 kV/2 kV criteria B
– Immunity to conducted RF disturbances IEC/EN 61000-4-6 10 V criteria A
– Power frequency field immunity IEC/EN 61000-4-8 30 A/m criteria A
– Mains voltage dips and interruptions IEC/EN 61000-4-11 criteria B/C
– Voltage sag immunity SEMI F47 (230 VAC) criteria A
Environment – Railway applications shock and vibration according EN 61373
– Vibration acc. IEC 60068-2-6-3 3 axis, 2 g sine sweep, 10–55 Hz, 11 okt/min
– Shock acc. IEC 60068-2-27 3 axis, 25 g half sine, 11 ms
Enclosure material – Chassis aluminium
– Cover stainless steel
Mounting DIN-rail mounting for DIN-rails as per EN 50022-3515/7.5
Environmental compliance – Reach www.tracopower.com/info/reach-declaration.pdf
– RoHS RoHS directive 2011/65/EU
Connection screw terminals
All specifications valid at nominal input voltage, full load and +25°C after warm-up time unless otherwise stated.
www.tracopower.com Page 4 of 6
TIB 080 Series, 80 Watt
Function Specification
Output Characteristic
Characteristic: Output voltage vs output current for overload conditions until switch off after
4 s at nominal input voltages
www.tracopower.com Page 5 of 6
TIB 080 Series, 80 Watt
Output Characteristic (continued)
Derating: max load vs input voltage
Derating: Load vs ambient temperature
www.tracopower.com
© Copyright 2019 Traco Electronic AG Specifications can be changed without notice!
Page 6 of 6
Rev. March 7, 2019
TIB 080 Series, 80 Watt
Outline Dimensions
Model
Industrial Power Supply
80 W
V adj.
24 VDC/
3.4 A
100-240 VAC,50-60 Hz
2.00-0.90 A
DC
ON
DC OK
L N
* Measurement from fron panel to DIN-Rail
98,6 ±1 *
94,2 ±1
32 ±1
6,35
M3
Combi Head
6,35
M3
Combi Head
Weight: 367g (12.95 oz)
114,2 ±1
DIN-Rail
Hook
TIB 080-124
Model
Industrial Power Supply
80 W
V adj.
24 VDC/
3.4 A
100-240 VAC,50-60 Hz
2.00-0.90 A
DC
ON
DC OK
L N
TIB 080-124
Alternative side mounting:
DC ON