1
Mechatronic Analog Timer H3AM
Large Setting Dial and Moving Pointers
Ideal for Easy Operation and Monitoring
Incorporating
an easy-to-see large setting dial with
moving pointers.
Wide time-setting range of 0.2 s to 60 h (available
through three time-range model types)
Wide AC power supply range (100 to 240 VAC)
IP65 watertight and dust-tight front panel.
Approved by UL and CSA.
Conforms to IEC61812-1 (VDE0435/P2021)
Conforms to IEC60664-1 (VDE0110) 4KV/2
Conforms to EMC standards.
Six-language instruction manual provided.
Programmable contact enables the building of a
self-holding relay circuit as well as built-in
instantaneous contact. (-NS)
Memory retention (-NSR)
Finger protection terminal block
High immunity to inverter noise
Enables easy sequence checks through instanta-
neous
outputs for a zero set value at any time
range
R C
Ordering Information
Rated
supply
lt
Resetting
t
Control output T
ime range
a ed supp y
voltage
ese g
system
Co o ou pu
0.5 s to 30 h
(30 s, 3 min,
30 min, 3 h, 30 h)
1 s to 60 h (60 s,
6 min, 60 min, 6
h, 60 h)
0.2 s to 12 h
(12 s, 120 s
12 min, 120 min,
12 h)
100 to 240 V
AC Self-resetting
DPDT contact output
(T
ime-limit output SPDT and
switchable SPDT
(time-limit
instantaneous))
H3AM-NS-A H3AM-NS-B H3AM-NS-C
Electric
resetting
DPDT contact output
(T
ime-limit output SPDT and
instantaneous output SPDT)
H3AM-NSR-A H3AM-NSR-B H3AM-NSR-C
Model Number Legend
H3AM - NS 12
1.
Resetting System
None:Self-resetting
R:
Electric resetting
3. Accessory
None: Without accessory
300: W
aterproof Packing
(Y92S-35) provided
-3
-
2.
T
ime Range
A:
0.5 s to 30 h
B:
1 s to 60 h
C:
0.2 s to 12 h
Accessory
Item Model
Waterproof
Packing
Y92S-35
H3AM H3AM
2
Specifications
General
Operating
mode
ON-delay
Screw tightening torque
0.98 N
S
m (10 kgf) max.
Input type
V
oltage input
Output type Relay: DPDT
Mounting method
Flush/Panel mounting, no restriction on mounting angle.
Approved standards
UL 508, CSA C22.2 No. 14
Conforms to EN61812-1 (VDE0435/P2021), IEC60664-1 (VDE01104 kV/2, VDE0106/P100)
Conforms to EN50081-2 and EN50082-2
Time Ranges
Model Full
scale on
di l
Set time unit
ode
u scaeo
dial s
10 s
min
10 min
h (hour)
10 h (hour)
H3AM-jjj-A 3 ---
0.5 to 30 s
0.05 to 3 min 0.5 to 30 min 0.05 to 3 h 0.5 to 30 h
H3AM-jjj-B 6 ---
1 to 60 s
0.1 to 6 min 1 to 60 min 0.1 to 6 h 1 to 60 h
H3AM-jjj-C 12
0.2 to12 s 2 to 120 s
0.2 to 12 min 2 to 120 min 0.2 to 12 h
---
Note:
Instantaneous output is obtained by turning the time setting knob below “0” until the time setting knob stops.
Ratings
Rated
supply voltage
100 to 240 V
AC (50/60 Hz)
Operating voltage range
85% to 1
10% of rated supply voltage
Power reset (-NS)
Minimum power-opening time:
0.5 s
Reset input time (-NSR)
Minimum input time:
0.5 s
Reset voltage range (-NSR)
H level:
85 to 264 V
AC
L level:
0 to 10 V
AC
Power consumption
Approx. 9 V
A (Approx. 5 W)
Control output
Contact output: 5 A at 250 V
AC, resistive load (cosφ
= 1)
Ambient temperature
Operating: –10°
C to 55
°
C (with no icing)
Storage: –25°
C to 65
°
C (with no icing)
Ambient humidity
Operating:
35% to 85%
H3AM H3AM
3
Characteristics
Accuracy
of operating time
±
0.7% FS max.
Setting error ±
2% FS max.
Reset time
Power reset: 0.5 s max.
Reset input time: 0.5 s max.
Influence of voltage
±
1% FS max.
Influence of temperature
±
2% FS max.
Insulation resistance
100 M
max. (at 500 VDC)
Dielectric strength
2,000 V
AC (50/60 Hz) for 1 min between exposed non-current-carrying metal parts and
current-carrying metal parts
2,000 V
AC (50/60 Hz) for 1 min between the operating circuit and control output terminals
1,000 V
AC (50/60 Hz) for 1 min between the operating power supply circuit and reset input circuit
(H3AM-NSR only)
1,000 V
AC (50/60 Hz) for 1 min between contacts not located next to each other
2,000 V
AC (50/60 Hz) for 1 min between contacts of opposite poles
Impulse withstand voltage
3 kV between power terminals
4.5 kV between exposed non-current-carrying metal parts and current-carrying metal parts
Noise immunity
±
1.5 kV (between power terminals) square-wave noise by a noise simulator
(pulse width: 100 ns/1
µs, 1-ns rise)
Static immunity
Malfunction: 8 kV
Destruction: 15 kV
V
ibration resistance
Destruction:
10 to 55 Hz, 0.75-mm single amplitude
Malfunction:
10 to 55 Hz, 0.5-mm single amplitude
Shock resistance
Destruction:
300 m/s
2
(approx. 30G)
Malfunction:
150 m/s
2
(approx. 15G) (100 m/s
2
(approx. 10G) in the front/back direction)
Life expectancy
Mechanical:
5,000,000 times min. (under no load at 1,800 times/h)
Electrical:
100,000 times min. (5-A at 250 V
AC, resistive load at 1,800 times/h)
EMC (EMI): 50081-2
Emission Enclosure: EN55022 class A
Emission AC Mains:
EN55022 class A
(EMS): 50082-2
Immunity ESD:
EN61000-4-2:
4 kV contact discharge (level 2)
8 kV air discharge (level 3)
Immunity RF-interference:
ENV50140:
10 V/m (80 MHz to 1 GHz) (level 3)
ENV50204:
10 V/m (900 MHz
±
5 MHz) (level 3)
Immunity Power Frequency Magnetic Fields:
EN61000-4-8:
30 A/m (50 Hz) (level 4)
Immunity Conducted Disturbance:
ENV50141:
10 V (0.15 to 80 MHz) (level 3)
Immunity Burst:
EN61000-4-4:
2 kV power-line (level 3)
2 kV I/O signal-line (level 4)
Immunity Surge:
EN61000-4-5:
1 kV line to line
2 kV line to ground (level 3)
Enclosure rating
IP65 (front panel only) (see note) IP20 (terminal section)
Weight
Approx. 350 g
Note: A
separately sold
waterproof packing (Y92S-35) is necessary to ensure IP65 waterproofing between the T
imer and installation panel.
The H3AM-NSj-j
-300 model with waterproof packing is available.
H3AM H3AM
4
Nomenclature
Moving Pointer (green):
Displays remaining time.
Power Indicator
Setting pointer (orange)
Displays set value.
Output Indicator
Time Unit Indicator
Instantaneous or Time-limit
Output Selector for R2 Relay:
Default setting is time-limit
output
Time Unit Selector
Model Applicable time unit
Full
scale
on
dial
s 10 s min 10 min h 10 h
H3AM-jjj-A
H3AM-jjj-B
H3AM-jjj-C
3
6
12
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Applicable
T
ime Unit
(Illustrated Model: H3AM-
jjj-C)
H3AM H3AM
5
Operation
Timing Charts
Power supply (1-2)
Time-limit contact NC (3-4)
Time-limit contact NO (3-5)
Instantaneous contact NC (7-8)
Instantaneous contact NO (6-8)
Power indicator
Output indicator
Note: 1. The
R2 contacts (7-8 and 6-8) are programmable and can be set to either instantaneous or time-limit contact.
2.
“Rt” indicates reset time and “t” indicates set time.
Power supply (1-2)
Time-limit contact NC (3-4)
Time-limit contact NO (3-5)
Instantaneous contact NC (7-8)
Instantaneous contact NO (6-8)
Power indicator
Output indicator
Note:
Rt’ ” indicates reset input time and “t” indicates set
time.
Reset (9-10)
Rt’ Rt’
Time-limit contact NC (7-8)
Time-limit contact NO (6-8)
(see note 1)
H3AM-NS
H3AM-NSR
H3AM H3AM
6
Dimensions
Note: All
units are in millimeters unless otherwise indicated.
H3AM (Flush Mounting)
Mounting
Holes
Four, 5-dia. holes
27.5 dia. 81-dia. hole
96
77.5 dia.
Four, M4x17.5 screw boss
Note: Tightening
torque for panel mounting
is as follows:
300
m N
S
m
±
50 m N
S
m (3 kgf
S
cm
±
0.5 kgf
S
cm)
96
Waterproof Packing (Sold Separately)
Prevents
water ingress between the T
imer and panel.
Y92S-35
Installation
Internal Connections and Terminal Arrangement
H3AM-NS H3AM-NSR
Power supply
(See
note)
*
Power supply
Use
the same power source for the power sup
-
ply
and reset input and wire
the circuit so that the
terminals (1) and (10) terminals (2) and (9) be-
come the same phase respectively.
Reset
Note: The
R2 relay can be set
to either instantaneous or time-limit contact using the switch located on the bottom of the T
imer (H3AM-NS
models).
H3AM H3AM
7
Precautions
Before Use
Before using the H3AM-NSR, apply voltage between terminals 9
and
10 to reset the operation.
When
changing the setting time of the H3AM-NSR to a longer time
value,
be sure to apply voltage between terminals 9 and 10
during
the
change, otherwise the T
imer may malfunction.
Correct Use
Setting
Changes
Be
sure to
adjust the time unit selector and instantaneous or time-
limit
output selector for R2 relay only before the T
imer is turned ON,
otherwise
the T
imer may be damaged or malfunction.
Be
sure
to set the time only when T
imer has stopped, otherwise the
Timer
may malfunction.
Power Supply
Use
a switch or relay contact to impose supply voltage on the T
imer
at one time. If the supply voltage
is
imposed on the T
imer gradually
,
the
T
imer may not reset or a time-up error may result.
T
ime Setting
Do
not turn the time setting knob beyond the permissible range. If
a
precise
time setting is required, check the operation of the T
imer in
trial
operation before the T
imer is put in actual operation.
Operating Environment
If
the T
imer is used in any place that may be af
fected by noise, be
sure
to separate the T
imer
, input device, and connecting wires from
the
noise source. The use of shielded wires for the input line is rec
-
ommended.
The
external surfaces of the T
imer may be af
fected by organic sol
-
vents
such as thinner
, benzine, or a strong alkaline or strong acidic
substance.
Do
not use the T
imer in a location where the T
imer is exposed to cor
-
rosive
gas or direct sunlight or where there is excessive dust.
W
ater Protection
When
mounting the T
imer on a panel, evenly tighten the T
imer to
a
specified torque. If the T
imer using waterproof packing is tightened
to
a torque other than the specified value,
required waterproof prop
-
erties
will not be achieved.
Others
If
the T
imer is mounted on a control panel, dismount the T
imer from
the control panel or short-circuit the circuitry before carrying out a
voltage withstand test between the electric circuitry and non cur-
rent-carrying
metal part
of the machine, in order to prevent the inter
-
nal
circuitry of the TImer from damage.
The
internal elements may be damaged if a voltage other than the
rated
supply voltage is applied.
Precautions for VDE Conformance
The
H3AM as a built-in timer conforms to VDE0435/P2021 provided
that
the following conditions are satisfied:
The
output section of the H3AM is provided only with basic
isolation.
To
ensure reinforced
isolation required by the VDE standards, pro
-
vide supplementary basic isolation on the load side connected to
the
output.
The H3AM itself is designed according to the following:
Overvoltage category III
Pollution degree 2
On the above basis:
Operation parts on the front and bottom: Reinforced isolation
With
clearance of 5.5 mm and creepage distance of 5.5 mm at
240
V
AC
Output: Basic isolation
With
clearance of 3.0 mm and creepage distance of 3.0 mm at
240 V
AC
H3AM H3AM
8
OMRON Corporation
Industrial
Devices and Components Division
Supervisory Control Devices Division
28th Fl., Crystal T
ower Bldg.
1-2-27, Shiromi, Chuo-ku,
Osaka 540-6028 Japan
Phone:
(81)6-949-6014 Fax: (81)6-949-6069
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To
convert millimeters into inches, multiply by 0.03937. T
o convert grams into ounces, multiply by 0.03527.
Cat. No. L095-E1-1 In the interest of product improvement, specifications are subject to change without notice.
Printed
in Japan
0998-2M (0298)