SPECIFICATIONS
Standard Current Ratings 2.5, 3, 4, 5, 6, 7, 8, 10, 12, 15, 16, 20 Amps (AC - inductive, DC - resistive)
Voltage Ratings 125 / 250 VAC, 50/60 Hz, 50 VDC
Max Breaking Capacity 8x In for < 6A, 60A max. > 6A
Conditional Short Circuit Capacity
Inc1 (PC1) per EN 60934
1000A 125 / 250VAC, 50VDC,SC:1kA, C1, 125 / 250VAC, 50VDC
Ref. CSA 22.2 No. 235-04, UL 1077
Rated Short Circuit Capacity Icn
Ref. EN 60934
Min. 6 X Rated Current (6 X In), 250VAC inductive
Min. 4 X Rated Current (4 X In), 50VDC resistive
Tripping Current Code (TC) TC2 ref: CSA22.2, No. 235-04
Insulation Resistance Min 100 MΩ @ 500VDC
Dielectric Strength 1.5 KV for 1 min. (per EN60934)
Initial Withstand Voltage 2.5 KV (per EN60934)
Operational Life 1000 Cycles @ 2 x In
Overload Rating OL0 240Vac, 50Vdc, ref: CSA22.2, No. 235-04
Overload Switching Capacity 6x In AC Up to 9A, 4x In DC Up to 12A
60A Max. from 10A to 12A
Max Operating Temperature 60°C (140°F) Ambient
Application Type General Industrial ref: CSA22.2, No. 235-04
Method of Tripping Thermal “TO”, trip-free
Type of Actuation Reset button, type “R”
Weight Approximately 17 grams
Applicable Approvals UL 1077, CSA 22.2 No. 235-04, TÜV EN 60934
FEATURES
• Protectionrangeandoperatingvoltage:
0.1 to 16.0 Amps, 240 VAC, 50 VDC (cЯUus,cCSAus)
0.5 to 12 Amps, 240 VAC, 24 VDC (VDE)
• RoHScompliant,singlepole,thermalcurrentoverloadprotector
• Reliable,trip-freeoperationoncurrentoverloads
•Warranty:24-monthsfromdateofmanufacture
DESCRIPTION
The Airpax™ ATR20 product family is a single pole, thermally operated overload protector with a snap-acting trip mechanism that
provides reliable, trip-free operation on current overloads. The ATR20 series is designed with multiple mounting configurations