603221/011
System pro M
Modular devices for
low voltage installations
Technical catalogue
1
Introduction
MCBs
RCDs
Other modular devices Protection devices
Command devices
Load management devices
Measurement devices
Other modular functions
Unifix cabling system
Technical details
Overall dimensions
Application sheets
Product by product general contents
Code list
1
2
3
4
5
6
7
8
9
10
11
12
13
CONTENTS
14
II ABB SACE
The ABB Group’s involvement in research projects and pilot ventures which are
capable of combining the objectives of economic growth with the main social and
environmental needs is behind its commitment to ensure that all the
manufacturing and services sites worldwide obtain ISO 14001 environmental
management system certification.
ABB SACE is one of the forerunners among the companies in the Group in
dedicating considerable resources towards reaching its objectives of sustainable
development and environmental protection. This is confirmed by the fact that all
the company manufacturing sites have been awarded ISO 9001 quality
certification and most of them have also been awarded ISO 14001 environmental
management system certification. The plants in Frosinone and Patrica also have
been awarded the Quality, Enviroment and Safety integrated system certification
and are certified in compliance with the BS 8800 Standards for health and safety
in the workplace.
ABB SACE is actively involved in continuing the policy of improving environmental
management by rationalizing the consumption of raw materials and energy,
preventing pollution, respecting water and air, reducing noise levels to a minimum,
reducing waste from production processes and carrying out periodic
environmental checks at the main suppliers’ premises.
By using analysis tools such as LCA (Life Cycle Analysis), from the initial design
stages ABB SACE assesses and improves the environmental performance of its
products throughout their entire life cycle in order to guarantee maximum
efficiency in technical and energy performance during operation, control and
reduce environmental impact in the manufacturing stage and define end-of-life
procedures.
All these goals and activities are the result of a far-sightedness in adopting
ecological policies and methods of reducing environmental impact and, here too,
ABB SACE is, as already seen in the quality of its products, a leader on the Italian
company scene.
ABB SACE
and its commitment to protecting the
environment
II
III
ABB SACE
Plant in Pomezia - Rome III
1/2
1
ABB SACE
Introduction
Selection and design tools
Flexible management, services and advice: a complete package
To make selecting its products easier, ABB SACE guarantees 360° support both before and after
purchase and provides tools for designing and sizing electrical installations which make calculations
quicker, ensure that installations comply with regulations and reduce the risk of error:
The main ABB SACE compu-
ter tools for designing and
estimating costs in electrical
installations include:
-D.O.C./Win (Design Opti-
mization & Computation),
a system used to size low
voltage industrial electrical in-
stallations correctly and is
based on calculation models
from the most recent regula-
tions;
-C.A.T. (Computer Aided
Technical Selection), an
electronic catalogue and
technical tool used to select
and accessorize moulded-
case and air circuit-breakers
and ABB SACE products for
industrial applications.
Other tools
Four different coloured slide-
rules, which are part of the ABB
Kit, are used to rapidly calcu-
late the sizing of an electrical
installation, and more specifi-
cally, size cables and calculate
short-circuit currents, check
protection devices for direct
contacts and cable short-
circuiting, effect selective and
support coordination and size
motor lines and transformer
boot-strapping.
The calculation methods and
data shown on the rules are
based on the CEI, IEC and NFC
Standards in force and on plant
practice and experience.
Prompt orders and flexible
management
ABB SACE’s order procedures
have been conceived to ensure
efficient and flexible manage-
ment of their warehouses.
An order file can be generated
in the EDIFACT standard (Metel
or ABB) and transmitted elec-
tronically via EDI (Electronic
Data Interchange).
Using the EDI protocol to send
an order rationalizes the sup-
ply chain and reduces transfer
times and the risk of error. With
the EDI system, it is possible to
automatically load the order at
ABB SACE so that the request
is sent to production and con-
firmation of the order, a dis-
patch note and the invoice are
immediately sent to the cus-
tomer.
Training: an essential tool
for professionals
ABB SACE shares its own ex-
perience gained in over 60
years of activity by holding
technical courses which pro-
vide all sector operators with
training and discussion with
experts in the field.
Information and training are in-
1/3
1
ABB SACE
Introduction
Selection and design tools
creasingly becoming success
factors for professional growth
and development. Professional
training, both from a technical
and legislative point of view, is
indeed essential considering
the important implications it has
for safety of personnel and in-
stallations. Our main aim is to
meet the information needs of
the experts, converting techni-
cal and legislative concepts into
practical terms which can be di-
rectly applied to the different
products and installations.
1/4
1
ABB SACE
Many of the most important
automation system compo-
nents that ABB SACE supplies
to meet the modern demands
for building management (bus
systems) are constructed in
modular form and can therefore
be installed on a DIN rail.
These systems, which operate
in compliance with the EIB Eu-
ropean Standards, ensure high
quality level integration with the
Introduction
Building automation components
control functions of technologi-
cal installations: lighting, heat-
ing, ventilation, air conditioning,
control of electric loads, signal-
ling, alarms, motorized loads
(blinds, gates, pumps, etc.).
They are suitable for buildings
with very complex manage-
ment problems such as offices,
factories, schools, hotels, hos-
pitals but their highly flexible
application means that they can
also be used in private homes.
From an installation point of
view, the first big difference be-
tween bus systems and tradi-
tional installations is the differ-
ent wiring system used.
As is common knowledge, in
bus systems there is no direct
connection between each con-
trol device (eg.: switch) and the
loads (eg.: lamps) it must con-
trol. The signals and com-
mands are sent by way of the
transmission bus and only col-
lected by the relevant loads.
In most modern applications,
the transmission bus consists
of a single dedicated cable but
it may also consist of optical fi-
bre cables or electric cables, for
example 220V cables, which
are already in the building
(power line system).
The main advantage of bus
systems lies with the reduction
in installation time and number
of cables required. When a
dedicated duplex cable is used,
the power cables (220V, 380V)
must be laid exclusively to take
the electric supply to the loads
and must not be wired to con-
nect the control devices di-
rectly, whereas with power line
systems it is not necessary to
add new cables to the already
existing ones.
Another advantage is the flex-
ibility of installations. Since sig-
nals and commands are ex-
changed between devices us-
ing coded addresses and each
data element which circulates
on the bus is therefore only col-
lected by the devices whose
address corresponds to the
one coded in the message, it
follows that by using software
to modify the addresses the
correlations between the de-
vices and the operating condi-
tions of the installation can be
modified without having to
1/5
1
ABB SACE
Introduction
Building automation components
Input terminal
Special
device
BUS LINE
Output
terminal Coordination and
supervision
workstation
(if necessary)
Command
by way of
terminal
relay
Loads
Power line
……
Conventional devices
(voltage-free contacts)
touch the wiring.
This flexibility, together with the
use of the EIB standard proto-
col (which enables components
from different suppliers to be
entered, each one with their
own specialized field: electrical,
thermal, hydraulic, etc.), means
that the customer has a very
wide range of functions at his
disposal which can be custom-
ized according to the specific
requirements of each installa-
tion and load.
For further information on the
building automation systems,
ABB SACE can supply the rel-
evant technical documentation.
1/6
1
ABB SACE
Introduction
System pro
M
modular devices for
low voltage installations
TEPM0010
System pro M is a modular system developed by ABB SACE which
is capable of meeting the requirements of the most modern and
up-to-date installations for low voltage applications.
Project criteria
The system is based on two main criteria: complete functionality
and optimum sizing of the devices. The first means there is a wide
range of devices which leads to increased safety for the user and
greater diversification in switching and load management; the
second, based on the modular structure used, allows the internal
space of the switchboard to be used in the best possible way,
reduces wiring operations and improves functionality and
appearance of the switchboards.
Functions
Protection, command, measure and load management: for each
of these four basic functions which characterize the low voltage
electrical applications, the System pro M series proposes the right
device.
The protection sector which is the basis of the system consists of
MCBs, RCBOs, RCCBs and RCD blocks.
These miniature modular devices are technologically advanced,
which speeds up installation and simplifies maintenance.
OEPM0010
1/7
1
ABB SACE
Introduction
System pro
M
modular devices for
low voltage installations
Standards and certification
Each device in the System pro M series has been designed in
accordance with strict criteria for safety and functionality in
compliance with the dictates imposed by international, European
and Italian Standards.
For this reason, the devices in the System pro M series have
obtained standardization issued by the certifying bodies both in
Italy and overseas.
Tropicalization
All the devices in the System pro M series, and especially those
used for protection, have been carefully designed and constructed
to guarantee the maximum operating safety even in difficult
environmental conditions. According to the type of device, the metal
parts of the switching mechanisms are protected with a suitable
galvanic coating or are made of stainless steel to avoid oxidation
which may impair operating; even the conductive parts are
protected by galvanic coating. The tropicalized devices can
withstand the test conditions established in the relevant current
Standards (VDE DIN 40046, IEC 68.2, DIN 50016).
TEPM0011
OEPM0011
2/1
2
ABB SACE
MCBs
Contents
General information ..............................................................................................................2/2
General characteristics and breaking capacities ..............................................................2/4
S 9.. range ..............................................................................................................................2/7
S 2.. range ............................................................................................................................2/19
S 290 range ..........................................................................................................................2/49
S 500 range ..........................................................................................................................2/57
S 700 range ..........................................................................................................................2/69
ABB SACE
2/2
2
ABB SACE
MCBs
General information
Designed to protect against
overload and short-circuit,
MCBs are vitally important de-
vices for reliable and safe ope-
rating of installations.
National and international
Standards establish the basic
requirements of these circuit-
breakers, but the task of cor-
rectly developing the various
characteristics of a circuit-
breaker so that it is really reli-
able depends on the expe-
rience of the manufacturer.
For this reason, the reliability
and versatility of ABB’s MCBs
is the result of perfectly harmo-
nizing different parameters
which define the technical and
installation characteristics in-
cluding:
tripping characteristics (B, C,
D, K, Z) which are suitable for
the different applications;
limiting the specific let-
through energy i2(t)dt down-
stream of the circuit-breakers
2/3
2
ABB SACE
MCBs
General information
in the event of short-
circuiting, thereby avoiding
damage to cables and equip-
ment;
limiting the peak current Ip;
current rated value In;
breaking capacity, referring to
the Standards established for
a particular field of applica-
tion;
wide range of auxiliary
elements (auxiliary contacts,
signal contacts, undervoltage
releases, shunt trips, me-
chanical interlocks, etc.);
life cycle guaranteed by a
large number of electric and
mechanic operations;
adequate resistance to
bumps and vibrations;
suitable protective criteria
(tropicalization) for harsh en-
vironmental conditions in
which the equipment may be
used.
Series
Characteristics
Rated current [A]
Breaking capacity [kA]
Reference Standards n° poles Ue [V]
IEC 898/EN 60898-1 Icn 230/400
IEC 947-2/EN 60947-2 Icu 1 127
alternating current 230
1P+N 127
230
2 230
400
3,4 230
400
3 500
690
Ics 1 127
230
1P+N 127
230
2 230
400
3,4 230
400
3 500
690
EN 60898-2 Icu 124
IEC 947-2/EN 60947-2 60
direct current 75
250
248
75
125
250
500
3 250
500
750
Ics 124
60
75
250
248
75
125
250
500
3 250
500
750
S 941N S 951N S 971N S 240
CB CB CBC
2 In 40 6 In 40 2 In 40 6 In 40 2 In 40 6 In 40 6 In 40
4.5 4.5 6 6 10 10 4.5
10
6
10 10 15 15 25 25 10
6 6 10 10 15 15 6
7.5
7.5
10
7.5
10
6
6 6 10 10 15 15 10
4.5 4.5 6 6 10 10 6
7.5
5.6
10
5.6
8
6
8
6
6
8
6
8
6
6
Automatici
NOTE: the breaking capacity of the circuit-breakers with rated
currents lower or equal to 2A can be considered infinite since the
high value of the coil inductance limits any short-circuit current to
values which the device can interrupt.
2/4
2
MCBs
General characteristics and breaking capacities
S 250 S 27 S 280
C B K C, D B K B, C, D K, Z
3 In 63 6 In 63 6 In 63 3 In 63 6 In 63 6 In 63 10 In 25 32 In 40 6-50-63 10 In 25 32 In 40
6 6 10 10 25 15 10
30 30 30 35 35 35 50 40 35 50 40
10 10 10 15 15 15 25 20 15 25 20
30 30 30 35 35 35
10 10 10 15 15 15
20 20 20 25 25 25 40 30 25 40 30
10 10 10 15 15 15 25 20 15 25 20
20 20 20 20 20 20 40 30 20 40 30
10 10 10 15 15 15 25 20 15 25 20
22.75 22.75 22.75 26.2 26.2 26.2 37.5 30 26.2 37.5 30
7.5 7.5 7.5 11.2 11.2 11.2 25 20 11.2 25 20
22.75 22.75 22.75 26.2 26.2 26.2
7.5 7.5 7.5 11.2 11.2 11.2
15 15 15 18.7 18.7 18.7 30 22.5 18.7 30 22.5
7.5 7.5 7.5 11.2 11.2 11.2 18.75 15 11.2 18.75 15
15 15 15 15 15 15 30 22.5 15 30 22.5
7.5 7.5 7.5 11.2 11.2 11.2 12.5 10 11.2 12.5 10
20 20 20 30 30 30 30 30 20 30 30
10 10 10 15 15 15 15 15 10 15 15
20 20 20 30 30 30 30 30 20 30 30
10 10 10 15 15 15 15 15 10 15 15
10 10 10 15 15 15 15 15 10 15 15
20 20 20 30 30 30 30 30 20 30 30
10 10 10 15 15 15 15 15 10 15 15
20 20 20 30 30 30 30 30 20 30 30
10 10 10 15 15 15 15 15 10 15 15
10 10 10 15 15 15 15 15 10 15 15
S 280 UC S 290 S 500 S 500 UC S 700
K,Z B,C,K, Z C, D B, C, D K reg. B K E sel.
3-6-50-63 0.5 In 40 50 In 63 80 In 12 6 In 63 0.1 In 11 10 In 45 6 In 63 0.1 In 45 25 In 100
10 25
35 50 20 50 50
15 12.5 12.5 15 50 50
25 25 10 25 50 50
15 12.5 4.5 15 50 30
20 25 50 50 30 50
15 15 50 50 30 30
15 20 15 15
66 6 10
26.2 50 20 25 25
11.2 12.5 12.5 10 25 25
18.7 25 10 20 25 25
11.2 12.5 4.5 10 25 15
15 20 25 30 25 25
11.2 10 25 30 25 15
11 15 11 7.5
33 3 5
20 50 50 15 30 50 50
10 30 40 15 30 50 50
15 20 30 50 50
64.5 30 30
20 50 50 20 30 50 50
10 30 40 15 30 50 50
10 30 40 15 30 50 50
25 25 50 50
64.5 30 30
50 50
50 50
30 30
20 50 50 15 30 50 50
10 30 30 15 30 50 50
15 15 30 50 50
66 30 30
20 50 50 20 30 50 50
10 30 40 15 30 50 50
10 30 40 15 30 50 50
25 25 50 50
64.5 30 30
50 50
50 50
30 30
2/6
2/6 ABB SACE
The S 9 range of circuit-
breakers is the widest range
of 1P+N MCBs in one mod-
ule.
These circuit-breakers are
available with rated currents
from 2 to 40A when using the
characteristic “C” and with
rated currents from 6 to 40A
when using the characteris-
tic “B”.
For each current, there are
also four different breaking
capacities available: 3kA (S
931N series), 4.5kA (S 941N
series), 6kA (S 951N series)
and 10kA (S 971N series).
These circuit-breakers have
been designed so that they
ensure, in the last closing
section, that the closing
speed of the contacts is in-
dependent of the rotating
speed of the knob.
(16 mm2 on all versions) have
been developed.
The S 9 range circuit-break-
ers have been designed for
wiring with the ABB SACE
Unifix rapid system using spe-
cial connections.
These circuit-breakers are
also supported by a complete
group of auxiliary elements
which effect many functions
and configurations such as
auxiliary contacts, signal con-
tacts, undervoltage releases
and shunt trips.
The trip device (ABB interna-
tional patent) ensures perfect
closure every time thus con-
siderably improving the perfor -
mance of these devices and
extending the average life
cycle.
A redesigned red/green
toggle makes the ON/OFF
status immediately evident.
The terminals have also been
designed for safe and easy
use and, to this end, new high
capacity cage type terminals
2/7
2
ABB SACE
S 9.. range
Contents
Technical characteristics .........................................................................................................2/8
Order information
S 931 N series ......................................................................................................................2/10
S 941 N series ......................................................................................................................2/11
S 951 N series ......................................................................................................................2/12
S 971 N series ......................................................................................................................2/13
Auxiliary elements
Shunt trips .............................................................................................................................2/15
Auxiliary/signal contacts........................................................................................................2/16
Undervoltage releases ..........................................................................................................2/17
2/8
2
ABB SACE
S 9.. range
Technical characteristics
S 931N S 941N
Standards IEC 898 / EN 60898, IEC 947-2 / EN 60947-2
Rated current In [A] 2 <In < 40
Poles 1P+N
Rated voltage Ue 1P+N AC [V] 230
Insulation voltage Ui [V] 500
Max. operating voltage Ub max. [V] 250
Min. operating voltage Ub min. [V] 12VAC - 12VDC
Rated frequency [Hz] 50…60
Rated breaking capacity Icn [A] 3000 4500
acc. to IEC 898
Rated breaking capacity ultimate Icu [kA] 4.5 6
acc. to IEC 947-2
1P+N - 230 V service Ics [kA] 4.5 4.5
Voltage withstanding impulse (1,2/50)
capacity Uimp [kV] 5 5
at rated freq.
(50-60Hz) x 1 min. [kV] 3 3
Thermomagnetic release B: 3 In < Im < 5 In
characteristic C: 5 In < Im < 10 In
D: 10 In < Im < 20 In
K: 8 In < Im < 14 In
Z: 2 In < Im < 3 In
Limitation class 3
Toggle black sealable in ON-OFF position
Electrical life 10000
Mechanical life 20000
Protection degree housing IP4X/IPXXD (excluding terminal area)
terminals IP2X/IPXXB
Self-extinguishing degree V0 thickness 1.6 UL 94 yellow paper
Mechanical shock resistance minimum 30 g - 2 shocks - duration 13 ms
Resistance to vibrations acc. to IEC 68-2-6 > 6 g
Tropicalization humid heat [°C/RH] 28 cycles with 55/95…100
acc. to IEC 68-2 constant climatic
conditions [°C/RH] 23/83 - 40/93 - 55/20
variable climatic
conditions [°C/RH] 25/95 - 40/95
Ambient temperature
(with daily average<+35°C) [°C] -25…+55
Storage temperature [°C] -40…+70
Terminal size upper/lower per cable [mmq] 16/16
Mounting on DIN rail EN 50022 (35mm) by means of rapid fixing device
Pole dimensions [mm] H: 83 x D: 70 x W: 17.8
Pole weight [g] 110
2/9
2
ABB SACE
S 951N S 971N
IEC 898 / EN 60898, IEC 947-2 / EN 60947-2
2 <In < 40
1P+N
230
500
250
12VAC - 12VDC
50…60
6000 10000
10 15
610
55
33
••
••
3
black sealable in ON-OFF position
10000
20000
IP4X/IPXXD (excluding terminal area)
IP2X/IPXXB
V0 thickness 1.6 UL 94 yellow paper
minimum 30 g - 2 shocks - duration 13 ms
> 6 g
28 cycles with 55/95…100
23/83 - 40/93 - 55/20
25/95 - 40/95
-25…+55
-40…+70
16/16
on DIN rail EN 50022 (35mm) by means of rapid fixing device
H: 83 x D: 62 x W: 17.8
110
2/10
2
ABB SACE
Breaking capacity
acc. to IEC 898 / EN 60898
In [A] poles voltage [V] Icn [kA]
2...40 1+N 230 3
S 9.. range
S 931 N series
Accessories ................................................... pg. 2/15 Technical details ........................................... pg. 10/4 Overall dimensions ........................................ pg. 11/4
Rated
currents Code
In Characteristics
[A] C
1P+N - S 931 N type
211861114
411861115
611861116
10 11861117
16 11861118
20 11861119
25 11861120
32 11861121
40 11861122
IMQ approval
S 931 N 230V
4.5kA B-C characteristics
In = 2…40A
1P+N
B (Im = 3…5 In)
C (Im = 5…10 In)
Tripping characteristics
Breaking capacity
IEC 898 / EN 60898: Icn = 3kA, Icn1 = 3kA
IEC 947-2 / EN 609472: Icu = 4.5kA, Ics = 4.5kA
Application: residential or similar
Connections for UNIFIX available
RCBO version
DS 941 SERIES
TEPM0060
2/11
2
ABB SACE
Breaking capacity
acc. to IEC 898 / EN 60898
In [A] poles voltage [V] Icn [kA]
2...40 1+N 230 4.5
S 9.. range
S 941 N series
Accessories ................................................... pg. 2/15 Technical details ........................................... pg. 10/4 Overall dimensions ........................................ pg. 11/4
Rated
currents Code
In Characteristics
[A] B C
1P+N - S 941 N type
2EE 550 8
4EE 551 6
6EE 540 9 EE 552 4
10 EE 541 7 EE 553 2
16 EE 542 5 EE 554 0
20 EE 543 3 EE 555 7
25 EE 544 1 EE 556 5
32 EE 545 8 EE 557 3
40 EE 546 6 EE 558 1
IMQ approval
S 941 N 230V
4.5kA B-C characteristics
In = 2…40A
1P+N
B (Im = 3…5 In)
C (Im = 5…10 In)
Tripping characteristics
Breaking capacity
IEC 898 / EN 60898: Icn = 4.5kA, Icn1 = 3kA
IEC 947-2 / EN 60947-2: Icu = 6kA, Ics = 4.5kA
Application: residential or similar
Connections for UNIFIX available
RCBO version
DS 941 SERIES
TEPM0060
2/12
2
ABB SACE
Breaking capacity
acc. to IEC 898 / EN 60898
In [A] poles voltage [V] Icn [kA]
2...40 1+N 230 6
Accessories .................................................... pg. X/X Technical details .............................................pg. X/X Overall dimensions ......................................... pg. X/X
S 9.. range
S 951 N series
IMQ approval
S 951 N 230V
6kA B-C characteristics
In = 2…40A
1P+N
Rated
currents Code
In Characteristic
[A] B C
1P+N - S 951 N type
2EE 570 6
4EE 571 4
6EE 560 7 EE 572 2
10 EE 561 5 EE 573 0
16 EE 562 3 EE 574 8
20 EE 563 1 EE 575 5
25 EE 564 9 EE 576 3
32 EE 565 6 EE 577 1
40 EE 566 4 EE 578 9
B (Im = 3…5 In)
C (Im = 5…10 In)
Tripping characteristics
Breaking capacity
IEC 898 / EN 60898: Icn =6kA, Icn1 = 3kA
IEC 947-2 EN 60947-2: Icu = 10kA, Ics = 6kA
Application: residential, commercial
Connections for UNIFIX available
RCBO version
DS 951 SERIES
TEPM0060
Accessories ................................................... pg. 2/15 Technical details ........................................... pg. 10/4 Overall dimensions ........................................ pg. 11/4
2/13
2
ABB SACE
Breaking capacity
acc. to IEC 898 / EN 60898
In [A] poles voltage [V] Icn [kA]
2...40 1+N 230 10
S 9.. range
S 971 N series
Accessories ................................................... pg. 2/15 Technical details ........................................... pg. 10/4 Overall dimensions ........................................ pg. 11/4
Rated
currents Code
In Characteristic
[A] B C
1P+N - S 971 N type
2EE 590 4
4EE 591 2
6EE 580 5 EE 592 0
10 EE 581 3 EE 593 8
16 EE 582 1 EE 594 6
20 EE 583 9 EE 595 3
25 EE 584 7 EE 596 1
32 EE 585 4 EE 597 9
40 EE 586 2 EE 598 7
IMQ approval
S 971 N 230V
10kA B-C characteristics
In = 2…40A
1P+N
B (Im = 3…5 In)
C (Im = 5…10 In)
Tripping characteristics
Breaking capacity
IEC 898 / EN 60898: Icn = 10kA, Icn1 = 3kA
IEC 947-2 / EN 60947-2: Icu = 15kA, Ics = 10kA
Application: commercial or industrial
Connections for UNIFIX available
RCBO version
DS 971 SERIES
TEPM0060
2/14
2
ABB SACE
S9-V
UNDERVOLTAGE
RELEASE
ONE-POLE
+ NEUTRAL
S941 N
S951 N
S971 N
MCB
S9-T
SHUNT TRIP
S9-X
AUXILIARY
CONTACT OR
S9-S SIGNAL
CONTACT
S9-X
AUXILIARY
CONTACT
S9-X
AUXILIARY
CONTACT
S 9.. range
Auxiliary elements
Overall dimensions ...................................... pg. 11/10
For the S 9 circuit-breakers
undervoltage releases and con-
tacts (auxiliary and signal) are
available.
The accessories are installed in
different positions: shunt trips
and undervoltage releases are
installed to the left of the circuit-
breaker whereas the contacts
(signal and auxiliary) are installed
to the right.
These elements provide addi-
tional functions and are all
coupled directly to the circuit-
breaker without the use of other
components such as pins or
clips.
The auxiliary contact is equipped
with a green indicator which
shows the position of the circuit-
breaker (when the circuit-
breaker is in the “open” position
the indicator protrudes. The
same indicator also enables a
TEST of the auxiliary circuit.
The signal contact is equipped
with a yellow indicator which
protrudes out when the circuit-
breaker trips. This indicator also
manually resets the signal circuit
(RESET).
The signal contact is also
equipped with a test button
(TEST) which tests the signal cir -
cuit contact irrespective of the
state of the MCB.
On each circuit-breaker in the
S 9 range, up to a maximum of
3 contacts can be used (the sig-
nal contact, if necessary , should
be installed directly on the cir-
cuit-breaker and only one can
be used).
Shunt trips and undervoltage
releases are equipped with a
protruding red indicator which
shows opening of the circuit-
breaker (if caused by the re-
lease).
There are also two versions of
the undervoltage releases
equipped with a tripping delay
of 100ms (S 9-V24CA and
S 9-V24CC types), which pre-
vents undesirable tripping
caused by microinterruption or
drop in the network voltage
which lasts less than 100ms.
The rules for accessorizing are
shown in the figure below.
Examples of combinations of S 941N, S 951 N and S 971 N circuit-breakers with auxiliary elements (maximum configurations)
TEPM0424
2/15
2
ABB SACE
S 9.. range
Auxiliary elements
Overall dimensions ...................................... pg. 11/10
Shunt trips
They are used to trigger remote opening of the MCBs.
They have an integrated signal contact that indicates the contact position of the breaker they are
connected to.
Code Type Description
(for S 941 N, S 951 N and S 971 N series)
EE 619 1 S 9-T24 12-24V a.c./d.c.
EE 620 9 S 9-T130 48-130V a.c./48-60V d.c.
EE 621 7 S 9-T415 220-415V a.c./110-250V d.c.
Technical characteristics
Type S 9-T24 S 9-T130 S 9-T415
Coil voltage [V] a.c. 12…24 48…130 220…415
[V] d.c. 12…24 48…60 110…250
Frequency [Hz] 50…60
Consumption on
release [VA] 20VA (12V a.c.) 22VA (48V a.c.) 40VA (220V a.c.)
90VA (24V a.c.) 200VA (130V a.c.) 130VA (415V a.c.)
20VA (12V d.c.) 22VA (48V d.c.) 10VA (110V d.c.)
90VA (24V d.c.) 20VA (250V d.c.)
Terminals [mm2]2 x 1.5
S971N
S9-T24, S9-T130, S9-T415
TEPM0421
OEPM0285
OEPM0286
1
2
C1
C2
,,
Installation only on left
s
2/16
2
ABB SACE
S 9.. range
Auxiliary elements
Overall dimensions ...................................... pg. 11/10
Auxiliary/signal contacts
The auxiliary contact indicates the position of the circuit-breaker contact. When the position of the
contacts change, whether manually or automatically, they indicate their status.
The signal contact indicates the position of the circuit-breaker contacts after automatic release of the
circuit-breaker caused by overload or short-circuit. For manual operation, it does not trip. The signal
contacts in the S 941 N, S 951 N and S 971 N series breakers are equipped with a test button on the
front of the accessory which simulates the functions without acting directly on the circuit-breaker.
Code Type Description
(for S 941 N, S 951 N and S 971 N series)
EE 610 0 S9-X auxiliary contact 1NO + 1 NC (1/2 module)
EE 611 8 S9-S signal contact (1/2 module)
S9-X S9-S
N
S971N
OFF
11 1
2
12 14
95 1
2
96 98
TEPM0422
OEPM0287
OEPM0288
2/17
2
ABB SACE
S 9.. range
Auxiliary elements
Overall dimensions ...................................... pg. 11/10
Undervoltage releases
These are used and/or to effect a positive safety emergency stop and/or to protect the load in the
event of a voltage drop (threshold between 70% and 35% of its rated value). If used for an emergency
stop, they cause undesirable tripping also for temporary micr ointerruptions of the voltage for a few
dozen milliseconds. Shunt trips equipped with a tripping time delay of 100ms (S 9-V24CA and S 9-
V24CC types) are different and eliminate undesirable tripping when there is an interruption in the
network voltage which is less than 100ms. ABB SACE has also developed DDA AE blocks which
perform the residual current function and the positive safety emergency stop without use of an
auxiliary energy source (battery) and auxiliary circuits. The DDA AE block performs the functions of
an undervoltage release but without the disadvantages of an undesirable tripping (see page 3/54).
Code Type Description
(for S 941 N, S 951 N, S 971 N series)
EE 612 6 S 9-V24CA 24V a.c. undervoltage release with delay
EE 613 4 S 9-V24CC 24V d.c. undervoltage release with delay
EE 614 2 S 9-V48CA 48V a.c. undervoltage release
EE 615 9 S 9-V48CC 48V d.c. undervoltage release
EE 616 7 S 9-V230CA 230V a.c. undervoltage release
1
2
D1
D2
S971N
TEPM0423
OEPM0286
OEPM0289
2/18 ABB SACE
The S 2 range consists of 6
series of circuit-breakers which
are capable of meeting all the
protection requirements of cir-
cuits up to 63A, from domestic
to industrial applications.
The S 240 – S 250 – S 270 –
S 280 series are available in 1P-
2P-3P-4P versions with
thermomagnetic releases in C
(S 240 – S 250 – S 270 – S
280), B (S 250 – S 270 – S 280),
D (S 270 – S 280), K (S 270 – S
280) and Z characteristic (S
280).
These 4 series have the follow-
ing breaking capacities accord-
ing to IEC 898 / EN 60898:
4.5kA for the S 240 series, 6kA
for the S 250 series, 10kA for
the S 270 series and 25kA for
the S 280 (10A In 25A) se-
ries.
Recently the S 280 series has
been enlarged with the new
80A and 100A rated current
versions (one pole, one mo-
dule) available in B and C cha-
racteristics, 6kA breaking ca-
pacity according to IEC 898 /
EN 60898 Standard and
35mm2 size of the terminals.
The range also includes the S
280 UC series which protects
direct current circuits with up to
250V d.c. per pole.
The M 280 series has recently
been developed and consists
of 1P-2P-3P-4P circuit-break-
TEPM0026
TEPM0027
TEPM0028
TEPM0029
ers with magnetic only releases
which are particularly suitable
for protecting motors with high
start-up currents.
All circuit-breakers in the S 2
range have self-supporting
mechanical parts; in these
breakers, there is no specific
mechanical constraint between
the case and the internal me-
chanical components which
form three independent func-
tional blocks; in this way, any
distortion of the case, in the
event of thermal shock, does
not affect the corr ect function-
ing of the circuit-breaker.
The supply lines of the pro-
tected circuits can be con-
nected to either the upper or
lower terminals of the circuit-
breakers (reversibility of con-
nections).
Another feature of the circuit-
breakers in this range is the
double terminal which enables
simultaneous connection of
cables and busbars.
Almost all the series are manu-
factured with the maximum self-
extinguishing degree (V0 level
with 1.6 mm thickness), non-
toxicity and non-opaque smoke
at the highest level, as requir ed
in the Standards of cables and
Specifications for railways and
undergrounds.
All the circuit-breakers in the
S 2 range with C and B cha-
racteristics have IMQ approval
which demonstrates the high
level of quality achieved.
On some of the series, approval
from the Italian Naval Register
(R.I.Na.) and the main naval
certifying bodies (see detailed
indications for each series) is
also available.
2/19
2
ABB SACE
S 2.. range
Contents
Technical characteristics .......................................................................................................2/20
Order information
S 240 series ..........................................................................................................................2/22
S 250 series ..........................................................................................................................2/24
S 270 series ..........................................................................................................................2/27
S 280 B-C-D series ...............................................................................................................2/30
S 280 K-Z series ...................................................................................................................2/32
S 280 UC series ....................................................................................................................2/34
M 280 magnetic only series ..................................................................................................2/36
Auxiliary elements
Shunt trips .............................................................................................................................2/39
Auxiliary/signal contacts........................................................................................................2/40
Undervoltage releases ..........................................................................................................2/41
Mechanical interlocks............................................................................................................2/42
Mechanical interlocks with signal contact .............................................................................2/43
Accessories
S 2.. range accessories ........................................................................................................2/45
2/20
2
ABB SACE
S 2.. range
Technical characteristics
S 240 S 250 S 270
Standards IEC 898 / EN 60898, IEC 947-2 / EN 60947-2
Rated current In [A] 6 <In < 40 0.5 <In < 63 0.5 <In < 63
Poles 1P, 1P+N, 2P, 3P, 4P
Rated voltage Ue one-pole a.c. [V] 230
multiple-pole a.c. [V] 230/400
one-pole d.c. [V] 60
two-pole d.c. [V] 125
Insulation voltage Ui [V] 500
Max. operating voltage Ub max. [V] 440
Min. operating voltage Ub min. [V] 12VAC - 12VDC
Rated frequency [Hz] 50…60
Rated breaking capacity Icn [A] 4500 6000 10000
acc. to IEC 898
Rated breaking capacity ultimate Icu [kA] 7.5 20 25
acc. to IEC 947-2
2 poles - 230 V service Ics [kA] 7.5 15 18.7
Rated breaking capacity ultimate Icu [kA] 7.5 10 15
acc. to IEC 947-2
3,4 poles - 400 V service Ics [kA] 5.6 7.5 11.2
Voltage withstanding capacity impulse (1,2/50) Uimp [kV] 5
at rated freq. (50-60Hz)
x 1 min. [kV] 3
Thermomagnetic release B: 3 In < Im < 5 In
characteristic C: 5 In < Im < 10 In
D: 10 In < Im < 20 In
K: 8 In < Im < 14 In
Z: 2 In < Im < 3 In
Limitation class 3
Toggle black sealable in ON-OFF position
Electrical life 10000
Mechanical life 20000
Protection degree housing IP4X/IPXXD (excluding terminal area)
terminals IP2X/IPXXB
Self-extinguishing degree V0 thickness 1.6 UL 94 yellow paper
Mechanical shock resistance minimum 30 g - 2 shocks - duration 13 ms
Resistance to vibrations acc. to IEC 68-2-6 5 g - 20 cycles at frequency 5…150…5 Hz with load 0,8 In
Tropicalization humid heat [°C/RH] 28 cycles with 55/95…100
acc. to IEC 68-2 constant climatic
conditions [°C/RH] 23/83 - 40/93 - 55/20
variable climatic
conditions [°C/RH] 25/95 - 40/95
Ambient temperature
(with daily average<+35°C) [°C] -25…+55
Storage temperature [°C] -40…+70
Terminal size upper/lower per cable [mm2]25/25
Mounting on DIN rail EN 50022 (35mm) by means of rapid fixing device
Pole dimensions [mm] H: 90 x D: 68 x W: 17,5
Pole weight [g] 125
2/21
2
ABB SACE
S 280
10 <In < 25 32 <In < 40 50 <In < 63 80 <In < 100
1P, 2P, 3P, 4P 1P, 2P, 3P
230
230/400
60
125
500
440
12VAC - 12VDC
50…60
25000 15000 10000 6000
40 30 25 10
30 22.5 18.7 10
25 20 15 6
12.5 10 11.2 6
••••
••••
•••
•••
•••
3
black sealable in ON-OFF position
10000
20000
IP4X/IPXXD (excluding terminal area)
IP2X/IPXXB
V0 thickness 1.6 UL 94 yellow paper
minimum 30 g - 2 shocks - duration 13 ms
5 g - 20 cycles at frequency 5…150…5 Hz with load 0.8 In
28 cycles with 55/95…100
23/83 - 40/93 - 55/20
25/95 - 40/95
-25…+55
-40…+70
25/25 35/35
on DIN rail EN 50022 (35mm) by means of rapid fixing device
H: 90 x D: 68 x W: 17,5
140 160
2/22
2
ABB SACE
TEPM0034
S 2.. range
S 240 series
Accessories ................................................... pg. 2/39 Technical details ........................................... pg. 10/4 Overall dimensions ........................................ pg. 11/4
Rated
currents Code
In Characteristic
[A] C
1P - S 241 type
6EF 010 2
8EF 016 9
10 EF 011 0
13 EF 017 7
16 EF 012 8
20 EF 013 6
25 EF 014 4
32 EF 015 1
40 EF 018 5
1P+N - S 241Na type
6EF 020 1
8EF 026 8
10 EF 021 9
13 EF 027 6
16 EF 022 7
20 EF 023 5
25 EF 024 3
32 EF 025 0
40 EF 028 4
2P - S 242 type
6EF 030 0
8EF 036 7
10 EF 031 8
13 EF 037 5
16 EF 032 6
20 EF 033 4
25 EF 034 2
32 EF 035 9
40 EF 038 3
C (Im = 5…10 In)
Tripping characteristics
Application: residential and similar
Connections for UNIFIX available
RCBO version
DS 640 SERIES
RCD blocks
DDA 25/40/63A
TEPM0032
TEPM0033
2/23
2
ABB SACE
Breaking capacity
acc. to IEC 898 / EN 60898
In [A] poles voltage [V] Icn [kA]
6...40 All 230/400 4.5
acc. to IEC 947-2 / EN 60947-2
In [A] poles voltage [V] Icu [kA] Ics [kA]
6...40 1, 1+N 127 10 10
230 6 6
2230 7.5 7.5
400 7.5 5.6
3, 4 230 10 10
400 7.5 5.6
Breaking capacity
acc. to IEC 947-2 / EN 60947-2
In [A] poles volt. [V] d.c. Icu [kA] Ics [kA]
6...40 124 8 8
60 6 6
248 8 8
125 6 6
Rated
currents Code
In Characteristic
[A] C
3P - S 243 type
6EF 040 9
8EF 046 6
10 EF 041 7
13 EF 047 4
16 EF 042 5
20 EF 043 3
25 EF 044 1
32 EF 045 8
40 EF 048 2
4P - S 244 type
6EE 380 0
8EE 381 8
10 EE 382 6
13 EE 383 4
16 EE 384 2
20 EE 385 9
25 EE 386 7
32 EE 387 5
40 EE 388 3
S 2.. range
S 240 series
Accessories ................................................... pg. 2/39 Technical details ........................................... pg. 10/4 Overall dimensions ........................................ pg. 11/4
TEPM0035
TEPM0036
IMQ approval
S 240 230/400V
4.5kA Characteristic C
In = 6 ... 40A
1P, 1P+N, 2P, 3P, 4P
2/24
2
ABB SACE
B (Im = 3…5 In); C (Im = 5…10 In)
K (Im = 8…14 In)
Tripping characteristics
Application: residential, commercial and industrial
Connections for UNIFIX available
RCBO version
DS 650 SERIES
RCD blocks
DDA 25/40/63A
S 2.. range
S 250 series
Accessories ................................................... pg. 2/39 Technical details ........................................... pg. 10/4 Overall dimensions ........................................ pg. 11/4
Rated
currents Code
In Characteristic
[A] B C D K
1P - S 251 type
0.5 EF 536 6 11178108 EF 160 5
1EF 537 4 11178109 EF 161 3
1.6 EF 538 2 11178110 EF 162 1
2EF 539 0 11178111 EF 163 9
3EF 540 8 11178112 EF 164 7
4EF 541 6 11178113 EF 165 4
6EF 110 0 EF 060 7 11178114 EF 166 2
8EF 111 8 EF 061 5 EF 167 0
10 EF 112 6 EF 062 3 11178115 EF 168 8
13 EF 176 1 EF 177 9
16 EF 113 4 EF 063 1 11178116 EF 169 6
20 EF 114 2 EF 064 9 11178117 EF 170 4
25 EF 115 9 EF 065 6 11178118 EF 171 2
32 EF 116 7 EF 066 4 11178119 EF 172 0
40 EF 117 5 EF 067 2 11178120 EF 173 8
50 EF 118 3 EF 068 0 11178121 EF 174 6
63 EF 119 1 EF 069 8 11178122 EF 175 3
TEPM0037
2/25
2
ABB SACE
Breaking capacity
acc. to IEC 898 / EN 60898
Infinite up to 2A
In [A] poles voltage [V] Icn [kA]
3...63
All
230/400 6
acc. to IEC 947-2 / EN 60947-2
In [A] poles voltage [V] Icu [kA] Ics [kA]
3...63 1, 1+N 127 30 22.75
230 10 7.5
2230 20 15
400 10 7.5
3, 4 230 20 15
400 10 7.5
Breaking capacity
acc. to IEC 947-2 / EN 60947-2
Infinite up to 2A
In [A] poles voltage [V] Icu [kA] Ics [kA]
3...63 124 20 20
60 10 10
248 20 20
125 10 10
Rated
currents Code
In Characteristic
[A] B C K
1P+N - S 251 Na type
0.5 EF 542 4 EF 180 3
1EF 543 2 EF 181 1
1.6 EF 544 0 EF 182 9
2EF 545 7 EF 183 7
3EF 546 5 EF 184 5
4EF 547 3 EF 185 2
6EF 120 9 EF 070 6 EF 186 0
8EF 121 7 EF 071 4 EF 187 8
10 EF 122 5 EF 072 2 EF 188 6
13 EF 196 9 EF 197 7
16 EF 123 3 EF 073 0 EF 189 4
20 EF 124 1 EF 074 8 EF 190 2
25 EF 125 8 EF 075 5 EF 191 0
32 EF 126 6 EF 076 3 EF 192 8
40 EF 127 4 EF 077 1 EF 193 6
50 EF 128 2 EF 078 9 EF 194 4
63 EF 129 0 EF 079 7 EF 195 1
S 2.. range
S 250 series
Accessories ................................................... pg. 2/39 Technical details ........................................... pg. 10/4 Overall dimensions ........................................ pg. 11/4
TEPM0038
IMQ approval
S 250 230/400V
6kA B-C characteristics
In = 6 ... 63A
1P, 1P+N, 2P, 3P, 4P
R.I.Na. approval
The S 252, S 253, S 254 types (B-C-K characteristics)
have obtained R.I.Na. approval for naval application at
voltages of 230, 400, 440V a.c.
2/26
2
ABB SACE
S 2.. range
S 250 series
Accessories ................................................... pg. 2/39 Technical details ........................................... pg. 10/4 Overall dimensions ........................................ pg. 11/4
Rated
currents Code
In Characteristic
[A] B C D K
2P - S 252 type
0.5 EF 548 1 11178123 EF 200 9
1EF 549 9 11178124 EF 201 7
1.6 EF 550 7 11178125 EF 202 5
2EF 551 5 11178126 EF 203 3
3EF 552 3 11178127 EF 204 1
4EF 553 1 11178128 EF 205 8
6EF 130 8 EF 080 5 11178129 EF 206 6
8EF 131 6 EF 081 3 EF 207 4
10 EF 132 2 EF 082 1 11178130 EF 208 2
13 EF 216 5 EF 217 3
16 EF 133 2 EF 083 9 11178131 EF 209 0
20 EF 134 0 EF 084 7 11178132 EF 210 8
25 EF 135 7 EF 085 4 11178133 EF 211 6
32 EF 136 5 EF 086 2 11178134 EF 212 4
40 EF 137 3 EF 087 0 11178135 EF 213 2
50 EF 138 1 EF 088 8 11178136 EF 214 0
63 EF 139 9 EF 089 6 11178137 EF 215 7
3P - S 253 type
0.5 EF 554 9 11178138 EF 220 7
1EF 555 6 11178139 EF 221 5
1.6 EF 556 4 11178140 EF 222 3
2EF 557 2 11178141 EF 223 1
3EF 558 0 11178142 EF 224 9
4EF 559 8 11178143 EF 225 6
6EF 140 7 EF 090 4 11178144 EF 226 4
8EF 141 5 EF 091 2 EF 227 2
10 EF 142 3 EF 092 0 11178145 EF 228 0
13 EF 236 3 EF 237 1
16 EF 143 1 EF 093 8 11178146 EF 229 8
20 EF 144 9 EF 094 6 11178147 EF 230 6
25 EF 145 6 EF 095 3 11178148 EF 231 4
32 EF 146 4 EF 096 1 11178149 EF 232 2
40 EF 147 2 EF 097 9 11178150 EF 233 0
50 EF 148 0 EF 098 7 11178151 EF 234 8
63 EF 149 8 EF 099 5 11178152 EF 235 5
4P - S 254 type
0.5 EF 840 2 11178153 EE 390 9
1EF 841 0 11178154 EE 391 7
1.6 EF 842 8 11178155 EE 392 5
2EF 843 6 11178156 EE 393 3
3EF 844 4 11178157 EE 394 1
4EF 845 1 11178158 EE 395 8
6EF 883 2 EF 846 9 11178159 EE 396 6
8EF 884 0 EF 847 7 EE 397 4
10 EF 885 7 EF 848 5 11178160 EE 398 2
13 EF 886 5 EF 849 3
16 EF 887 3 EF 850 1 11178161 EE 399 0
20 EF 888 1 EF 851 9 11178162 EE 400 6
25 EF 889 9 EF 852 7 11178163 EE 401 4
32 EF 890 7 EF 853 5 11178164 EE 402 2
40 EF 891 5 EF 854 3 11178165 EE 403 0
50 EF 892 3 EF 855 0 11178166 EE 404 8
63 EF 893 1 EF 856 8 11178167 EE 405 5
TEPM0040
TEPM0041
TEPM0038
2/27
2
ABB SACE
Breaking capacity
acc. to IEC 898 / EN 60898
Infinite up to 2A
In [A] poles voltage [V] Icn [kA]
3...63 All 230/400 10
acc. to IEC 947-2 / EN 60947-2
In [A] poles voltage [V] Icu [kA] Ics [kA]
3...63 1, 1+N 127 35 26.2
230 15 11.2
2230 25 18.7
400 15 11.2
3, 4 230 20 15
400 15 11.2
Breaking capacity
acc. to IEC 947-2 / EN 60947-2
Infinite up to 2A
In [A] poles voltage [V] Icu [kA] Ics [kA]
3...63 124 30 30
60 15 15
248 30 30
125 15 15
S 2.. range
S 270 series
Accessories ................................................... pg. 2/39 Technical details ........................................... pg. 10/4 Overall dimensions ........................................ pg. 11/4
Rated
currents Code
In Characteristic
[A] B C K D
1P - S 271 type
0.5 EF 566 3 EF 360 1 EF 600 0
1EF 567 1 EF 361 9 EF 601 8
1.6 EF 568 9 EF 362 7 EF 602 6
2EF 569 7 EF 363 5 EF 603 4
3EF 570 5 EF 364 3 EF 604 2
4EF 571 3 EF 365 0 EF 605 9
6EF 310 6 EF 260 3 EF 366 8 EF 606 7
8EF 311 4 EF 261 1 EF 367 6 EF 607 5
10 EF 312 2 EF 262 9 EF 368 4 EF 608 3
13 EF 830 3 EF 835 2
16 EF 313 0 EF 263 7 EF 369 2 EF 609 1
20 EF 314 8 EF 264 5 EF 370 0 EF 610 9
25 EF 315 5 EF 265 2 EF 371 8 EF 611 7
32 EF 316 3 EF 266 0 EF 372 6 EF 612 5
40 EF 317 1 EF 267 8 EF 373 4 EF 613 3
50 EF 318 9 EF 268 6 EF 374 2 EF 614 1
63 EF 319 7 EF 269 4 EF 375 9 EF 615 8
IMQ approval
S 270 230-400V
10kA B-C characteristics
In = 0.5 ... 63A (C) In = 6 ... 63A (B)
1P, 1P+N, 2P, 3P, 4P
R.I.Na. approval
The S 272, S 273 types (B-C-K characteristics) and S 274
(B-C characteristics) have obtained R.I.Na. approval for
naval application at voltages 230, 400, 440V a.c.
TEPM0042
B (Im = 3…5 In); C (Im = 5…10 In)
D (Im = 10…20 In); K (Im = 8…14 In)
Tripping characteristics
Application: commercial, industrial
Connections for UNIFIX available
RCBO version
DS 670 SERIES
RCD blocks
DDA 25/40/63A
2/28
2
ABB SACE
S 2.. range
S 270 series
Accessories ................................................... pg. 2/39 Technical details ........................................... pg. 10/4 Overall dimensions ........................................ pg. 11/4
Rated
currents Code
In Characteristic
[A] B C K D
1P+N - S 271 Na type
0.5 EF 572 1 EF 380 9 EF 616 6
1EF 573 9 EF 381 7 EF 617 4
1.6 EF 574 7 EF 382 5 EF 618 2
2EF 575 4 EF 383 3 EF 619 0
3EF 576 2 EF 384 1 EF 620 8
4EF 577 0 EF 385 8 EF 621 6
6EF 320 5 EF 270 2 EF 386 6 EF 622 4
8EF 321 3 EF 271 0 EF 387 4 EF 623 2
10 EF 322 1 EF 272 8 EF 388 2 EF 624 0
13 EF 831 1 EF 836 0
16 EF 323 9 EF 273 6 EF 389 0 EF 625 7
20 EF 324 7 EF 274 4 EF 390 8 EF 626 5
25 EF 325 4 EF 275 1 EF 391 6 EF 627 3
32 EF 326 2 EF 276 9 EF 392 4 EF 628 1
40 EF 327 0 EF 277 7 EF 393 2 EF 629 9
50 EF 328 8 EF 278 5 EF 394 0 EF 630 7
63 EF 329 6 EF 279 3 EF 395 7 EF 631 5
2P - S 272 type
0.5 EF 578 8 EF 400 5 EF 632 3
1EF 579 6 EF 401 3 EF 633 1
1.6 EF 580 4 EF 402 1 EF 634 9
2EF 581 2 EF 403 9 EF 635 6
3EF 582 0 EF 404 7 EF 636 4
4EF 583 8 EF 405 4 EF 637 2
6EF 330 4 EF 280 1 EF 406 2 EF 638 0
8EF 331 2 EF 281 9 EF 407 0 EF 639 8
10 EF 332 0 EF 282 7 EF 408 8 EF 640 6
13 EF 832 9 EF 837 8
16 EF 333 8 EF 283 5 EF 409 6 EF 641 4
20 EF 334 6 EF 284 3 EF 410 4 EF 642 2
25 EF 335 3 EF 285 0 EF 411 2 EF 643 0
32 EF 336 1 EF 286 8 EF 412 0 EF 644 8
40 EF 337 9 EF 287 6 EF 413 2 EF 645 5
50 EF 338 7 EF 288 4 EF 414 6 EF 646 3
63 EF 339 5 EF 289 2 EF 415 3 EF 647 1
TEPM0043
TEPM0044
2/29
2
ABB SACE
S 2.. range
S 270 series
Accessories ................................................... pg. 2/39 Technical details ........................................... pg. 10/4 Overall dimensions ........................................ pg. 11/4
Rated
currents Code
In Characteristic
[A] B C K D
3P - S 273 type
0.5 EF 584 6 EF 420 3 EF 648 9
1EF 585 3 EF 421 1 EF 649 7
1.6 EF 586 1 EF 422 9 EF 650 5
2EF 587 9 EF 423 7 EF 651 3
3EF 588 7 EF 424 5 EF 652 1
4EF 589 5 EF 425 2 EF 653 9
6EF 340 3 EF 290 0 EF 426 0 EF 654 7
8EF 341 1 EF 291 8 EF 427 8 EF 655 4
10 EF 342 9 EF 292 6 EF 428 6 EF 656 2
13 EF 833 7 EF 838 6
16 EF 343 7 EF 293 4 EF 429 4 EF 657 0
20 EF 344 5 EF 294 2 EF 430 2 EF 658 8
25 EF 345 2 EF 295 9 EF 431 0 EF 659 6
32 EF 346 0 EF 296 7 EF 432 8 EF 660 4
40 EF 347 8 EF 297 5 EF 433 6 EF 661 2
50 EF 348 6 EF 298 3 EF 434 4 EF 662 0
63 EF 349 4 EF 299 1 EF 435 1 EF 663 8
4P - S 274 type
0.5 EF 700 8 EE 410 5 EE 430 3
1EF 701 6 EE 411 3 EE 431 1
1.6 EF 702 4 EE 412 1 EE 432 9
2EF 703 2 EE 413 9 EE 433 7
3EF 704 0 EE 414 7 EE 434 5
4EF 706 5 EE 415 4 EE 435 2
6EF 945 9 EF 707 3 EE 416 2 EE 436 0
8EF 946 7 EF 708 1 EE 417 0 EE 437 8
10 EF 947 5 EF 709 9 EE 418 8 EE 438 6
13 EF 948 3 EF 800 6
16 EF 949 1 EF 801 4 EE 419 6 EE 439 4
20 EF 963 2 EF 804 8 EE 420 4 EE 440 2
25 EF 964 0 EF 805 5 EE 421 2 EE 441 0
32 EF 965 7 EF 806 3 EE 422 0 EE 442 8
40 EF 966 5 EF 807 1 EE 423 8 EE 443 6
50 EF 967 3 EF 808 9 EE 424 6 EE 444 4
63 EF 968 1 EF 809 7 EE 425 3 EE 445 1
TEPM0045
TEPM0046
2/30
2
ABB SACE
acc. to IEC 947-2 / EN 60947-2
Infinite up to 2A
In [A] poles voltage [V] Icu [kA] Ics [kA]
10...25 1127 50 37.5
230 25 25
2230 40 30
400 25 28.75
3, 4 230 40 30
400 25 12.5
In [A] poles voltage [V] Icu [kA] Ics [kA]
32...40 1127 40 30
230 20 20
2230 30 22.5
400 20 15
3, 4 230 30 22.5
400 20 10
In [A] poles voltage [V] Icu [kA] Ics [kA]
3-4-6-8-50-63 1127 35 26.2
230 15 11.2
2230 25 18.7
400 15 11.2
3, 4 230 20 15
400 15 11.2
In [A] poles voltage [V] Icu [kA] Ics [kA]
80-100 1230 6 100%
400 100%
2 230 10 100%
400 6 100%
3 230 10 100%
400 6 100%
Breaking capacity
acc. to IEC 898 / EN 60898
Infinite up to 2A
In [A] poles voltage [V] Icn [kA]
10...25
All
230/400 25
32 – 40
All
230/400 15
6 – 50 – 63
All
230/400 10
80-100
All
230/400 6
TEPM0048
S 2.. range
S 280 B-C-D series
Accessories ................................................... pg. 2/39 Technical details ........................................... pg. 10/4 Overall dimensions ........................................ pg. 11/4
Rated
currents Code
In Characteristic
[A] B C D
1P - S 281 type
6KU 647 0 KU 657 9 KU 674 4
10 KU 648 8 KU 658 7 KU 810 4
13 KU 654 6 KU 664 5
16 KU 649 6 KU 659 5 KU 811 2
20 KU 650 4 KU 660 3 KU 812 0
25 KU 651 2 KU 661 1 KU 813 8
32 KU 652 0 KU 662 9 KU 814 6
40 KU 653 8 KU 663 7 KU 815 3
50 KU 655 3 KU 665 2 KU 817 9
63 KU 656 1 KU 666 0 KU 818 7
80 11178645 11178643 11178647
100 11178646 11178644 11178648
2P - S 282 type
6KU 687 6 KU 697 5 KU 819 5
10 KU 688 4 KU 698 3 KU 820 3
13 KU 694 2 KU 704 9
16 KU 689 2 KU 699 1 KU 821 1
20 KU 680 0 KU 700 7 KU 822 9
25 KU 681 8 KU 701 5 KU 823 7
32 KU 682 6 KU 702 3 KU 824 5
40 KU 683 4 KU 703 1 KU 825 2
50 KU 695 9 KU 705 6 KU 827 8
63 KU 696 7 KU 706 4 KU 828 6
80 11178651 11178649 11178653
100 11178652 11178650 11178654
B (Im = 3…5 In); C (Im = 5…10 In); D (Im = 10…20 In)
Tripping characteristics
Application: commercial, industrial
Connections for UNIFIX available
RCD blocks
DDA 25/40/63 A
TEPM0047
2/31
2
ABB SACE
Breaking capacity
acc. to IEC 947-2 / EN 60947.2
Infinite up to 2A
In [A] poles voltage [V] Icu [kA] Ics [kA]
10...40 124 30 30
60 15 15
248 30 15
125 30 15
In [A] poles voltage [V] Icu [kA] Ics [kA]
3-4-6-8-50-63 124 20 20
60 10 10
248 20 20
125 10 10
Rated
currents Code
In Characteristic
[A] B C D
3P - S 283 type
6KU 707 2 KU 717 1 KU 829 4
10 KU 708 0 KU 718 9 KU 830 2
13 KU 714 8 KU 724 7
16 KU 709 8 KU 719 7 KU 831 0
20 KU 710 6 KU 720 5 KU 832 8
25 KU 711 4 KU 721 3 KU 833 6
32 KU 712 2 KU 722 1 KU 834 4
40 KU 713 0 KU 723 9 KU 835 1
50 KU 715 5 KU 725 4 KU 837 7
63 KU 716 3 KU 726 2 KU 838 5
80 11178657 11178655 11178659
100 11178658 11178656 11178660
4P - S 284 type
6KU 727 0 KU 737 9 KU 839 3
10 KU 728 8 KU 738 7 KU 840 1
13 KU 734 6 KU 744 5
16 KU 729 6 KU 739 5 KU 841 9
20 KU 730 4 KU 740 3 KU 842 7
25 KU 731 2 KU 741 1 KU 843 5
32 KU 732 0 KU 742 9 KU 844 3
40 KU 733 8 KU 743 7 KU 845 0
50 KU 735 3 KU 745 2 KU 677 7
63 KU 736 1 KU 676 9 KU 678 5
S 2.. range
S 280 B-C-D series
Accessories ................................................... pg. 2/39 Technical details ........................................... pg. 10/4 Overall dimensions ........................................ pg. 11/4
Type Code
S 282 C 0.5 11865333
S 282 C 1 11865334
S 282 C 1.6 11865335
S 282 C 2 11865336
S 282 C 3 11865337
S 282 C 4 11865338
S 282 C 8 11865340
S 282 B 8 11865324
TEPM0050
TEPM0049
R.I.Na. approval
The S 282 and S 283 types with B-C characteristics with rated
currents from 0.5 to 63A have obtained R.I.Na, Lloyd’s Register, Det
Norske Veritas, Bureau Veritas approval for naval application at
voltages:
- S 282 (60V d.c. / 230-440V a.c.)
- S 283 (230-440V a.c.)
The codes for ordering the S 280 B-C circuit-breakers with naval
approval with rated currents below 6A and for rated current 8A are
listed below.
Type Code
S 283 C 0.5 11866313
S 283 C 1 11866314
S 283 C 1.6 11866315
S 283 C 2 11866316
S 283 C 3 11866317
S 283 C 4 11866318
S 283 C 8 11866320
S 283 B 8 11866349
IMQ approval
S 280 230/400V
B-C characteristics:
25kA In = 10 ... 25A;
15kA In = 32 ... 40A;
10kA In = 6-50-63A
1P, 2P, 3P, 4P
2/32
2
ABB SACE
Breaking capacity
acc. to IEC 947-2 / EN 60947-2
Infinite up to 2A
In [A] poles voltage [V] Icu [kA] Ics [kA]
10...25 1127 50 37.5
230 25 25
2230 40 30
400 25 28.75
3, 4 230 40 30
400 25 12.5
32...40 1127 40 30
230 20 20
2230 30 22.5
400 20 15
3, 4 230 30 22.5
400 20 10
3-4-6-8- 1127 35 26.2
50-63 230 15 11.2
2230 25 18.7
400 15 11.2
3, 4 230 20 15
400 15 11.2
TEPM0052
S 2.. range
S 280 K-Z series
Accessories ................................................... pg. 2/39 Technical details ........................................... pg. 10/4 Overall dimensions ........................................ pg. 11/4
Rated
currents Code
In Characteristic
[A] K Z
1P - S 281 type
0.5 KU 750 2
1KU 751 0
1.6 KU 752 8
2KU 753 6
3KU 754 4
4KU 755 1
6KU 866 6 KU 756 9
10 KU 867 4 KU 757 7
13 KU 873 2 KU 886 4
16 KU 868 2 KU 758 5
20 KU 869 0 KU 759 3
25 KU 870 8 KU 760 1
32 KU 871 6 KU 761 9
40 KU 872 4 KU 762 7
50 KU 874 0 KU 763 5
63 KU 875 7 KU 764 3
2P - S 282 type
0.5 KU 765 0
1KU 766 8
1.6 KU 767 6
2KU 768 4
3KU 769 2
4KU 770 0
6KU 856 7 KU 771 8
10 KU 857 5 KU 772 6
13 KU 863 3 KU 887 2
16 KU 858 3 KU 773 4
20 KU 859 1 KU 774 2
25 KU 860 9 KU 775 9
32 KU 861 6 KU 776 7
40 KU 862 5 KU 777 5
50 KU 864 1 KU 778 3
63 KU 865 8 KU 779 1
K (Im = 8…14 In)
Z (Im = 2…3 In)
Tripping characteristics
Application: industrial
Connections for UNIFIX available
RCD blocks
DDA 25/40/63A
TEPM0051
2/33
2
ABB SACE
Rated
currents Code
In Characteristic
[A] K Z
3P - S 283 type
0.5 KU 780 9
1KU 781 7
1.6 KU 782 5
2KU 783 3
3KU 784 1
4KU 785 8
6KU 675 1 KU 786 6
10 KU 847 6 KU 787 4
13 KU 853 4 KU 888 0
16 KU 848 4 KU 788 2
20 KU 849 2 KU 789 0
25 KU 850 0 KU 790 8
32 KU 851 8 KU 791 6
40 KU 852 6 KU 792 4
50 KU 854 2 KU 793 2
63 KU 855 9 KU 794 0
4P - S 284 type
0.5 KU 795 7
1KU 796 5
1.6 KU 797 3
2KU 798 1
3KU 799 9
4KU 800 5
6KU 876 5 KU 801 3
10 KU 877 3 KU 802 1
13 KU 883 1 KU 889 8
16 KU 878 1 KU 803 9
20 KU 879 9 KU 804 7
25 KU 880 7 KU 805 4
32 KU 881 5 KU 806 2
40 KU 882 3 KU 807 0
50 KU 884 9 KU 808 8
63 KU 885 6 KU 809 6
S 2.. range
S 280 K-Z series
Accessories ................................................... pg. 2/39 Technical details ........................................... pg. 10/4 Overall dimensions ........................................ pg. 11/4
Breaking capacity
acc. to IEC 947-2 / EN 60947-2
Infinite up to 2A
In [A] poles voltage [V] Icu [kA] Ics [kA]
10...40 124 30 30
60 15 15
248 30 15
125 30 15
In [A] poles voltage [V] Icu [kA] Ics [kA]
3-4-6-8-50-63 124 20 20
60 10 10
248 20 20
125 10 10 Type Code
S 282 K 0.5 11865375
S 282 K 1 11865376
S 282 K 1.6 11865377
S 282 K 2 11865378
S 282 K 3 11865379
S 282 K 4 11865380
S 282 K 8 11865382
R.I.Na. approval
S 282 and S 283 types with K characteristic with rated currents
from 0.5 to 63A have obtained R.I.Na, Lloyd’s Register, Det Norske
Veritas, Bureau Veritas approval for use at the following voltages:
– S 282 (60V d.c. / 230-440V a.c.)
– S 283 (230-440V a.c.)
The codes for ordering S 280 K circuit-breakers with naval approval
with rated currents below 6A and rated current 8A are listed below.
Type Code
S 283 K 0.5 11866329
S 283 K 1 11866330
S 283 K 1.6 11866331
S 283 K 2 11866332
S 283 K 3 11866333
S 283 K 4 11866334
S 283 K 8 11866336
TEPM0054
TEPM0053
2/34
2
ABB SACE
S 2.. range
S 280 UC series
Accessories ................................................... pg. 2/39 Technical details ........................................... pg. 10/4 Overall dimensions ........................................ pg. 11/4
B (Im = 3…5 In); C (Im = 5…10 In)
K (Im = 8…14 In); Z (Im = 2…3 In)
Tripping characteristics (defined in a.c.*)
Application: industrial
Connections for UNIFIX available
Rated Code
currents
In Characteristics
[A] B C K Z
1P - S 281 UC type
0.5 EF 720 6 EF 752 9 EF 784 2
1EF 721 4 EF 753 7 EF 785 9
1.6 EF 722 2 EF 754 5 EF 786 7
2EF 723 0 EF 755 2 EF 787 5
3EF 724 8 EF 756 0 EF 788 3
4EF 725 5 EF 757 8 EF 789 1
6EF 690 1 EF 726 3 EF 758 6 EF 790 9
8EF 691 9 EF 727 1 EF 759 4 EF 791 7
10 EF 692 7 EF 728 9 EF 760 2 EF 792 5
16 EF 693 5 EF 729 7 EF 761 0 EF 793 3
20 EF 694 3 EF 730 5 EF 762 8 EF 794 1
25 EF 695 0 EF 731 3 EF 763 6 EF 795 8
32 EF 696 8 EF 732 1 EF 764 4 EF 796 6
40 EF 697 6 EF 733 9 EF 765 1 EF 797 4
50 EF 698 4 EF 734 7 EF 766 9 EF 798 2
63 EF 699 2 EF 735 4 EF 767 7 EF 799 0
* for time/current curve in d.c., see Chap. 10
TEPM0055
Technical characteristics
Rated current In [A] 0.5...63
Rated voltage a.c. [V] 230/400
Insulation voltage Vi [V] 500
Min. operating
voltage [V] 12 a.c.- 12 d.c.
Electric operations [n°]10,000
Mechanic operations [n°]20,000
Tropicalization at 55°C
acc. to DIN 40046 95%UR
Termnals per cable cage type up to 25mm2
Self-extinguishing degree V0 thickness 1.6mm
Poles
1P 2P 3P 4P
Weight [g] 125 250 375 500
2/35
2
ABB SACE
Breaking capacity
acc. to IEC 947-2 / EN 60947-2
In [A] poles voltage[V] Icu [kA] Ics [kA]
0.5...40 1230 12.5 12.5
2127 50 50
230 25 25
400 12.5 12.5
50...63 1230 12.5 12.5
2127 20 20
230 10 10
400 4.5 4.5
Breaking capacity
acc. to IEC 947-2 / EN 60947-2
In [A] poles voltage[V] Icu [kA] Ics [kA]
0.5...40 1 24 50 50
60 30 30
75 15 15
250 6 6
2 48 50 50
75 30 30
110 30 30
250 25 25
500 6 6
Rated Code
currents
In Characteristic
[A] B C K Z
2P - S 282 UC type
0.5 EF 736 2 EF 768 5 EF 810 5
1EF 737 0 EF 769 3 EF 811 3
1.6 EF 738 8 EF 770 1 EF 812 1
2EF 739 6 EF 771 9 EF 813 9
3EF 740 4 EF 772 7 EF 814 7
4EF 741 2 EF 773 5 EF 815 4
6EF 710 7 EF 742 0 EF 774 3 EF 816 2
8EF 711 5 EF 743 8 EF 775 0 EF 817 0
10 EF 712 3 EF 744 6 EF 776 8 EF 818 8
16 EF 713 1 EF 745 3 EF 777 6 EF 819 6
20 EF 714 9 EF 746 1 EF 778 4 EF 820 4
25 EF 715 6 EF 747 9 EF 779 2 EF 821 2
32 EF 716 4 EF 748 7 EF 780 0 EF 822 0
40 EF 717 2 EF 749 5 EF 781 8 EF 823 8
50 EF 718 0 EF 750 3 EF 782 6 EF 824 6
63 EF 719 8 EF 751 1 EF 783 4 EF 825 3
3P - S 283 UC type
0.5...4 on request on request on request
6...63 on request on request on request on request
4P - S 284 UC type
0.5...4 on request on request on request
6...63 on request on request on request on request
S 2.. range
S 280 UC series
Accessories ................................................... pg. 2/39 Technical details ........................................... pg. 10/4 Overall dimensions ........................................ pg. 11/4
TEPM0056
TEPM0057
TEPM0058
R.I.Na. approval
S 282 UC type with B-C-K characteristics has obtained
R.I.Na, Lloyd’s Register, Det Norske Veritas and Bureau
Veritas approval for naval application at voltages
230V d.c./230V a.c.
S 282 UC type with Z characteristic with currents from 4 to
40A has obtained R.I.Na approval for naval application at
voltages 60 and 250V d.c.
2/36
2
ABB SACE
S 2.. range
M 280 magnetic only series
Accessories ................................................... pg. 2/39 Technical details ........................................... pg. 10/4 Overall dimensions ........................................ pg. 11/4
Rated currents Code
In I magn
[A] [A]
1P - M 281 type
0.5 7 KU 470 7
114KU 471 5
1.6 23 KU 472 3
2.5 32 KU 473 1
456KU 474 9
6.3 88 KU 475 6
10 140 KU 476 4
12.5 175 KU 477 2
16 192 KU 478 0
20 240 KU 479 8
25 300 KU 480 6
32 384 KU 481 4
40 480 KU 482 2
50 600 KU 483 0
63 700 KU 484 8
2P - M 282 type
0.5 7 KU 602 5
114KU 603 3
1.6 23 KU 604 1
2.5 32 KU 605 8
456KU 606 6
6.3 88 KU 607 4
10 140 KU 608 2
12.5 175 KU 609 0
16 192 KU 610 8
20 240 KU 611 6
25 300 KU 612 4
32 384 KU 613 2
40 480 KU 614 0
50 600 KU 615 7
63 700 KU 616 5
TEPM0062
Protection against short-circuit overcurrents in the supply
circuits of motors. For protection against overload
currents, additional thermal protection is necessary.
Application
Connections for UNIFIX available
RCD blocks
DDA 63 A
2/37
2
ABB SACE
Rated currents Code
In I magn
[A] [A]
3P - M 283 type
0.5 7 KU 617 3
114KU 618 1
1.6 23 KU 619 9
2.5 32 KU 620 7
456KU 621 5
6.3 88 KU 622 3
10 140 KU 623 1
12.5 175 KU 624 9
16 192 KU 625 6
20 240 KU 626 4
25 300 KU 627 2
32 384 KU 628 0
40 480 KU 629 8
50 600 KU 630 6
63 700 KU 631 4
4P - M 284 type
0.5 7 KU 632 2
114KU 633 0
1.6 23 KU 634 8
2.5 32 KU 635 5
456KU 636 3
6.3 88 KU 637 1
10 140 KU 638 9
12.5 175 KU 639 7
16 192 KU 640 5
20 240 KU 641 3
25 300 KU 642 1
32 384 KU 643 9
40 480 KU 644 7
50 600 KU 645 4
63 700 KU 646 2
Technical characteristics
Rated current In [A] 0.5...63
Rated voltage a.c. [V] 230/400
Insulation voltage Vi [V] 500
Min. operating
voltage [V] 12 a.c. - 12 d.c.
Electric operations [n°]10,000
Mechanic operations [n°]20,000
Tropicalization at 55°C
acc. to DIN50016 95%UR
Terminals per cable cage type up to 25 mm2
Self-extinguishing degree V0 thickness 1.6mm
Poles 1P 2P 3P 4P
Weight [g] 125 250 375 500
S 2.. range
M 280 magnetic only series
Accessories ................................................... pg. 2/39 Technical details ........................................... pg. 10/4 Overall dimensions ........................................ pg. 11/4
Breaking capacity
acc. to IEC 947-2 / EN 60947-2
In [A] poles [V] Icu [kA] Ics %]
0.5...1.6 - 10…25 all 230 40 75
2.5...6.3 - 50…63 all 230 25 75
32…40 all 230 30 75
0.5...1.6 - 10…25 all 400 25 50
2.5...6.3 - 50…63 all 400 15 50
32…40 all 400 20 50
TEPM0063
2/38
2
ABB SACE
S2-H..
AUXILIARY
CONTACT
S2-S/H
AUXILIARY
CONTACT
+ SIGNAL
CONTACT
S2-A1I, S2-A2I
UNDERVOLTAGE
RELEASE
S2-H..
AUXILIARY
CONTACT
S2-BP
MACHANICAL
INTERLOCK
S2-BPS
MECHANICAL
INTERLOCK
WITH SIGNAL
CONTACT
S2-A1I, S2-A2I
SHUNT TRIP
S2-BP, S2-BPS
MECHANICAL
INTERLOCK
S2-BM.
UNDERVOLTAGE
RELEASE
S2-S/H
AUXILIARY
CONTACT
+ SIGNAL
CONTACT
S2-S
SIGNAL
CONTACT
S2-BM..
SUNT
TRIP
S2-S
SIGNAL
CONTACT
S240-S250-S270-S280
MCB
DDA
RCD
BLOCK
Examples of combinations of S 240, S 250, S 270 and S 280 series circuit-breakers with auxiliary elements (maximum configurations)
S 2.. range
Auxiliary elements
The S 2 range circuit-breakers
are supported by a whole
group of auxiliary elements with
many functions and configura-
tions.
Undervoltage releases, shunt
trips, auxiliary contacts, signal
contacts, mechanical interlocks
and motor operating devices
are available.
Each auxiliary element has
been studied so that it can be
installed on the highest possi-
ble number of circuit-breakers
thus simplifying selection for the
sector operators.
A wide range of auxiliary ele-
ments considerably improves
the performance of the circuit-
breakers and enables innova-
tive and integrated solutions to
be used in every installation.
TEPM0425
2/39
2
ABB SACE
S 2.. range
Auxiliary elements
Overall dimensions ...................................... pg. 11/10
Shunt trips
These are used for remote tripping of the circuit-br eakers. If an auxiliary contact or signal contact is
also required, they must be installed to the left of the shunt trips.
Code Type Description
For use with S 240, S 250, S 270, S 280, S 280 UC, DS 640, DS 650, DS 670, DS 850 series
KU 918 5 S2-A1 I shunt trip
12-60V a.c./d.c.
KU 919 3 S2-A2 I shunt trip
110-415V a.c. and 110-250V d.c.
Technical characteristics
Type S2-A1 I S2-A2 I
Rated voltage [V]
a.c. 12 ÷ 60 110 ÷ 415
d.c. 12 ÷ 60 110 ÷ 250
Max. release duration [ms]< 10 < 10
Min. release [V]
voltage a.c. 7 55
d.c. 10 80
Consumption on release [VA]
a.c. 40 ÷ 200 55 ÷ 210
d.c. 40 ÷ 200 55 ÷ 110
Coil resistance []3.7 225
Terminals [mm2]25 25
Tightening torque [Nm] 2 2
Dimens.(WxDxH) [mm]
17.5x68x90 17.5x68x90
1
2
C1
C2
1
2
C1
C2
S2-A1 I,
S2-A2 I
Installation on left or right side
OEPM0015
TEPM0135
C1
C2
C1
C2
OEPM0290
2/40
2
ABB SACE
S 2.. range
Auxiliary elements
Overall dimensions ...................................... pg. 11/10
Auxiliary/signal contacts
The auxiliary contact indicates the position of the circuit-breaker contacts. When the position of the
contacts changes, whether manually or automatically, it indicates their status.
The signal contact indicates the position of the circuit-breaker after automatic release of the circuit-
breaker caused by overload or short-circuit. For manual operation, it does not trip.
Code Type Description
For use with S 240, S 250, S 270, S 280, S 280 UC, DS 640, DS 650, DS 670, DS 850 series
KU 925 0 S2-H11 I auxiliary contacts 1 NO+ 1 NC (1/2 module)
KU 926 8 S2-H02 I auxiliary contacts 2 NC (1/2 module)
KU 927 6 S2-H 20 I auxiliary contacts 2NO (1/2 module)
KU 897 1 S2-H11X auxiliary contacts 1 NO+ 1 NC (1/2 module) with Faston connections
KU 899 7 S2-H20X auxiliary contacts 2 NO (1/2 module) with Faston connections
KU 898 9 S2-H02X auxiliary contacts 2 NC (1/2 module) with Faston connections
KU 891 4 S2-H21 auxiliary contacts 2 NO +1 NC (1/2 module)
KU 890 6 S2-H12 auxiliary contacts 1 NO+2NC (1/2 module)
KU 893 0 S2-H30 auxiliary contacts 3 NO (1/2 module)
KU 892 2 S2-H03 auxiliary contacts 3 NC (1/2 module)
KU 903 7 S2-S signal contacts (1/2 module)
KU 902 9 S2-S/H signal contacts + auxiliary contacts (1/2 module)
TEPM0140
TEPM0139 TEPM0138
Key
S2-H = Auxiliary contact
S2-S = Signal contact
S2-SH = Auxiliary + signal contact
=Signal contact (1 change over contact)
=Auxiliary + signal contact (2 change over contacts)
Technical characteristics
Type S2-H11 I S2-H20 I S2-H02 I S2-H21 S2-H12 S2-H30 S2-H03 S2-S S2-SH
S2-H11 X S2-H20 X S2-H02 X
Description 1NO+1NC 2NO 2NC 2NO+1NC 1NO+2NC 3NO 3NC ∂∑
Alternating Ue [V] ••••••••••••••••••••••••••••••• 240 415 ••••••••••••••• ••••• 415 240 •••••
current Ie [A] ••••••••••••••••••••••••••••••• 62 ••••••••••••••• ••••• 26 •••••
Direct Ue [V] •••••••••••••••••••••••• 24 60 110 250 •••••••••••••••••••••••••• 250 110 60 24
current Ie [A] •••••••••••••••••••••••• 421.51 •••••••••••••••••••••••••• 0.5 1 1 4
Min.operating
voltage [V] 12 a.c. - 12 d.c.
Min. operating
current [mA] 12
Terminals [mm2]up to 2 x 1.5
Dielectric strength [kV] 3
Resistance to short-circuit
at 240V a.c. [A] 1000 (protected with S 2 breaker characteristic K - 6A)
Impulse voltage withstand
capacity (1.2 x 50) [kV] 4
Tightening torque [Nm] 0.7
Dimensions (WxDxH) [mm] 8.75x68(58 for S2-H)x90
NB: the auxiliary contacts S2-H11 X, S2-H20 X, S2-H02 X dif fer from the contacts S2-H11, S2-H20, S2-H02 in that they do not have a terminal to tighten the cable which
is replaced by a bayonet for the Faston connection.
13
14
21
22
1
2
13
14
23
24
1
2
11
12
21
22
1
2
1
2
96
95
98 12
1
2
11
1496
95
98
11
12
21
22
1
2
11
12
23
24
1
2
11
12
21
22
1
2
13
14
23
24
1
2
33
34
33
34
33
34
31
32
OEPM0018
2/41
2
ABB SACE
S 2.. range
Auxiliary elements
Overall dimensions ...................................... pg. 11/10
1
2
D1
D2
OEPM0020
Undervoltage releases
These are used to pr otect the load in the event of a voltage drop (between 70% and 35% of its rated
value) and/or to effect a positive safety emergency stop. If used for an emergency stop, they cause
undesirable tripping also for temporary microinterruptions of the voltage for a few dozen milliseconds.
ABB SACE has also developed DDA AE blocks which perform the r esidual curr ent function and the
positive safety emergency stop without use of an auxiliary energy source (battery) and auxiliary circuits.
The DDA AE block performs the functions of a shunt trip but without the disadvantages of an
undesirable release (see page 3/54).
Code Type Description
For use with S 240, S 250, S 270, S 280, S 280 UC, DS 640, DS 650, DS 670, DS 850 series
KU 912 8 S2-BM1 12 V d.c. undervoltage release (1 module)
KU 913 6 S2-BM2 24 V a.c. and d.c. undervoltage release (1 module)
KU 914 4 S2-BM3 48 V a.c. and d.c. undervoltage release (1 module)
KU 915 1 S2-BM4 110 V c.a and d.c. undervoltage release (1 module)
KU 916 9 S2-BM5 220 V a.c. and d.c. undervoltage release (1 module)
KU 917 7 S2-BM6 380 V a.c. undervoltage release (1 module)
Technical characteristics
Type S2-BM1 S2-BM2 S2-BM3 S2-BM4 S2-BM5 S2-BM6
Standards IEC 947-1 / EN 60947-1
Rated [V] a.c. - 24 48 110 220-240 380
voltage [V] d.c. 12 24 48 110 220 -
Frequency [Hz] 50...60
Release trip [V] 0.35 Un > V >0.7Un
Terminals [mm2]2 x 1.5
Consumption [mA] 10
Resistance to corrosion [°C/RH] constant atmosphere: 23/83 - 40/93 - 55/20; variable atmosphere: 25/95 - 40/93
Protection degree IPXXB/IP2X
Tightening torque [Nm] 0.4
Dimensions (LxDxH) [mm] 17.5x68x90
TEPM0145
2/42
2
ABB SACE
S 2.. range
Auxiliary elements
Overall dimensions ...................................... pg. 11/10
Mechanical interlocks
Auxiliary element for MCBs and RCBOs. It automatically releases the relative circuit-breaker when
the panel of the electric switchboard is opened or r emoved. The r elease is only mechanical and acts
on the release elements of the circuit-breakers.
Code Type Description
For use with S 240, S 250, S 270, S 280, S 280 UC, DS 640, DS 650, DS 670, DS 850 series
EF 998 8 S2-BP mechanical interlock
TEPM0146
Technical characteristics
Dimensions (WxDxH) [mm] 17.5x68x90
1
2
BP
OEPM0021
2/43
2
ABB SACE
Mechanical interlock with signal contact
It automatically releases the relative circuit-breaker when the panel or the door of the electric
switchboard is opened or removed and indicates that this has occurred by way of a contact.
Code Type Description
For use with S 240, S 250, S 270, S 280, S 280 UC, DS 640, DS 650, DS 670, DS 850 series
EF 999 6 S2-BPS mechanical interlock with signal contact
S 2.. range
Auxiliary elements
Overall dimensions ...................................... pg. 11/10
Technical characteristics
Max. contact capacity at 250 Va.c. 8A ohmic
[In] 2A inductive
Max. contact capacity at 24Vd.c. 4A ohmic
[In] 2A inductive
Mechanical endurance 4000
Operating
temperature [°C] -25...+80
Contact material silver alloy, gold-plated
Insulation voltage terminal/terminal:
[V] 1000
terminal/earth:
[V] 1500
TEPM01426
1
2
BP
2/44
2
ABB SACE
S 2.. range
Accessories
Overall dimensions ...................................... pg. 11/10
The S 2.. range has a varied and
comprehensive group of
accessories which can quickly
and easily resolve even the
smallest of installation problems
and effect functional and safe
installations in the best possible
way.
Terminal cover: enables wall
mounting of MCBs and RCDs
(wall-mounting consumer units
with 2/4/6/8 module capacity
for installation of single circuit-
breakers).
Spacer - false pole: completes
a line of modular circuit-
breakers in switchboards and
consumer units, with projecting
elements with the same profile
as the S 2.. range circuit-
breakers (making the front of the
circuit-breakers uniform).
Mechanical lock: blocks the
circuit-breaker knob.
END clamp: laterally blocks the
circuit-br eakers on the DIN rail.
Flange for rear board
mounting: mounts the circuit-
breaker on the door or front
panel of switchboards.
One-pole withdrawable kit:
makes the circuit-breaker
extractable. It is installed
horizontally or vertically onto the
DIN rail.
Screw protection cover:
insulates and seals the terminal
screws so that they are
inaccessible and raises the
protection degree to IP40.
Block for rotary operation:
transforms operating of the
circuit-br eaker knob into rotary
operation.
Motor operating device:
activates the opening/closing
command of S 2.. two-pole,
three-pole and four -pole MCBs.
Connection busbars: enable
parallel power supply of several
circuit-breakers with the same
number of poles.
TEPM01427
2/45
2
ABB SACE
S 2.. range
Accessories
Overall dimensions ...................................... pg. 11/10
Code Type Description
For use with S 240, S 250, S 270, S 280, DS 640, DS 650, DS 670, DS 850 series
EB 185 6 PCD/N2 terminal cover - 2 modules
EB 186 4 PCD/N4 terminal cover - 4 modules
EB 187 2 PCD/N6 terminal cover - 6 modules
EB 188 0 PCD/N8 terminal cover - 8 modules
EC 068 3 PB sealing kit for PCD/N
EB 176 5 FP1 spacer - false pole - 1 module
EB 177 3 FP2 spacer - false pole - 2 modules
EB 178 1 FP4 spacer - false pole - 4 modules
EB 179 9 FP6 spacer - false pole - 6 modules
EB 183 1 SFP support for FP spacer - false pole
EA 214 5 BSA1 mechanical block
EA 213 7 BSA2 padlock for BSA1
EA 215 2 END CLAMP clamp for DIN rail
KU 930 0 ME1 flange for rear board fixing 1 module
KU 931 8 ME2 flange for rear board fixing 2 modules
KU 932 6 ME3 flange for rear board fixing 3 modules
KU 933 4 ME4 flange for rear board fixing 4 modules
KU 934 2 ME6 flange for rear board fixing 6 modules
KU 935 9 ME8 flange for rear board fixing 8 modules
KU 939 1 S2-MP2 rear terminal for rear board fixing 25mm2 for S 2
Mechanical block BSA1
Padlock BSA2
Flange for rear board fixing ME4
FP2 spacer - false pole
+ SFP support
Support for SFP spacer - false
pole
PCD/N2
Terminal S2-MP2
2/46
2
ABB SACE
S 2.. range
Accessories
Overall dimensions ...................................... pg. 11/10
Code Type Description
KU 943 3 CPV2 sealable screw protection cover for S 2.. circuit-breakers
KU 922 7 S2-EST withdrawable kit for S 2 circuit-breakers up to 32A
EP 742 9 ST label carrier
EP 743 7 ST-E neutral labels
KU 894 8 S2-DH block for rotary operation for S 2.. circuit-breakers
EO 070 6 OXS 5X 330 shaft for rotary operation block 330 mm long
EO 010 2 OHB 2AJ handle for rotary operation block, red/yellow, padlock possible
ST label carrier
CPV 2
S2-EST
S2-DH; OXS SX 330; OHB 2A
2/47
2
ABB SACE
S 2.. range
Accessories
Overall dimensions ...................................... pg. 11/10
Code Type Description
insulated busbars (1m long- max. 56 poles) - fork type
EA 643 5 BCF 1/100 for one-pole circuit-breaker
EA 644 3 BCF 1H/100 for one-pole circuit-breaker with auxiliary contact
EA 645 0 BCF 2/100 for two-pole circuit-breaker
EA 646 8 BCF 3/100 for three-pole circuit-breaker
EA 647 6 BCF 4/100 for four-pole circuit-breaker
EA 648 4 EK-C lateral end cover for busbars BCF 2/100 and BCF 3/100
EA 649 2 EK-C-4 lateral end cover for busbars BCF 4/100
insulated busbars (1m long - max. 56 poles) - pin type
EA 650 0 BCP 1/100 for one-pole circuit-breaker
EA 524 7 BCP 2/N for two-pole circuit-breaker
EA 525 4 BCP 3/N for three-pole circuit-breaker
EA 526 2 BCP 4/N for four-pole circuit-breaker
EA 549 4 EK-B lateral end cover for busbars BCP 2/N
EA 550 2 EK-M lateral end cover for busbars BCP 3/N-4/N
EA 546 0 MR/35 S terminal for supply cable for busbars BCF/N and BCP/N
EA 109 7 4E 1905 rail busbar EN 50022 (DIN) mm 35 2m long
motor operating devices 230V a.c.
KU 936 7 S2-CM2 for two-pole MCBs
KU 937 5 S2-CM3 for three-pole MCBs
KU 938 3 S2-CM4 for four-pole MCBs
BCF 4/100
BCF 1/100
BCP 4/N
2/48 ABB SACE
The S 290 ranges of circuit-
breakers enables the use of
switchboards and consumer
units for modular devices with
45 mm slotting and rated cur-
rents up to 125A.
They can be mounted along-
side standard modular circuit-
breakers because of their
modular design and ability to be
installed on a 35 mm DIN EN
50022 rail.
The S 290 ranges circuit-brea-
kers are available in 1-2-3-4
pole versions with a width equal
to 1 1/2 modules per pole (27
mm).
The time-current characteris-
tics available are C and D, as
normally required for circuit-
breakers which are used for
main switchboard functions or
are however installed upstream
of other MCBs.
The fact that these devices fully
comply with the IEC 898 / EN
60898 Standards means that
they can be used by untrained
staff, as sometimes required for
circuit-breakers with these
rated currents.
The S 290 circuit-breakers have
a series of special auxiliary ele-
ments which effect the normal
TEPM01429
TEPM01428
TEPM01430
functions required in modern
installations (indication of trip-
ping, remote release, etc).
2/49
2
ABB SACE
S 290 range
Contents
Technical characteristics .......................................................................................................2/50
Order information
S 290 series ..........................................................................................................................2/51
Auxiliary elements
Shunt trips .............................................................................................................................2/53
Auxiliary/signal contacts........................................................................................................2/54
Undervoltage releases ..........................................................................................................2/55
2/50
2
ABB SACE
S 290 range
Technical character istics
S 290
Standards IEC 898 / EN 60898, IEC 947-2 / EN 60947-2
Rated current In [A] 80 <In < 125
Poles 1P, 2P, 3P, 4P
Rated voltage Ue one-pole a.c. [V] 230
multiple-pole a.c. [V] 230/400
one-pole d.c. [V] 60
two-pole d.c. [V] 125
Insulation voltage Ui [V] 500
Max. operating voltage Ub max. [V] 440
Min. operating voltage Ub min. [V] 12VAC - 12VDC
Rated frequency [Hz] 50…60
Rated breaking capacity Icn [A] 10000
acc. to IEC 898
Rated breaking capacity ultimate Icu [kA] 25
acc. to IEC 947-2
2 poles - 230 V service Ics [kA] 20
Rated breaking capacity ultimate Icu [kA] 15
acc. to IEC 947-2
3,4 poles - 400 V service Ics [kA] 10
Voltage withstanding capacity impulse (1,2/50) Uimp [kV] 5
at rated freq.
(50-60Hz) x 1 min. [kV] 2.5
Thermomagnetic release B: 3 In < Im < 5 In
characteristic C: 5 In < Im < 10 In
D: 10 In < Im < 20 In
K: 8 In < Im < 14 In
Z: 2 In < Im < 3 In
Limitation class 3
Toggle black sealable in ON-OFF position
Electrical life 10000
Mechanical life 20000
Protection degree housing IP4X/IPXXD (excluding terminal area)
terminals IP2X/IPXXB
Self-extinguishing degree V0 thickness 1.6 UL 94 yellow paper
Mechanical shock resistance minimum 30 g - 2 shocks - duration 13 ms
Resistance to vibrations acc. to IEC 68-2-6 5 g - 20 cycles at frequency 5…150…5 Hz with load 0.8 In
Tropicalization humid heat [°C/RH] 28 cycles with 55/95…100
acc. to IEC 68-2 constant climatic
conditions [°C/RH] 23/83 - 40/93 - 55/20
variable climatic
conditions [°C/RH] 25/95 - 40/95
Ambient temperature
(with daily average<+35°C) [°C] -25…+55
Storage temperature [°C] -40…+70
Terminal size upper/lower per cable [mm2] 50/50
Mounting on DIN rail EN 50022 (35mm) by means of rapid fixing device
Pole dimensions [mm] H: 90 x D: 70 x W: 26.25
Pole weight [g] 200
2/51
2
ABB SACE
Breaking capacity
acc. to IEC 898 / EN 60898
In [A] poles voltage [V] Icn [kA]
80...125
All
230/400 10
acc. to IEC 947-2 / EN 60947-2
In [A] poles voltage [V] Icn [kA] Ics [kA]
80...125 1 230 15 10
2 127 50 25
230 25 20
400 15 10
3, 4 230 25 20
400 15 10
Breaking capacity
acc. to IEC 947-2 / EN 60947-2
In [A] poles voltage [V] Icn [kA] Ics [kA]
80...125 160 15 15
2 110 15 15
S 290 range
S 290 series
Accessories ................................................... pg. 2/53 Technical details ........................................... pg. 10/4 Overall dimensions ........................................ pg. 11/4
C (Im = 5…10 In); D (Im = 10…20 In)
Tripping characteristics
Application: industrial
RCD blocks
DDA 100A only on C curve circuit-breakers
Rated currents Code
In Characteristic
[A] C D
1P - S 291 type
80 KU 950 8 KU 974 8
100 KU 951 6 KU 975 5
125 KU 952 4
2P - S 292 type
80 KU 953 2 KU 977 1
100 KU 954 0 KU 978 9
125 KU 955 7
3P - S 293 type
80 KU 956 5 KU 980 5
100 KU 957 3 KU 981 3
125 KU 958 1
4P - S 294 type
80 KU 959 9 KU 983 9
100 KU 960 7 KU 984 7
125 KU 961 5
Note: the 100A DDA RCD blocks are suitable for assembly with the S 290
series MCBs with C characteristic and In 100A
TEPM0070
TEPM0059
TEPM0071
TEPM0072
2/52
2
ABB SACE
S 290 range
Auxiliary elements
S290 - A
SHUNT
TRIP
S290 - UA
UNDERVOLTAGE
RELEASE
S290 - H11
AUXILIARY
CONTACT S290 - S
SIGNAL
CONTACT
S290 - H11
AUXILIARY
CONTACT
S290 - A
SHUNT
TRIP
S290 - UA
UNDERVOLTAGE
RELEASE
DDA
RCD BLOCK
S290 - S
SIGNAL
CONTACT
S290 - S
SIGNAL
CONTACT
S290
MCB
S290 - H11
AUXILIARY
CONTACT
S290 - S
SIGNAL
CONTACT
S290 - H11
AUXILIARY
CONTACT
Examples of combinations of S 290 series circuit-breakers with auxiliary elements (maximum configurations)
The S 290 circuit-breakers are
supplied with special shunt
trips, undervoltage releases
and contacts (auxiliary and sig-
nal).
All the accessories are installed
to the right of the circuit-
breaker. The left part is used for
installing RCD blocks.
The rules for accessorizing are
shown in the figure below.
TEPM01431
2/53
2
ABB SACE
Technical characteristics
Type S 290 A1 S 290 A2
Rated voltage [V]
a.c. 110...415 24...48
d.c. 110...250 24...48
Max. release duration [ms]< 10 < 10
Consumption on release [VA]
a.c. 20 ÷ 180 40 ÷ 200
d.c. 20 ÷ 180 40 ÷ 200
Terminals [mm2]25 25
Tightening torque [Nm] 2 2
Dimensions (WxDxH) [mm]
17.5x68x90 17.5x68x90
S 290 range
Auxiliary elements
Overall dimensions ...................................... pg. 11/10
Shunt trips
These are used for remote tripping of the circuit-breakers.
Code Type Description
(for S 290 series)
KU 989 6 S 290 A1 shunt trip
110-415V a.c. and 110V d.c.
KU 991 2 S 290 A2 shunt trip
24-48V a.c./d.c.
TEPM0137 TEPM0136
1
2
C1
C2
S290 A1
S290 A2
Installation only on right
2/54
2
ABB SACE
S 290 range
Auxiliary elements
Overall dimensions ...................................... pg. 11/10
Auxiliary/signal contacts
The auxiliary contact indicates the position of the circuit-breaker contacts. When the position of the
contacts changes, whether manually or automatically, it indicates their status.
The signal contact indicates the position of the contact of the circuit-breaker after automatic release
of the circuit-breaker caused by overload or short-circuit. For manual operation, it does not trip.
An auxiliary contact and a signal contact can be installed side by side on the same circuit-breaker.
Code Type Description
(for S 290 series)
KU 987 0 S 290 H11 auxiliary contact 1 NO+1NC
(1/2 module)
KU 988 8 S 290 S signal contact (1/2 module)
Technical characteristics
Type S 290 H11 S 290 S
Description 1NO+1NC
Alternating Ue [V] 230 400
current Ie [A] 62
Direct Ue [V] 24/60/110/220
current Ie [A] 3/3/3/1
Min. operating voltage [V] 12 a.c. -12 d.c.
Min. operating current [mA] 5
Terminals [mm2] 0.5 x 2.5
Dielectric strength [kV] 3
Resistance to short- [A] 1000 (protected with S 2
circuit at 240V a.c. breaker char. K 6A)
Impulse voltage withstand
capacity [kV] 4
Tightening torque [Nm] 1
Dimensions (WxDxH) [mm] 8.75x68x90
TEPM0142 TEPM0141
13
14
21
22
1
2
13
14
21
22
1
2
OEPM0019
2/55
2
ABB SACE
S 290 range
Auxiliary elements
Overall dimensions ...................................... pg. 11/10
Undervoltage releases
These are used to protect the load in the event of a voltage drop (between 70% and 35% of its rated
value) and/or to effect an emergency stop in positive safety.
Code Type Description
(for S 290 series)
KU 990 4 S 290 UA 230 230V a.c. undervoltage release (1 module)
Technical characteristics
Type S 290-UA 230
Standards VDE0660 part I - CEI EN 60947.1
Rated [V] a.c. 230
voltage [V] d.c. -
Frequency [Hz] 50...60
Release trip threshold [V] 0.35 Un > V > 0.7Un
Terminals [mm2] 2 x 1.5
Consumption [mA] 10
Resistance [°C/RH] constant atmosphere:
to corrosion 23/83 - 40/93 - 55/20;
variable atmosphere:
25/95 - 40/93
Protection degree IPXXB/IP2X
Tightening torque [Nm] 0.4
Dimensions (WxDxH) [mm] 17.5x68x90
1
2
D1
D2
OEPM0020
TEPM01432
2/56 ABB SACE
The S 500 circuit-breakers have
a high breaking capacity which
is obtained using the “double
interruption” technique.
These circuit-breakers have a
special movable fork contact
which operates with two sepa-
rate breaking chambers for
each pole in the device.
This structure leads to a high
energy limitation capacity and,
consequently, a high breaking
capacity.
Because of the tripping speed
(less than 3 ms up to 50kA), the
S 500 breakers offer consider-
able protection to the standard
modular circuit-breakers in-
stalled downstream.
If they are installed downstream
of moulded-case circuit-brea-
kers, on the other hand, they
easily carry out selective coor-
dination with the upstream pro-
tection devices.
The S 500 circuit-breakers are
available in 1-2-3-4 pole ver-
sions with width equal to 1 1/2
modules per pole (27 mm), up
to a rated current of 63A.
The time-current characteristics
available are C and B for pro-
tecting circuits in alternating
current and B for protecting cir-
cuits in direct current (S 500 UC
series).
S 500-K versions with adjus-
table thermal and S 500-KM
versions with magnetic only
releasers are also available.
TEPM01434
TEPM01433
2/57
2
ABB SACE
S 500 range
Contents
Technical characteristics .......................................................................................................2/58
Order information
S 500 B-C-D series ...............................................................................................................2/60
S 500 UC series (especially for direct current) ....................................................................2/62
S 500-K motor protection series with adjustable thermal release,
S 500-KM magnetic only .......................................................................................................2/64
Auxiliary elements and accessories
Auxiliary/signal contacts........................................................................................................2/66
Shunt trips .............................................................................................................................2/67
Undervoltage releases ..........................................................................................................2/67
Accessories...........................................................................................................................2/68
2/58
2
ABB SACE
S 500 range
Technical character istics
S 500
Standards IEC 898 / EN 60898, IEC 947-2 / EN 60947-2, UL 1077, CE conformity,
CAN/CSA-C22.2 N235-M89
Poles 1P, 2P, 3P, 4P
Rated current In [A] 6 < In < 63
Rated voltage Ue [V] 690
Rated breaking capacity Icn [kA] 25
acc. to IEC 898 service Ics [kA] 12.5
Rated breaking capacity ultimate Icu [kA] 50
acc. to IEC 947-2 - 230 /400V service Ics [kA] 25
Rated breaking capacity ultimate Icu [kA] 30
acc. to IEC 947-2 - 440V service Ics [kA] 22
Rated breaking capacity ultimate Icu [kA] 15
acc. to IEC 947-2 - 500V service Ics [kA] 11
Rated breaking capacity ultimate Icu [kA] 6
acc. to IEC 947-2 - 690V service Ics [kA] 3
Rated breaking capacity Icc [kA] 30 (In < 25 A); 18 (25 < In < 63 A)
acc. to UL 1077 and CSA - 240V
Rated breaking capacity Icc [kA] 14
acc. to UL 1077 and CSA - 277/480V
Rated breaking capacity Icc [kA] 6
acc. to UL 1077 and CSA - 600V
Thermomagnetic release B: 3 In < Im < 5 In
characteristic C: 5 In < Im < 10 In
D: 10 In < Im < 20 In
K: 8 In < Im < 14 In
Z: 2 In < Im < 3 In
Reference temperature [°C] 30
Rated frequency 16 2/3 …60 Hz (S500-X:> 60 … 400 Hz)
Tropicalization DIN 50016
Current limitation at Icc 30 kA Ip < 8000 A
Total short-circuit breaking time max. 2.5 ms at Icc 30 kA
Mechanical life 20000
Protection degree IP20
Ambient temperature
(with daily average<+35°C) [°C] -25…+55
Mounting on DIN rail EN 50022 (35mm) by means of rapid fixing device
Line connection top/bottom
Terminal size upper/lower per cable [mm2] 25/25
2/59
2
ABB SACE
S 500 range
Technical character istics
S 500UC-B S 500UC-K S 500-K S 500-KM
Standards IEC 898 / EN 60898, IEC 947-2 / EN 60947-2, UL 1077, CE conformity,
CAN/CSA-C22.2 N235-M89
Poles 1P, 2P, 3P, 4P 1P, 2P, 3P 3P
Rated current In fixed [A] 6 < In < 63 1,6 < In < 75
adjustable [A] 0.1 < In < 45 0.1 < In < 11 11 < In < 45
Rated voltage Ue [V] 250 VDC (1P), 500 VDC (2P), 690 AC
750 VDC (3P)
Rated breaking capacity ultimate Icu [kA] 50 30 25
acc. to IEC 947-2 - 230 /400V service Ics [kA] 30 25
Rated breaking capacity ultimate Icu [kA] 30 25
acc. to IEC 947-2 - 440V service Ics [kA] 22 22
Rated breaking capacity ultimate Icu [kA] 20 15
acc. to IEC 947-2 - 500V service Ics [kA] 15 11
Rated breaking capacity ultimate Icu [kA] 6 6
acc. to IEC 947-2 - 690V service Ics [kA] 3 3
Rated breaking capacity Icc [kA] 30 18
acc. to UL 1077 and CSA - 240V
Rated breaking capacity Icc [kA] 14 14
acc. to UL 1077 and CSA - 277/480V
Rated breaking capacity Icc [kA] 6 6
acc. to UL 1077 and CSA - 600V
Rated breaking capacity [kA] 30
acc. to UL 1077, CSA and IEC 947-2 - 250Vd.c. (1P),
500Vd.c. (2P), 750Vd.c. (3P) L/R 15 ms
Thermomagnetic release 5 In < Im < 7 In (DC) 8 In < Im < 10 In (DC & AC, In < 0.21)
characteristic 3 In < Im < 5 In (AC) 10 In < Im < 12 In (DC & AC, 0,2 < In < 0.42)
12 In < Im < 14 In (DC & AC, In > 0.38)
Reference temperature [°C] 30 40
Rated frequency 16 2/3 …60 Hz (S500-X:> 60 … 400 Hz)
Tropicalization DIN 50016
Current limitation at Icc 30 kA I < 3000 A I < 8000 A
Total short-circuit breaking time max. 2.5 ms at Icc 30 kA
Mechanical life 20000
Protection degree IP20
Ambient temperature
(with daily average<+35°C) [°C] -25…+55
Mounting on DIN rail EN 50022 (35mm) by means of rapid fixing device
Line connection top/bottom
Terminal size upper/lower per cable [mm2] 25/25
2/60
2
ABB SACE
S 500 range
S 500 B-C-D series
Accessories ................................................... pg. 2/66 Technical details ........................................... pg. 10/4 Overall dimensions ........................................ pg. 11/5
B (Im = 3…5 In); C (Im = 5…10 In)
D (Im = 10…20 In)
Tripping characteristics
Application: commercial, industrial
RCBO version
F 500
Rated currents Code
In Characteristic
[A] B C D
1P - S 501 type
6EI 060 4 EI 100 8 -
10 EI 061 2 EI 101 6 on request
13 EI 062 0 EI 102 4 on request
16 EI 063 8 EI 103 2 on request
20 EI 064 6 EI 104 0 on request
25 EI 065 3 EI 105 7 on request
32 EI 066 1 EI 106 5 on request
40 EI 067 9 EI 107 3 on request
50 EI 068 7 EI 108 1 on request
63 EI 069 5 EI 109 9 on request
2P - S 502 type
6EI 070 3 EI 110 7 -
10 EI 071 1 EI 111 5 on request
13 EI 072 9 EI 112 3 on request
16 EI 073 7 EI 113 1 on request
20 EI 074 5 EI 114 9 on request
25 EI 075 2 EI 115 6 on request
32 EI 076 0 EI 116 4 on request
40 EI 077 8 EI 117 2 on request
50 EI 078 6 EI 118 0 on request
63 EI 079 4 EI 119 8 on request
TEPM0073
TEPM0074
2/61
2
ABB SACE
Breaking capacity
acc. to IEC 898 / EN 60898
In [A] poles voltage [V] Icn [kA]
6...63 All 230/400 25
acc. to IEC 947-2 / EN 60947-2
In [A] poles voltage [V] Icu [kA] Ics [kA]
6...63 All 230/400 50 25
440 30 22
500 15 11
690 6 3
Breaking capacity
acc. to IEC 947-2 / EN 60947-2
In [A] poles voltage [V] Icu [kA] Ics [kA]
6...63 1753030
2 125 30 30
Rated currents Code
In Characteristic
[A] B C D
3P - S 503 type
6EI 080 2 EI 120 6 -
10 EI 081 0 EI 121 4 on request
13 EI 082 8 EI 122 2 on request
16 EI 083 6 EI 123 0 on request
20 EI 084 4 EI 124 8 on request
25 EI 085 1 EI 125 5 on request
32 EI 086 9 EI 126 3 on request
40 EI 087 7 EI 127 1 on request
50 EI 088 5 EI 128 9 on request
63 EI 089 3 EI 129 7 on request
4P - S 504 type
6EI 090 1 EI 130 5 -
10 EI 091 9 EI 131 3 on request
13 EI 092 7 EI 132 1 on request
16 EI 093 5 EI 133 9 on request
20 EI 094 3 EI 134 7 on request
25 EI 095 0 EI 135 4 on request
32 EI 096 8 EI 136 2 on request
40 EI 097 6 EI 137 0 on request
50 EI 098 4 EI 138 8 on request
63 EI 099 2 EI 139 6 on request
S 500 range
S 500 B-C-D series
Accessories ................................................... pg. 2/66 Technical details ........................................... pg. 10/4 Overall dimensions ........................................ pg. 11/5
TEPM0075
TEPM0076
The MCBs S 502, S 503, S 504 (B, C, D) 10…63A have obtained
R.I.Na. approval for naval application at voltages 400, 440, 500, 690V
a.c.
R.I.Na. approval
2/62
2
ABB SACE
S 500 range
S 500 UC series (especially for direct current)
Accessories ................................................... pg. 2/66 Technical details ........................................... pg. 10/4 Overall dimensions ........................................ pg. 11/5
B (Im = 3…5 In); K (Im = 8…14 In)
Tripping characteristics
Application: protection of circuits in d.c.
Rated currents Code
In Characteristic
[A] B K
1P S 501 UC type
6EI 315 2
10 EI 316 0
13 EI 317 8
16 EI 318 6
20 EI 319 4
25 EI 320 2
32 EI 321 0
40 EI 322 4
50 EI 323 6
63 EI 324 6
2P S 502 UC type
6EI 325 1
10 EI 326 9
13 EI 327 7
16 EI 328 5
20 EI 329 3
25 EI 330 1
32 EI 331 9
40 EI 332 7
50 EI 333 5
63 EI 334 3
TEPM0078
TEPM0077
2/63
2
ABB SACE
Breaking capacity
acc. to IEC 947-2 / EN 60947-2
In [A] poles voltage [V] Icu [kA] Ics [kA]
0.1…63 1P 250 30 30
2P 500 30 30
3P 750 30 30
in alternating current they maintain the same
performance as S 500 B, K
S 500 range
S 500 UC series (especially for direct current)
Accessories ................................................... pg. 2/66 Technical details ........................................... pg. 10/4 Overall dimensions ........................................ pg. 11/5
Rated currents Code
In Characteristic
[A] B K
3P S 503UC type
6EI 335 0
10 EI 336 8
13 EI 337 6
16 EI 338 4
20 EI 339 2
25 EI 340 0
32 EI 341 8
40 EI 342 6
50 EI 343 4
63 EI 344 2
1, 2, 3, 4P S 501UC-K, S 502UC-K, S 503UC-K and S 504UC-K motor protection with adjustable thermal
types*
0.1 - 0.16 on request
... on request
38 - 45 on request
* The adjustment ranges are the same as those for the S 500-K circuit-breakers (see following page)
TEPM0079
2/64
2
ABB SACE
Breaking capacity
acc. to IEC 947-2 / EN 60947-2
In [A] poles voltage [V] Icu [kA] Ics [kA]
0.1...11 1, 2, 3 230/400 50 30
440 30 22
500 20 15
690 6 3
10...45 1, 2, 3 230/400 30 25
440 25 22
500 15 11
690 6 3
S 500 range
S 500-K motor protection series with adjustable thermal
release, S 500-KM magnetic only
Accessories ................................................... pg. 2/66 Technical details ........................................... pg. 10/4 Overall dimensions ........................................ pg. 11/5
K (Im = 8…14 In); KM (Im = 8…14 In)
Tripping characteristics
Application
Rated currents Code
In Characteristic K
[A] 1P 2P 3P
S 500 K type
0.1 - 0.15 EI 450 7 EI 475 4 EI 345 9
0.14 - 0.21 EI 451 5 EI 476 2 EI 346 7
0.2 - 0.3 EI 452 3 EI 477 0 EI 347 5
0.28 - 0.42 EI 453 1 EI 478 8 EI 348 3
0.38 - 0.58 EI 454 9 EI 479 6 EI 349 1
0.53 - 0.8 EI 454 6 EI 480 4 EI 350 9
0.73 - 1.1 EI 456 4 EI 481 2 EI 351 7
1 - 1.5 EI 457 2 EI 482 0 EI 352 5
1.4 - 2.1 EI 458 0 EI 483 8 EI 353 3
2 - 3 EI 459 8 EI 484 6 EI 354 1
2.8 - 4.2 EI 460 6 EI 485 3 EI 355 8
3.8 - 5.8 EI 461 4 EI 486 1 EI 356 6
5.3 - 8 EI 462 2 EI 487 9 EI 357 4
7.3 - 11 EI 463 0 EI 488 7 EI 358 2
10 - 15 EI 464 8 EI 489 5 EI 359 0
14 - 20 EI 465 5 EI 490 3 EI 360 8
18 - 26 EI 466 3 EI 491 1 EI 361 6
23 - 32 EI 467 1 EI 492 9 EI 362 4
29 - 37 EI 468 9 EI 493 7 EI 363 2
34 - 41 EI 469 7 EI 494 5 EI 364 0
38 - 45 EI 470 5 EI 495 2 EI 365 7
Rated currents Code
In Characteristic
[A] KM 3P
3P - S 503 KM magnetic only type*
1.6 EI 417 6
2.5 EI 418 4
4EI 419 2
6EI 420 0
9EI 421 8
20 EI 422 6
32 EI 423 4
52 EI 424 2
63 EI 425 9
75 EI 428 3
(*) 1P, 2P, 4P versions also on request
specific for protection of motors
(with adjustable thermal: K; magnetic only: KM)
TEPM0080
TEPM0081
2/65
2
ABB SACE
For the S 500 range of circuit-
breakers, shunt trips,
undervoltage releases and con-
tacts (auxiliary and signal) are
available.
Only the auxiliary contacts can
be mounted by the installer; the
undervoltage releases and
shunt trips are installed directly
at the factory and, for this rea-
son, cannot be ordered sepa-
rately.
Four shunt trips for voltages of
24V a.c./d.c, 110V a.c./d.c,
220V a.c./d.c, and 400V a.c./
d.c, and eight undervoltage re-
S 500 range
Auxiliary elements
leases for voltages equal to 24V
a.c., 110V a.c., 230V a.c., 400V
a.c., 24V d.c., 110V d.c., 230V
d.c., 400V d.c. are available.
These auxiliary elements can
also be mounted on the corre-
sponding RCBO version (F 500
series).
The S 500 circuit-breakers are
also equipped with a rotary
drive with the possibility of se-
lection from different rotary han-
dle.
TEPM01435
2/66
2
ABB SACE
Auxiliary/signal contacts
The auxiliary contact indicates the position of the circuit-breaker contacts. When the position of the
contacts changes, whether manually or automatically, it indicates their status.
The signal contact indicates the position of the contact after automatic release of the circuit-breaker
caused by overload or short-circuit. For manual operation, it does not trip.
(for S 500, F 500 series)
EI 410 1 S5-H11 auxiliary contacts 1NO+1NC
(12.5 mm)
EI 411 9 S5-H20 auxiliary contacts 2NO (12.5 mm)
EI 412 7 S5-S11 signal contacts 1NO+1NC
(12.5 mm)
EI 413 5 S5-S20 signal contacts 2NO
(12.5 mm)
Technical characteristics
Type S5-H11 S5-H20 S5-S11 S5-S20
Description 1NO + 1NC 2NO 1NO + 1NC 2NO
Alternating Ue [V] 230 400
current Ie [A] 2 1
Direct Ue [V] 220
current Ie [A] 0.5
Min. operating voltage [V] 12 a.c. -12 d.c.
Min. operating current [mA] 10
Terminals [mm2] 0.5 x 2.5
Dielectric strength [kV] 3
Resistance to short-
circuit at 240V a.c. [A] 1000 (protected with S 2 breaker characteristic K 6A)
Impulse voltage [kV] 4
withstand capacity
Tightening torque [Nm] 1
Dimensions (WxDxH) [mm] 12.5 x 92 x 92.5
13
14
21
22
1
2
13
14
23
24
1
2
13
14
21
22
1
2
13
14
23
24
1
2
S 500 range
Auxiliary elements
Overall dimensions ...................................... pg. 11/10
TEPM0143
TEPM0144
2/67
2
ABB SACE
Shunt trips
Code Type Description
(for S 500, F 500 series)
* S5 AL 24V shunt trip
24V a.c./d.c.
* S5 AL 110V shunt trip
110V a.c./d.c.
* S5 AL 220V shunt trip
220V a.c./d.c.
* S5 AL 400V shunt trip
400V a.c./d.c.
* The S5 AL type shunt trips must be ordered with the S 500 circuit-breaker or the F 500 RCD, since they are
installed directly in the factory (they cannot be installed by the customer).
Undervoltage releases
Code Type Description
(for S 500, F 500 series)
* S5-UA 24V ca 24V c.a undervoltage release
(1/2 module)
* S5-UA 110V ca 110V a.c. undervoltage releases
(1/2 module)
* S5-UA 230V ca 230V a.c. undervoltage release
(1/2 module)
* S5-UA 400V ca 400V a.c. undervoltage release
(1/2 module)
* S5-UA 24V cc 24V d.c. undervoltage release
(1/2 module)
* S5-UA 110V cc 110V d.c. undervoltage release
(1/2 module)
* S5-UA 230V cc 230V d.c. undervoltage release
(1/2 module)
* S5-UA 400V cc 400V d.c. undervoltage release
(1/2 module)
*The S5 UA undervoltage releases must be ordered with the S 500 circuit-breaker or the F 500 RCD since they
are installed directly in the factory (they cannot be installed by the customer).
S 500 range
Auxiliary elements
Overall dimensions ...................................... pg. 11/10
1
2
C1
C2
S5 AL
Installation only on left
s
(fitted in factory)
2/68
2
ABB SACE
S 500 range
Accessories
Overall dimensions ...................................... pg. 11/10
EI 409 3 S 500 RD3 rotary control knob for 1P, 2P, 3P S 500 circuit-breakers
EI 426 7 S 500 RD4 rotary control knob for 4P S 500 circuit-breakers
* when using S 500 circuit-breakers with undervoltage releases or shunt trips, the rotary control knob to order is
S 500 RD4 independently from the poles of the circuit-breakers.
for S 500 and F 500 series
EI 427 5 S 500 H2B1 rotary control knob; black IP 65 with interlock
ON, padlock possible in OFF position
EI 437 4 S 500 H2Y1 rotary control knob; red/yellow IP 65 with interlock
ON, padlock possible in OFF position
EI 438 2 S 500 H2B2 rotary control knob; black IP 65 with interlock
ON, padlock possible in OFF position with manual release
EI 439 0 S 500 H2Y2 rotary control knob; red/yellow IP 65 with interlock
ON, padlock possible in OFF position with manual release
EI 442 4 S 500 HP2B emergency plate - black
EI 443 2 S 500 HP2Y emergency plate - red/yellow
EI 416 8 S 500 S 51 drive shaft L=85 mm
EI 415 0 S 500 S 52 drive shaft L=180 mm
EI 440 8 S 500 H8B rotary control knob; black IP 65 with
interlock ON, padlock possible in OFF position with
manual release
EI 441 6 S 500 H8Y rotary control knob for circuit-breakers; red/yellow IP 65 with
interlock ON, padlock possible in OFF
position with manual release
EI 444 0 S 500 S 56 drive shaft L=265 mm
S500 RD3
S500 H2B1
S500 H2B2
S500 H8B
S500 H8Y
S500 S51
S500 S52
S500 S56
2/69
2
ABB SACE
S 700 range
Contents
Technical characteristics .......................................................................................................2/70
Order information
S 700 series and accessories ...............................................................................................2/71
2/70
2
ABB SACE
Breaking capacity
acc. to IEC 947-2 / EN 60947-2
In [A] poles voltage [V] Icu [kA] Ics [kA]
25...100 1 230 50 25
2 230 50 25
400 30 15
3, 4 230 50 25
400 30 15
4 500 15 7.5
690 10 5
E sel. (Im = 5…6.25 In)
Tripping characteristics
Application: industrial, naval * The S 702, S 703 MCBs for naval application have obtained R.I.Na.
approval
R.I.Na. approval
Rated current In [A] 25...100
Rated voltage a.c. [V] 400
Min. operating voltage [V] 125
Electric operations [n°] 4,000
Mechanic operations [n°] 10,000
Tropicalization at 55°C acc. to DIN 40046 95%UR
Terminals per cable cage type up to 70mm2
Self-extinguishing degree V0 thickness. 3.2mm
Poles 1P 2P 3P 4P
Weight [g] 550 1100 1650 2200
2/71
2
ABB SACE
S 700 range
S 700 series and accessories
Technical details ............................................ pg. 10/4 Overall dimensions ....................................... pg. 11/5
Rated currents Code
In Characteristic
[A] E sel.
1P - S 701 type
25 EG 700 7
35 EG 701 5
50 EG 702 3
63 EG 703 1
80 EG 704 9
100 EG 705 6
2P - S 702 type naval application*
25 EG 706 4 EG 730 4
35 EG 707 2 EG 731 2
50 EG 708 0 EG 732 0
63 EG 709 8 EG 733 8
80 EG 710 6 EG 734 6
100 EG 711 4 EG 735 3
3P - S 703 type naval application*
25 EG 712 2 EG 736 1
35 EG 713 0 EG 737 9
50 EG 714 8 EG 738 7
63 EG 715 5 EG 739 5
80 EG 716 3 EG 740 3
100 EG 717 1 EG 741 1
4P - S 704 type
25 EG 718 9
35 EG 719 7
50 EG 720 5
63 EG 721 3
80 EG 722 1
100 EG 723 9
Accessories for S 700 series
EG 035 8 BT3 plate for assembly on EN50022 rail
(1 piece for 1P, 2 pieces for 2P, 3P, 4P)
EG 037 4 KA1 pair of terminal covers
(2 pieces per pole)
EG 040 8 SA connection flange and fixing on busbars
EG 041 6 SPA plate for blocking manual opening
EG 042 4 SPB1 transparent plate for blocking operation, for lever position inspection
EG 044 0 SPE toggle locking device, padlock possible
EL 175 6 BA50 transparent label carrier; covers and assorted labels
EG 046 5 EST1 withdrawable kit on NH base (2 pieces per pole)
EG 047 3 EST2 terminal protection for withdrawable version NH base (2 pieces per pole)
TEPM0082
TEPM0083
TEPM0084
TEPM0085
3/1
3
ABB SACE
RCDs
Contents
RCBOs-DS 9.. range .............................................................................................................3/3
RCBOs-DS ... - F 500 range................................................................................................3/23
RCCBs-F 3.. - F 6.. - F 800 ranges .....................................................................................3/35
RCD blocks-DDA and D ranges.........................................................................................3/49
3/2 ABB SACE
With the new range of RCBOs
DS 9.. ABB SACE is able to
provide a protection solution for
all type of single-phase circuits
in modern applications.
All the RCBOs are characteri-
zed by an innovative design
with a single red/green two-
color operating lever and re-
sidual current trip signal on
the front of the apparatus.
The DS 9.. range satisfies all
protection r equir ements in two
modules, offering the opportu-
nity of choosing between thr ee
different breaking capacities,
five different sensitivities, and
for each of these, the possibili-
ty of choosing between type A
or type AC residual current pro-
tection.
The DS 9.. range consists of
three series, DS 941 - DS 951
- DS 971, with 4.5kA, 6kA and
10kA respectively of breaking
capacity according to IEC
1009.
Overload and short-circuit pro-
tection is provided by the same
thermomagnetic component as
the S 9.. MCBs range; the DS
9.. range thus offers all the ben-
efits of the mechanics of these
devices, in particular the clos-
ing velocity of the contacts
which is indipendent from the
rotation velocity of the toggle;
this is ensured by a trip mecha-
nism patented by ABB SACE.
The B and C characteristics are
available for all types, with rated
current from 6 up to 40A. The
availability of curve B in this
range can offer protection to
lines of extended lenght, typi-
cally found in terminal single-
phase circuits.
Each series is available in all
required sensitivities for these
type of RCBOs: 30mA –
100mA – 300mA – 500mA –
1000mA, giving the widest pos-
sible choice. For DS 941 series
only , the 10mA sensitivity is also
available with tripping charac-
teristic B.
RCBOs type AC are suitable for
all the installations where ther e
may be loads with alternate
faults currents. Type A are de-
signed to be used in case of
alternate and pulsating DC fault
currents; typical use in installa-
tion where users are equipped
with electronic devices meant
to rectify currents or other
physical variables.
All the RCBOs are insensitive
to temporary surge currents
generated by lightning, opera-
tions on the power network,
interferences, etc.
According with ABB SACE’s
quality policy, the whole DS 9..
range has already obtained the
TEPM01436
TEPM01437
TEPM01438
TEPM01440
following approvals: IMQ, VDE,
UTE, KEMA.
The whole range can be fitted
with the same accessories of
the S 9... range, therefore per-
mitting many different functions
and configurations.
3/3
3
ABB SACE
Contents
Technical characteristics .........................................................................................................3/4
Order information
DS 941 series .........................................................................................................................3/6
DS 951 series .......................................................................................................................3/10
DS 971 series .......................................................................................................................3/14
Auxiliary elements (*)
Shunt trips .............................................................................................................................3/19
Auxiliary/signal contacts........................................................................................................3/20
Undervoltage releases ..........................................................................................................3/21
RCBOs-DS 9.. range
(*) The auxiliary elements are the same as those from the range of miniature circuit-breakers
S 9..
3/4
3
ABB SACE
RCBOs-DS 9.. range
Technical characteristics
DS 941
Standards IEC 1009 / EN 61009
Type AC, A
Rated current In [A] 6 <In < 40
Poles 1P+N
Rated voltage Ue one-pole AC [V] 230
Max. operating voltage Ub max. [V] 250
Min. operating voltage Ub min. [V] 110
Rated breaking capacity Icn [A] 4500
acc. to IEC 1009
Rated breaking capacity ultimate Icu [kA] 6
acc. to IEC 947-2 1P+N - 230V service Ics [kA] 4.5
Voltage withstanding impulse (1,2/50)
capacity Uimp [kV] 5
at rated freq.
(50-60Hz) x 1 min. [kV] 3
Thermomagnetic B: 3 In < Im < 5 In
release characteristic C: 5 In < Im < 10 In
Limitation class 3
Max. operating voltage
of circuit test [V] 253
Min. operating voltage
of circuit test [V] 110
Surge current
resistance [A] 250 A (8/20 wave) acc. to VDE 0432 Part 2
Rated frequency [Hz] 50..60
Rated sensitivity In[mA]
Tripping threshold AC type 0.5…1 In
A type 0.11…1.4 In
Tripping time at In[ms] < 220
2 In[ms] < 80
5 In[ms] < 40
500 A [ms] < 40
Toggle black sealable in ON-OFF position
Electrical life 10000
Mechanical life 20000
Protection degree housing IP4X/IPXXD (excluding terminal area)
terminals IP2X/IPXXB
Self-extinguishing degree V0 thickness 1.6 UL 94 yellow paper
Mechanical shock resistance 26 g half wave, duration 6 ms, 2000 shocks
Resistance to vibrations acc. to IEC 68-2-6 minimum 5 g, duration 30 min., at frequency 0…80 Hz
Tropicalization humid heat [°C/RH] 28 cycles with 55/95…100
acc. to IEC 68-2 constant climatic
conditions [°C/RH] 23/83 - 40/93 - 55/20
variable climatic
conditions [°C/RH] 25/95 - 40/95
Ambient temperature
(with daily average<+35°C) [°C] -25…+55
Storage temperature [°C] -35…+70
Terminal size upper/lower per cable [mm2]16/16
Mounting on DIN rail EN 50022 (35mm) by means of rapid fixing device
Pole dimensions [mm] H: 83 x D: 62 x W: 35,6
Pole weight [g] 200
3/5
3
ABB SACE
DS 951 DS 971
IEC 1009 / EN 61009
AC, A
6 <In < 40
1P+N
230
250
110
6000 10000
10 15
610
5
3
3
253
110
250 A (8/20) acc. to VDE 0432 Part 2
50..60
0.5…1 In
0.11…1.4 In
< 220 < 220
< 80 < 80
< 40 < 40
< 40 < 40
black sealable in ON-OFF position
10000
20000
IP4X/IPXXD (excluding terminal area)
IP2X/IPXXB
V0 thickness 1.6 UL 94 yellow paper
26 g half wave, duration 6 ms, 2000 shocks
minimum 5 g, duration 30 min., at frequency 0…80 Hz
28 cycles with 55/95…100
23/83 - 40/93 - 55/20
25/95 - 40/95
-5…+55
-20…+70
16/16
on DIN rail EN 50022 (35mm) by means of rapid fixing device
H: 83 x D: 62 x W: 35,6
200
3/6
3
ABB SACE
RCBOs-DS 9.. range
DS 941 type AC series
Accessories ................................................... pg. 3/19 Technical details .........................................pg. 10/40 Overall dimensions ........................................ pg. 11/6
B (Im = 3…5 In)
C (Im = 5…10 In)
Tripping characteristics
Application: residential and similar
Connections for UNIFIX available
Rated currents Code
In Characteristic
[A] B C
DS 941 type AC - sensitivity 30mA
6EB 000 7 EB 039 5
10 EB 001 5 EB 040 3
16 EB 002 3 EB 041 1
20 EB 003 1 EB 042 9
25 EB 004 9 EB 043 7
32 EB 005 6 EB 044 5
40 EB 006 4 EB 045 2
DS 941 type AC - sensitivity 100mA
6EB 007 2 * EB 046 0 *
10 EB 008 0 * EB 047 8 *
16 EB 009 8 * EB 048 6 *
20 EB 010 6 * EB 049 4 *
25 EB 011 4 * EB 050 2 *
32 EB 012 2 * EB 051 0 *
40 EB 013 0 * EB 052 8 *
* version on request
Type
AC
TEPM01441
3/7
3
ABB SACE
Breaking capacity
Acc. to IEC 1009 / EN 61009
In [A] poles voltage [V] Icn [kA] Idm [kA]
6…40 1P+N 230 4.5 3
Acc. to IEC 947-2 / EN 60947-2
In [A] poles voltage [V] Icu [kA] Ics [kA]
6…40 1P+N 230 6 4.5
Rated currents Code
In Characteristic
[A] B C
DS 941 type AC - sensitivity 300mA
6EB 014 8 EB 053 6
10 EB 015 5 EB 054 4
16 EB 016 3 EB 055 1
20 EB 017 1 EB 056 9
25 EB 018 9 EB 057 7
32 EB 019 7 EB 058 5
40 EB 020 5 EB 059 3
DS 941 type AC - sensitivity 500mA
6EB 021 3 * EB 060 1 *
10 EB 022 1 * EB 061 9 *
16 EB 023 9 * EB 062 7 *
20 EB 024 7 * EB 063 5 *
25 EB 025 4 * EB 064 3 *
32 EB 026 2 * EB 065 0 *
40 EB 027 0 * EB 066 8 *
DS 941 type AC - sensitivity 1000mA
6EB 028 8 * EB 082 5 *
10 EB 029 6 * EB 083 3 *
16 EB 030 4 * EB 084 1 *
20 EB 031 2 * EB 085 8 *
25 EB 032 0 * EB 086 6 *
32 EB 033 8 * EB 087 4 *
40 EB 034 6 * EB 088 2 *
* version on request
Accessories ................................................... pg. 3/19 Technical details .........................................pg. 10/40 Overall dimensions ........................................ pg. 11/6
RCBOs-DS 9.. range
DS 941 type AC series
IMQ approval
The RCBOs series DS 941 have obtained the IMQ approval
TEPM01441
3/8
3
ABB SACE
Rated currents Code
In Characteristic
[A] B C
DS 941 type A - sensitivity 10mA
6EB 355 5
10 EB 356 3
16 EB 357 1
20
25
32
40
DS 941 type A - sensitivity 30mA
6EB 375 3 EB 410 8
10 EB 376 1 EB 411 6
16 EB 377 9 EB 412 4
20 EB 378 7 EB 413 2
25 EB 379 5 EB 414 0
32 EB 380 3 EB 415 7
40 EB 381 1 EB 416 5
DS 941 type A - sensitivity 100mA
6EB 382 9 * EB 417 3 *
10 EB 383 7 * EB 418 1 *
16 EB 384 5 * EB 419 9 *
20 EB 385 2 * EB 420 7 *
25 EB 386 0 * EB 421 5 *
32 EB 387 8 * EB 422 3 *
40 EB 388 6 * EB 423 1 *
• pending approval
* version on request
RCBOs-DS 9.. range
DS 941 type A series
Accessories ................................................... pg. 3/19 Technical details .........................................pg. 10/40 Overall dimensions ........................................ pg. 11/6
B (Im = 3…5 In)
C (Im = 5…10 In)
Tripping characteristics
Application: residential or similar
Connections for UNIFIX available
Type
A
TEPM01441
3/9
3
ABB SACE
Breaking capacity
Acc. to IEC 1009 / EN 61009
In [A] poles voltage [V] Icn [kA] Idm [kA]
6…40 1P+N 230 4.5 3
Acc. to IEC 947-2 / EN 60947-2
In [A] poles voltage [V] Icu [kA] Ics [kA]
6…40 1P+N 230 6 4.5
Rated currents Code
In Characteristic
[A] B C
DS 941 type A - sensitivity 300mA
6EB 389 4 * EB 424 9 *
10 EB 390 2 * EB 425 6 *
16 EB 391 0 * EB 426 4 *
20 EB 392 8 * EB 427 2 *
25 EB 393 6 * EB 428 0 *
32 EB 394 4 * EB 429 8 *
40 EB 395 1 * EB 430 6 *
DS 941 type A - sensitivity 500mA
6EB 396 9 * EB 431 4 *
10 EB 397 7 * EB 432 2 *
16 EB 398 5 * EB 433 0 *
20 EB 399 3 * EB 434 8 *
25 EB 400 9 * EB 435 5 *
32 EB 401 7 * EB 436 3 *
40 EB 402 5 * EB 437 1 *
DS 941 type A - sensitivity 1000mA
6EB 403 3 * EB 438 9 *
10 EB 404 1 * EB 439 7 *
16 EB 405 8 * EB 440 5 *
20 EB 406 6 * EB 441 3 *
25 EB 407 4 * EB 442 1 *
32 EB 408 2 * EB 443 9 *
40 EB 409 0 * EB 444 7 *
* version on request
Accessories ................................................... pg. 3/19 Technical details .........................................pg. 10/40 Overall dimensions ........................................ pg. 11/6
RCBOs-DS 9.. range
DS 941 type A series
IMQ approval
The RCBOs series DS 941 have obtained the IMQ
approval
TEPM01441
3/10
3
ABB SACE
Rated currents Code
In Characteristic
[A] B C
DS 951 type AC - sensitivity 30mA
6EB 100 5 EB 135 1
10 EB 101 3 EB 136 9
16 EB 102 1 EB 137 7
20 EB 103 9 EB 138 5
25 EB 104 7 EB 139 3
32 EB 105 4 EB 140 1
40 EB 106 2 EB 141 9
DS 951 type AC - sensitivity 100mA
6EB 107 0 * EB 142 7 *
10 EB 108 8 * EB 143 5 *
16 EB 109 6 * EB 144 3 *
20 EB 110 4 * EB 145 0 *
25 EB 111 2 * EB 146 8 *
32 EB 112 0 * EB 147 6 *
40 EB 113 8 * EB 148 4 *
* version on request
RCBOs-DS 9.. range
DS 951 type AC series
Accessories ................................................... pg. 3/19 Technical details .........................................pg. 10/40 Overall dimensions ........................................ pg. 11/6
B (Im = 3…5 In)
C (Im = 5…10 In)
Tripping characteristics
Application: residential, commercial
Connections for UNIFIX available
Type
AC
TEPM01441
3/11
3
ABB SACE
Breaking capacity
Acc. to IEC 1009 / EN 61009
In [A] poles voltage [V] Icn [kA] Idm [kA]
6…40 1P+N 230 6 3
Acc. to IEC 947-2 / EN 60947-2
In [A] poles voltage [V] Icu [kA] Ics [kA]
6…40 1P+N 230 10 6
Rated currents Code
In Characteristic
[A] B C
DS 951 type AC - sensitivity 300mA
6EB 114 6 * EB 149 2
10 EB 115 3 * EB 150 0
16 EB 116 1 * EB 151 8
20 EB 117 9 * EB 152 6
25 EB 118 7 * EB 153 4
32 EB 119 5 * EB 154 2
40 EB 120 3 * EB 155 9
DS 951 type AC - sensitivity 500mA
6EB 121 1 * EB 156 7 *
10 EB 122 9 * EB 157 5 *
16 EB 123 7 * EB 158 3 *
20 EB 124 5 * EB 159 1 *
25 EB 125 2 * EB 160 9 *
32 EB 126 0 * EB 161 7 *
40 EB 127 8 * EB 162 5 *
DS 951 type AC - sensitivity 1000mA
6EB 128 6 * EB 163 3 *
10 EB 129 4 * EB 164 1 *
16 EB 130 2 * EB 165 8 *
20 EB 131 0 * EB 166 6 *
25 EB 132 8 * EB 167 4 *
32 EB 133 6 * EB 168 2 *
40 EB 134 4 * EB 169 0 *
* version on request
Accessories ................................................... pg. 3/19 Technical details .........................................pg. 10/40 Overall dimensions ........................................ pg. 11/6
RCBOs-DS 9.. range
DS 951 type AC series
IMQ approval
The RCBOs series DS 951 have obtained the IMQ
approval
TEPM01441
3/12
3
ABB SACE
RCBOs-DS 9.. range
DS 951 type A series
Accessories ................................................... pg. 3/19 Technical details .........................................pg. 10/40 Overall dimensions ........................................ pg. 11/6
Rated currents Code
In Characteristic
[A] B C
DS 951 type A - sensitivity 30mA
6EB 475 1 EB 515 4
10 EB 476 9 EB 516 2
16 EB 477 7 EB 517 0
20 EB 478 5 EB 518 8
25 EB 479 3 EB 519 6
32 EB 480 1 EB 520 4
40 EB 481 9 EB 521 2
DS 951 type A - sensitivity 100mA
6EB 482 7 * EB 522 0 *
10 EB 483 5 * EB 523 8 *
16 EB 484 3 * EB 524 6 *
20 EB 485 0 * EB 525 3 *
25 EB 486 8 * EB 526 1 *
32 EB 487 6 * EB 527 9 *
40 EB 488 4 * EB 528 7 *
* version on request
B (Im = 3…5 In)
C (Im = 5…10 In)
Tripping characteristics
Application: residential, commercial
Connections for UNIFIX available
Type
A
TEPM01441
3/13
3
ABB SACE
Breaking capacity
Acc. to IEC 1009 / EN 61009
In [A] poles voltage [V] Icn [kA] Idm [kA]
6…40 1P+N 230 6 3
Acc. to IEC 947-2 / EN 60947-2
In [A] poles voltage [V] Icu [kA] Ics [kA]
6…40 1P+N 230 10 6
Rated currents Code
In Characteristic
[A] B C
DS 951 type A - sensitivity 300mA
6EB 489 2 * EB 529 5 *
10 EB 490 0 * EB 530 3 *
16 EB 491 8 * EB 531 1 *
20 EB 492 6 * EB 532 9 *
25 EB 493 4 * EB 533 7 *
32 EB 494 2 * EB 534 5 *
40 EB 495 9 * EB 535 2 *
DS 951 type A - sensitivity 500mA
6EB 496 7 * EB 536 0 *
10 EB 497 5 * EB 537 8 *
16 EB 498 3 * EB 538 6 *
20 EB 499 1 * EB 539 4 *
25 EB 500 6 * EB 540 2 *
32 EB 501 4 * EB 541 0 *
40 EB 502 2 * EB 542 8 *
DS 951 type A - sensitivity 1000mA
6EB 503 0 * EB 543 6 *
10 EB 504 8 * EB 544 4 *
16 EB 505 5 * EB 545 1 *
20 EB 506 3 * EB 546 9 *
25 EB 507 1 * EB 547 7 *
32 EB 508 9 * EB 548 5 *
40 EB 509 7 * EB 549 3 *
* version on request
Accessories ................................................... pg. 3/19 Technical details .........................................pg. 10/40 Overall dimensions ........................................ pg. 11/6
RCBOs-DS 9.. range
DS 951 type A series
IMQ approval
The RCBOs series DS 951 have obtained the IMQ
approval
TEPM01441
3/14
3
ABB SACE
RCBOs-DS 9.. range
DS 971 type AC series
Accessories ................................................... pg. 3/19 Technical details .........................................pg. 10/40 Overall dimensions ........................................ pg. 11/6
Rated currents Code
In Characteristic
[A] B C
DS 971 type AC - sensitivity 30mA
6EB 195 5 * EB 315 9
10 EB 196 3 * EB 316 7
16 EB 197 1 * EB 317 5
20 EB 198 9 * EB 318 3
25 EB 199 7 * EB 319 1
32 EB 200 3 * EB 320 9
40 EB 201 1 * EB 321 7
DS 971 type AC - sensitivity 100mA
6EB 202 9 * EB 322 5 *
10 EB 203 7 * EB 323 3 *
16 EB 204 5 * EB 324 1 *
20 EB 205 2 * EB 325 8 *
25 EB 206 0 * EB 326 6 *
32 EB 207 8 * EB 327 4 *
40 EB 208 6 * EB 328 2 *
* version on request
B (Im = 3…5 In)
C (Im = 5…10 In)
Tripping characteristics
Application: commercial, industrial
Connections for UNIFIX available
Type
AC
TEPM01441
3/15
3
ABB SACE
Breaking capacity
Acc. to IEC 1009 / EN 61009
In [A] poles voltage [V] Icn [kA] Idm [kA]
6…40 1P+N 230 10 3
Acc. to IEC 947-2 / EN 60947-2
In [A] poles voltage [V] Icu [kA] Ics [kA]
6…40 1P+N 230 15 10
Rated currents Code
In Characteristic
[A] B C
DS 971 type AC - sensitivity 300mA
6EB 209 4 * EB 329 0 *
10 EB 210 2 * EB 330 8 *
16 EB 211 0 * EB 331 6 *
20 EB 212 8 * EB 332 4 *
25 EB 213 6 * EB 333 2 *
32 EB 214 4 * EB 334 0 *
40 EB 215 1 * EB 335 7 *
DS 971 type AC - sensitivity 500mA
6EB 216 9 * EB 336 5 *
10 EB 217 7 * EB 337 3 *
16 EB 218 5 * EB 338 1 *
20 EB 219 3 * EB 339 9 *
25 EB 220 1 * EB 340 7 *
32 EB 221 9 * EB 341 5 *
40 EB 222 7 * EB 342 3 *
DS 971 type AC - sensitivity 1000mA
6EB 223 5 * EB 343 1 *
10 EB 224 3 * EB 344 9 *
16 EB 225 0 * EB 345 6 *
20 EB 226 8 * EB 346 4 *
25 EB 227 6 * EB 347 2 *
32 EB 228 4 * EB 348 0 *
40 EB 229 2 * EB 349 8 *
* version on request
Accessories ................................................... pg. 3/19 Technical details .........................................pg. 10/40 Overall dimensions ........................................ pg. 11/6
RCBOs-DS 9.. range
DS 971 type AC series
IMQ approval
The RCBOs series DS 971 have obtained the IMQ
approval
TEPM01441
3/16
3
ABB SACE
RCBOs-DS 9.. range
DS 971 type A series
Accessories ................................................... pg. 3/19 Technical details .........................................pg. 10/40 Overall dimensions ........................................ pg. 11/6
Rated currents Code
In Characteristic
[A] B C
DS 971 type A - sensitivity 30mA
6EB 575 8 * EB 665 7
10 EB 576 6 * EB 666 5
16 EB 577 4 * EB 667 3
20 EB 578 2 * EB 668 1
25 EB 579 0 * EB 669 9
32 EB 580 8 * EB 670 7
40 EB 581 6 * EB 671 5
DS 971 type A - sensitivity 100mA
6EB 582 4 * EB 672 3 *
10 EB 583 2 * EB 673 1 *
16 EB 584 0 * EB 674 9 *
20 EB 585 7 * EB 675 6 *
25 EB 586 5 * EB 676 4 *
32 EB 587 3 * EB 677 2 *
40 EB 588 1 * EB 678 0 *
* version on request
B (Im = 3…5 In)
C (Im = 5…10 In)
Tripping characteristics
Application: commercial, industrial
Connections for UNIFIX available
Type
A
TEPM01441
3/17
3
ABB SACE
Breaking capacity
Acc. to IEC 1009 / EN 61009
In [A] poles voltage [V] Icn [kA] Idm[kA]
6…40 1P+N 230 10 3
Acc. to IEC 947-2 / EN 60947-2
In [A] poles voltage [V] Icu [kA] Ics [kA]
6…40 1P+N 230 15 10
Rated currents Code
In Characteristic
[A] B C
DS 971 type A - sensitivity 300mA
6EB 589 9 * EB 679 8 *
10 EB 590 7 * EB 680 6 *
16 EB 591 5 * EB 681 4 *
20 EB 592 3 * EB 682 2 *
25 EB 593 1 * EB 683 0 *
32 EB 594 9 * EB 684 8 *
40 EB 595 6 * EB 685 5 *
DS 971 type A - sensitivity 500mA
6EB 596 4 * EB 686 3 *
10 EB 597 2 * EB 687 1 *
16 EB 598 0 * EB 688 9 *
20 EB 599 8 * EB 689 7 *
25 EB 600 4 * EB 690 5 *
32 EB 601 2 * EB 691 3 *
40 EB 602 0 * EB 692 1 *
DS 971 type A - sensitivity 1000mA
6EB 603 8 * EB 693 9 *
10 EB 604 6 * EB 694 7 *
16 EB 605 3 * EB 695 4 *
20 EB 606 1 * EB 696 2 *
25 EB 607 9 * EB 697 0 *
32 EB 608 7 * EB 698 8 *
40 EB 609 5 * EB 699 6 *
* version on request
Accessories ................................................... pg. 3/19 Technical details .........................................pg. 10/40 Overall dimensions ........................................ pg. 11/6
RCBOs-DS 9.. range
DS 971 type A series
IMQ approval
The RCBOs series DS 971 have obtained the IMQ
approval
TEPM01441
3/18
3
ABB SACE
Auxiliary contacts
The auxiliary contact indicates
the “open” or “closed” position
of the circuit-breaker. Every
variation of the open/closed
state, whether manual or auto-
matic, permits the activation of
a remote segnalling (e.g. light
segnalling), through its switch-
ing contact. The auxiliary con-
tact has a green indicator, al-
lowing determination of the
open/closed position of the cir -
cuit-breaker (when the circuit-
breaker is in the “open” posi-
tion, the indicator projects fr om
the contact). The indicator also
allows execution of the TEST
trial (temporary switching of the
auxiliary circuit) by pressure on
the indicator itself. A maximum
of three contacts (signal and/or
auxiliary) can be applied on
each circuit-breaker of the DS
9….. series.
Signal contacts
The signal contact (or tripped
relay) signals an automatic trip-
ping caused by an overload or
short-circuit. When the circuit-
RCBOs-DS 9.. range
Auxiliary elements
S9-V
UNDERVOLTAGE
RELEASE
ONE-POLE +
NEUTRAL
DS941
DS951
DS971
RCBO
S9-T
SHUNT TRIP
S9-X
AUXILIARY
CONTACT
OR
S9-S
SIGNAL
CONTACT
S9-X
AUXILIARY
CONTACT
S9-X
AUXILIARY
CONTACT
signal contact is also fitted with
a test button (TEST) which ef-
fects temporary switching of
the signalling circuit whatever
the ON/OFF state of the
magnetothermic circuit-
breaker.
Shunt trips are used for re-
mote tripping of miniature
circuit-breakers. The shunt
trips are equipped both with
automatic de-energization
contacts (for the protection of
the coil) in case of held com-
mand, and an ON/OFF contact
for signalling the state of the coil
(energized or de-energized). A
DS 9... circuit-breaker having a
shunt trip and 3 auxiliary con-
tacts, can display 4 signals in
total. A projecting r ed indicator
signals the opening of the cir-
cuit-breaker (if caused by the
shunt trip itself).
The undervoltage releases
are used to pr otect the load in
the event of a voltage drop
(threshold between 70% and
35% of its rated value) and/or
to effect a positive safety
emergency stop. There are also
two versions fitted with a trip-
ping delay of 100ms (types S
9..-V24AC and S 9.. V24DC),
which prevent unexpected trips
in the pre-sence of micr o inter-
ruptions of the voltage in the
network lower than 100ms. A
projecting red indicator indi-
cates the opening of the circuit-
breaker (if caused by the
undervoltage release itself). The
DS 9.. range is also preset for
the use of the ABB rapid wiring
system, Unifix (L and SL ver-
sions), which simplifies the job
of installers and panel builders
by means of its L1- N, L2-N,
L3-N rigid connections.
breaker is operated manually it
does not indicate any change
of state in the circuit-breaker.
The signal contact has a yel-
low indicator projecting from
the case if the circuit-breaker
is tripped (this indicator also al-
lows manual resetting of the
signalling circuit - RESET). The
Examples of combination of circuit-breakers series DS 941, DS 951, and DS 971 with auxiliary elements (highest configuration)
TEPM01442
3/19
3
ABB SACE
RCBOs-DS 9.. range
Auxiliary elements
Overall dimensions ...................................... pg. 11/10
Shunt trips
They are used for the remote opening of the MCBs.
The shunt trips are equipped with an auto de-energizing contact and an ON-OFF contact which
indicate the “Open” or “Closed” position of the device they are connected to.
Code Type Description
(for DS 941, DS 951 and DS 971 series)
EE 619 1 S 9..-T 24. 12-24V a.c./d.c. shunt trip
EE 620 9 S 9..-T 130 48-130V a.c./48-60V d.c. shunt trip
EE 621 7 S 9..-T 415 220-415V a.c./110-250V d.c. shunt trip
Technical characteristics
Type S 9..-T 24. S 9..-T1 30. S 9..-T 415
Voltage [V] a.c. 12÷24 48÷130 220÷415
[V] d.c. 12÷24 48÷60 110÷250
Frequency [V] 50…60
Consumption [VA] 20VA (12V a.c.) 22VA (48V a.c.) 40VA (220V a.c.)
on release 90VA (24V a.c.) 200VA (130V a.c.) 130VA (415V a.c.)
20VA (12V d.c.) 22VA (48V d.c.) 10VA (110V d.c.)
90VA (24V d.c.) 20VA (250V d.c.)
Terminals [mm2]2 x 1.5
S 9..-T 24., S 9..-T 130, S 9..-T 415
TEPM01421
OEPM0292
OEPM0291
1
2
C1
C2
Installation only on left
3/20
3
ABB SACE
RCBOs-DS 9.. range
Auxiliary elements
Overall dimensions ...................................... pg. 11/10
Auxiliary/signal contacts
The auxiliary contact indicates the position of the circuit-breaker contact. When the position of the
contact changes, whether manually or automatically, it indicates its status.
The signal contact indicates the position of the circuit-breaker contact after automatic trip of the
circuit-breaker caused by overloading or short-cir cuiting. For manual operation, it does not indicate
the change in contact position. The contacts in the S 941 N, S 951 N and S 971 N series breakers are
equipped with a test button on the front of the accessory which simulates the functions without acting
directly on the circuit-breaker.
Code Type Description
(for DS 941, DS 951 and DS 971 series)
EE 610 0 S 9..-X auxiliary contact 1NO + 1NC (1/2 module)
EE 611 8 S 9..-S signal contact (1/2 module)
S 9..-X S 9..-S
N
OFF
11 1
2
12 14
95 1
2
96 98
OEPM0293
TEPM01422
3/21
3
ABB SACE
RCBOs-DS 9.. range
Auxiliary elements
Overall dimensions ...................................... pg. 11/10
Undervoltage releases
These are used to pr otect the load in the event of a voltage drop (between 70% and 35% of its rated
value) and/or to effect a positive safety emergency stop. If used for an emergency stop, they cause
unwanted tripping also for temporary micr ointerruptions of the voltage for a few dozen milliseconds.
Undervoltage releases equipped with a tripping time delay of 100ms (S 9-V24CA and S 9-V24CC
types) are different and eliminate unwanted tripping when there is an interruption in the network
voltage which is less than 100ms. ABB SACE has also developed DDA AE blocks which perform the
residual current function and the positive safety emergency stop without use of an auxiliary energy
source (battery) and auxiliary circuits. The DDA AE block performs the functions of a shunt trip but
without the disadvantages of an unwanted tripping.
Code Type Description
(for DS 941, DS 951, DS 971 series)
EE 612 6 S 9..-V24AC 24V a.c. undervoltage release with delay
EE 613 4 S 9..-V24DC 24V d.c. undervoltage release with delay
EE 614 2 S 9..-V48AC 48V a.c. undervoltage release
EE 615 9 S 9..-V48DC 48V d.c. undervoltage release
EE 616 7 S 9..-V230AC 230V a.c. undervoltage release
1
2
D1
D2
TEPM01421
OEPM0292
3/22 ABB SACE
The DS... range of RCBOs
combines in a single device the
residual current protection and
the thermal+magnetic protec-
tion which is typical of MCBs;
they trip in both the case of
earth leakage and overload or
short-circuit.
These RCBOs series are de-
rived from the corresponding
series of MCBs, from which
they take the characteristics
and performances with regard
to the thermomagnetic part.
To be precise, in the DS 640
the overcurrent protection is
provided by the same thermo-
magnetic release of the S 240.
In the same way the DS 650
and the DS 750 use the same
thermomagnetic release of the
S 250, and the DS 670 the
same thermomagnetic release
of the S 270.
TEPM01444
TEPM01443
All DS 640, DS 650 and DS 670
mount a residual current release
type AC, while the DS 750 have
an A type release.
Also available is the double sen-
sitivity AC type DS 850 series,
known as VARIMAT.
F 500 is the type A residual cur-
rent circuit-breaker with
overcurrent protection derived
from the S 500 heavy duty cir-
cuit-breaker.
3/23
3
ABB SACE
RCBOs -
DS ... - F 500 range
Contents
Technical characteristics .......................................................................................................3/24
Order information
Elettrostop DS 640 series .....................................................................................................3/26
Elettrostop DS 650 series .....................................................................................................3/27
Elettrostop DS 670 series .....................................................................................................3/29
Varistop DS 750 series..........................................................................................................3/31
Double sensitivity Varimat DS 850 series .............................................................................3/32
F 500 range...........................................................................................................................3/33
N.B. Being the auxiliary elements and accessories the same as those in the circuit-breakers
series S2.. please refer to the relevant chapter.
3/24
3
ABB SACE
RCBOs DS ... - F 500 range
Technical characteristics
DS 640 DS 650
Standards IEC 1009 / EN 61009
Type AC
Rated current In [A] 6 <In < 32 0,5 <In < 63
Poles 1P+N, 2P 1P+N, 2P, 4P
Rated voltage Ue one-pole AC [V] 230
multi-pole AC [V] 230/400
Max. operating voltage Ub max. [V] 440
Min. operating voltage Ub min. [V] 110
Rated breaking capacity ultimate Icn [A] 4500 6000
acc. to IEC 1009
Rated breaking capacity ultimate Icu [kA] 6 20 (15 1P+N)
acc. to IEC 947-2
2 poles - 230 V service Ics [kA] 6 15 (10 1P+N)
Rated breaking capacity ultimate Icu [kA] 10
acc. to IEC 947 -2 4 poles - 400V service Ics [kA] 7.5
Voltage withstanding capacity impulse (1.2/50) Uimp [kV] 5
at rated freq. (50-60Hz)
x 1 min. [kV] 3
Thermomagnetic release B: 3 In < Im < 5 In
characteristic C: 5 In < Im < 10 In
Limitation class 3
Max. operating voltage of circuit test [V] 440
Min. operating voltage of circuit test [V] 195
Surge current resistance [A] 250 A (8/20) acc. to VDE 0432 Part 2
Rated frequency [Hz] 50…60
Rated sensitivity In[A] 0.03 - 0.3 0.03 - 0.1 - 0.3
Tripping threshold AC type 0.5…1 In
A type
Tripping time at In[ms] < 220
2 In[ms] < 80
5 In[ms] < 40
500 A [ms] < 40
Toggle 1P+N black sealable in ON-OFF position
2P, 4P black (MCB part) sealable in ON-OFF position + blue (RDC part) operating just from OFF po
Electrical life 10000
Mechanical life 20000
Protection degree housing IP4X/IPXXD (excluding terminal area)
terminals IP2X/IPXXB
Self-extinguishing degree V0 thickness 1.6 UL 94 yellow paper
Mechanical shock resistance 26 g half wave, duration 6 ms, 2000 shocks
Resistance to vibrations acc. to IEC 68-2-6 minimum 5 g, duration 30 min., at frequency 0…80 Hz
Tropicalization humid heat [°C/RH] 28 cycles with 55/95…100
acc. to IEC 68-2 constant climatic
conditions [°C/RH] 23/83 - 40/93 - 55/20
variable climatic
conditions [°C/RH] 25/95 - 40/95
Ambient temperature (with daily average<+35°C) [°C] -5…+55 -5…+55
Storage temperature [°C] -20…+70
Terminal size upper/lower per cable [mm2]10/16, 25/25 10/16, 25/25
Mounting on DIN rail EN 50022 (35mm) by means of rapid fixing device
Dimensions 1P+N [mm] 35 35
H: 94 x D: 68 x W: 2P [mm] 70 70
4P (In < 32A) [mm] 105
4P (In > 40A) [mm] 140
Weight 1P+N [g] 280 280
2P [g] 460/550 460/550
4P [g] 710/770
3/25
3
ABB SACE
DS 670 DS 750
IEC 1009 / EN 61009
A
0.5 <In < 63 6 <In < 32
1P+N, 2P, 4P 1P+N
230
230/400
440
110
10000 6000
25 (20 1P+N) 20 (15 1P+N)
18,7 (15 1P+N) 15 (10 1P+N)
15 10
11.2 7.5
5
3
••
3
440
195
250 A (8/20 wave) acc. to VDE 0432 Part 2
50…60
0.03 - 0.3 0.03 - 0.3
0.5…1 In0.51 In
0.11…1.4 In
< 220
< 80
< 40
< 40
black sealable in ON-OFF position
osition black (MCB part) sealable in ON-OFF position + blue (RDC part) operating just from OFF position
10000
20000
IP4X/IPXXD (excluding terminal area)
IP2X/IPXXB
V0 thickness 1.6 UL 94 yellow paper
26 g half wave, duration 6 ms, 2000 shocks
minimum 5 g, duration 30 min., at frequency 0…80 Hz
28 cycles with 55/95…100
23/83 - 40/93 - 55/20
25/95 - 40/95
-5…+55 -25…+55
-20…+70
10/16, 25/25 10/16
on DIN rail EN 50022 (35mm) by means of rapid fixing device
35 35
70
105
140
280 280
460/550
710/770
3/26
3
ABB SACE
Breaking capacity
Acc. to IEC 1009 / EN 61009
In [A] poles voltage [V] Icn [kA] Idm [kA]
6...32 1P+N 230 4,5 4.5
Acc. to IEC 947-2 / EN 60947-2
In [A] poles voltage [V] Icu [kA] Ics [kA]
6...32 1P+N 230 6 4.5
DS 640
In = 6…32A
In = 0.03A
AC
Type
Application: residential or similar
Connections for UNIFIX available
RCBOs DS ... - F 500 range
Elettrostop DS 640 series
Characteristic C
Rated currents Code
In Sensitivity
[A] 0.03A 0.3A
2P - DS 642 P type (4 modules)
6EY 021 8
8EY 037 4
10 EY 022 6
13 EY 038 2
16 EY 023 4
20 EY 024 2
25 EY 025 9
32 EY 026 7
1P+N - DS 642 type (2 modules)
6EY 011 9 EY 031 7
8EY 017 6 EY 037 4
10 EY 012 7 EY 032 5
13 EY 018 4 EY 038 2
16 EY 013 5 EY 033 3
20 EY 014 3 EY 034 1
25 EY 015 0 EY 035 8
32 EY 016 8 EY 036 6
TEPM0088
TEPM0090
C (Im = 5…10 In) at 30°C
Tripping characteristics
Technical details .......................................... pg. 10/40 Overall dimensions ....................................... pg. 11/6
IMQ approval
3/27
3
ABB SACE
Breaking capacity
Acc. to IEC 1009 / EN 61009
In [A] poles voltage [V] Icn [kA] Idm [kA]
0,5...63 all 230/400 6 6
Acc. to IEC 947-2 / EN 60947-2
In [A] poles voltage [V] Icu [kA] Ics [kA]
6...32 1P+N 230 15 10
0.5...63 2P 230 20 15
0.5...63 2P 400 10 6
0.5...63 4P 400 10 6
IMQ approval
DS 650
In = 6…63A
In = 0.01-0.03-0.1-0.3A
AC
Type
Application: residential or commercial
Connections for UNIFIX available
RCBOs DS ... - F 500 range
Elettrostop DS 650 series
C (Im = 5…10 In) at 30°C, B (Im = 3…5 In) at 30°C
K (Im = 8…12 In) at 20°C
Tripping characteristics
Characteristic C
Rated currents Code
In Sensitivity
[A] 0.01A 0.03A 0.1A 0.3A
1P+N - DS 651 type
6EY 560 5 EY 570 4
8EY 566 2
10 16250069 EY 561 3 11170563 EY 571 2
13 EY 567 0
16 16250085 EY 562 1 11170564 EY 572 0
20 EY 563 9 11170565 EY 573 8
25 EY 564 7 EY 574 6
32 EY 565 4 EY 575 3
Characteristic K
Rated currents Code
In Sensitivity
[A] 0.03A 0.1A 0.3A
1P+N - DS 651 type
611170771 11170787
10 11170773 11170789
16 11170774 11170790
20 11170775 11170791
25 11170776
32 11170777
Technical details .......................................... pg. 10/40 Overall dimensions ....................................... pg. 11/6
TEPM0090
3/28
3
ABB SACE
RCBOs DS ... - F 500 range
Elettrostop DS 650 series
Technical details .......................................... pg. 10/40 Overall dimensions ....................................... pg. 11/6
Characteristic B
Rated currents Code
In Sensitivity
[A] 0.03A 0.3A
1P+N - DS 651 type (2 modules)
6EY 580 3 EY 800 5
8EY 581 1 EY 801 3
10 EY 582 9 EY 802 1
13 EY 583 7 EY 803 9
16 EY 584 5 EY 804 7
20 EY 585 2 EY 805 4
25 EY 586 0 EY 806 2
32 EY 587 8 EY 807 0
Characteristic C
Rated currents Code
In Sensitivity
[A] 0.01A 0.03A 0.3A
2P - DS 652 type (4 modules)
0.5 EY 700 7
1EY 701 5
1.6 EY 702 3
2EY 703 1
3EY 704 9
4EY 705 6
6EY 040 8 EY 050 7 EY 060 6
8EY 041 6 EY 051 5 EY 061 4
10 EY 042 4 EY 052 3 EY 062 2
13 EY 589 4 EY 590 2
16 EY 043 2 EY 053 1 EY 063 0
20 EY 044 0 EY 054 9 EY 064 5
25 EY 055 6 EY 065 5
32 EY 056 4 EY 066 3
40 EY 057 2 EY 067 1
50 EY 058 0 EY 068 9
63 EY 059 8 EY 069 7
Characteristic C
Rated currents Code
In Sensitivity
[A] 0.03A 0.3A
4P - DS 654 type (8 modules)
0.5 EY 712 2
1EY 713 0
1.6 EY 714 8
2EY 715 5
3EY 716 3
4EY 717 1
6EY 110 9 EY 120 8
8EY 111 7 EY 121 6
10 EY 112 5 EY 122 4
13 EY 595 1 EY 596 9
16 EY 113 3 EY 123 2
20 EY 114 1 EY 124 0
25 EY 115 8 EY 125 7
32 EY 191 9 EY 126 5
40 EY 192 7 EY 127 3
50 EY 118 2 EY 128 1
63 EY 119 0 EY 129 9
TEPM0091
TEPM0092
TEPM0093
3/29
3
ABB SACE
Breaking capacity
Acc. to IEC 1009 / EN 61009
In [A] poles voltage [V] Icn [kA] Idm [kA]
0.5...63 all 230/400 10 10
Acc. to IEC 947-2 / EN 60947-2
In [A] poles voltage [V] Icu [kA] Ics [kA]
6...32 1P+N 230 20 10
0.5...63 2P 230 25 12.5
0.5...63 2P 400 15 10
0.5...63 4P 400 15 10
AC
Type
Application: commercial, industrial
Connections for UNIFIX available
RCBOs DS ... - F 500 range
Elettrostop DS 670 series
C (Im = 5…10 In) at 30°C
Technical details .......................................... pg. 10/40 Overall dimensions ....................................... pg. 11/6
Characteristic C
Rated currents Code
In Sensitivity
[A] 0.03A
1P+N - DS 671 type (2 modules)
611812281
10 11812282
16 11812283
20 11812284
25 11812285
32 11812286
Characteristic C
Rated currents Code
In Sensitivity
[A] 0.03A
2P - DS 672 type (4 modules)
0.5 EY 730 4
1EY 731 2
1.6 EY 732 0
2EY 733 8
3EY 734 6
4EY 735 3
6EY 200 8
8EY 201 6
10 EY 202 4
13 EY 774 2
16 EY 203 2
20 EY 204 0
25 EY 205 7
32 EY 206 5
40 EY 207 3
50 EY 208 1
63 EY 209 9
TEPM0094
IMQ approval
DS 670
In = 0.5…63A
In = 0.03-0.3A
TEPM0093
Tripping characteristics
3/30
3
ABB SACE
Characteristic C
Rated currents Code
In Sensitivity
[A] 0.03A 0.3A
4P - DS 674 type
0.5 EY 742 9
1EY 743 7
1.6 EY 744 5
2EY 745 2
3EY 746 0
4EY 747 8
6EY 260 2 EY 270 1
8EY 261 0 EY 271 9
10 EY 262 8 EY 272 7
13 EY 776 7 EY 778 3
16 EY 263 6 EY 273 5
20 EY 264 4 EY 274 3
25 EY 265 1 EY 275 0
32 EY 266 9 EY 276 8
40 EY 267 7 EY 277 6
50 EY 268 5 EY 278 4
63 EY 269 3 EY 279 2
RCBOs DS ... - F 500 range
Elettrostop DS 670 series
Technical details .......................................... pg. 10/40 Overall dimensions ....................................... pg. 11/6
TEPM0121
3/31
3
ABB SACE
Breaking capacity
Acc. to IEC 1009 / EN 61009
In [A] poles voltage [V] Icn [kA] Idm [kA]
6...32 1P+N 230 6 6
Acc. to IEC 947-2 / EN 60947-2
In [A] poles voltage [V] Icu [kA] Ics [kA]
6...32 1P+N 230 10 6
IMQ approval
DS 750
In = 6…32A
In = 0.01-0.03-0.3A
A
Type
Application: residential or commercial
RCBOs DS ... - F 500 range
Varistop DS 750 series
C (Im = 5…10 In) at 30°C, B (Im = 3…5 In) at 30°C
K (Im = 8…12 In) at 20°C
Tripping characteristics
Technical details .......................................... pg. 10/40 Overall dimensions ....................................... pg. 11/6
Characteristic B
Rated currents Code
In Sensitivity
[A] 0.03A 0.3A
1P+N - DS 751 type (2 modules)
6KV 050 6 KV 056 3
10 KV 051 4 KV 057 1
13 KV 089 4 KV 049 8
16 KV 052 2 KV 058 9
20 KV 053 0 KV 059 7
25 KV 054 8 KV 060 5
32 KV 055 5 KV 061 3
Characteristic C
Rated currents Code
In Sensitivity
[A] 0.01A 0.03A 0.3A
1P+N - DS 751 type (2 modules)
6KV 063 9 KV 069 6
10 11170387 KV 064 7 KV 070 4
13 KV 087 8 KV 088 6
16 11170389 KV 065 4 KV 071 2
20 KV 066 2 KV 072 0
25 KV 067 0 KV 073 8
32 KV 068 8 KV 074 6
Characteristic K
Rated currents Code
In Sensitivity
[A] 0.03A 0.3A
1P+N - DS 751 type (4 modules)
6KV 075 3 KV 081 1
10 KV 076 1 KV 082 9
16 KV 077 9 KV 083 7
20 KV 078 7 KV 084 5
25 KV 079 5 KV 085 2
32 KV 080 3 KV 086 0
TEPM0090
TEPM0093
3/32
3
ABB SACE
Breaking capacity
Acc. to IEC 1009 / EN 61009
In [A] poles voltage [V] Icn [kA] Idm [kA]
10...20 all 230/400 6 6
Acc. to IEC 947-2 / EN 60947-2
In [A] poles voltage [V] Icu [kA] Ics [kA]
10...20 2P 230 20 10
10...20 2P 400 10 6
AC
Type
Application: residential or commercial
Connections for UNIFIX available
RCBOs DS ... - F 500 range
Double sensitivity Varimat DS 850 ser ies
C (Im = 5…10 In) at 30°C
Tripping characteristics
Technical details .......................................... pg. 10/40 Overall dimensions ....................................... pg. 11/6
TEPM0097
Characteristic C
Rated currents Code
In Sensitivity
[A] 0.03A/0.2A
2P - DS 852 type
10 EY 188 5
16 EY 189 3
20 EY 190 1
PE
PE
3/33
3
ABB SACE
Breaking capacity
Acc. to IEC 1009 / EN 61009
In [A] poles voltage [V] Icn [kA]
6...63 2P, 4P 230/400 25
Acc. to IEC 947-2 / EN 60947-2
In [A] poles voltage [V] Icu [kA]
6...63 2P, 4P 230/400 50
A
Type
Application: industrial
RCBOs DS ... - F 500 range
F 500 range
C (Im = 5…10 In) at 30°C, D (Im = 10…20 In) at 30°C
Tripping characteristics
Technical details .......................................... pg. 10/40 Overall dimensions ....................................... pg. 11/7
Characteristic C
Rated currents Code
In Sensitivity
[A] 0.01A 0.03A 0.3A
2P - F 502 type
10 on request EI 371 5 EI 381 4
16 on request EI 372 3 EI 382 2
20 on request EI 373 1 EI 383 0
25 on request EI 374 9 EI 384 8
40 - EI 376 4 EI 386 3
63 - - -
4P - F 504 type
10 on request EI 391 3 EI 401 4
16 on request EI 392 1 EI 402 8
20 on request EI 393 9 EI 403 6
25 on request EI 394 7 EI 404 4
40 - EI 396 2 EI 406 9
63 - EI 398 8 EI 408 5
Characteristic D
2P, 4P - F 502, F 504 types
Available on request with In 25…63A and In 0.03 - 0.3A
Characteristic K
2P, 4P - F 502, F 504 types
Available on request with In 0.28…45A (adjustable thermal) and In 0.01 - 0.03 - 0.3A
Technical characteristic
Rated current [A] In=10...63
Rated voltage [V] Ue=230/400
Min. operating voltage [V] Umin=110
Breaking capacity to earth [kA] Idm=25
Electric operations [n°]10,000
Mechanic operations [n°]20,000
Poles 2P 4P
Weigth [g] 800, 1600
Self-extinguishing degree V0 thickness 1.6mm
Cage terminals [mm2]up to 25
Tropicalization acc. to DIN 50016 95% R.H. at 55°C
Rated impulse withstand [A] 250 peak (wave 8/20µs)
voltage acc.to VDE 0432 Part 2
Mounting position Any
TEPM0095
TEPM0096
3/34 ABB SACE
RCCBs are sensitive only to
fault currents to earth. Over-
loads or short circuits are not
detectable. These breakers
have to be connected in series
with a MCB or fuse that pro-
tects them against thermal and
dynamic stresses of occasional
overcurrents, when these reach
values that may damage the
device.
RCCBs can be used in instal-
lations already equipped with
an MCB in order to limit the let-
through energy and they can
also operate as main load break
switches upstream of shunted
MCBs, preferably of the cur-
rent-limiting type (e.g. in small
consumer units).
The ABB SACE range of
RCCBs gives protection
against indirect contact in any
plant engineering situation.
Apart from the traditional AC
type known as ELETTROSTOP
(for the detection of alternate
leakege current) and the A type
known as VARISTOP (for the
detection of alternate/
pulsanting leakege current with
DC components), the range
also includes the selective type
that provides RCDs selectivity.
RCCBs for special applications
are also available, like the F 3.
suitable for high frequencies
which give protection up to
400 Hz, and the F 800 capable
of detecting DC type residual
currents.
Since the RCCBs can be
tripped by impulsive distur-
bances in the power supply , for
example atmospheric dis-
charges or rough operation of
on the network, they can be the
cause of out of services or mal-
functions with economic con-
sequences that sometimes
may be very serious. ABB
SACE has a solution for this
problem with the F 3-AR circuit-
breakers series.
The F 3-AR circuit-breakers are
single block RCCBs F 3 type
factory fitted with an electronic
automatic reclosing device.
The electronic device conti-
nually monitors the network
and closes automatically the
RCCB after detecting its ope-
ning state. By means of a se-
lector switch placed on the
front of the F 3-AR it is possible
to select one or three automatic
reclosing or to disable the auto-
reclosing device.
In case of residual current trip,
the F 3-AR effects the first
automatic reclosing after about
three seconds.
If the residual current device
performs a second trip and if
just one trip has been selected,
F 3-AR will keep the open sta-
te; if three reclosings have been
selected, F 3-AR performs a
second and then a third
reclosing. If after three
reclosings the RCCB trips
again, F 3-AR will remain
definitively open.
The disabling of the auto-
reclosing device doesn’t modify
the residual current device
performances, that continue to
assure the protection against
indirect contacts without
realising the automatic
reclosing.
The automatic reclosing device
is self-supplied (it’s not
necessary to provide an
auxiliary supply) and its
dimensions correspond to four
modules.
F 3-AR overall dimensions
correspond to four modules in
addition to the dimensions of
the F 3 assembled.
The range of F 3-AR is
composed by eight types of
circuit-breakers that are
fabricated using the F 360, F
370 and F 390 ranges of
RCCBs in 25-40-63A rated
currents with 0.03-0.3-0.5A
sensitivity.
On the front of the F 3-AR there
are 3 signalling leds that enable
the visualization of the
functioning state. A green led
shows the presence of supply,
while the other green led and
the red led point respectively
out the regular functioning
(residual current device
operating – circuit supplied) or
the block state (it means that
after the expected reclosing,
the assembled residual curr ent
device has tripped).
A change-over contact is also
available, that can be used for
remote signalling of the “block
state”.
The F 3-AR series is ideal for
use in domestic systems where
a continuous power supply is
needed for priority lines (refri-
gerator, computer), and in not
monitorized industrial plants
such as cooling, piping and
pumping, air conditioning,
telephone, terrain sensing, data
transmission, etc.
3/35
3
ABB SACE
Contents
Technical characteristics .......................................................................................................3/36
Order information
Elettrostop F 360 series ........................................................................................................3/38
Elettrostop F 660 series ........................................................................................................3/39
Varistop F 370 series ............................................................................................................3/40
Varistop F 670 series ............................................................................................................3/41
Selective Varistop F 390 series.............................................................................................3/42
F 360 AR, F 370 AR, F 390 AR with automatic reclosing device series ...............................3/43
F 370 for high frequencies (400 Hz) series ...........................................................................3/44
F 800 range for leakage currents with continuous components............................................3/45
Auxiliary elements and accessories
Auxiliary elements and accessories for F3.. and F6.. ranges ...............................................3/46
RCCBs
F 3.. - F 6.. - F 800 ranges
3/36
3
ABB SACE
RCCBs F 3.. - F 6.. - F 800 ranges
Technical characteristics
F 360 F 660
Standards IEC 1008 / EN 61008
Type AC AC
Rated current In [A] 16 < In < 80 80 < In < 125
Poles 2P, 4P
Rated voltage Ue [V] 230/400
Max. operating voltage Ub max. [V] 440
Min. operating voltage Ub min. [V] 110 110
(special versions for lower voltage)
Rated residual 2P [kA] 0.5
breaking capacity Im4P [kA] 1.5 2
Rated conditional SCPD - fuse gL 63 A 6
short-circuit current Inc SCPD - S 250 - S 290 5
SCPD - S 270 6
SCPD - S 280 6
SCPD - fuse gL 125 A 6 (In=80A) 10
Voltage withstanding capacity impulse (1.2/50) Uimp [kV] 6
at rated freq. (50-60Hz)
x 1 min. [kV] 2.5
Max. operating voltage of circuit test [V] 254
Min. operating voltage of circuit test [V] 110
Surge current resistance [A] 250 A (8/20 wave) acc. to VDE 0432 Part 2
Rated frequency [Hz] 50…60
Rated sensitivity In[A] 0.01 - 0.03 - 0.3 - 0.5 0.03 - 0.3
Tripping threshold AC type 0.5…1 In0.51 In
A type
Tripping time at In[ms] < 220
2 In[ms] < 80
5 In[ms] < 40
500 A [ms] < 40
Toggle In < 100 A blue sealable in ON-OFF position
In =125 A blue rotative
Electrical life 10000 (4000 for In=125 A)
Mechanical life 20000 (10000 for In=125 A)
Protection degree housing IP4X/IPXXD (excluding terminal area)
terminals IP2X/IPXXB
Self-extinguishing degree V0 thickness 1.6 UL 94 yellow paper
Mechanical shock resistance 26 g half wave, duration 6 ms, 2000 shocks
Resistance to vibrations acc. to IEC 68-2-6 minimum 5 g, duration 30 min., at frequency 0…80 Hz
Tropicalization humid heat [°C/RH] 28 cycles with 55/95…100
acc. to IEC 68-2 constant climatic
conditions [°C/RH] 23/83 - 40/93 - 55/20
variable climatic
conditions [°C/RH] 25/95 - 40/95
Ambient temperature (with daily average<+35°C) [°C] -5…+55 -5…+55
Storage temperature [°C] -20…+70
Terminal size In < 63 A [mm2]25/25
upper/lower per cable 63 A <In < 125 A [mm2]50/50
Mounting on DIN rail EN 50022 (35mm) by means of rapid fixing device
Dimensions
H: 94 x D: 68 x W: 2P In < 80 A [mm] 35
4P In < 100 A [mm] 70
H: 107 x D: 85 x W: 4P In =125 A [mm] 87.5
Weight 2P [g] 345/355
4P In < 100 A [g] 460
4P In =125 A [g] 1000
3/37
3
ABB SACE
F 370 F 670 F 390
AAA (selective)
16 < In < 80 80 < In < 125 40 < In < 63
2P, 4P
230/400
440
110 110 195
1.5 1.5
1.5 2 1.5
6—6
5—5
6—6
6—6
6 (In=80A) 10
2.5
254
110
250 A (8/20 wave) acc. to VDE 0432 Part 2 3000 A (8/20 wave) …
50…60
0.01 - 0.03 - 0.3 - 0.5 0.03 - 0.3 0.3 - 0.5
0.5…1 In0.51 In0.51 In
0.11…1.4 In0.11…1.4 In0.11…1.4 In
< 220 130…500
< 80 60…200
< 40 50…150
< 40 40…150
—blue sealable in ON-OFF position
10000 (4000 for In=125 A)
20000 (10000 for In=125 A)
IP4X/IPXXD (excluding terminal area)
IP2X/IPXXB
V0 thickness 1.6 UL 94 yellow paper
26 g half wave, duration 6 ms, 2000 shocks
minimum 5 g, duration 30 min., at frequency 0…80 Hz
28 cycles with 55/95…100
23/83 - 40/93 - 55/20
25/95 - 40/95
-25…+55 -25…+55 -25…+55
-20…+70
25/25
50/50
on DIN rail EN 50022 (35mm) by means of rapid fixing device
35
70
87.5
345/355
460
1000
3/38
3
ABB SACE
Code
In Sensitivity
[A] 0.01A 0.03A 0.3A 0.5A
2P - F 362 type
16 EY 600 9
25 EY 601 7 EY 605 8
40 EY 602 5 EY 606 6
63 EY 603 3 EY 607 4
80 EY 604 1 EY 608 2
4P - F 364 type
16
25 EY 622 3 EY 625 6 EY 628 0
40 EY 623 1 EY 626 4 EY 629 8
63 EY 624 9 EY 627 2 EY 630 6
Accessories ................................................... pg. 3/46 Technical details .........................................pg. 10/40 Overall dimensions ........................................ pg. 11/7
IMQ approval
F 360 2P
In = 25…63A
In = 0.03-0.3A
AC
Type
Application: residential, commercial, industrial
Connections for UNIFIX available - for In 63A
RCCBs F 3.. - F 6.. - F 800 ranges
Elettrostop F 360 series
TEPM0109
TEPM0110
1
2 4
3
1
2
3
4
5
68
7
N
N
3/39
3
ABB SACE
Code
In Sensitivity
[A] 0.01A 0.03A 0.3A
2P - F 662 type
80 EB 876 0 EB 878 6
100 EB 877 8 EB 879 4
4P - F 664 type
80 EB 880 2 EB 883 6
100 EB 881 0 EB 884 4
125* EB 947 9 EB 966 9
* rotary lever
RCCBs F 3.. - F 6.. - F 800 ranges
Elettrostop F 660 series
TEPM0111
AC
Type
Application: commercial, industrial
Connections for UNIFIX available - for In 63A
Accessories ................................................... pg. 3/46 Technical details .........................................pg. 10/40 Overall dimensions ........................................ pg. 11/7
1
24
3
TEPM0110
1
2
3
4
5
68
7
N
N
3/40
3
ABB SACE
IMQ approval
F370 2P
In = 25…63A
In = 0.03-0.3A
A
Type
Application: residential, commercial, industrial
Connections for UNIFIX available - for In 63A
RCCBs F 3.. - F 6.. - F 800 ranges
Varistop F 370 series
Code
In Sensitivity
[A] 0.01A 0.03A 0.3A 0.5A
2P - F 372 type
16 EY 609 0
25 EY 610 8 EY 614 0
40 EY 611 6 EY 615 7
63 EY 612 4 EY 616 5
80 EY 613 2 EY 617 3
4P - F 374 type
16
25 EY 631 4 EY 634 8 EY 637 1
40 EY 632 2 EY 635 5 EY 638 9
63 EY 633 0 EY 636 3 EY 639 7
80
TEPM0113
TEPM0114
Accessories ................................................... pg. 3/46 Technical details .........................................pg. 10/40 Overall dimensions ........................................ pg. 11/7
1
24
3
1
2
3
4
5
68
7
N
N
3/41
3
ABB SACE
Code
In Sensitivity
[A] 0.01A 0.03A 0.3A 0.5A
2P - F 672 type
80 EB 892 7
100 EB 893 5
4P - F 674 type
80 EB 886 9 EB 889 3
100 EB 887 7 EB 890 1
125* EB 950 3 EB 998 2
* rotary lever
A
Type
Application: commercial, industrial
Connections for UNIFIX available - for In 63A
RCCBs F 3.. - F 6.. - F 800 ranges
Varistop F 670 series
TEPM0115
Accessories ................................................... pg. 3/46 Technical details .........................................pg. 10/40 Overall dimensions ........................................ pg. 11/7
1
2 4
3
TEPM0110
1
2
3
4
5
68
7
N
N
3/42
3
ABB SACE
Selective A
Type
Application: commercial, industrial
Connections for UNIFIX available
RCCBs F 3.. - F 6.. - F 800 ranges
Selective Var istop F 390 ser ies
Code
In Sensitivity
[A] 0.3A 0.5A
2P - F 392 type
40 EY 618 1 EY 620 7
63 EY 619 9 EY 621 5
4P - F 394 type
40 EY 640 5 EY 642 1
63 EY 641 3 EY 643 9
TEPM0118
TEPM0117
Accessories ................................................... pg. 3/46 Technical details .........................................pg. 10/40 Overall dimensions ........................................ pg. 11/7
1
24
3
1
2
3
4
5
68
7
N
N
3/43
3
ABB SACE
RCCBs F 3.. - F 6.. - F 800 ranges
F 3.. AR with automatic reclosing device series
F 360 AR
Rated currents Code
In Sensitivity
[A] 0.03 0.3 0.5
2P - F 362 AR type
25 EY 646 2
40 EY 647 0
4P - F 364 AR type
63 EY 651 2 EY 652 0
F 370 AR
2P - F 372 AR type
25 EY 648 8
40 EY 649 6
4P - F 374 AR type
63 EY 653 8
F 390 AR
4P - F 394 AR type
63 EY 654 6
Through the output contacts it is possible to use the re-
mote signalling of the failure state of the plant.
Example
NO C
light on = fault
24 V
OEPM0013
L1 N
L1 N
L3 N
L3 N
L1 L2
L1 L2
IN
OUT
IN
OUT
Wiring diagram
two-pole four-pole
OEPM0014
TEPM0123
TEPM0124
Accessories ................................................... pg. 3/46 Technical details .........................................pg. 10/40 Overall dimensions ........................................ pg. 11/8
1
24
3
1
2
3
4
5
68
7
N
N
3/44
3
ABB SACE
RCCBs F 3.. - F 6.. - F 800 ranges
F 370 for high frequencies (400 Hz) series
Accessories ................................................... pg. 3/46 Technical details .........................................pg. 10/40 Overall dimensions ........................................ pg. 11/7
Increasing the frequency generates an increase of the magnetic r eluctance of the toroidal transformer
of the RCCB and what follows is the value of the increasing operating residual current at 400Hz
reaching values 4-5 times higher than those of the residual current at 50Hz.
The RCCB F 370/400Hz guarantees protection against dir ect contact considering that the operating
residual current doesn’t increase with the increase of the network frequency.
The use of these RCCBs is expecially suitable for the industrial sector, i.e. installation where high
speed FM lines are used, laboratories, textile industries and telecommunications.
Rated currents Code
In Sensitivity
[A] 0.03A
4p - F 374/400Hz type
25 EY 786 6
40 EY 787 4
Technical characteristics
Rated conditional short-circuit
current SCPD [kA] 6 with 63A gL fuse
Rated current [A] In = 25 - 40
Rated voltage [V] Ue = 230 - 400 a.c.
Rated breaking
capacity [kA] Idm = 1.5
Minimum operating
voltage [V] Umin = 110
Frequency [Hz] 50/400
Sensitivity [A] 0.03
Poles 4P
Weight [g] 460
Self-extinguishing degree V0 thickness 1.6 mm
Protection degree IP XXB/IP2X
Operating temperature [°C] -25...+55
Electric operations [n°]10000
Mechanic operations [n°]20000
Terminals [mm2]25
Tropicalization acc. to
DIN40046 95% UR at 55°C
Surge current [A] 250 peaks
resistance (8/20µs)
as per VDE 0432 part 2
Mounting position Any
A
Type
Application: industrial
Connections for UNIFIX available
3/45
3
ABB SACE
RCCBs F 3.. - F 6.. - F 800 ranges
F 800 for leakage currents with continuous components
Accessories ................................................... pg. 3/46 Technical details .........................................pg. 10/40 Overall dimensions ........................................ pg. 11/8
In some specific applications, leakage can generate in dir ect current systems with low r esidual ripple
(<10%), undetectable by the RCBOs type AC or type A.
This occurs, for example, in Class I equipment that contain three-phase rectifier bridges.
In these cases, the Standards r ecommend the application of type B RCBOs as defined in V ariation 2
IEC 755 Standard (that indicates all the characteristics to be satisfied and the tests that must be
carried out), allowing the best solution to technical and economic problems.
These circuit-breakers are manufactured as type A RCBOs (where operation is unrelated to the
network voltage), and are equipped with a further electronic unit, with operation dependent on the
network voltage capable of detecting the leakage direct current.
With these circuit-breakers it is possible to protect every kind of equipment against indirect contact
further increasing the safety level in protecting people and at the same time maintaining maximum
operation reliability in TT and TN systems.
Among the most typical applications are the starters of dir ect curr ent motors for lifts, machine tools,
pumps, etc.
Rated currents Code
In Sensitivity
[A] 0,03 0,3
4P - F 804 type
63 EY 788 2 EY 789 0
TEPM0125
Technical characteristics
Rated conditional short-circuit
current SCPD [kA] 10 with 100A gL fuse
Rated current [A] 63
Rated voltage [V] 230 - 400 a.c.
Operating voltage [V] 175/440 a.c.
Frequency [Hz] 50/60
Sensitivity [A] 0.03 - 0.3
Poles 4P
Protection degree
- front IP XXB/IP2X
- mounted in housing
or in consumer unit IP XXD/IP4X
Operating temperature [°C] -25...+40
Electric operations [n°]>10000
Mechanical operations [n°]>10000
Shell terminals [mm2]25
Surge current [A] 250 peaks
resistance (8/20µs)
acc. to VDE 0432 part 2
Mounting position Any
Wiring diagram
135N
246N
T
OEPM0024
3/46
3
ABB SACE
RCCBs F 3.. - F 6.. - F 800 ranges
Auxiliary elements and accessories for F 3.. and F 6.. ranges
The F 3.. and F 6.. series of RCCBs can be equipped with auxiliary contact.
Accessories for installation are also available for the F 3... series.
Code Type Description
Auxiliary elements for F 360, F 370, F 390 series
KU 909 4 F 3..-H .. auxiliary contact 1NO + 1NC
Auxiliary elements for F 670 rotary operating RCCB only
KU 904 5 F6-H11 auxiliary contact 1NO + 1NC
Code Type Description
Accessories for F 360, F 370, F 390 series
EB 185 6 PCD/N2 terminal cover - 2 modules
EB 186 4 PCD/N4 terminal cover - 4 modules
EB 187 2 PCD/N6 terminal cover - 6 modules
EB 188 0 PCD/N8 terminal cover - 8 modules
EC 068 3 PB sealing kit for PCD/N
EB 176 5 FP1 spacer - false pole - 1 module
EB 177 3 FP2 spacer - false pole - 2 modules
EB 178 1 FP4 spacer - false pole - 4 modules
EB 179 9 FP6 spacer - false pole - 6 modules
EB 183 1 SFP support for spacer - false pole FP
Overall dimensions ...................................... pg. 11/10
Spacer - false pole FP2
+ SFP support
Support for spacer - false
pole SFP
PCD/N2
3/47
3
ABB SACE
Code Type Description
EA 214 5 BSA1 mechanical block
EA 213 7 BSA2 padlock for BSA1
EA 215 2 END/CLAMP clamp for DIN rail
KU 930 0 ME1 flange for rear board fixing 1 module
KU 931 8 ME2 flange for rear board fixing 2 modules
KU 932 6 ME3 flange for rear board fixing 3 modules
KU 933 4 ME4 flange for rear board fixing 4 modules
KU 934 2 ME6 flange for rear board fixing 6 modules
KU 935 9 ME8 flange for rear board fixing 8 modules
EP 742 9 ST label carrier
EP 743 7 ST-E neutral labels
Overall dimensions ...................................... pg. 11/10
Mechanical block BSA1
Padlock BSA2
Flange for rear board fixing ME4
Label carrier ST
RCCBs F 3.. - F 6.. - F 800 ranges
Auxiliary elements and accessories for F 3.. and F 6.. ranges
3/48 ABB SACE
The IEC 1009, EN 61009 Stan-
dard of 1994 introduced the
possibility to create RCBOs
through the assembly of an
MCB and a device (RCD block)
capable of detecting the re-
sidual current and control, con-
sequently, the opening of the
RCBO. The application field of
the RCD blocks is that of the
RCBOs series they are coupled
to. The DDA series of RCD
blocks includes devices from
25 to 100A, suitable for bipo-
lar, three-pole and four-pole
MCBs. The DDA blocks are
available in AC type (DDA 60
series), A type (DDA 70 series)
and selective type (DDA 90 se-
ries). In each series the blocks
from 25 to 63A are suitable for
assembly with MCBs in the S
240, S 250, S 270, S 280 se-
ries; the blocks from 100A are
suitable for assembly with
MCBs in the S 290 character-
istic C only series.
In compliance with IEC 1009,
EN 61009 Standard that de-
fines that the RCD-blocks can
be assembled with an MCB
only once, the DDA blocks are
equipped with an anti-tamper-
ing seal that has to be inserted
in an appropriate opening at the
end of the assembly process.
They are furthermore supplied
with coupled elements and with
purposely modelled pins, that
prevent incorrect assembly be-
tween the elements when the
rated current of the block is
lower than the current of the
circuit-breaker.
The DDA series of RCD blocks
are not sensitive to impulsive
atmospheric and operational
discharges; therefore, they are
not subject to unexpected trip-
ping according to EN 61008-
1, EN 61009-1 (wave 8/20 µs
up to 250A according to VDE
0432 T2).
Special versions of RCD blocks
(AC type) are also available,
such as DDA 60 AP and DDA
60 AE. The APs are special anti-
disturbance versions, while the
AEs combine the protection
function to the positive safety
emergency stop function for
remote tripping, as illustrated in
the technical details section.
D 60, D 70 and D 90 RCD
blocks are also available for
fixing on ABB Stotz Kontakt S
260, S 270 and
S 280 MCBs since for these
series DDA blocks aren’t
suitable.
TEPM01446
TEPM01445
3/49
3
ABB SACE
RCD blocks-DDA and D ranges
Contents
DDA range
Technical characteristics .......................................................................................................3/50
Order information
DDA 60 series .......................................................................................................................3/51
DDA 70 series .......................................................................................................................3/52
Selective DDA 90 series .......................................................................................................3/53
DD A 60 AE for emergency stop series..................................................................................3/54
Anti-disturbance DD A 60 AP series ......................................................................................3/55
Auxiliary elements and accessories ......................................................................................3/56
D range for ABB Stotz Kontakt MCBs
Technical characteristics .......................................................................................................3/57
Order information
D 60 series ............................................................................................................................3/58
D 70 series ............................................................................................................................3/59
Selective D 90 series ............................................................................................................3/60
3/50
3
ABB SACE
RCD blocks-DDA range
Technical characteristics
DDA 60 DDA 70 DDA 90
Standards IEC 1009 - EN 61009 Ann.G
Type AC A A (selective)
Size [A] 25, 40, 63, 100 25, 63, 100 63, 100
Poles size 25, 40, 63 A 2P, 3P, 4P
size 100 A 2P, 4P
Rated voltage Ue [V] 230/400
Max. operating voltage Ub max. [V] 440
Min. operating voltage Ub min. [V] 195; 125 (size 100 A)
Rated breaking capacity acc. to IEC 1009 [A] according to the breaking capacity of the associated MCB
Rated breaking capacity acc. to IEC 947-2 [A] according to the breaking capacity of the associated MCB
Rated residual with S 240 [kA] 4.5
breaking capacity Imwith S 250 [kA] 6
with S 270 [kA] 7.5
with S 280 (In 1025A)[kA] 12.5
with S 280 (In 3240A)[kA] 7.5
with S 280 (In 5063A)[kA] 7.5
with S 290 [kA] 7.5
Voltage withstanding capacity impulse (1,2/50) Uimp[kV] 5
at rated freq. (50-60Hz)
x 1 min. [kV] 3
Max. operating voltage of circuit test [V] 440; 250 (size 100A)
Min. operating voltage of circuit test [V] 195; 125 (size 100A)
(special version down to 125 V )
Surge current resistance [A] 250 A (8/20 wave) acc. to VDE 0432 Part 2
Rated frequency [Hz] 50…60
Rated sensitivity In[A] 0.03 - 0.1 - 0.3 0.03 - 0.1 - 0.3 0.1 - 0.3
0.5 - 1 - 2 0.5 - 1 0.5 - 1 - 2
Tripping threshold AC type 0.5…1 In
A type 0.11…1.4 In
Tripping time at In[ms] < 220 < 220 130…500
2 In[ms]< 80 < 80 60…200
5 In[ms]< 40 < 40 50…150
500 A [ms] < 40 < 40 40…150
Toggle size 25, 40, 63A blue operating just from OFF position
size 100A black operating from ON-OFF position
Electrical life 10000; 20000 (size 100A)
Mechanical life 20000
Protection degree housing IP4X/IPXXD (excluding terminal area)
terminals IP2X/IPXXB
Self-extinguishing degree V0 thickness 1,6 UL 94 yellow paper
Mechanical shock resistance 26 g half wave, duration 6 ms, 2000 shocks
Resistance to vibrations acc. to IEC 68-2-6 minimum 5 g, duration 30 min., at frequency 0…80 Hz
Tropicalization humid heat [°C/RH] 28 cycles with 55/95…100
acc. to IEC 68-2 constant climatic
conditions [°C/RH] 23/83 - 40/93 - 55/20
variable climatic
conditions [°C/RH] 25/95 - 40/95
Ambient temperature
(with daily average<+35°C) [°C] -5...+55 -25...+55 -25...+55
Storage temperature [°C] -20…+70
Terminal size 2P size up to 63 A [mm2]25
3P/4P size 25 A [mm2]10
3P/4P size 40 A [mm2]16
3P/4P size 63 A [mm2]25
2P/4P size 100 A [mm2]35
Mounting on DIN rail EN 50022 (35mm)
Dimensions 2P size up to 63 A [mm] 35
H: 94 x D: 68 x W: 3P/4P size 25 A [mm] 35
3P/4P size 40 A [mm] 52.5
3P/4P size 63 A [mm] 70
2P size 100 A [mm] 52.5
4P size 100 A [mm] 105
Weight 2P size up to 63 A [g] 190/210
3P/4P size up to 63 A [g] 270/330
2P size 100 A [g] 325
4P size 100 A [g] 600
3/51
3
ABB SACE
AC
Type
For MCBs
RCD blocks-DDA range
DDA 60 series
Technical details .......................................... pg. 10/40 Overall dimensions ....................................... pg. 11/9
Code
Size Sensitivity
[A] 0.03A 0.1A 0.3A 0.5A 1A 2A
2P - DDA 62 type
25 EY 850 0 EY 854 2
40 EY 851 8 EY 855 9 EY 858 3
63 EY 852 6 EY 853 4 EY 856 7 EY 859 1 EY 860 9 EY 861 7
100 KV 900 2 KV 901 0
3P - DDA 63 type
25 EY 862 5 EY 866 6 EY 869 0
40 EY 863 3 EY 870 8
63 EY 864 1 EY 865 8 EY 868 2 EY 871 6 EY 872 4
4P - DDA 64 type
25 EY 874 0 EY 878 1 EY 881 5
40 EY 875 7 EY 879 9 EY 882 3
63 EY 876 5 EY 877 3 EY 880 7 EY 883 1 EY 884 9 EY 885 6
100 KV 904 4 KV 905 1
TEPM0098
TEPM0099
TEPM0100
Breaking capacity
Im
acc. to IEC 1009 / EN 61009 equivalent to coupled MCB
acc. to IEC 947-2 / EN 60947-2 equivalent to coupled MCB
IMQ approval
DDA 60 2P 3P 4P
In = 25…63A
In = 0.03-0.3-0.5-1A
S 240, S 250, S 270, S 280, S 290 (characteristic C, up to
100A)
3/52
3
ABB SACE
A
Type
For MCBs
RCD blocks-DDA range
DDA 70 series
Technical details .......................................... pg. 10/40 Overall dimensions ....................................... pg. 11/9
IMQ approval
DDA 70 2P 3P 4P
In = 25…63A
In = 0.03-0.1-0.3-0.5-1A
S 240, S 250, S 270, S 280, S 290 (characteristic C, up to
100A)
Breaking capacity
Im
acc. to IEC 1009 / EN 61009 equivalent to coupled MCB
acc. to IEC 947-2 / EN 60947-2 equivalent to coupled MCB
Code
Size Sensitivity
[A] 0.03A 0.1A 0.3A 0.5A 1A
2P - DDA 72 type
25 EY 890 6
63 EY 892 2 EY 893 0 EY 896 3 EY 899 7 EY 900 3
100 KV 906 9 KV 907 7
3P - DDA 73 type
25
63 EY 904 5 EY 905 2 EY 908 6 EY 911 0 EY 912 8
4P - DDA 74 type
25 EY 913 6
63 EY 915 1 EY 916 9 EY 919 3 EY 922 7 EY 923 5
100 KV 910 1 KV 911 9
TEPM0101
TEPM0102
TEPM0103
3/53
3
ABB SACE
Selective A
Type
For MCBs
RCD blocks-DDA range
Selective DDA 90 series
Technical details .......................................... pg. 10/40 Overall dimensions ....................................... pg. 11/9
S 240, S 250, S 270, S 280, S 290 (characteristic C, up to
100A)
Breaking capacity
Im
acc. to IEC 1009 / EN 61009 equivalent to coupled MCB
acc. to IEC 947-2 / EN 60947-2 equivalent to coupled MCB
Code
Size Sensitivity
[A] 0.1A 0.3A 0.5A 1A 2A
2P - DDA 92 type
63 EY 930 0 EY 931 8 EY 932 6 EY 933 4
100 KV 912 7 KV 913 5
3P - DDA 93 type
63 EY 927 6 EY 928 4 EY 929 2
4P - DDA 94 type
63 EY 935 9 EY 936 7 EY 937 5 EY 938 3
100 KV 916 8 KV 917 6
TEPM0107
TEPM0108
TEPM0122
3/54
3
ABB SACE
AC
Type
For MCBs
RCD blocks-DDA range
DDA 60 AE for emergency stop series
Technical details .......................................... pg. 10/40 Overall dimensions ....................................... pg. 11/9
S 240, S 250, S 270, S 280
Breaking capacity
Im
acc. to IEC 1009 / EN 61009 equivalent to coupled MCB
acc. to IEC 947-2 / EN 60947-2 equivalent to coupled MCB
Code
Size Sensitivity
[A] 0.03A 0.3A 0.5A 1A
bipolar - DDA 62 AE type
63 EY 952 4 EY 953 2 EY 954 0 EY 955 7
three-pole - DDA 63 AE type
63 EY 956 5 EY 957 3 EY 958 1 EY 959 9
four-pole - DDA 64 AE type
63 EY 960 7 EY 961 5 EY 962 3 EY 963 1
TEPM0107
TEPM0108
TEPM0122
3/55
3
ABB SACE
AC
Type
For MCBs
RCD blocks-DDA range
Anti-disturbance DDA 60 AP series
Technical details .......................................... pg. 10/40 Overall dimensions ....................................... pg. 11/9
S 240, S 250, S 270, S 280
Code
Size Sensitivity
[A] 0.03A 0.3A
bipolar - DDA 62 AP type
40 EY 964 9 EY 965 6
four-pole - DDA 64 AP type
63 EY 966 4 EY 967 2
Breaking capacity
Im
acc. to IEC 1009 / EN 61009 equivalent to coupled MCB
acc. to IEC 947-2 / EN 60947-2 equivalent to coupled MCB
TEPM0098
TEPM0100
3/56
3
ABB SACE
Code Type Description
KU 939 1 S2-MP2 rear terminal for rear board fixing 25mm2 for DDA 63 A
KU 944 1 CPV3 sealable screw protection cover only for DDA 25 A
KU 945 8 CPV4 sealable screw protection cover only for DDA 63 A
Terminal S2-MP2
CPV
RCD blocks-DDA range
Auxiliary elements and accessories
Technical details .......................................... pg. 10/40 Overall dimensions ....................................... pg. 11/9
3/57
3
ABB SACE
RCD blocks – D range
Technical characteristics
D 60 D 70 D 90
Standards IEC 1009 - EN 61009 (when coupled)
Type AC A A (selective)
Size [A] 32, 63 32, 63 63
Poles 2P, 3P, 4P
Rated voltage Ue [V] 230/400
Max. operating voltage Ub max. [V] 440
Min. operating voltage Ub min. [V] 195
Rated breaking capacity acc.
to IEC 1009 [A] according to the breaking capacity of the associated MCB
Rated breaking capacity acc.
to IEC 947-2 [A] according to the breaking capacity of the associated MCB
Rated residual with S 240 [kA] 4.5
breaking capacity Imwith S 250 &
S 260 [kA] 6
with S 270 [kA] 7.5
with S 280
(In 10…25 A) [kA] 12.5
with S 280
(In 32…40 A) [kA] 7.5
with S 280
(In 50…63 A) [kA] 7.5
Voltage withstanding capacity impulse
(1.2/50) Uimp [kV] 5
at rated freq.
(50-60Hz) x 1 min. [kV] 3
Max. operating voltage
of circuit test [V] 254
Min. operating voltage
of circuit test [V] 110
Surge current resistance [A] 250 A (8/20 wave) acc. to VDE 0432 Part 2
Rated frequency [Hz] 50…60
Rated sensitivity In[A] 0,01 - 0,03 0.01 - 0.03 0,3 - 1
0.3 - 0.5 0.3 - 0.5
Tripping threshold AC type 0.5…1 In
A type 0.11…1.4 In
Tripping time at In[ms]< 220 < 220 130…500
2 In[ms]< 80 < 80 60…200
5 In[ms]< 40 < 40 50…150
500 A [ms] < 40 < 40 40…150
Toggle blue operating just from OFF position
Electrical life 10000
Mechanical life 20000
Protection degree housing IP4X/IPXXD (excluding terminal area)
terminals IP2X/IPXXB
Self-extinguishing degree V0 thickness 1.6 UL 94 yellow paper
Mechanical shock resistance 26 g half wave, duration 6 ms, 2000 shocks
Resistance to vibrations acc. to IEC 68-2-6 minimum 5 g, duration 30 min., at frequency 0…80 Hz
Tropicalization humid heat [°C/RH] 28 cycles with 55/95…100
acc. to IEC 68-2 constant climatic
conditions [°C/RH] 23/83 - 40/93 - 55/20
variable climatic
conditions [°C/RH] 25/95 - 40/95
Ambient temperature
(with daily average<+35°C) [°C] -5…+55 -25…+55 -25…+55
Storage temperature [°C] -25…+70
Terminal size 2P size up to 63 A [mm2]25
3P/4P size 32 A [mm2]10
3P/4P size 63 A [mm2]25
Mounting on DIN rail EN 50022 (35mm)
Dimensions 2P size up to 63 A [mm] 35
H: 94 x D: 68 x W: 3P/4P size 32 A [mm] 35
3P/4P size 63 A [mm] 70
Weight 2P size up to 63 A [g] 190/210
3P/4P size 32 A [g] 190/210
3P/4P size 63 A [g] 270/330
3/58
3
ABB SACE
AC
Type
For ABB STOTZ KONTAKT MCBs
RCD blocks – D range
D 60 blocks for ABB Stotz Kontakt MCBs
Technical details .......................................... pg. 10/40 Overall dimensions ....................................... pg. 11/9
S 260, S 270, S 280
Size Code
[A] Sensitivity
0.01A 0.03A 0.3A 0.5A 1A
2P – D 62 type
1A
16 11176027
32 11176028 11176032 11176034
63 11176029 11176033 11176035
Size Code
[A] Sensitivity
0.01A 0.03A 0.3A 0.5A 1A
3P – D 63 type
32 11176036 11176040
63 11176037 11176041
Size Code
[A] Sensitivity
0.01A 0.03A 0.3A 0.5A 1A
4P – D 64 type
32 11176044 11176048 11176050
63 11176045 11176049 11176051
Breaking capacity
Im
acc. to IEC 1009 / EN 61009 equivalent to coupled MCB
acc. to IEC 947-2 / EN 60947-2 equivalent to coupled MCB
3/59
3
ABB SACE
Size Code
[A] Sensitivity
0.01A 0.03A 0.3A 0.5A 1A
2P – D 72 type
16 11176127
32 11176128 11176132
63 11176129 11176133
Size Code
[A] Sensitivity
0.01A 0.03A 0.3A 0.5A 1A
3P – D 73 type
32 11176136 11176140
63 11176137 11176141
Size Code
[A] Sensitivity
0.01A 0.03A 0.3A 0.5A 1A
4P – D 74 type
32 11176144 11176148
63 11176145 11176149
RCD blocks – D range
D 70 blocks for ABB Stotz Kontakt MCBs
A
Type
For ABB STOTZ KONTAKT MCBs
Technical details .......................................... pg. 10/40 Overall dimensions ....................................... pg. 11/9
S 260, S 270, S 280
Breaking capacity
Im
acc. to IEC 1009 / EN 61009 equivalent to coupled MCB
acc. to IEC 947-2 / EN 60947-2 equivalent to coupled MCB
3/60
3
ABB SACE
Size Code
[A] Sensitivity
0.01A 0.03A 0.3A 0.5A 1A
2P – D 92 type
63 11176233
Size Code
[A] Sensitivity
0.01A 0.03A 0.3A 0.5A 1A
4P – D 94 type
63 11176249 11176252
RCD blocks – D range
D 90 blocks for ABB Stotz Kontakt MCBs
A (selective)
Type
For ABB STOTZ KONTAKT MCBs
Technical details .......................................... pg. 10/40 Overall dimensions ....................................... pg. 11/9
S 260, S 270, S 280
Breaking capacity
Im
acc. to IEC 1009 / EN 61009 equivalent to coupled MCB
acc. to IEC 947-2 / EN 60947-2 equivalent to coupled MCB
4/1
4
Other modular devices
Protection devices
ABB SACE
Contents
RD2 residual current monitors ............................................................................................4/2
OVR surge protective devices
Monobloc surge protective devices .........................................................................................4/3
Withdrawable-cartridge surge protective devices ...................................................................4/5
MS 225 manual motor starters ............................................................................................4/7
E 930 fuse holders ...............................................................................................................4/10
M2160 - M2060 fuse switches ...........................................................................................4/12
4/2
4
ABB SACE
A
Type
Protection devices
RD2 residual current monitors
In = 30 mA … 2 A
In
Technical details .......................................... pg. 10/48 Overall dimensions ..................................... pg. 11/14
Residual current monitors (RCMs) with external transformer can detect leakage currents. Through
minidip you can set sensitivity and intervention time. According to the same diameter, transformers
are made in a single version for all relay sensitivity values.
Code Type Description
EG 316 2 RD2 residual current monitor
EG 276 8 TR35 toroidal transformer ø 35 mm
EG 277 6 TR60 toroidal transformer ø 60 mm
EG 278 4 TR80 toroidal transformer ø 80 mm
EG 279 2 TR110 toroidal transformer ø 110 mm
EG 280 0 TR210 toroidal transformer ø 210 mm
EG 281 8 TR210/A toroidal transformer ø 210 mm
(opening version)
EG 299 0 TRM modular toroidal transformer
ø 29 mm
Technical characteristics
Standard IEC 62020
Operating voltage [V] 110÷400 a.c.; 48÷110 d.c.
Frequency [Hz] 50÷60
Sensitivity settings [In] 0.03; 0.1; 0.3; 0.5; 1; 2A
Intervention time [s] 0.05 (fast); 0.3; 0.5; 1; 2; 5
settings
Contact capacity [A] 10 at 250V a.c. (ohmic)
Contact type change over
Operating temperature [°C] –5…+40
Power consumption [W] 0.8 at 110V a.c.; 1.8 at 230V a.c.;
6.8 at 400V a.c.
0.2 at 48V d.c.; 1 at 110V d.c.
Number of modules [No] 2
TEPM0119
TEPM0120
L1
L2
L3
678
12345
910
NO NC
N
Power supply
110V÷400Va.c.
48V÷110Vd.c.
COM
0.03 0.1 0.3 0.5 1 2
Fast 0.3 0.5 1 2 5
0.03
In(A)
0.1
0.3
0.5
1
2
Fast
Time
(sec.)
0.3
0.5
1
2
5
Selection of calibration
Indications
Green led: rated voltage
Red led: alarm status
More functions
The connection between
the toroidal transformer
and the residual current
relay is continually
controlled by the relay;
when the connection
breaks the residual current
relay enters the “alarm”
status.
The ”test” pushbutton si-
mulates a failure inside the
residual current relay: if
pushed it must enter the
alarm status.
The “reset” pushbutton
allows the residual current
relay to return to the
starting condition.
N.B.: if the configuration is not appropriate, the
device will automatically consider as valid the
first configuration (according to the diagram) and
enter the maximum safety.
OEPM0294
OEPM0295
4/3
4
ABB SACE
Protection devices
OVR surge protective devices (SPD)
The OVERSTOP system allows the protection from possible transient overvoltages peaks, for both
the appliances and the systems.
These overvoltages, mostly due to atmospheric discharges, sudden switch operations, and parasitic
interferences inside the circuits themselves, are caused by problems that can be prevented using
monobloc and withdrawable-cartridge OVR surge arresters.
Monobloc surge protective devices
There are three different solutions of the product that, for their technical characteristics, allow for a
capillary “cascaded” protection:
1) protection for main power lines
2) protection for secondary power lines
3) protection for telephone/data transmission lines.
These devices are characterized by several discharge currents among which it is possible to choose
the most appropriate surge arrester according to the installation point on the energy feeder line.
The protection provided is of a differential and common mode types, therefore by overvoltages
between active conductors or between active conductors and earth.
Code Type Description
Three-phase and single-phase MAIN power line protections
EA 881 1 OVR/365 three-phase protection 65kA (4 modules)
EA 878 7 OVR/165 single-phase protection 65kA (2 modules)
EA 880 3 OVR/340 three-phase protection 40kA (4 modules)
EA 877 9 OVR/140 single-phase protection 40kA (2 modules)
TEPM0155
Technical characteristics
Protection for three-phase and single-phase
MAIN power lines
OVR/365 OVR/165 OVR/340 OVR/140
Max. continuous
operating voltage Uc [V] 250/440 250/440 250/440 250/440
Frequency [Hz] 50 50 50 50
Transient discharge
current Imax (8/20µs) [kA] 65 65 40 40
Transient discharge
current In (8/20µs) [kA] 20 20 10 10
Protection type common and differential mode
Protection level Up [kV] 2 2 1.2/1.8 1.2/1.8
End of life indication optical on the product,
remote both optical and acoustic
with OVR/SIGN accessory
Modules [No] 4 2 4 2
Standards IEC 61643-1
Test class (IEC 61643-1) II II II II
Technical details .......................................... pg. 10/49 Overall dimensions ..................................... pg. 11/15
OVR
L1
N
OVR
L1
L2
L3
N
OVR
L1
N
MCB or
fuse holder
OVR
L1
L2
L3
N
MCB or
fuse holder
MCB or
fuse holder
MCB or
fuse holder
Wiring diagram A The connection in
diagram A privileges
the continuity of
service.
The connection in
diagram B privileges
the protection
function.
In both cases the
wiring between the
line and the
equipotential bar
(through OVR) has to
be as short as
possible (< 50cm).
Wiring diagram B
Back-up protection
4/4
4
ABB SACE
Technical details .......................................... pg. 10/49 Overall dimensions ..................................... pg. 11/15
Protection devices
OVR surge protective devices (SPD)
Technical characteristics
Three-phase and single-phase SECONDARY power line
protections
OVR/315 OVR/115
Max. continuous
operating voltage Uc [V] 230/400 230
Frequency [Hz] 50 50
Transient discharge
current Imax (8/20µs) [kA] 15 15
Transient discharge
current In (8/20µs) [kA] 5 5
Type of protection common and differential mode
Protection level Up [kV] 1.2/1.8 1.2/1.8
End of life indication optical on the product,
remote both optical and acoustic
with OVR/SIGN accessory
Modules [No] 4 2
Standards IEC 61643-1
Test class (IEC 61643-1) II II
Telephone and data transmission line protections
OVR/TEL
Max. continuous
operating voltage Uc [V] from 48 d.c. to 200 d.c.
Transient discharge
current Imax (8/20µs) [kA] 10
Transient discharge
current In (8/20µs) [kA] 5
Protection level Up [kV] 0.3
Response time [ns] <25
End of life indication optical on the product,
remote both optical and acoustic
with OVR/SIGN accessory
Modules [No] 1
Indication
OVR/SIGN
Max. continuous
operating voltage Un [V] 230 a.c.
Contact capacity [A] 5 (ohmic)
Insulation voltage
between contacts [kV] 1
Insulation voltage
between contact and coil [kV] 2.5
Contact NC 2-4 / NA 4-6
Modules [No] 1+1
Code Type Description
Three-phase and single-phase SECONDARY power line protections
EA 879 5 OVR/315 three-phase protection 15kA (4 modules)
EA 876 1 OVR/115 single-phase protection 15kA (2 modules)
TELEPHONE and DATA TRANSMISSION line up to 200V d.c. protections
EA 882 9 OVR/TEL protection for telephony and data transmission from 48V d.c.
up to 200V d.c. 10kA (1 module)
Indication
EA 883 7 OVR/SIGN accessory for remote end of life indication OVR (1+1 modules)
TEPM0156
TEPM0326
TEPM0157
TEPM0158
4/5
4
ABB SACE
Withdrawable-cartridge surge protective devices
Withdrawable-cartridge surge arresters operate with the same principles as the monobloc surge
arresters, but when reaching the end of life, they provide the possibility to replace the cartridge only,
not the whole product.
The solutions offered in the withdrawable-cartridge version are:
1) main power line protection
2) secondary power line protection.
Two types of cartridge-holder bases are also available: one-pole + neutral (OVR/BASE1N) and three-
pole + neutral (OVR/BASE3N) equipped with a signal contact which can indicate remotely the product
end of life (the same function is carried out by the OVR/SIGN accessory, which can be used in
combination with withdrawable-cartridge surge arresters).
Code Type Description
Three-phase and single-phase MAIN power line protections
EA 841 5 OVR/365P three-phase protection 65KA (4 modules)
EA 840 7 OVR/165P single-phase protection 65KA (2 modules)
EA 839 9 OVR/340P three-phase protection 40KA (4 modules)
EA 838 1 OVR/140P single-phase protection 40KA (2 modules)
Protection devices
OVR surge protective devices (SPD)
TEPM0183
Technical characteristics
Three-phase and single-phase MAIN
power line protections
OVR/365P OVR/165P
Max. continuous
operating voltage Uc [V] 250/440 250/440
Frequency [Hz] 50 50
Transient discharge
current Imax (8/20µs) [KA] 65 65
Transient discharge
current In (8/20µs) [kA] 20 20
Type of protection
common and differential mode
Protection level Up [kV] 1.5 1.5
End of life indication optical on the product, remote by
OVR/SIGN accessory or BASE1N and
BASE3N
Modules [No] 4 2
Standards IEC 61643-1
Test class (IEC 61643-1) II II
OVR/340P OVR/140P
Max. continuous
operating voltage Uc [V] 250/440 250/440
Frequency [Hz] 50 50
Transient discharge
current Imax (8/20µs) [kA] 40 40
Transient discharge
current In (8/20µs) [kA] 15 15
Type of protection common and differential mode
Protection level Up [kV] 1.2 1.2
Response time [ns] <25 <25
End of life indication optical on the product, remote by
OVR/SIGN accessory or BASE1N and
BASE3N
Modules [No] 4 2
Standards IEC 61643-1
Test class (IEC 61643-1) II II
Technical details .......................................... pg. 10/49 Overall dimensions ..................................... pg. 11/15
L1 L2 L3
N
4/6
4
ABB SACE
Protection devices
OVR surge protective devices (SPD)
Technical characteristics
Three-phase and single-phase SECONDARY power line
protections
OVR/315P OVR/115P
Max. continuous
operating voltage Uc [V] 230/400 230
Frequency [Hz] 50 50
Transient discharge
current Imax (8/20µs) [kA] 15 15
Transient discharge
current In (8/20µs) [kA] 5 5
Type of protection common and differential mode
Protection level Up [kV] 1.2 1.2
Response time [ns] <25 <25
End of life indication optical on the product,
remote
by OVR/SIGN accessory
by BASE1N and BASE3N
Modules [No] 4 2
Standards IEC 61643-1
Test class (IEC 61643-1) II II
OVR
L1
N
OVR
L1
L2
L3
N
OVR
L1
N
MCB or
fuse holder
OVR
L1
L2
L3
N
MCB or
fuse holder
MCB or
fuse holder
MCB or
fuse holder
Wiring diagram A The connection in
diagram A
privileges the
continuity of
service.
The connection in
diagram B
privileges the
protection function.
In both cases the
wiring between the
line and the
equipotential bar
(through OVR) has
to be as short as
possible (< 50cm).
Code Type Description
Three-phase and single-phase SECONDARY power line protections
EA 837 3 OVR/315P three-phase protection 15kA (4 modules)
EA 836 5 OVR/115P single-phase protection 15kA (2 modules)
Accessories
Cartridges can be used as spare parts for OVR/…P or, if appropriately coupled to OVR/BASE.., can
make up a complete withdrawable-cartridge surge arrester with a built-in signal contact.
For example, you build up a single-phase surge arrester 40KA with remote signalling by assembling
an OVR/BASE1N to an OVR/40P and an OVR/N.
Cartridge-holder bases and cartridges
EA 858 9 OVR/BASE1N one-pole base + neutral with signal contact
(for OVR/15P, OVR/40P, OVR/65P , and OVR/N cartridges)
EA 859 7 OVR/BASE3N three-pole base + neutral with signal contact
(for OVR/15P, OVR/40P, OVR/65P , and OVR/N cartridges)
EA 860 5 OVR/15P 15kA phase cartridge
EA 861 3 OVR/40P 40kA phase cartridge
EA 862 1 OVR/65P 65kA phase cartridge
EA 863 9 OVR/N 15, 40, 65kA neutral cartridge
TEPM0184
TEPM0185
TEPM0186
Technical details .......................................... pg. 10/49 Overall dimensions ..................................... pg. 11/15
Wiring diagram B
Back-up protection
4/7
4
ABB SACE
Protection devices
MS 225 manual motor starters
Technical details .......................................... pg. 10/56 Overall dimensions ..................................... pg. 11/15
These devices, realized in a range of 14 different tripping fields (from 0.1 to 25A), are appropriate to
protect small motors feeded by consumer units.
The protection of terminals against accidental contacts and the monobloc structure guarantee the
maximum operating safety.
A wide range of accessories which allows to satisfy multiple installation needs is also available.
Code Type Description
EP 680 1 MS225/0.16 adjustment range 0.1...0.16A
EP 681 9 MS225/0.25 adjustment range 0.16...0.25A
EP 682 7 MS225/0.4 adjustment range 0.25...0.4A
EP 683 5 MS225/0.63 adjustment range 0.4...0.63A
EP 684 3 MS225/1 adjustment range 0.63...1A
EP 685 0 MS225/1.6 adjustment range 1...1.6A
EP 686 8 MS225/2.5 adjustment range 1.6...2.5A
EP 687 6 MS225/4 adjustment range 2.5...4A
EP 688 4 MS225/6.3 adjustment range 4...6.3A
EP 689 2 MS225/9 adjustment range 6.3...9A
EP 690 0 MS225/12.5 adjustment range 9...12.5A
EP 691 8 MS225/16 adjustment range 12.5...16A
EP 692 6 MS225/20 adjustment range 16...20A
EP 693 4 MS225/25 adjustment range 20...25A
I > I > I >
I > I > I >
1/L1
3/L2
5/L3
2/T1
4/T2
6/T3
Technical characteristics of
auxiliary and signal contacts
Insulation rated
voltage [V] 400
Rated thermal
current Ith [A] 6
Min. utilization current 12V d.c.: 10mA; 24V d.c.: 5mA
Utilization current
in AC15 220V: 2A ; 380V: 0.5A
in DC13 60V: 2.5A; 110V: 0.6A;
220V: 0.25A
Protection fuse [A] gL: 10; aM: 6
Weight [g] 300
Connections [mm2] 0.5...2.5
Technical characteristics of
shunt trips
Insulation rated
voltage Ui [V] 400
Rated frequency [Hz] 50
Operating field
operation 80...110 %Un
release trip 35...75 %Un
Consumption [VA]
pickup 0.9
holding 0.9
TEPM0159
4/8
4
ABB SACE
Protection devices
MS 225 manual motor starters
Technical details .......................................... pg. 10/56 Overall dimensions ..................................... pg. 11/15
Auxiliary/accessory elements
Code Type Description
Auxiliary contacts
EP 842 7 HK 11 1NO +1NC
EP 843 5 HK 20 2NO
EP 844 3 HK 02 2NC
EP 977 1 HK F11 1NO + 1NC (front)
EP 978 9 HK F20 2NO (front)
Tripping signal contacts with overcurrent protection
EP 845 0 SK 10 1NO
EP 846 8 SK 01 1NC
EP 979 7 HK 11 1NO + 1NC
Minimum voltage release coils
EP 834 4 UA 415V a.c. 415V a.c. coil - direct internal power supply
EP 835 1 UA 24V a.c. 24V a.c. coil - external power supply
EP 836 9 UA 48V a.c. 48V a.c. coil - external power supply
EP 837 7 UA 60V a.c. 60V a.c. coil - external power supply
EP 838 5 UA 110V a.c. 110V a.c. coil - external power supply
EP 839 3 UA 230V a.c. 230V a.c. coil - external power supply
EP 840 1 UA 415V a.c. 415V a.c. coil -external power supply
EP 841 9 UA 500V ac 500V a.c. coil - external power supply
TEPM0160
TEPM0161
TEPM0163
Coordinated short-circuit protection (50KA)
Ics breaking capacity and max gauge of protection fuses for
Icc >Ics (coordinated class C according to IEC292-1).
220/240 380/400 415 500 660 690
V a.c. V a.c. V a.c. V a.c. V a.c. V a.c.
Adjustment range KA A KA A KA A KA A KA A KA A
thermal release
0.1...0.16A
0.16...0.25A FUSE NOT NECESSARY (50KA)
0.25...0.4A
0.4...0.63A
0.63...1A
1...1.6A 40 25 30 25 30 25
1.6...2.5A 40 25 20 25 20 25
2.5...4A 30 35 8 35 8 35
4...6.3A 40 35 30 40 3 35 3 35
6.3...9A 40 40 30 40 20 50 3 35 3 35
9...12.5A 30 50 20 50 20 63 3 35 3 35
12.5...16A 40 63 30 63 10 63 10 80 3 35 3 35
16...20A 20 80 10 80 10 80 10 80 2 40 2 40
20...25A 20 100 10 100 10 100 5 100 2 40 2 40
4/9
4
ABB SACE
Protection devices
MS 225 manual motor starters
Technical details .......................................... pg. 10/56 Overall dimensions ..................................... pg. 11/15
Code Type Description
Undervoltage releases
EP 915 1 1SAM101909R0001 24…60V a.c. power supply
EP 916 9 1SAM101909R0002 110…240V a.c. power supply
Electric connection blocks
EP 847 6 AS for connecting external power supply coils
Adapters for the installation on plates and rails
EP 893 0 GA 02 for mounting MS225 and Bsu contactor on DIN rail
EP 866 6 1 SA 12-2 for mounting MS225 and contactor Bsu on rails
EP 890 6 CONB6/7 electric connection between MS225 and B6/7
EP 891 4 CONVB6/7 electric connection between MS225 and VB6/7
EP 892 2 BSA 325 electric connection between A9…A16 contactors
Housings
EP 981 3 OTPA325A1P1 IP65 housing with red/yellow handle
EP 982 1 OTPA325B1P1 IP65 housing with black handle
EP 983 9 OTPA325A2P1 IP65 housing with protected red/yellow handle
EP 984 7 OTPA325B2P1 IP65 housing with protected black handle
Adapters for shaft and handle back installation on a door
EP 894 8 ADAT allows the use of OX…180 shaft type with OH.2AJ handle
for OT16…125 disconnectors
Labels
EP 849 2 COP-1 transparent covers
EP 850 0 TAR-1 neutral label
Signalling lamps
EP 853 4 PG 16 A 220...240V a.c. transparent
EP 854 2 PG 16 B 380...415V a.c. transparent
EP 855 9 PG 16 C 220...240V a.c.green
EP 856 7 PG 16 D 380...415V a.c. green
Locking systems
EP 862 5 SA 1 padlock not provided
EP 863 3 SA 3 padlock provided
Connection busbars
EP 867 4 PS3-2-0 for 2 MS225 without auxiliary contacts
EP 868 2 PS3-2-1 for 2 MS225 with 1 block of auxiliary contacts
EP 869 0 PS3-2-2 for 2 MS225 with 2 blocks of auxiliary contacts
EP 870 8 PS3-4-0 for 4 MS225 without auxiliary contacts
EP 871 6 PS3-4-1 for 4 MS225 with 1 block of auxiliary contacts
EP 872 4 PS3-4-2 for 4 MS225 with 2 blocks of auxiliary contacts
Connection terminals
EP 873 2 S3-M1 for connecting cables max 25mm2
EP 874 0 S3-M2 for connecting bars
TEPM0166
TEPM0165
TEPM0172
TEPM0173
4/10
4
ABB SACE
Protection devices
E 930 fuse holders
Technical details .......................................... pg. 10/60 Overall dimensions ..................................... pg. 11/16
Technical characteristics of
fuse holders for 8.5x31.5mm and 10.3x38mm fuses
Rated voltage Un[V] a.c. 400 a.c. 400
Max. rated current In[A] 20 32
Rated frequency [Hz] 50/60 50/60
Fuse dimension [mm] 8.5 x 31.5 10.3 x 38
Power consumption per pole See technical details
Modules [No] 1, 2, 3 1, 2, 3
Standards IEC 60269.2
Approvals IMQ, UTE IMQ, UTE
E 930 fuse holders are appropriate to protect against overloads and short circuits. They are designed
for use with cylindrical fuses of 8.5x31.5mm (up to 20A), 10.3x38mm (up to 32A), 14x51mm (up to
50A) and 22x58mm (up to 125A).
They are provided with IP20 protection degree, and for each version (1P, 1P+N, …) are also available
on request sizes of 8.5x23mm (up to 10A), 10.3x25mm (up to 16A) and 10.3x31.5mm (up to 25A).
Code Type Description
1P – Fuse holders for 8.5x31.5mm and 10.3x38mm fuses
EA 191 5 E 931/20 single-pole 8.5x31.5mm fuse holder (1 module)
EA 201 2 E 931/32 single-pole 10.3x38mm fuse holder (1 module)
1P+N – Fuse holders for 8.5x31.5mm and 10.3x38mm fuses
EA 291 3 E 931N/20 single-pole 8.5x31.5mm fuse holder with disconnectable neutral on the right
(1 module)
EA 293 9 E 931N/32 single-pole 10.3x38mm fuse holder with disconnectable neutral on the right
(1 module)
2P – Fuse holders for 8.5x31.5mm and 10.3x38mm fuses
EA 193 1 E 932/20 two-pole 8.3x31.5mm fuse holder (2 modules)
EA 203 8 E 932/32 two-pole 10.3x38mm fuse holder (2 modules)
3P – Fuse holders for 8.5x31.5mm and 10.3x38mm fuses
EA 194 9 E 933/20 three-pole 8.5x31.5mm fuse holder (3 modules)
EA 204 6 E 933/32 three-pole 10.3x38mm fuse holder (3 modules)
3P+N – Fuse holders for 8.5x31.5mm and 10.3x38mm fuses
EA 292 1 E 933N/20 three-pole 8.5x31.5mm fuse holder with disconnectable neutral on the right
(3 modules)
EA 294 7 E 933N/32 three-pole 10.3x38mm fuse holder with disconnectable neutral on the right
(3 modules)
TEPM0321
TEPM0322
TEPM0323
TEPM0324
TEPM0325
4/11
4
ABB SACE
Protection devices
E 930 fuse holders
Technical details .......................................... pg. 10/60 Overall dimensions ..................................... pg. 11/16
Technical characteristics of
fuse holders for 14x51mm and 22x58mm fuses
Rated voltage Un
[V] a.c. 690 a.c. 690
Max. rated current In
[A] 50 125
Rated frequency
[Hz] 50/60 50/60
Fuse dimension
[mm] 14x51 22x58
Power consump. per pole
[W] 0.25...5 0.3…12.5
Modules
[No] 1
1/2
, 3, 4
1/2
, 6 2, 4, 6, 8
Standards
IEC269.2
Approvals UL, CSA UL, CSA
Fuse holders for 14x51mm fuses
EA 051 1 E 931/50 one-pole fuse holder disconnector
EA 052 9 E 931N/50 one-pole fuse holder disconnector with disconnectable neutral
EA 053 7 E 932/50 bipolar fuse holder disconnector
EA 054 5 E 933/50 three-pole fuse holder disconnector
EA 055 2 E 933N/50 three-pole fuse holder disconnector with disconnectable neutral
Fuse holders for 32x58mm fuses
EA 058 6 E 931/125 one-pole fuse holder disconnector
EA 059 4 E 931N/125 one-pole fuse holder disconnector with disconnectable neutral
EA 060 2 E 932/125 bipolar fuse holder disconnector
EA 061 0 E 933/125 three-pole fuse holder disconnector
EA 062 8 E 933N/125 three-pole fuse holder disconnector with disconnectable neutral
Accessories
EA 065 1 E 930/MCR1P50 microswitch for remote signalling on one-pole
fuse holders for 50A fuses with built-in striker
EA 066 9 E 930/MCR3P50 microswitch for remote signalling on three-pole
fuse holders for 50A fuses with built-in striker
EA 067 7 E 930/MCR1P125 microswitch for remote signalling on one-pole
fuse holders for 125A fuses with built-in striker
EA 068 5 E 930/MCR3P125 microswitch for remote signalling on one-pole
fuse holders for 125A fuses with built-in striker
EA 069 3 E 930/ACP50 kit for coupling max. 10 single 50A poles
EA 070 1 E 930/ACP125 kit for coupling max. 10 single 125A poles
EA 211 1 E 930/KIT transparent cover for signalling 20A and 32A fuse trip
1
2
3
4
2P
1
2
N
1P+N
1
2
1P
1
2
3
4
3P+N
5
6
N1
2
3
4
3P
5
6
N N
OEPM0027
TEPM0181 TEPM0180
TEPM0420
4/12
4
ABB SACE
Protection devices
M2160 - M2060 fuse switches
Technical details .......................................... pg. 10/61 Overall dimensions ..................................... pg. 11/16
Technical characteristics
Rated voltage Un[V] a.c. 400
Rated current In[A] 20
Rated frequency [Hz] 50/60
Fuse dimension [mm] 8.5x31.5; 10.3x38
Power consumption See technical details
Modules [No] 1, 2, 3, 4
1
2
3
4
2P
1
2
N
1P+N
1
2
1P
1
2
3
4
3P+N
5
6
N1
2
3
4
3P
5
6
N N
OEPM0028
Fuse switches are used in tertiary and small industrial plants to open/close under load circuits,
allowing protection against short circuits and overloads. The contact tongs are of silver-plated copper
(fuse is not provided).
Code Type Description
Switches + fuses
M2160 (for 8.5x31.5 fuses)
EA 953 8 M2161 switch + one-pole fuse holder (1 module)
EA 954 6 M2161 Na switch + one-pole fuse holder + neutral (2 modules)
EA 955 3 M2162 switch + bipolar fuse holder (2 modules)
EA 956 1 M2163 switch + three-pole fuse holder (3 modules)
EA 957 9 M2163 Na switch + three-pole fuse holder + neutral (4 modules)
M2060 (for 10.3x38 fuses) only up to 20A
EA 948 8 M2061 switch + one-pole fuse holder (1 module)
EA 949 6 M2061 Na switch + one-pole fuse holder + neutral (2 modules)
EA 950 4 M2062 switch + bipolar fuse holder (2 modules)
EA 951 2 M2063 switch + three-pole fuse holder (3 modules)
EA 952 0 M2063 Na switch + three-pole fuse holder + neutral (4 modules)
TEPM0182
5/1
5
ABB SACE
Other modular devices
Command devices
Contents
E 240 - E 270 switch disconnectors ....................................................................................5/2
RS 370 rotary switch disconnectors ...................................................................................5/4
E 220 switches ......................................................................................................................5/6
E 220 pushbuttons and indicator lamps .............................................................................5/8
Contactors and installation relays
ESB series contactors...........................................................................................................5/10
EN series contactors .............................................................................................................5/12
E 259 installation relays ........................................................................................................5/13
Latching relays
E 250 electro-mechanical .....................................................................................................5/14
E 260 electronic ....................................................................................................................5/16
5/2
5
ABB SACE
Command devices
E 240 - E 270 switch disconnectors
Technical details .......................................... pg. 10/64 Overall dimensions ..................................... pg. 11/18
Suitable for under load operations and equipped with sealable control lever in both positions. For
correct operation, it is necessary an upstream protection by devices against short-circuit and overload
(fuses, MCBs).
Code Type Decription
1P - E 241 - E 271 switch disconnectors
EF 931 9 E 241/16 16A rated current (1 module)
EF 935 0 E 241/32 32A rated current (1 module)
EF 939 2 E 241/45 45A rated current (1 module)
EF 950 9 E 271/63 63A rated current (1 module)
EF 943 4 E 271/80 80A rated current (1 module)
EF 944 2 E 271/100 100A rated current (1 module)
EF 973 1 E 271/125 125A rated current (1 module)
2P - E 242 - E 272 switch disconnectors
EF 932 7 E 242/16 16A rated current (2 modules)
EF 936 8 E 242/32 32A rated current (2 modules)
EF 940 0 E 242/45 45A rated current (2 modules)
EF 951 7 E 272/63 63A rated current (2 modules)
EF 954 1 E 272/80 80A rated current (2 modules)
EF 957 4 E 272/100 100A rated current (2 modules)
EF 960 8 E 272/125 125A rated current (2 modules)
Technical characteristics
Rated voltage Un[V] a.c. 230/400
Rated current In[A] 16…125
Rated frequency [Hz] 50/60
Rated short-time
withstand current Icw [A] 20 times In x 1 second
Utilization category AC22 (E 240);
AC23 (E 270, 63…100A)
AC22 (E 270, 125A)
Power consumption See technical details
Modules [No] 1, 2, 3, 4
Standards IEC/EN 60947-3
Approvals E 271/2/4 63A:
VDE, SEV;
E 273 63 A:
VDE, SEV,
DEMKO, FI
TEPM0190
TEPM0191
5/3
5
ABB SACE
Technical details .......................................... pg. 10/64 Overall dimensions ..................................... pg. 11/18
Command devices
E 240 - E 270 switch disconnectors
Code Type Decription
3P - E 243 - E 273 switch disconnectors
EF 933 5 E 243/16 16A rated current (3 modules)
EF 937 6 E 243/32 32A rated current (3 modules)
EF 941 8 E 243/45 45A rated current (3 modules)
EF 952 5 E 273/63 63A rated current (3 modules)
EF 955 8 E 273/80 80A rated current (3 modules)
EF 958 2 E 273/100 100A rated current (3 modules)
EF 961 6 E 273/125 125A rated current (3 modules)
4P - E 244 - E 274 switch disconnectors
EF 934 3 E 244/16 16A rated current (4 modules)
EF 938 4 E 244/32 32A rated current (4 modules)
EF 942 6 E 244/45 45A rated current (4 modules)
EF 953 3 E 274/63 63A rated current (4 modules)
EF 956 6 E 274/80 80A rated current (4 modules)
EF 959 0 E 274/100 100A rated current (4 modules)
EF 962 4 E 274/125 125A rated current (4 modules)
TEPM0193
TEPM0192
5/4
5
ABB SACE
Command devices
RS 370 rotary switch disconnectors
Technical details .......................................... pg. 10/65 Overall dimensions ..................................... pg. 11/18
Technical characteristics
Rated voltage Un[V] a.c. 690
Rated current In[A] 45, 63, 80, 100
Rated frequency [Hz] 50/60
Utilization category AC23
Electric operations [No] 10,000
Mechanic operations [No] 20,000
Power consumption See technical details
Modules [No] 3, 4
Standards IEC /EN 60947-3
For advanced performance, these switches allow under load opening and closing. The range is
accessorizable with auxiliary contacts and delayed rotary operation (replacing the knob). The production
knob also allows the “door lock” function as shown in the picture.
Code Type Description
3P - Rotary switch disconnectors from 45 to 100A, 400V a.c.
EA 120 4 RS 373/45 45A rated current
EA 121 2 RS 373/63 63A rated current
EA 122 0 RS 373/80 80A rated current
EA 123 8 RS 373/100 100A rated current
4P - Rotary switch disconnectors from 45 to 100A, 400V a.c.
EA 124 6 RS 374/45 45A rated current
EA 125 3 RS 374/63 63A rated current
EA 126 1 RS 374/80 80A rated current
EA 127 9 RS 374/100 100A rated current
TEPM0194
TEPM0195
5/5
5
ABB SACE
Command devices
RS 370 rotary switch disconnectors
Technical details .......................................... pg. 10/65 Overalla dimensions ................................... pg. 11/18
O
OFF
I
ON
O
OFF
I
ON
Door lock handle
OEPM0130
RS 373
3P
1
2
3
4
5
6
1
2
3
4
5
6
7
8
RS 374
4P
RS 370/11
1 NC + 1NO
13
14
21
22
(N)
(N)
OEPM0040
Auxiliary elements/accessories
Code Type Description
Fourth pole
EA 128 7 RS 370/4P for RS 373 from 45A to 100A
Auxiliary contact blocks
EA 129 5 RS 370/11 1NC+1NO
Short handle for delayed operation
EA 132 9 RS 370/SH short handle without door-lock function
Terminal covers
EA 134 5 RS 370/3S terminal covers for RS 373
EA 133 7 RS 370/1S terminal covers for the fourth pole
TEPM0196
TEPM0197
TEPM0199
TEPM0200
5/6
5
ABB SACE
Command devices
E 220 switches
Technical details .......................................... pg. 10/65 Overall dimensions ..................................... pg. 11/18
Technical characteristics
Rated voltage Un[V] a.c. 400
Rated current In[A] 16, 25, 32
Rated frequency [Hz] 50/60
Insulation voltage [kV] 3
Power consumption See technical details
Modules [No] 1
Standards IEC/EN 60947-3
Approvals VDE, DEMKO, SEMKO,
NEMKO, FI, OVE, SEV, CEBEC
Suitable for under load operations and equipped with sealable control lever in both positions. All
devices are manufactured in a single module through simple, quick and safety procedures. For
correct operation, they need an upstream protection by devices against short-circuit and overload
(fuses, MCBs).
Code Type Description
Rated current 16A - 230/400V a.c.
EF 901 2 E 221-10 one-pole switch
EF 909 5 E 221-10x lighted one-pole switch
EF 903 8 E 221-20 bipolar switch
EF 910 3 E 221-20x lighted bipolar switch
EF 905 3 E 221-30 three-pole switch
EF 907 9 E 221-40 four-pole switch
EA 151 9 E 221-11 bipolar switch 1NO+1NC (1 module)
EA 152 7 E 221-22 four-pole switch 2NO+2NC (1 module)
EA 153 5 E 221-31 four-pole switch 3NO+1NC (1 module)
EA 150 1 E 221-30x lighted three-pole switch (1 module)
EF 911 1 E 221-6 one-polar switch
EF 912 9 E 221-6/2 bipolar switch
EF 913 7 E 221-4 one-polar switch
EF 914 5 E 221-4/2 bipolar switch
1
2
NL
3
APPLIANCE
1
2
NL
3
APPLIANCE
1
2
NL
3
APPLIANCE
green
red
Wiringdiagram B
Wiringdiagram A E221-6 switch
The E 220 series lighted
switches allow double wiring.
Wiring diagram A
Upstream connection of the
switch: in this case the indica-
tor switching-on signals voltage
and serves as lamp.
TEPM0201
5/7
5
ABB SACE
Command devices
E 220 switches
Technical details .......................................... pg. 10/65 Overall dimensions ..................................... pg. 11/18
1
2
NL
3
APPLIANCE
green
red
III
0
E221-4 switch
OEPM0032
Wiring diagram B
Downstream connection of the
switch: in this case the indica-
tor switching-on signals switch-
controlled load is powered.
Code Type Description
25A rated current - 230/400V a.c.
EF 916 0 E 222-10x one-pole switch
EF 917 8 E 222-20x lighted bipolar switch
EA 154 3 E 222-10 one-pole switch 1NO (1 module)
EA 155 0 E 222-20 bipolar switch 2NO (1 module)
EA 156 8 E 222-30 three-pole switch 3NO (1 module)
EA 157 6 E 222-40 four-pole switch 4NO (1 module)
EA 159 2 E 222-11 bipolar switch 1NO + 1NC
EA 158 4 E 222-30x ligthed three-pole switch 3NO
EF 918 6 E 222-6 one-pole switch
EF 919 4 E 222-4 one-pole switch
32A rated current - 230/400V a.c.
EF 902 0 E 223-10 one-pole switch
EF 904 6 E 223-20 bipolar switch
EF 906 1 E 223-30 three-pole switch
EF 908 7 E 223-40 quadripole switch
Terminal position
OEPM0031
Lighted switch
1
2
1 NO
3 1
2
2 NO
3 7
8
Switch
1
2
One-pole
3 1
2
Bipolar
3 7
8
5
Switch
1
2
One-pole
3 1
2
Bipolar
3 7
8
5
2 4
6 8
5 7
1 3
Switch
2 NO
1
2
3
4
1
2
1 NO 3 NO
1
2
3
4
5
6
4 NO
1
2
3
4
5
6
7
8
TEPM0203 TEPM0202
5/8
5
ABB SACE
Command devices
E 220 pushbuttons and indicator lamps
Overall dimensions ...................................... pg. 11/19
Technical characteristics
Rated voltage Un[V] a.c. 250
Rated current In[A] 16
Rated frequency [Hz] 50/60
Power consumption [W] 0.96 ... 1.50
Modules [No] 1
Standards IEC/EN 60669-1
IEC/EN 60947-5-1
The pushbuttons are used for remotely control in every kind of electric installation (public, tertiary,
industrial).
The indicator lamps signal any event in every kind of electric installation (public, tertiary, industrial).
Code Type Description
Not lighted pushbuttons
EF 920 2 E 225-11B gray not lighted pushbutton with contacts 1NO+1NC
EA 715 1 E 225-11C red not lighted pushbutton with contacts 1NO+1NC
EA 716 9 E 225-11D green not lighted pushbutton with contacts 1NO+1NC
EA 717 7 E 225-11E yellow not lighted pushbutton with contacts 1NO+1NC
EA 160 0 E 225-11F black not lighted pushbutton 1NO+1NC
EA 161 8 E 225-11G blue not lighted pushbutton 1NO+1NC
EA 162 6 E 225-11Z not lighted pushbutton without hood 1NO+1NC
Lighted pushbuttons
EA 718 5 E 227-11 B transparent lighted pushbutton with contact 1NO+1NC
EF 921 0 E 227-11C red lighted pushbutton with contact 1NO+1NC
EF 922 8 E 227-11 D green lighted pushbutton with contact 1NO+1NC
EA 719 3 E 227-11 E yellow lighted pushbutton with contact 1NO+1NC
EA 163 4 E 227-11 G blue lighted pushbutton 1NO+1NC
EA 164 4 E 227-11 Z lighted pushbutton without button 1NO+1NC
Indicator lamps
EA 720 1 E 229-B transparent indicator lamp with 220V a.c. bulb
EF 923 6 E 229-C red indicator lamp with 220V a.c. bulb
EA 721 9 E 229-D green indicator lamp with 220V a.c. bulb
EA 722 7 E 229-E yellow indicator lamp with 220V a.c. bulb
EA 165 9 E 229-G blue indicator lamp
EA 166 7 E 229-Z indicator lamp without hood
TEPM0206 TEPM0205 TEPM0204
5/9
5
ABB SACE
Command devices
E 220 pushbuttons and indicator lamps
Overall dimensions .................................... pag. 11/19
Code Type Description
Spare buttons for E 227 indicator lamps
EF 926 9 E 220-B transparent button
EF 924 4 E 220-C red button
EF 925 1 E 220-D green button
EA 723 5 E 220-E yellow button
EA 172 5 E 220-G blue button
Spare hoods for E 229 indicator lamps
EF 929 3 E 220-B3 trasparent hood
EF 927 7 E 220-C3 red hood
EF 928 5 E 220-D3 green hood
EA 724 3 E 220-E3 yellow hood
Hoods for not lighted pushbuttons
EA 167 5 E 220-B1 gray hood for not lighted pushbutton
EA 168 3 E 220-C1 red hood for not lighted pushbutton
EA 169 1 E 220-D1 green hood for not lighted pushbutton
EA 170 9 E 220-E1 yellow hood for not lighted pushbutton
EA 171 7 E 220-G1 blue hood for not lighted pushbutton
Spare bulbs
EA 173 3 E 10/12 12V a.c. bulb for pushbuttons and indicator lamps
EA 174 1 E 10/24 24V a.c. bulb for pushbuttons and indicator lamps
EA 175 8 E 10/48 48V a.c. bulb for pushbuttons and indicator lamps
EA 176 6 E 10/60 60V a.c. bulb for pushbuttons and indicator lamps
EA 177 4 E 10/110 110V a.c. bulb for pushbuttons and indicator lamps
EF 915 2 E 10/220 220V - 0.5W bulb for pushbuttons and indicator lamps
5
6
7
8
13
24
1
2
7
8
Max. 2W
E227 lighted pushbutton
1NO
1
2
Max. 2W
Indicator
lamp
E225 pushbutton
1NO + 1NC
1
2
7
8
OEPM0033
TEPM0208 TEPM0207
5/10
5
ABB SACE
Command devices
Contactors and installation relays
Technical details .......................................... pg. 10/66 Overall dimensions ..................................... pg. 11/19
Technical characteristics
ESB 20 ESB 24
Rated
voltage Un[V] a.c. 230 a.c. 400
Rated current In in AC1 [A] 20 24
Rated power in AC3 [kW]
230V 1.3 2.2
400V - 4
Rated frequency [Hz] 50/60 40/450
Control circuit
a.c. a.c./d.c.
voltage [V]
12, 24, 48, 110, 230 12, 24, 230
Electric operations [No] 1 million 1 million
Mechanic operations
in AC1 [No] 150,000 130,000
in AC3 [No] 150,000 500,000
Power consumption [W]
1 per pole 1, 2 per pole
Modules [No] 1 2
Standards IEC 60947-4-1 IEC 60947-4-1
IEC 61095 IEC 61095
For loads to be automatically controlled through high number of operations; i.e, building automation,
controlling of small pumps, ventilations, heating systems, lighting systems, and so on.
ESB series contactors
The series consists of various models differing in the number of contacts, rated current and control
circuit voltage.
Code Type Description
ESB 20 (20A) contactors
EL 869 4 ESB 20-11/12 control circuit voltage 12V a.c. - 1NO+1NC contacts
EL 870 2 ESB 20-11/24 control circuit voltage 24V a.c. - 1NO+1NC contacts
EL 871 0 ESB 20-11/48 control circuit voltage 48V a.c. - 1NO+1NC contacts
EL 872 8 ESB 20-11/110 control circuit voltage 110V a.c. - 1NO+1NC contacts
EL 873 6 ESB 20-11/230 control circuit voltage 230V a.c. - 1NO+1NC contacts
EL 874 4 ESB 20-02/12 control circuit voltage 12V a.c. - 2NC contacts
EL 875 1 ESB 20-02/24 control circuit voltage 24V a.c. - 2NC contacts
EL 876 9 ESB 20-02/48 control circuit voltage 48V a.c. - 2NC contacts
EL 877 7 ESB 20-02/110 control circuit voltage 110V a.c. - 2NC contacts
EL 878 5 ESB 20-02/230 control circuit voltage 230V a.c. - 2NC contacts
EL 879 3 ESB 20-20/12 control circuit voltage 12V a.c. - 2NO contacts
EL 880 1 ESB 20-20/24 control circuit voltage 24V a.c. - 2NO contacts
EL 881 9 ESB 20-20/48 control circuit voltage 48V a.c. - 2NO contacts
EL 882 7 ESB 20-20/110 control circuit voltage 110V a.c. - 2NO contacts
EL 883 5 ESB 20-20/230 control circuit voltage 230V a.c. - 2NO contacts
ESB 24 (24A) contactors
EL 884 3 ESB 24-40/12 control circuit voltage 12V a.c./d.c. - 4NO contacts
EL 885 0 ESB 24-40/24 control circuit voltage 24V a.c./d.c. - 4NO contacts
EL 888 4 ESB 24-40/230 control circuit voltage 230V a.c./d.c. - 4NO contacts
TEPM0211
TEPM0210
5/11
5
ABB SACE
Command devices
Contactors and installation relays
Technical details .......................................... pg. 10/66 Overall dimensions ..................................... pg. 11/19
ESB 20
1
2
2NO
3
4
A1
A2
R1
R2
R3
R4
A1
A2
2NC
R3
R4
A1
A2
1NO + 1NC
1
2
1
2
3
4
A1
A2
5
6
7
8
(13)
(14)
ESB 24
ESB 40
ESB 63
OEPM0034
Technical characteristics
ESB 40 ESB 63
Rated
voltage Un[V] a.c. 400 a.c.400
Rated current In in AC1 [A] 40 63
Rated power in AC3 [kW]
230V 5.5 8.5
400V 11 15
Rated frequency [Hz] 40/450 40/450
Control circuit
a.c./d.c. a.c./d.c.
voltage [V] 24, 230 24, 230
Electric operations [No] 1 million 1 million
Mechanic operations
in AC1 [No] 150,000 150,000
in AC3 [No] 170,000 240,000
Power consumption [W]
3 per pole 6 per pole
Modules [No] 3 3
Standards IEC 60947-4-1 IEC 60947-4-1
IEC 61095 IEC 61095
Technical characteristics of the auxiliary contact
Thermal current Ith [A] 6
Operating rated
current Ie AC15 a
< 240V a.c. [A] 4
< 380/415V a.c. [A] 3
< 500V a.c. [A] 2
Minimum load 12V 300mA
Code Type Description
ESB 40 (40A) contactors
EL 890 0 ESB 40-40/24 control circuit voltage 24V a.c./d.c. - 4NO contacts
EL 893 4 ESB 40-40/230 control circuit voltage 230V a.c./d.c. - 4NO contacts
ESB 63 (63A) contactors
EL 895 9 ESB 63-40/24 control circuit voltage 24V a.c./d.c. - 4NO contacts
EL 898 3 ESB 63-40/230 control circuit voltage 230V a.c./d.c. - 4NO contacts
Auxiliary elements/accessories
Available for ESB 24/40/63
Code Type Description
Auxiliary contact
EL 900 7 EH 04-20 2NO contacts
EL 901 5 EH 04-11 1NO+1NC contacts
Other accessories
EL 902 3 ESB-DIS spacer
EL 903 1 ESB-PLK 24 terminal covers for ESB 24
EL 904 9 ESB-PLK 40/63 terminal covers for ESB 40/63
TEPM0213 TEPM0212
5/12
5
ABB SACE
Command devices
Contactors and installation relays
Technical details .......................................... pg. 10/66 Overall dimensions ..................................... pg. 11/19
Technical characteristics
EN 20 EN 24 EN 40
Rated voltage Un[V]
a.c. 230/400 a.c. 230/400 a.c. 230/400
Rated current In
in AC1 [A] 20 24 40
Rated output in AC3
230 [kW] 1.3 2.2 5.5
400 [kW] - 4 11
Rated frequency [Hz] 50/60 40/450 40/450
Control circuit
voltage [V] a.c. 230
Power consumption [W] 1 1.2 3
per pole per pole per pole
Modules [No] 1 2 3
Standards
IEC/EN 61095 IEC/EN 61095 IEC/EN 61095
Approvals UTE
EN series contactors
Equipped with front switch to select operation mode (override): permanent OFF, automatic operation,
manual ON.
Code Type Description
EN 20 (20A) contactors
EL 820 7 EN 20-20/230 control circuit voltage 230V a.c. - 2NO contacts
EN 24 (24A) contactors
EL 821 5 EN 24-30/230 control circuit voltage 230V a.c. - 3NO contacts
EL 822 3 EN 24-40/230 control circuit voltage 230V a.c. - 4NO contacts
EN 40 (40A) contactors
EL 823 1 EN 40-20/230 control circuit voltage 230V a.c. - 2NO contacts
EL 824 9 EN 40-30/230 control circuit voltage 230V a.c. - 3NO contacts
EL 825 6 EN 40-40/230 control circuit voltage 230V a.c. - 4NO contacts
EN 20-20
EN 40-20
1
2
3
4
A1
A2
1
2
3
4
A1
A2
5
6
7
8
(13)
(14)
EN 24-40
EN 40-40
EN 24-30
EN 40-30
1
2
5
6
A1
A2
3
4
OEPM0035
TEPM0216
TEPM0217
TEPM0218
5/13
5
ABB SACE
Command devices
Contactors and installation relays
Technical details .......................................... pg. 10/66 Overall dimensions ..................................... pg. 11/20 Application sheet ........................................... pg. 12/4
E 259 installation relays
For applications in public/tertiary sectors (i.e, control of lamps), they are equipped with manual
command (temporary) and contact position indicator (visual on the product).
Code Type Description
E 259 contactors
EA 588 2 E 259 R 10-8V control circuit voltage 8V a.c. - 1NO contacts
EA 589 0 E 259 R 10-12V control circuit voltage 12V a.c. - 1NO contacts
EA 590 8 E 259 R 10-24V control circuit voltage 24V a.c. - 1NO contacts
EA 591 6 E 259 R 10-230V control circuit voltage 230V a.c. - 1NO contacts
EA 592 4 E 259 R 11-8V control circuit voltage 8V a.c. - 1NO+1NC contacts
EA 593 2 E 259 R 11-12V control circuit voltage 12V a.c. - 1NO+1NC contacts
EA 594 0 E 259 R 11-24V control circuit voltage 24V a.c. - 1NO+1NC contacts
EA 595 7 E 259 R 11-230V control circuit voltage 230V a.c. - 1NO+1NC contacts
EA 596 5 E 259 R 20-8V control circuit voltage 8V a.c. - 2NO contacts
EA 597 3 E 259 R 20-12V control circuit voltage 12V a.c. - 2NO contacts
EA 598 1 E 259 R 20-24V control circuit voltage 24V a.c. - 2NO contacts
EA 599 9 E 259 R 20-230V control circuit voltage 230V a.c. - 2NO contacts
Technical characteristics
Rated voltage Un[V] a.c. 400/250
Rated current In[A] 10/16
Rated frequency [Hz] 50/60
Contact capacity [W] 2300 (incandescent lamps)
1300 (power factor uncorrected
fluorescent lamps cosϕ=0.6)
500 (power factor corrected lamps
in parallel)
Control circuit
voltage [V] 8, 12, 24, 230
Electric operations [No] 100,000
Mechanic operations [No] 1,000,000
Power consumption [W] 4 (1 and 2 contacts);
6 (4 contacts)
Modules [No] 1
Standards IEC/EN 61095
Approvals DEMKO, SEV
More technical characteristics
Contact material sintered silver + cadmium oxide
Distance across contacts [mm] 3
Duration of movement [ms] 3
Frequency of operation 103/h
Minimum contact capacity 6V a.c. / 50mA
A1
A2
1
2
3
4
A1
A2
3
4
1
2
A1
A2
1
2
Terminalnumbering
E259 R10- E259 R11- E259 R20-
1 3
2 4
A1
A2
OEPM0036
TEPM0219
5/14
5
ABB SACE
Command devices
Latching relays
Technical details .......................................... pg. 10/70 Overall dimensions ..................................... pg. 11/20 Application sheet ........................................... pg. 12/5
E 250 electro-mechanical
Electro-mechanical latching relays allow contact switching for each impulse sent to coil using normally
open pushbuttons. Ideal for lamp controlling from different positions, they are available in various
versions according to pick-up voltage and to contact positions. They also allow manual operation on
the product and contact position indicator (visual on the product).
Code Type Description
E 250 latching relays with 1 and 2 contacts
EA 380 4 E 251-8V relay with 1 contact - 8V a.c.
EA 584 1 E 251-12V relay with 1 contact - 12V a.c.
EA 381 2 E 251-24V relay with 1 contact - 24V a.c.
EA 382 0 E 251-230V relay with 1 contact - 230V a.c.
EA 383 8 E 252-8V relay with 2 contacts - 8V a.c.
EA 585 8 E 252-12V relay with 2 contacts - 12V a.c.
EA 384 6 E 252-24V relay with 2 contacts - 24V a.c.
EA 385 3 E 252-230V relay with 2 contacts- 230V a.c.
EA 389 5 E 256-8V relay with 1 NC + 1 NO contact - 8V a.c.
EA 587 4 E 256-12V relay with 1 NC + 1 NO contact - 12V a.c.
EA 390 3 E 256-24V relay with 1 NC + 1 NO contact - 24V a.c.
EA 391 1 E 256-230V relay with 1 NC + 1 NO contact - 230V a.c.
EA 580 9 E 255-8V relay with 2 sequential contacts - 8V a.c.
EA 581 7 E 255-12V relay with 2 sequential contacts - 12V a.c.
EA 582 5 E 255-24V relay with 2 sequential contacts - 24V a.c.
EA 583 3 E 255-230V relay with 2 sequential contacts - 230V a.c.
E 250 latching relays with 4 contacts
EA 386 1 E 254-8V relay with 4 NC contacts - 8V a.c.
EA 586 6 E 254-12V relay with 4 NC contacts - 12V a.c.
EA 387 9 E 254-24V relay with 4 NC contacts - 24V a.c.
EA 388 7 E 254-230V relay with 4 NC contacts - 230V a.c.
Technical characteristics
Rated voltage Un[V] a.c. 400/250
Rated current In[A] 10/16
Rated frequency [Hz] 50/60
Contact capacity [W] 2300 (incandescent lamps)
1300 (power factor uncorrected
fluorescent lamps cosϕ=0.6)
500 (power factor corrected
fluorescent lamps in parallel)
Minimum value
of control impulse [mA] 50
Circuit
voltage [V] 8, 12, 24, 230
Electric operations [No] 100,000
Mechanic operations [No] 1 million
Power consumption [W] 2 (1 and 2 contacts);
6 (4 contacts)
Modules [No] 1, 2
Standards IEC/EN 60669-2
Approvals DEMKO, NEMKO, SEMKO, SEV, FI
TEPM0220
TEPM0221
5/15
5
ABB SACE
Command devices
Latching relays
Technical details .......................................... pg. 10/70 Overall dimensions ..................................... pg. 11/20 Application sheet ........................................... pg. 12/5
E 251-
10
A
0
A
2
CONTACT
SWITCHING
A
E 252-
1
2
3
4
0
A+B
0
A+B
ABAB
CONTACT
SWITCHING
E 256-
3 1
42
B
A
B
A
AB
CONTACT
SWITCHING
E 255-
1 3 0
B
A+B
A
24
AB
SEQUENCE OF
CONTACT SWITCHING
E 254-
10
A+B+C+D
0
A+B+C+D
3 5 7
2468
ABCD
CONTACT
SWITCHING
OEPM0037
E 251-230 E 252-230
L1
N
L1
N
Examples of connection
Latching relay control with more buttons in parallel;
current of light bulbs - max 5mA (e.g. neon signalling
lamps)
Latching relay control with more buttons in parallel;
back signalling of “ON” state on the pushbuttons
OEPM0038
5/16
5
ABB SACE
Command devices
Latching relays
Technical details .......................................... pg. 10/70 Overall dimensions ..................................... pg. 11/20 Application sheet ........................................... pg. 12/6
E 260 electronic
The electronic version of relays guarantees maximum reliability, life and noiseless operation. The E
260 C version also allows centralized reset function (ON and OFF).
Code Type Description
Electronic latching relays
EA 610 4 E 261-24V relay with 1 contact - 24V a.c./d.c.
EA 611 2 E 261-230V relay with 1 contact - 230V a.c.
EA 613 8 E 262-24V relay with 2 contacts - 24V a.c./d.c.
EA 614 6 E 262-230V relay with 2 contacts - 230V a.c.
EA 616 1 E 266-24V relay with 1 NC + NO contact - 24V a.c./d.c.
EA 617 9 E 266-230V relay with 1 NC + NO contact - 230V a.c.
Technical characteristics
Rated voltage Un[V] 250 a.c. +10% –20%
Rated current In[A] 10
Rated frequency [Hz] 50/60
Contact capacity [W] 1000 (incandescent lamps)
700 (power factor uncorrected
fluorescent lamps cosϕ=0,6; power
factor corrected
fluorescent lamps not allowed)
Control circuit
voltage [V] 24 a.c./d.c., 230 a.c.
Control current
E 260 24V a.c./d.c. [mA] 140 (80 after 10 sec ± 20%)
230V a.c. [mA] 115 (8 after 10 sec ± 20%)
E 260 C 24V a.c./d.c. [mA] 17/26 ± 20%
230V a.c. [mA] 8 (3 after 10 sec ± 20%)
Electric operations [No] 100,000
Mechanic operations [No] 2 millions
Power consumption [W] 0.50 (1 contact) ; 1 (2 contacts)
Modules [No] 1
Standards IEC/EN 60669-2
Approvals DEMKO, NEMKO, SEMKO, SEV
TEPM0222
5/17
5
ABB SACE
OEPM0039
TEPM0223
Command devices
Latching relays
Code Type Description
Latching relays with centralized ON-OFF control
EA 618 7 E 261 C -12V relay with 1 contact - 12V a.c./d.c.
EA 619 5 E 261 C -24V relay with 1 contact - 24V a.c./d.c.
EA 620 3 E 261 C -230V relay with 1 contact - 230V a.c.
EA 621 1 E 262 C -12V relay with 2 contacts - 12V a.c./d.c.
EA 622 9 E 262 C -24V relay with 2 contacts - 24V a.c./d.c.
EA 623 7 E 262 C -230V relay with 2 contacts - 230V a.c.
EA 624 5 E 266 C -12V relay with 1 NC + NO contact - 12V a.c./d.c.
EA 625 2 E 266 C -24V relay with 1 NC + NO contact - 24V a.c./d.c.
EA 626 0 E 266 C -230V relay with 1 NC + NO contact - 230V a.c.
Technical details .......................................... pg. 10/70 Overall dimensions ..................................... pg. 11/20 Application sheet ........................................... pg. 12/6
6/1
6
ABB SACE
Other modular devices
Load management devices
Contents
E 234 time delay relays .........................................................................................................6/2
Time switches
ETS electro-mechanical ..........................................................................................................6/3
DTS digital ..............................................................................................................................6/4
E 232 electro-mechanical and E 232 electronic staircase timers ....................................6/5
SWD staircase switch-off warning devices ........................................................................6/6
TWS-1 twilight switches .......................................................................................................6/7
RAL overload alarms ............................................................................................................6/8
LSS1/2 load shedding switches ..........................................................................................6/9
SQZ3 phase and sequence relays .....................................................................................6/10
LE power failure signalling lamps .....................................................................................6/11
E 228 WM alarm indicators ................................................................................................6/12
Min./max. current/voltage ammetric and volmetric relays .............................................6/13
STD universal dimmers ......................................................................................................6/14
ABB SACE
6/2
6
ABB SACE
Load management devices
E 234 time delay relays
Technical details .......................................... pg. 10/74 Overall dimensions ..................................... pg. 11/22 Application sheet .................................. pg. 12/7-12/8
Used when, according to the time, the automatic load control is required for lighting, heating, ventilation
systems, access barriers, gates, machine tools, etc.
Code Type Description
Time delay relays
EA 635 1 E 234-AV delayed at pick-up
EA 636 9 E 234-RV delayed at drop-out
EA 642 7 E 234-TI2 impulse generation
EA 638 5 E 234-AW on de-energization
EA 639 3 E 234-EW on energization
EA 634 4 E 234-MFR multipurpose
16 18
15
B1 A2A1
16
1815
A2
A1
Wiring diagram
15-16 = contact NC
15-18 = contact NO
A1/A2 = command input 12…230V d.c.+/a.c.
A2 = in a.c. connect the neutral
= in d.c. connect the “–”
B1/A2 = rated voltage
12…230V a.c./d.c.
The switching contact is free; the insulation rated voltage
for power supply and command input is of 250V.
OEPM0045
Technical characteristics
Rated voltage Un[V] a.c./d.c. 12…230
Rated current In[A] 10
Rated frequency [Hz] 50/60
Contact capacity [W] 1000 (incandescent lamps)
700 (power factor uncorrected
fluorescent lamps
cosϕ=0,6; power factor corrected
fluorescent lamps not allowed)
Control circuit
voltage [V] d.c./a.c. 12…230
Load management current [mA] 6-25
Electric operations [no] 1 million
Mechanic operations [no] 10 million
Times from 0.1s to 40h
Power consumption [W] 2.5
Modules [No] 1
TEPM00235
6/3
6
ABB SACE
Overall dimensions ...................................... pg. 11/22 Application sheet .......................................... pg. 12/9
Load management devices
Time switches
ETS electro-mechanical
They control circuit opening and closing according to scheduled planning. The time switches can be
set on permanent ON-OFF, available both daily and weekly programs. In addition to switchboard and
consumer unit mounting, the appropriate kit also allows wall mounting.
Code Type Description
Electro-mechanical time switches
EA 502 3 ETS-1M daily program without standby battery - 1 module
EA 503 1 ETS-1RM daily program with standby battery (200h) - 1 module
EA 511 4 ETS 1 daily program without standby battery - 3 modules
EA 512 2 ETS 1/R daily program with standby battery (200h) - 3 modules
EA 513 0 ETS 7/R weekly program with standby battery (200h) - 3 modules
ETS 1, ETS 1/R, ETS 7/R wall-mounting accessory
EA 510 6 ETS-KIT wall-mounting kit for ETS 3 modules
Technical characteristics
Rated voltage Un[V] a.c. 230 +/-10%
Rated contact capacity In[A] 16 cosϕ= 1
4 cosϕ= 0.6
Rated frequency [Hz] 50/60
Min. spread between 15 min (daily program)
two commands 2 hours (weekly program)
Max. number of [No] 96 (daily program)
command per cycle 84 (weekly program)
Operating accuracy 1s/24h
Life cycle [No] 10 years or 50,000 insertions
Operating temperature [°C] -10…+45
Power consumption [W] 0.5
Modules [No] 1-3
Standards IEC 60669-1, EN 60730-1
More technical characteristics
Free switching contact - ohmic load (cosϕ= 1)
max. capacity - AC 16A 250V; DC 2 A 48V
- inductive load (cosϕ=0.6)
- 4A 250V
- 900W 250V incandescent lamps
- 300W 250V a.c.power factor
corrected fluorescent lamps
- 400W 250V asyncronous motor
minimum capacity AC opening -10V - 2A
AC closing - 10V - 100mA
DC opening - 12V - 2A
DC closing - 12V - 100mA
Time base quartz
Operating temperature -10°C...+55°C
Storage temperature
- with standby battery - 10°C...+55°C
- without standby battery - 20°C...+70°C
Tunnel terminals cable section from 1 to 4 mm2
246 1012246 10
Manual control
- permanent OFF
- programmed operation
- permanent ON
12
0
1
230V~
OEPM0046
24
13
1
5
4
7
8
9
10
3
2
ETS-1M
ETS-1RM
1. Programming disk
2. Electric connections
3. Permanent ON/OFF switching
4. Time adjustment indicator
5. Clockwise rotation direction of
programming disk 24
13
7
8
9
10
2
1
4
3
L
N
ETS 1, ETS 1/R, ETS 7/R
Functions Wiring diagram
OEPM0064
TEPM0236
TEPM0254
6/4
6
ABB SACE
Load management devices
Time switches
Overall dimensions ...................................... pg. 11/22 Application sheet ........................................ pg. 12/10
DTS digital
The range includes single/multichannel daily/weekly program switches. These are functionally more
sophisticated and control several loads or independent groups of loads requiring different time controls
with an unique time reference. The EEPROM memory of DTS series devices eliminates the risk of
erasing configured program, regardless the duration of any voltage failure.
Code Type Description
Digital time switches
EA 554 4 DTS 1/1 daily program timer switch with standby battery (3 years), 1 channel
EA 555 1 DTS 7/1 daily/weekly program time switch with standby battery
(3 years), 1 channel
EA 556 9 DTS 7/2 daily/weekly program time switch with standby battery
(3 years), 2 channels
EA 557 7 DTS 7/2 I daily/weekly program time switch with standby battery
(3 years), 2 channels + pulse output
EA 558 5 DTS 7/3 daily/weekly program time switch with standby battery
(150h), 3 channels
23465798 10 1211
246108153
246108
OEPM0047
DTS 1/1, DTS 7/1
DTS 7/2, DTS 7/2 I
DTS 7/3
Technical characteristics
Rated voltage Un[V] a.c. 230
Rated contact capacity In[A] 16 cosϕ= 1
2.5 cosϕ= 0.6
Rated frequency [Hz] 50/60
Operating accuracy + 2.5s/24h
Max. switching [Fr°] 12 (daily program - 1 channel)
28 (weekly program-
1 channel)
42 (weekly program -
2 channels)
322 (daily/weekly program -
3 channels)
Power consumption [W] 5
Modules [No] 2, 6 (3 channels)
Standards IEC/EN 60730-1
TEPM0239
TEPM0240
6/5
6
ABB SACE
Load management devices
E 232 electro-mechanical and E 232 E
electronic staircase timers
Overall dimensions ...................................... pg. 11/23 Application sheet ........................................ pg. 12/11
They allow delayed management for passage areas (corridors, staircases halls, etc). The three timer
positions are: permanent ON, delayed and permanent OFF. Timer switch-off ranges from 40s to 5
minutes for electro-mechanical timers and from 0s to 10 minutes for electronic timers.
Code Type Description
EA 519 7 E 232-230 electro-mechanical staircase timer of 230V
EA 520 5 E 232 E-230 electronic staircase timer of 230V
EA 523 9 E 232 E 8-230 electro-mechanical staircase timer from 8…230V
Technical characteristics
Rated voltage Un[V] a.c. 230V ± 10%
Rated contact capacity In[A] 16 (maximum 2,000 W)
Rated frequency [Hz] 45/60
Minimum pick-up
current [mA] 150
Electric operations
- for electro-mechanical [No] 50,000 cosϕ= 1
[No] 20,000 cosϕ= 0.6
- for electronic [No] 100,000 cosϕ= 1
[No] 20,000 cosϕ= 0.6
Mechanic operations
- for electro-mechanical [No] 50,000 cosϕ= 1
- for electronic [No] 100,000 cosϕ= 1
Time delay
- for electro-mechanical from 45 s to 5 min,
can be reset after 30 s
- for electronic from 0 s to 12 min,
can be reset after 30 s
Connection with 3 or 4 cables
Power consumption
- for electro-mechanical [W] 4.5
- for electronic [W] 3.50
Modules [No] 1
OEPM0048
TEPM0242
TEPM0241
A1 3
A2 4
6/6
6
ABB SACE
Load management devices
SWD staircase switch-off warning devices
Overall dimensions ...................................... pg. 11/23
Used in combination with staircase timers for signalling imminent switch-off. The warning occurs
through decreasing 50% of lighting level of controlled lamps with adjustable time. The universal
connection with 2 cables is suitable for every kind of staircase timer.
Code Type Description
EG 405 3 SWD switch-off warning device
TEPM0243
Technical characteristics
Rated voltage Un[V] a.c. 230
Rated capacity [W] 1,300 (ohmic)
Rated frequency [Hz] 50/60
Power consumption [W] 3
Modules [No] 1
OEPM0049
6/7
6
ABB SACE
Load management devices
TWS-1 twilight switches
Overall dimensions ...................................... pg. 11/23 Application sheet .............................. pg. 12/12-12/13
They switch-on and/or switch-off operating illuminating devices at preset level of ambient lighting.
Used in combination with sensor detecting if lighting level is higher or lower than preset threshold.
Code Type Description
EG 573 8 TWS-1 twilight switch with sensor
EG 574 6 LS-1 sensor (as spare part)
TEPM0244
Technical characteristics
Rated voltage Un[V] a.c. 230
Rated contact capacity In[A] 16 (ohmic)
25 (inductive load cosϕ=0.6)
[W] 1000 (power factor corrected
fluorescent lamps)
Rated frequency [Hz] 50/60
Adjustment range [Lux] 2…300
Hysteresis [%] 1.3 (of preset value)
Delay [s]
switch-on + 50
switch-off + 50
Max. distance between
twilight switch and sensor [m] 100
Twilight switch
operating time [°C] -20…+55
Sensor
operating time [°C] -30…+70
Power consumption [W] 5
Modules [No] 2
Standards IEC 60669-1, EN 61000-3-2
More technical characteristics
TWS-1 twilight switches are equipped with delay function both at
switch-on and switch-off to avoid unexpected interventions due to
instantaneous variations of lighting (lightning, motorvehicles in
motion, etc.).
The control circuit is separated from the power supply circuit.
The sensor is very low voltage power supplied and uncoupled from
the network.
OEPM0050
1 2 3 5
230V~ LOAD
4
67
NA NCC
SENSOR
OEPM0050
TWS-1 LED
ON
50
sec. TWS-1 LED
OFF
50
sec.
4
3
5
4
3
5
4
3
5
4
3
5
Operating principle
6/8
6
ABB SACE
Load management devices
RAL overload alarms
Overall dimensions ...................................... pg. 11/24 Aplication sheet .......................................... pg. 12/14
Technical characteristics
Rated voltage Un[V] a.c. 230
Rated current In[A] 18.3 (for 4kW);
27.5 (for 6kW)
Rated contact capacity In[A] 12 cosϕ=1
4 cosϕ=0.8
Rated frequency [Hz] 50
Regulating thresholds [A] 0 ...18.3 / 0…27.5
Power consumption [W] 10
Modules [No] 2
Main circuit-breaker downstream installed, it constantly compares preset power consumption value
to effective system power consumption, which is related to the number of devices operating
simultaneously. An acoustic alarm alerts that it is necessary to switch-off some appliances in order to
avoid the tripping of the main circuit-breaker. The device calibration is 3kW.
Code Type Description
Overload alarms
EG 411 1 RAL 3 adjustable range 0/4kW
EG 412 9 RAL 6 adjustable range 0/6kW
TEPM0245
More technical characteristics
This device is equipped with an acoustic alarm which signals an
exceeding power consumption, allowing the user to disinsert loads
before the energy-limiting circuit-breaker trips.
An appropriate relay output contact allows the choice between
the following functions:
a) remote signalling (acoustic or lighting)
b) opening a specific divisional circuit-breaker and then disabling
a particular not primary electric appliance.
If appropriately used, the function b) causes the automatic switch-
off of one or more appliances in order to keep the power
consumption within the preset limits, avoiding the unexpected
tripping of ENEL current-limiting device installed outside the housing
(i.e. in the basement). Reset manually.
567
8
NU
3kW
MAX
L
230 V~
N.B.: overload
RAL alarm
cannot be
connected to a
contactor.
Main circuit-
breaker
Undervoltage
release (230V
a.c.) in case of
circuit-breaker
tripping
Dedicated
socket
Lights
RAL
58
13
L
N
230Va.c.
6
2
OEPM0052
OEPM0051
Acoustic alarm
Load release
6/9
6
ABB SACE
Load management devices
LSS1/2 load shedding switches
Technical details .......................................... pg. 10/76 Overall dimensions ..................................... pg. 11/24 Application sheet ......................................... pg. 12/15
Technical characteristics
Rated voltage Un[V] a.c. 230
Rated capacity In[A] 90
Rated contact capacity In[A] 16 each
NPL1 and NPL2 (terminals 12 and 14)
Rated frequency [Hz] 50/60
Regulating thresholds [A] 5 ... 30
10 ... 60
15 ... 90
Load reinsertion delay 5-7 min. (NPL1)
4-5, 50min.(NPL2)
Load disinsertion delay about 2 s
Indicators 1 green led=
voltage
2 red leds=
load OFF
Load OFF
remote signalling [A] 1 (terminals 11 and 13)
Terminals
primary load 35mm2
not primary loads 10mm2
Power consumption [W] 5
Modules [No] 5
Main circuit-breaker downstream installed, they compare the higher allowed and preset value of
power consumption to the effective system power consumption avoiding the tripping of the main
circuit-breaker through switching-off in sequence of maximum two not primary loads (NPL1 and
NPL2) when the preset threshold is exceeded. A green led signals the voltage and two red leds
indicate load OFF. At preset time intervals the device automatically tries to insert again not primary
disabled loads.
Code Type Description
EG 417 8 LSS 1/2 load shedding switch
LOAD
1 3 5 7 9 11 13 15
2 4 6 8 10 12 14 16
NL
230V~
PL
NPL1
NPL2
Possible
remote
signalling
Possible
forced NPL 1
and NPL 2
switch-off
N.B.:
- the device must
be main circuit-
breaker
downstream
inserted into
the network
- PL = Primary
Load
- NPL = Not
Primary Load
OEPM0150
Single-phase wiring diagram
TEPM0246
6/10
6
ABB SACE
Load management devices
SQZ3 phase and sequence relays
Overall dimensions ...................................... pg. 11/25 Application sheet ........................................ pg. 12/16
SQZ3 relay performs the following continue monitoring functions on three-phase networks
at 400V a.c.:
1. phase sequence;
2. phase failure;
3. minimum voltage (adjustable up to 70% of Vn).
If one of the three failures is detected, the output relay (safety switching contact) intervenes with a
delay adjustable from 2 to 20 seconds for minimum voltage only and controls the following:
- acoustic alarms;
- motor controlling contactors;
- circuit-breakers with coils.
Code Type Description
EG 617 3 SQZ3 phase and sequence relay (3 modules)
Technical characteristics
Rated voltage [Vn] 400V a.c.
Frequency [Hz] 50/60
Contact capacity [A] 10 (cos ϕ = 1)
Type of contact safety
switching
Minimum voltage [%] from 100 to 70 of Vn
regulating trimmer
Intervention delay
regulating trimmer [s] from 2 to 20
Insulation rating II
Protection degree [IP] 20
Operating temperature [°C] –10…+55
Power consumption [W] 10
Dimensions (number of modules) [No] 3
TEPM0255
L1
L2
L3
Output
contact Three-phase
motor
MCB
789
123456
SQZ3
400V
50-60Hz
10 11 12
Phases Sequence
400V 50Hz
OK
OK
OK
Three phases
Min Voltage
Min Voltage
Delay (s)
70% 100%
220
NA NC C
L1 L2 L3
10A 250V
OEPM0055
Wiring diagram
6/11
6
ABB SACE
Load management devices
LE power failure signalling lamps
Overall dimensions ...................................... pg. 11/25
Technical characteristics
Rated voltage Un[V] a.c. 230
Lighting level [lumen] 20
Rated frequency [Hz] 50/60
Standby battery [min] 45
Indications green led= standard
operation
red led=
lamp OFF
Max. recharge cycles [No] 500
Power consumption [W] 10
Modules [No] 2
More technical characteristics
The first of the two front interchangeable lamp glasses is mounted
on the device case edge and provides light on the front; the second
one, protruding about 10mm, provides diffuse light.
The glass can be removed easily, allowing the access to battery
saving. In this way it is possible to disconnect the lamp avoiding
power consumption in case of long power supply black-out in the
installation.
67
N
230Va.c.
8
L
5
OEPM0056
The built-in battery allows the charging of the lamp when the device is connected to network voltage.
It automatically switches on when the voltage fails allowing an easy and safe operation within the
consumer unit or the switchboard it is installed on. A green led signals the standard operation and a
red led indicates the device OFF for battery saving.
Code Type Description
EG 296 6 LE-230 power failure signalling lamp
TEPM0249
6/12
6
ABB SACE
Load management devices
E 228 WM alarm indicators
Overall dimensions ...................................... pg. 11/26
It can report an alarm signalling switched on by the closing of any kind of external contact (fault,
warning device, etc.) through an acoustic and lighting alarm.
Code Type Description
EF 930 1 E 228-WM alarm indicator
Technical characteristics
Rated voltage Un[V] a.c. 230
Rated frequency [Hz] 50
Power consumption [W] 4
Modules [No] 1
Operation
1
External contact NO (monitored) has
changed the initial position:
- LED 3 switches on (blinking)
- acoustic alarm on
2a and 2b
Acoustic alarm disabled on the product (2a)
or remotely (2b):
- LED 3 light is fixed up to system reset
3
Alarm indicator LED
N
N
L
T
1
2b
3
2a
OEPM0058
Wiring diagram
TEPM0251
6/13
6
ABB SACE
Load management devices
Min./max current/voltage ammetric and voltmetric relays
Technical details .......................................... pg. 10/77 Overall dimensions ..................................... pg. 11/26
These devices are used to measure current (ammetric) and voltage (voltmetric) on single-phase
electric networks for a perfect protection of devices used.
The range includes:
maximum current (RHI) and maximum voltage (RHV) relay. The control relay remains picked
up as long as the quantity to be measured is lower than the set threshold value;
minimum current (RLI) and minimum voltage (RLV) relay. The control relay remains pickep
up as long as the quantity to be measured is higher than the set threshold value.
In both cases the relay drops out with a delay adjustable by the potentiometer, which also allows to
adjust hysteresis (from 1 to 45%).
Code Type Description
EG 599 3 RHI maximum current ammetric relay
EG 597 7 RHV maximum voltage volmetric relay
EG 598 5 RLI minimum current ammetric relay
EG 596 9 RLV minimum voltage voltmetric relay
Technical characteristics
Rated voltage Un[V] a.c. 230
Switching contact capacity [A] 16
Rated frequency [Hz] 50/60
Ammetric relay alarm thresholds [A] 2, 5,10
Voltmetric relay alarm thresholds [V] 100, 300, 500
Adj. calibration of In and Vn% [%] 30...100
Adjustable hysteresis value [%] 1...45
Time delay [s] 1...30
Power consumption [W] 2
Modules [No] 3
More characteristics
Control relay intervention
lighting indication
red LED on = intervening
Power supply
lighting indication
green LED on = ON
Intervention
lighting indication
blinking green LED = intervening
123456
789101112
CNCNA
Output
100V
300V
500V
C
N
L
230V~ power supply
123456
789101112
CNCNA
Output
2A 5A10A
C
N
L
230V~ power supply
OEPM0060 OEPM0059
Hysteresis I %
30
100
Current I %
40
507090
1
30
Operatingtime (s)
1
45
10
20
30 40
20
10
Power ON
230 V~ 50...60Hz
16A (cos 1)
Alarm
RHI
Hysteresis V %
30
100
Voltage V %
40
507090
1
30
Operatingtime (s)
1
45
10
20
30 40
20
10
Power ON
230 V~ 50...60Hz
16A (cos 1)
Alarm
RHV
OEPM0062 OEPM0061
TEPM0252
6/14
6
ABB SACE
Load management devices
STD universal dimmers
Technical details .......................................... pg. 10/79 Overall dimensions ..................................... pg. 11/27
A particular self-test function allows STD universal dimmers to determine intervention based on
delay or advance of phase principle.
This specific characteristic allows the use of the same dimmer to easily control different illuminating
bodies, such as:
– incandescent lamps;
– halogen lamps;
– low voltage halogen lamps with electro-mechanic transformer;
– low voltage halogen lamps with electronic transformer;
– fluorescent lamps.
Suitable for power consumption from 420W/VA to 1000W/VA, STD universal dimmers can be equipped
with an appropriate module mounted in parallel to expand the power consumption to
18000W/VA.
Code Type Description
EG 742 9 STD-500MA modular universal dimmer - power 500W, 230V a.c.
for incandescent lamps or halogen lamps with
electro-mechanic or electronic transformer (2 modules)
EG 743 7 STD-420SL universal expantion - power 420W, 230V a.c. per
STD-500 dimmer, max. coupling 5 pieces (2 modules)
Technical characteristics
STD-420SL STD-500MA STD-1000U STD50-4 STD-MTS
Rated voltage Un[V] 230 a.c 230 a.c 230 a.c 230 a.c 0-10 d.c.
Rated current In[A, mA] 1.83A 2.17A 4.78A 4A 50mA
Max. rated output [VA] 420 500 1000 420 700
Min. operating power consumption [VA] 60 60 100 40 70
Rated frequency [Hz] 50 50 50 50 50
Maximum expandability [pz.] 6 6 18 1 1
Max. distance between STD-… and control pushbutton [m] 100 100 100 100 100
Operating temperature [°C] -10…+50 -10…+50 -10…+50 -10…+50 -10…+50
Relative humidity [%] 59 59 59 59 59
Power consumption [W] 6 6 10 5 1
Modules [No] 22432
Standards IEC/EN 55014
TEPM0327
TEPM0328
6/15
6
ABB SACE
Load management
STD universal dimmers
STD
MTS
NG1–+
L
N
N
+
-
LEVG
LGNDN1
L1
L2
L3
N
STD-1000U
5G–+
SG1DNL
L
N
STD-500MA
SGL
STD-420SL
SG1DNL
L
N
STD-500MA
TEPM0329
TEPM0330
Code Type Description
EG 744 5 STD-1000U universal modular dimmer-power consumption from 100 to 1000W
for incandescent lamps or halogen lamps with
electro-mechanic or electronic transformer (4 modules)
EG 745 2 STD50-4 modular pushbutton dimmer - power consumption from 40 to 420W,
230V a.c. for incandescent lamps or halogen lamps with
electronic transformer
EG 746 0 STD-MTS modular dimmer 0-10V d.c. for controlling fluorescent
lamps
Technical details .......................................... pg. 10/79 Overall dimensions ..................................... pg. 11/27
7/1
7
ABB SACE
Other modular devices
Measurement devices
Contents
Measurement instruments
Analogue instruments .............................................................................................................7/2
Digital instruments ..................................................................................................................7/4
MTM multimeters ....................................................................................................................7/5
Accessories for analogue and digital instruments
MCV - MCA voltmetric and ammetric switches .......................................................................7/6
Interchangeable scales for analogue instruments ..................................................................7/7
Current transformers ...............................................................................................................7/9
Electronic transducers ..........................................................................................................7/12
Shunts ...................................................................................................................................7/13
HMT and E 233 electro-mechanical hour meters ............................................................7/14
Electronic single-phase and three-phase energy meters
Three-phase DELTA METER series with digital display on LCD ..........................................7/15
EE MINI-METER and EMT 3 series......................................................................................7/17
Insulation monitors
Isoltester-C............................................................................................................................7/18
Selvtester-C ..........................................................................................................................7/19
QSD panels for remote signalling .........................................................................................7/19
ABB SACE
7/2
7
ABB SACE
Measurement devices
Measurement instruments
Accessories ..................................................... pg. 7/6 Technical details ......................................... pg. 10/83 Overall dimensions ...................................... pg. 11/30
Technical characteristics
Rated voltage Un [V] a.c. 300, 500; d.c. 100, 300
Rated currents in a.c. [A]
direct reading full scale values 5...30
indirect reading full scale values
5…2500
Rated currents in d.c. [A]
direct reading full scale values 0.1...30
indirect reading full scale values 5...500
Frequency [Hz] 50/60
Overload capacity [%] 20 compared to the voltage
or to the rated current
Accuracy class [%] 1.5 (0.5 for frequency meters)
Modules [No] 3
Standards EN 60051, IEC 60414
The range provided includes analogue and digital instruments. In addition to standard measurement
devices for electric quantities (voltmeters, ammeters, wattmeters, varmeters, frequency meters, power
factor meters), other special instruments (RPM meters, hour meters) and a set of accessories are
available, including ammetric transformers, which increase the functions of these instruments.
Analogue instruments
Suitable for direct or indirect measurement through the appropriate accessories.
Code Type Description
Analogue instruments
For alternating current
EG 051 5 VLM 1/300 direct voltmeter with 300V scale
EG 052 3 VLM 1/500 direct voltmeter with 500V scale
EG 059 8 AMT 1/5 direct ammeter with 5A scale
EG 053 1 AMT 1/10 direct ammeter with 10A scale
EG 054 9 AMT 1/15 direct ammeter with 15A scale
EG 055 6 AMT 1/20 direct ammeter with 20A scale
EG 056 4 AMT 1/25 direct ammeter with 25A scale
EG 057 2 AMT 1/30 direct ammeter with 30A scale
EG 058 0 AMT 1/A1 ammeter without scale for C.T. (sec. 5A), for A1 (SCL1) scales
EG 108 3 AMT 1/A5 ammeter without scale for C.T. (sec. 5A), for A5 (SCL1) scales
EG 060 6 FRZ1 100/280V 45-65Hz frequency meter with scale
TEPM0270
TEPM0271
More technical characteristics
Test voltage 2000V - 50Hz for 1 minute
Operating temperature - according to the accuracy class
(20±10)°C
- with guaranteed operation but
outside accuracy rating:
from -25° C to +75° C
Resistance to vibration ± 0.25 mm amplitude at 50 Hz
Installation position - vertical and horizontal
- versions for different angles
on request
Reading scale at full scale values according
to DIN 43802 Standard
Ammeter consumable power 5A: 0.3VA; 10A: 0.6VA; 25A:
1VA; 30A: 1.2VA
Voltmeter consumable power 300V: 1.5VA; 500V: 4VA
Frequency meter
consumable power <1.5VA
7/3
7
ABB SACE
Accessories ..................................................... pg. 7/6 Technical details ......................................... pg. 10/83 Overall dimensions ...................................... pg. 11/30
Measurement devices
Measurement instruments
Code Type Description
EG 313 9 CSF1 power factor meter with scale for transducer (1mA input)
For direct current
EG 071 3 VLM 2/100 direct voltmeter with 100V scale
EG 072 1 VLM 2/300 direct voltmeter with 300V scale
EG 138 0 AMT 2/0.01 direct ammeter with 10mA scale
EG 139 8 AMT 2/0.1 direct ammeter with 100mA scale
EG 140 6 AMT 2/1 direct ammeter with 1000mA scale
EG 073 9 AMT 2/5 direct ammeter with 5A scale
EG 074 7 AMT 2/10 direct ammeter with 10A scale
EG 075 4 AMT 2/15 direct ammeter with 15A scale
EG 076 2 AMT 2/20 direct ammeter with 20A scale
EG 077 0 AMT 2/25 direct ammeter with 25A scale
EG 078 8 AMT 2/30 direct ammeter with 30A scale
EG 081 2 AMT 2 ammeter without (SCL2) scale for shunt ../60mV
Wiring diagrams
Direct insertion Insertion by shunt
Indirect insertion
through C.T.
OEPM0065
12 34
+
A
12 34
L1
N
S1
P1
S2
P2
A
12 34
L1
N
A
12 34
L1
N
V
7/4
7
ABB SACE
Measurement devices
Measurement instruments
Accessories ..................................................... pg. 7/6 Technical details ......................................... pg. 10/83 Overall dimensions ...................................... pg. 11/30
Digital instruments
Suitable for direct or indirect measurement using appropriate accessories.
Measurements are displayed through 3-digit digital indicator with out-of-scale signalling.
As electronic instruments do not have parts subject to friction wear, they have a longer operation life
and high accuracy.
Code Type Description
Digital instruments
for alternating current
EG 408 7 VLM-D1 direct voltmeter from 0 to 600V a.c.
EG 406 1 AMT-D1 ammeter for C.T.; 15; 20; 25; 40; 60; 99,9; 150; 200; 250; 400;
600; 999A (selected through minidip)
for direct current
EG 409 5 VLM-D2 direct voltmeter from 0 to 600V d.c.
EG 407 9 AMT-D2 ammeter for shunt; 15; 20; 25; 40; 60; 99,9; 150; 200;
250; 400; 600; 999A (selected through minidip)
Frequency meter
EG 410 3 FRZ-D1 digital frequency meter
TEPM0304
TEPM0305
Technical characteristics
Rated voltage [V] a.c. 230
Rated frequency [Hz] 50/60
Overload capacity [In/Vn] 1.2
Accuracy rating [%] ±0.5 full scale
±1 digit at 25°C
Max. signal input value AMT-D1 5A a.c;
AMT-D2 60mV d.c;
VLM-D1 600V a.c;
VLM-D2 600V d.c;
FRZ-D1 0…99.9Hz
Measurement field AMT-D1 AMT-D2
0…999A (up to 1.99 with
led on)
VLM-D1 VLM-D2
0…999A (up to 1.999 with
led on)
FRZ-D1 40…80Hz (0.5% rating)
Selection of capacity through minidip
View 3-digit display + led for
out-of-scale signalling
Operating temperature [°C] -10…+55
Storage temperature [°C] -40…+70
Protection degree [IP] 20
Power consumption [VA] <2
Number of modules 3
Standards EN 61010-1
OEPM0066
Hz
12 34
FRZ-D1
Power supply
input
230Va.c.
Signal
input
max. 600Va.c.
V
12 34
VLM-D2
(+)
Power supply
input
230Va.c.
Signal
input
max. 600Vd.c.
V
12 34
VLM-D1
(N)
Power supply
input
230Va.c.
Signal
input
max. 600Va.c.
A
12 34
AMT-D2
Signal
input
max. 60mVd.c.
Power supply
input
230Va.c.
A
12 34
AMT-D1
5 A
max
S1 S2
P1 P2
Power supply
input
230Va.c.
Signal
input
max. 5A
Wiring diagrams
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
150 15
200 20
250 25
400 40
600 60
999
99,9
12345678 12345678
12345678 12345678
MINIDIP
OFF
ON
Full scale calibration:
to obtain the desired
full scale, move the
minidips as shown.
AMT-D1 / AMT-D2
7/5
7
ABB SACE
Measurement devices
Measurement instruments
Accessories ..................................................... pg. 7/6 Technical details ......................................... pg. 10/82 Overall dimensions ...................................... pg. 11/31
Application sheet ......................................... pg. 12/18
MTM multimeters
These instruments allow the measurement of the main electric quantities in three-phase networks at
230/400V a.c., grouping in a single instrument the functions of voltmeters, ammeters, power factor
meters, wattmeters, varmeters, frequency meters, and thermometers. The MTME multimeter detects
also active and reactive energy. Being more practical than that of multiple different instruments, the
use of these instruments is less difficult referring to the managing of dimensions and to the wiring,
and more convenient.
The 30 measurable quantities are viewed by the four red LED displays, which guarantee the
simultaneous reading of multiple values along with a good legibility.
In addition to instantaneous measured quantities (in effective value), it is possible for some of them to
view the average and the maximum peak as well.
Code Type Description
EG 616 5 MTM modular multimeter for measurement at 230/400 V a.c. (6 modules)
EA 140 2 MTME as above + active and reactive energy
EA 141 0 MTME-I as above + pulse output
EA 142 8 MTM-485 as MTME + output 485 + relay output
EA 143 6 CDI impulse concentrator (for MTME-I and MTME-485)
EA 144 4 CUS converter RS485-232
EA 145 1 SW01 management software (for MTME-I and MTME-485)
TEPM0332
19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
110V 400V
230V0
S2
S1
S2
S1
S2
S1
N
VL1 VL3
VL2
V aux
CT…/5A
Technical characteristics
Auxiliary rated
voltage [V] 110, 230, 400 a.c.
Rated frequency [Hz] 50/60
Rated input voltages [V] from 20 to 500
Permanent overload [%] +20
Rated input currents [A] 5
Permanent overload [%] +30
Current values
programmable for A.T. [A] from 0.02 to 10,000
Insulation voltage [kV] 2.5
Resistance to humidity [%] 90
Protection degree IP20
View by 3-digit display
Operating temperature [°C] -10…+60
Storage temperature [°C] -25…+80
Maximum/minimum
section of connection [mm2] 0.5-2.5
Weight [kg] 0.4
Modules [No] 6
Power consumption [W] <3
Standards EN 61010-1
TEPM0447
TEPM0448
7/6
7
ABB SACE
MCV - MCA voltmetric and ammetric switches
Cam rotary switches are suitable for mounting on EN 50022 rail. In three-phase systems they enable
the use of a single measurement instrument (single-phase) for viewing the current or voltage value
set through the switch itself.
Code Type Description
EG 590 2 MCV 4 voltmetric for 3 line voltages
(L1-L2; L2-L3; L3-L1)
EG 592 8 MCA 4 ammetric for 3 currents
(L1-;L2; L3)
EG 591 0 MCV 7 voltmetric for 6 voltages
(L1-L2; L2-L3; L3-L1; L1-N; L2-N; L3-N)
TEPM0275 TEPM0274
L1
L2
L3
R
S
T
537
L1
L2
L3
R
S
T
6593
N
3
L1
L2
L3
R
S
T
951
V
L1-L2
L2-L3
L3-L1
62
0
A
0
L1
L2
64
L3
V
0
L1-L2
10 12
L2-L3
L3-L1
L1-N
L2-N
L3-N
MCV4 MCA4 MCV7
Installation
1. Mount the switch on DIN rail
2. Wire it
3. Mount the cover and the knob and fix the screw
OEPM0067
Technical characteristics
Insulation voltage [V] 600
Rated thermal current [A] 12
Mechanic operations [No] 1,000,000
Power consumption [W] 0.23
Modules [No] 3
Measurement devices
Accessories for analogue and digital
instruments
Technical details .......................................... pg. 10/83 Overall dimensions ..................................... pg. 11/31
7/7
7
ABB SACE
Measurement devices
Accessories for analogue and digital
instruments
0
100
78°
0
100
90°
SCL1/A5/100
Full scale at 78°
(with extra scale)
SCL1/A1/100
Full scale at 90°
OEPM0068
Interchangeable scales for analogue instruments
Code Type Description
Interchangeable scales for analogue ammeters in a.c. AMT 1
EG 061 4 SCL 1/5 A1 - 5A
EG 062 2 SCL 1/10 A1 - 10A
EG 063 0 SCL 1/20 A1 - 20A
EG 171 1 SCL 1/25 A1 - 25A
EG 064 8 SCL 1/30 A1 - 30A
EG 172 9 SCL 1/40 A1 - 40A
EG 065 5 SCL 1/50 A1 - 50A
EG 173 7 SCL 1/60 A1 - 60A
EG 106 7 SCL 1/75 A1 - 75A
EG 066 3 SCL 1/80 A1 - 80A
EG 067 1 SCL 1/100 A1 - 100A
EG 068 9 SCL 1/150 A1 - 150A
EG 069 7 SCL 1/200 A1 - 200A
EG 048 1 SCL 1/250 A1 - 250A
EG 070 5 SCL 1/300 A1 - 300A
EG 083 8 SCL 1/400 A1 - 400A
EG 084 6 SCL 1/500 A1 - 500A
EG 174 5 SCL 1/600 A1 - 600A
EG 085 3 SCL 1/800 A1 - 800A
EG 086 1 SCL 1/1000 A1 - 1000A
EG 548 0 SCL 1/1500 A1 - 1500A
EG 549 8 SCL 1/2000 A1 - 2000A
EG 550 6 SCL 1/2500 A1 - 2500A
EG 087 9 SCL 1/A5/5 A5 - 5A
EG 088 7 SCL 1/A5/10 A5 - 10A
EG 089 5 SCL 1/A5/20 A5 - 20A
EG 090 3 SCL 1/A5/30 A5 - 30A
EG 109 1 SCL 1/A5/50 A5 - 50A
EG 110 9 SCL 1/A5/80 A5 - 80A
EG 119 0 SCL 1/A5/100 A5 - 100A
EG 120 8 SCL 1/A5/150 A5 - 150A
TEPM0276
7/8
7
ABB SACE
Measurement devices
Accessories for analogue and digital
instruments
Interchangeable scales for analogue ammeters in d.c. AMT 2
EG 082 0 SCL 2/5 A1 - 5A
EG 079 6 SCL 2/6 A1 - 6A
EG 080 4 SCL 2/10 A1 - 10A
EG 149 7 SCL 2/20 A1 - 20A
EG 150 5 SCL 2/30 A1 - 30A
EG 193 5 SCL 2/50 A1 - 50A
EG 194 3 SCL 2/80 A1 - 80A
EG 195 0 SCL 2/100 A1 - 100A
EG 196 8 SCL 2/150 A1 - 150A
EG 197 6 SCL 2/200 A1 - 200A
EG 198 4 SCL 2/250 A1 - 250A
EG 199 2 SCL 2/300 A1 - 300A
EG 102 6 SCL 2/400 A1 - 400A
EG 103 4 SCL 2/500 A1 - 500A
TEPM0277
7/9
7
ABB SACE
Measurement devices
Accessories for analogue and digital
instruments
Technical details .......................................... pg. 10/83 Overall dimensions ..................................... pg. 11/32
Current transformers
Used to transform primary currents (max. 2500A) into low secondary currents (max. 5A) indirectly
supplying power to analogue and digital measurement devices. They are available both with wound
and through primary. In the first case they are provided along with the bar or the primary terminal; in
the second case they have a hole to insert in the bar or the cable which forms the primary.
Code Type Description
Current transformer with wound primary, secondary .../5A
EG 750 2 CTR 0/1 Iprim 1A rating 0.5 - 3VA
rating 1 - 6VA
EG 751 0 CTR 0/5 Iprim 5A rating 0.5 - 3VA
rating 1 - 6VA
EG 752 8 CTR 0/10 Iprim 10A rating 0.5 - 3VA
rating 1 - 6VA
EG 753 6 CTR 0/15 Iprim 15A rating 0.5 - 3VA
rating 1 - 6VA
EG 754 4 CTR 0/20 Iprim 20A rating 0.5 - 3VA
rating 1 - 6VA
EG 755 1 CTR 0/25 Iprim 25A rating 0.5 - 3VA
rating 1 - 6VA
EG 756 9 CTR 0/40 Iprim 40A rating 0.5 - 3VA
rating 1 - 6VA
EG 757 7 CTR 0/50 Iprim 50A rating 0.5 - 3VA
rating 1 - 6VA
EG 758 5 CTR 0/60 Iprim 60A rating 0.5 - 3VA
rating 1 - 6VA
EG 759 3 CTR 0/80 Iprim 80A rating 0.5 - 3VA
rating 1 - 6VA
EG 760 1 CTR 0/100 Iprim 100A rating 0.5 - 3VA
rating 1 - 6VA
Technical characteristics
Primary rated current In [A] from 1 to 2500
Secondary rated current In [A] 5
Frequency [Hz] 40/60
Insulation class E
Terminals shell-type protected for cables
up to 10mm2 (CTR0; CTR1,
CTR3; CTR4)
double screw terminals per
cable (CTR6; CTR8)
Insulation air-dried
Standards IEC60044-1
Primary
Secondary
K-P1
(1) L-P2
(2)
k-s1 (3) I-s2 (4)
CTR 0
CTR 1
CTR 3
CTR 4
CTR 6
CTR 8
INSTRUMENT
OEPM0069
TEPM0281
7/10
7
ABB SACE
Measurement devices
Accessories for analogue and digital
instruments
Technical details .......................................... pg. 10/83 Overall dimensions ..................................... pg. 11/32
Code Type Description
Current transformers with through primary (cable ø 21mm), secondary.../5A
EG 761 9 CTR 1/40 Iprim 40A rating 3 - 1.5VA
EG 762 7 CTR 1/50 Iprim 50A rating 3 - 2VA
EG 763 5 CTR 1/60 Iprim 60A rating 3 - 2.5VA
EG 764 3 CTR 1/80 Iprim 80A rating 3 - 4VA
rating 1 - 1.5VA
EG 765 0 CTR 1/100 Iprim 100A rating 3 - 5VA
rating 1 - 2VA
EG 766 8 CTR 1/150 Iprim 150A rating 0.5 - 2VA
rating 1 - 3VA
rating 3 - 4VA
EG 767 6 CTR 1/200 Iprim 200A rating 0.5 - 2VA
rating 1 - 4VA
rating 3 - 6VA
EG 768 4 CTR 1/250 Iprim 250A rating 0.5 - 3VA
rating 1 - 5VA
rating 3 - 6VA
Current transformers with through primary (bar 30x10 mm, cable ø 22mm), secondary.../5A
EG 769 2 CTR 3/100 Iprim 100A rating 1 - 1.5VA
rating 3 - 3VA
EG 770 0 CTR 3/150 Iprim 150A rating 0.5 - 1.5VA
rating 1 - 2.5VA
rating 3 - 5VA
EG 771 8 CTR 3/200 Iprim 200A rating 0.5 - 2VA
rating 1 - 3VA
rating 3 -6VA
EG 772 6 CTR 3/250 Iprim 250A rating 0.5 - 2.5VA
rating 1 - 3.5VA
rating 3 - 7VA
EG 773 4 CTR 3/300 Iprim 300A rating 0.5 - 6VA
rating 1 - 10VA
rating 3 - 12VA
EG 774 2 CTR 3/400 Iprim 400A rating 0.5 - 10VA
rating 1 - 12VA
rating 3 - 12VA
EG 775 9 CTR 3/500 Iprim 500A rating 0.5 - 10VA
rating 1 - 12VA
rating 3 - 12VA
EG 776 7 CTR 3/600 Iprim 600A rating 0.5 - 10VA
rating 1 - 12VA
rating 3 - 12VA
Current transformers with through primary (bar 40x10mm, cable ø 32mm), secondary .../5A
EG 777 5 CTR 4/250 Iprim 250A rating 0.5 - 3VA
rating 1 - 6VA
EG 778 3 CTR 4/300 Iprim 300A rating 0.5 - 5VA
rating 1 - 8VA
EG 779 1 CTR 4/400 Iprim 400A rating 0.5 - 6VA
rating 1 - 10VA
EG 780 9 CTR 4/500 Iprim 500A rating 0.5 - 8VA
rating 1 - 15VA
EG 781 7 CTR 4/600 Iprim 600A rating 0.5 - 10VA
rating 1 - 15VA
EG 782 5 CTR 4/800 Iprim 800A rating 0.5 - 12VA
rating 1 - 15VA
EG 783 3 CTR 4/1000 Iprim 1000A rating 0.5 - 20VA
rating 1 - 25VA
TEPM0222
TEPM0283
TEPM0284
7/11
7
ABB SACE
Measurement devices
Accessories for analogue and digital
instruments
Technical details .......................................... pg. 10/83 Overall dimensions ..................................... pg. 11/32
Code Type Description
Current transformers with through primary (bar 80x10mm, cable ø 50mm), secondary .../5A
EG 784 1 CTR 6/400 Iprim 400A rating 0.5 - 5VA, rating 1 - 10VA
EG 785 8 CTR 6/500 Iprim 500A rating 0.5 - 6VA, rating 1 - 12VA
EG 786 6 CTR 6/600 Iprim 600A rating 0.5 - 8VA, rating 1 - 16VA
EG 787 4 CTR 6/800 Iprim 800A rating 0.5 - 10VA, rating 1 - 20VA
EG 788 2 CTR 6/1000 Iprim 1000A rating 0.5 - 15VA, rating 1 - 25VA
EG 789 0 CTR 6/1200 Iprim 1200A rating 0.5 - 15VA, rating 1 - 25VA
EG 790 8 CTR 6/1500 Iprim 1500A rating 0.5 - 15VA, rating 1 - 25VA
Current transformers with primary (bar 82x37mm), secondary .../5A
EG 792 4 CTR 8/800 Iprim 800A rating 0.5 - 15VA, rating 1 - 30VA
EG 793 2 CTR 8/1000 Iprim 1000A rating 0.5 - 20VA, rating 1 - 40VA
EG 794 0 CTR 8/1200 Iprim 1200A rating 0.5 - 25VA, rating 1 - 50VA
EG 795 7 CTR 8/1500 Iprim 150A rating 0.5 - 30VA, rating 1 - 60VA
EG 796 5 CTR 8/2000 Iprim 2000A rating 0.5 - 40VA, rating 1 - 80VA
EG 797 3 CTR 8/2500 Iprim 2500A rating 0.5 - 50VA, rating 1 - 100VA
Modular current transformers with primary (bar 125x50mm), secondary .../5A
EG 798 1 CTR 12/800 Iprim 800A - rating 0.5 - 25VA
EG 799 9 CTR 12/1000 Iprim 1000A - rating 0.5 - 40VA
EG 800 5 CTR 12/1200 Iprim 1200A - rating 0.5 - 40VA
EG 801 3 CTR 12/1500 Iprim 1500A - rating 0.5 - 50VA
EG 802 1 CTR 12/2000 Iprim 2000A - rating 0.5 - 80VA
EG 803 9 CTR 12/2500 Iprim 2500A - rating 0.5 - 100VA
EG 804 7 CTR 12/3000 Iprim 3000A - rating 0.5 - 100VA
EG 805 4 CTR 12/4000 Iprim 4000A - rating 0.5 - 100VA
Modular current transformers with through primary ø 29mm, secondary .../5A
EG 289 1 TRF M/40 Iprim 40A - rating 3 - 1VA
EG 290 9 TRF M/60 Iprim 60A - rating 1 - 2VA
EG 291 7 TRF M/100 Iprim 100A - rating 0.5 - 2VA
EG 292 5 TRF M/150 Iprim 150A - rating 0.5 - 3VA
EG 293 3 TRF M/250 Iprim 250A - rating 0.5 - 4VA
EG 294 1 TRF M/400 Iprim 400A - rating 0.5 - 6VA
EG 295 8 TRF M/600 Iprim 600A - rating 0.5 - 7VA
TEPM0286
TEPM0287
TEPM0285
7/12
7
ABB SACE
Measurement devices
Accessories for analogue and digital
instruments
Technical details .......................................... pg. 10/83 Overall dimensions ..................................... pg. 11/33
Technical characteristics
Power supply [V] 110, 230, 400 ±20%
Test voltage [kV] 2
Max. output [mA] 1 d.c.
Electronic transducers
Used in combination with power factor meters both on single-phase and three-phase lines. The
scale of the measurement instrument must be selected based on the voltage and A.Ts (see technical
details).
They are contained into cases of insulating material equipped with fast connection on EN50022 rail.
Code Type Description
EG 568 8 TCS 1 for power factor meter - single-phase
EG 569 6 TCS 2 for power factor meter - three-phase
TEPM0288
7/13
7
ABB SACE
Measurement devices
Accessories for analogue and digital
instruments
Technical details .......................................... pg. 10/83 Overall dimensions ..................................... pg. 11/33
Shunts
Shunts have 60mV voltage and must be used with a maximum load of 0.25 in combination with
measurement instruments in d.c. The included bipolar cable is 1m long with a section of 1.4 mm2,
equal to a resistence of 0.026 Ω.
For an appropriate operation:
both horizontal and vertical mounting are possible (the horizontal position enables a greater heat
consumption)
the faying surface must be completely used and clean; cover with specific grease after the connection
screws and bolts must be perfectly tight
shunts must be sufficiently ventilated; as they are not insulated, it is a good rule to protect them
against accidental contacts.
Code Type Description
shunt
EG 132 3 SNT 1/5 5A
EG 135 6 SNT 1/6 6A
EG 181 0 SNT 1/10 10A
EG 125 7 SNT 1/15 15A
EG 126 5 SNT 1/20 20A
EG 127 3 SNT 1/25 25A
EG 128 1 SNT 1/30 30A
EG 129 9 SNT 1/40 40A
EG 182 8 SNT 1/50 50A
EG 130 7 SNT 1/60 60A
EG 131 5 SNT 1/80 80A
EG 183 6 SNT 1/100 100A
EG 136 4 SNT 1/150 150A
EG 162 0 SNT 1/200 200A
EG 184 4 SNT 1/250 250A
EG 185 1 SNT 1/400 400A
EG 186 9 SNT 1/500 500A
EG 187 7 SNT 1/600 600A
EG 188 5 SNT 1/800 800A
EG 189 3 SNT 1/1000 1000A
EG 190 1 SNT 1/1500 1500A
EG 191 9 SNT 1/2000 2000A
EG 192 7 SNT 1/2500 2500A
TEPM0289
Technical characteristics
Voltage [mV] 60
Current rating [A] from 5 to 2500 (on request up to 8000)
Accurancy class 0.5 (from 10 to 30°C)
Max. load [] 0.25
Overload for 5s from 10 to 500A : 1xIn
from 600 to 2000A: 5xIn
at 2500A: 2xIn
INSTRUMENT
GU
OEPM0070
7/14
7
ABB SACE
Measurement devices
HMT and E 233 electro-mechanic hour meters
Overall dimensions ...................................... pg. 11/34
Provided with a 7-digit indicator (99,999.99) and available in one module (E 233) or 2 modules (HMT),
these hour meters cannot be reset.
Code Type Description
HMT hour meters
EG 401 2 HMT 1/24 24V a.c.
EG 402 0 HMT 1/110 110V a.c.
EG 403 8 HMT 1/230 230V a.c.
EG 107 5 HMT 11 double hour meter 230V a.c.
E 233 hour meters
EG 595 1 E 233-230 230V a.c.
EG 594 4 E 233-24 24V a.c.
EG 593 6 E 233-12/48 12...48V d.c.
TEPM0292
TEPM0291
Technical characteristics
Rated voltage Un [V] a.c. 24;
a.c. 110;
a.c. 230;
d.c. 12...48
Displayed digits (in hours) 99,999.9 (for HMT1 and HMT11)
99,999.99 (for E 233);
Accuracy class [%] 0.5 (for HMT);
0.01-0.1h (for E 233)
Frequency [Hz] 50
Power consumption [W] 1.1...2.2 (for HMT);
1.5 (for E 233)
Modules [No] 2 (HMT);
1 (E 233)
L
N
LOAD
HMT
o
r
E
233
OEPM0071
7/15
7
ABB SACE
Measurement devices
Electronic single-phase and three-phase energy meters
Technical details .......................................... pg. 10/84 Overall dimensions ..................................... pg. 11/35
Three-phase DELTA METER series with digital display on LCD
DELTA METER meters are designed to offer extremely easy and simple application. Suitable for
mounting on DIN rail, lightweight and small, they are ideal for the installation on switchboards, feeder
panels and tin boxes. The range includes devices for measuring active energy, reactive energy and
the combination of active and reactive energy. All DELTA METER meters are standardized according
to the international Standards IEC 61036 (for active energy) and IEC 61268 (for reactive energy).
Code Type Description
Direct insertion up to 65A
KX 891 1 DBB 22 17 00 three-phase active energy meter 3x230V for direct connection
KX 884 6 DBB 29 17 00 three-phase active energy meter 3x400V for direct connection
KX 883 8 DBB 21 17 00 three-phase active energy meter + neutral 3x230/400V for
direct connection
KX 890 3 DBB 21 17 10 three-phase active energy meter + neutral 3x230/400V for direct
connection, with RESET
KX 885 3 DDB 21 17 00 three-phase active reactive energy meter + neutral 3x230/400V for
direct connection
Indirect insertion through A.T...../5A
KX 892 9 DAB 22 15 00 three-phase active energy meter 3x230V for connection through C.T.
KX 881 2 DAB 29 15 00 three-phase active energy meter 3x400V for connection throug C.T.
KX 893 7 DAD 27 15 00 three-phase active energy meter 3x230/127V for connection through C.T.
KX 880 4 DAB 21 15 00 three-phase active energy meter + neutral 3x230/400V for connection
through C.T.
KX 889 5 DAB 21 15 10 three-phase active energy meter + neutral 3x230/400V for connection
through C.T., with RESET
KX 882 0 DCB 21 15 00 three-phase active/reactive energy meter + neutral 3x230/400V for
connection through C.T.
TEPM0306 TEPM0408
Technical characteristics
Voltage [V] 3x400, basic version; other voltages
available on request
Current [A]
65 (dir ect connection);
> 65 (indirect connection through C.T.)
Frequency [Hz] 50/60
Starting current [mA] 4
Pulse output [imp/kWh] 100 (direct connection);
frequency 1000 (indirect connection through C.T.);
other frequencies available on request
Impulse amplitude [ms] 100, basic version
Frequency of [imp/kWh] 5000, basic version
blinking of
LED and LCD segments
Pulse output
- max. current [mA] 100
- max. voltage
[V a.c./d.c.]
40
- max. cable section [mm2] 2.5
Accuracy class 2
Display LCD (liquid crystal) with 7 digits,
h=7mm
Terminal holder 10 mm2 (insertion through C.T.)
25 mm2 (direct insertion)
Protection degree IP51 (IP20 on the terminal holder
without cover)
Operating [°C] -25…+70
temperature
Power consumption [W] 1.5
Modules [No] 7
Standards IEC 61036 for active energy
meters; IEC 61268 for reactive
energy meters;
DIN 43864 for pulse
output
7/16
7
ABB SACE
Wiring diagrams
20 21
kWh
22 21
hVarh
20
kWh
2-pole balanced or 3-pole unbalanced
output for sending to a personal
computer information from energy
meter, encoded as numerical signal
Some types enable to connect an
external voltage to control telereset
Note
For connections through current
transformer, A.T. must have 5A
secondary and be connected
according to current polarities: P1_P2,
S1_S2
12345678911
L 1
L 2
L 3
N
S1
P1
S2
P2
S1
P1
S2
P2
S1
P1
S2
P2
DAB 21 15 00
DAB 21 15 10
DCB 21 15 00
Secondary measurement for Imax>65A
Connection through external current transformer to the
three-phase network +
neutral (4 cables) at 230/400V
Max. cable section: 10 mm
2
Adjustable transformation ratio
Secondary measurement for Imax>65A
Connection through external current
transformer to the three-phase network
without neutral (3 cables) at 230/400V
Max. cable section: 10 mm
2
Adjustable transformation ratio
123456789
L 1
L 2
L 3
S1
P1
S2
P2
S1
P1
S2
P2
DAB 29 15 00
Direct measurement up to Imax>65A
Direct connection to the three-phase network
without neutral (3 cables) at 230/400V
Max. cable section: 25 mm
2
123456789
L 1
L 2
L 3
DBB 29 17 00
12345678911
L 1
L 2
L 3
N
DBB 21 17 00
DBB 21 17 10
DDB 21 17 00
Direct measurement up to Imax>65A
Direct connection to the three-phase network +
neutral (4 cables) at 230/400V
Max. cable section: 25 mm
2
Measurement devices
Electronic single-phase and three-phase energy meters
Technical details .......................................... pg. 10/84 Overall dimensions ..................................... pg. 11/35
Auxiliary elements/accessories
Code Type Description
KX 886 1 DELTA/CPL terminal cover
KX 887 9 DELTA/DIN DIN rail for projecting installation
KX 888 7 DELTA/FRQ kit for front of board installation
7/17
7
ABB SACE
EE MINI-METER and EMT 3 series
Single-phase meters with a 4-digit display to read energy consumption in kWh. The series includes
5 versions each of them in 3 modules.
Code Type Description
KX 863 0 EE 20 energy meter 230V for direct and A.T. connection
KX 864 8 EE 20R as above + local reset
KX 865 5 EE 22 as EE 20 + pulse output (10, 100, 1000)
KX 866 3 EE 22R as above + local reset
KX 867 1 EE 22Rr as above + remote reset also
EG 578 7 EMT 3 single-phase energy meter (local reset, direct/indirect
reading)
Technical characteristics
Rated voltage Un[V] a.c. 230 single-phase
Direct insertion current [A]
up to 32 (for EE);
up to 25 (for EMT 3)
Indirect insertion current [A] through A.T. (by choise) …/5A
Rated frequency [Hz] 50/60
Starting current [mA] 25
Accuracy rating [%] 2 (for EE);
4 (for EMT3)
Data storage through internal EEPROM
Power consumption [W] 1.7
Modules [No] 3
Standards IEC 61036
TEPM0299 TEPM0298
1234
Direct connection
L
N
1234
Connection
through A.T.
L
N
N.B.: not
connect A.T.
to neutral or
to earth
OEPM0073
EE series
kWh
Reset key
(press for almost
15 sec.)
kWh
Display
kWh Wh
MAX 25A
123456
L
N
230V ~
-20% +15%
50/60Hz
LOAD
Reset key
(press for almost
15 sec.)
123456
L
N
../5A
Wiring diagram up to 25A
with direct reading Wiring diagram with
reading through wound
primary current
transformer
kWh
Reset key
(press for almost
15 sec.)
123456
L
N
../5A
Wiring diagram with
reading by through
primary current
transformer
N.B.: EMT 3 meter does not consider
cosϕ different from 1
EMT 3 series
Measurement devices
Electronic single-phase and three-phase energy meters
Technical details .......................................... pg. 10/86 Overall dimensions ..................................... pg. 11/35
7/18
7
ABB SACE
In compliance with IEC 60364 Standard, it is necessary to insulate network electric circuits using
insulation transformers in installations intended for environments with special needs. Insulation
transformers protect from indirect contacts without breaking the circuit on the first fault to earth.
Isoltester-C
Using an internal microprocessor, this device enables the permanent insulation status testing between
the active parts of an IT electric system and the available conductive parts made equipotential to the
single earth system.
Code Type Description
EB 246 6 Isoltester-C measurement and testing of insulated networks at 230V a.c.
TEPM0449
Isoltester-C technical characteristics
Rated voltage Un[V] a.c.230(±15%)
Rated frequency [Hz] 50-60
Network voltage to be measured [V] a.c. 230
Alarm threshold [k] adjustable 50-100-250
Measuring circuit voltage [V] 15Vd.c
Load management current [mA] <0,6
Rated contact capacity In[A] 5A at 250V (ohmic)
Power consumption [W] 3
Modules [No] 6
Standards IEC/EN 61557-8
More Isoltester-C characteristics
green LED standard operation
yellow LED alarm (exceeded threshold)
red LED connection failure alarm
(between PC and sequential node)
OEPM0296
Measurement devices
Insulation monitors
Technical details .......................................... pg. 10/88 Overall dimensions ..................................... pg. 11/36
230V-50-60HZ INSULATED NETWORK230V-50-60HZ NETWORK
QSD 230/24-C
REMOTE INDICATION PANEL
ISOLTESTER-C
DEVICE
TO ANY
FURTHER
REMOTE QSD
230/24-C
INDICATION
PANELS
AVAILABLE RELAY
CONTACT
EQUIPOTENTIAL NODE
If the central socket is not available on the secondary of the insulation transformer (FC), the terminal 9 of
the ISOLTESTER-C device must be connected to a phase of the secondary.
To insert control of capacitive component of insulation impedance to earth, bond the terminals 10 and 11
of the device.
7/19
7
ABB SACE
Selvtester-C
It is used to test permanently the insulation status of very low safety voltage circuits (up to 24V).
Code Type Description
EB 247 4 Selvtester-C measurement and testing of insulated networks at 24V a.c./d.c.
QSD panels for remote signalling
They are installed in combination with insulation testers to remotely report the signalling generated
by these devices.
Code Type Description
EB 248 2 QSD 230/24-C remote signalling panel for box flush-mounting
E 503 (already included) for Isoltester-C and Selvtester-C (one per product)
TEPM0450
TEPM0302
Selvtester-C technical characteristics
Rated voltage Un[V] a.c./d.c. 24
Rated frequency [Hz] 50-60
Network voltage
to be measured [V] a.c. 24
Alarm threshold [k] adjustable 10 ... 60
Measuring circuit
voltage [V] < d.c 24
Load management current [mA] <1
Rated contact
capacity In[A] 1 (125V ohmic)
Power consumption [W] 10
Modules [No] 3
Standards IEC/EN 61557-8
More Selvtester-C characteristics
green LED standard operation
yellow LED alarm
QSD technical characteristics
Operating voltage [V] 24 d.c.
Measurement devices
Insulation monitors
OEPM0297
Technical details .......................................... pg. 10/88 Overall dimensions ..................................... pg. 11/36
230V-50-60Hz network 230V-50-60Hz insulated network
QSD 230/24-C remote indication panel
available relay
contact
ISOLTESTER-C
device
To any further
remote QSD
230/24-C
indication panels Equipotential node
8/1
8
ABB SACE
Other modular devices
Other modular functions
ABB SACE
Contents
TM/TS bell transformers ......................................................................................................8/2
Bells and buzzers ..................................................................................................................8/4
Modular sockets ...................................................................................................................8/5
M 9100 modular housing for CBK pushbuttons .................................................................8/6
8/2
8
ABB SACE
Other modular functions
TM/TS bell transformers
Technical details .......................................... pg. 10/89 Overall dimensions ..................................... pg. 11/38
These transformers with secondary in very low safety voltage for feeding bells (discontinuous use)
are available in 4 series:
- failure-proof (TM series)
- short-circuit proof not by construction (TS8 series)
- short-circuit proof not by construction with switch 0-1
(TS8/SW series)
- short-circuit proof not by construction (TS16/TS24 series).
Code Type Description
Failure-proof transformers
EA 260 8 TM10/12 sec. 4-8-12V (10VA discontinuous)
EA 261 6 TM10/24 sec. 12-24V (10VA discontinuous)
EA 262 4 TM15/12 sec. 4-8-12V (15VA discontinuous)
EA 263 2 TM15/24 sec. 12-24V (15VA discontinuous)
EA 264 0 TM30/12 sec. 4-8-12V (30VA discontinuous)
EA 265 7 TM30/24 sec. 12-24V (30VA discontinuous)
EA 266 5 TM40/12 sec. 4-8-12V (40VA discontinuous)
EA 267 3 TM40/24 sec. 12-24V (40VA discontinuous)
Short-circuit transformers not by construction TS 8 series
EA 269 9 TS8/8 sec. 8V (8VA)
EA 270 7 TS8/12 sec. 12V (8VA)
EA 271 5 TS8/24 sec. 24V (8VA)
Short-circuit transformers not by construction with switch 0-1
EA 272 3 TS8/8SW sec. 8V (8VA)
EA 273 1 TS8/12SW sec. 12V (8VA)
EA 274 9 TS8/24SW sec. 24V (8VA)
EA 275 6 TS8/4-6-8SW sec. 4-6-8V (8-12-16VA)
EA 276 4 TS8/4-8-12SW sec. 4-8-12V (5.3-10.7-16VA)
Short-circuit transformers not by construction TS16/TS24 series
EA 277 2 TS16/8 sec. 8 V (16 VA)
EA 278 0 TS16/12 sec. 12 V (16 VA)
EA 279 8 TS16/24 sec. 24 V (16 VA)
EA 280 6 TS16/4-6-8 sec. 4-6-8 V (8-12-16 VA)
EA 281 4 TS16/4-8-12 sec. 4-8-12 V (5.3-10.7-16 VA)
EA 282 2 TS24/4-8-12 sec. 4-8-12 V (8-16-24 VA)
EA 283 0 TS24/8-12-24 sec. 8-12-24 V (8-16-24 VA)
Technical characteristics
Primary rated voltage Un[V] a.c. 230
Secondary rated voltage Un[V] 4, 6, 8, 12, 24
Rated frequency [Hz] 50
Power consumption [VA] 8, 10, 15, 16, 24, 30, 40
(discontinuous service)
Power consumption [W] 1.. 4
Modules [No] 2, 3
Standards EN 61558-1/2-8
TEPM0315
TEPM0314
TEPM0311
TEPM0312
TEPM0313
8/3
8
ABB SACE
Technical details .......................................... pg. 10/89 Overall dimensions ..................................... pg. 11/38
Other modular functions
TM/TS bell transformers
TS16/4-8-12
5
8
1 4
~ 50Hz 230V
7
6
12V~ 16VA
8V~
10,6VA
4V~
5,3VA
t 40°C/B
a
TS8/4-6-8 SW
5
8
1 4
~ 50Hz 230V
7
6
8V~ 8VA
6V~ 6VA
4V~ 4VA
t 40°C/B
a
TS16/4-6-8
5
8
1 4
~ 50Hz 230V
7
6
8V~ 16VA
6V~ 12VA
4V~ 8VA
t 40°C/B
a
TS8/4-8-12 SW
5 8
4 4
12V~
~ 50Hz 230V
7
8VA
8V~
5,3VA 4V~
2,7VA
t 40°C/B
a
TM40/24
811
2 5
24V~
~ 50Hz 230V
7
40VA
12V~
20VA 12V~
20VA
t 40°C/B
a
F
TM40/12
811
2 5
12V~
~ 50Hz 230V
7
40VA
8V~
27VA 4V~
13VA
t 40°C/B
a
F
TM30/12
811
2 5
12V~
~ 50Hz 230V
10
30VA
8V~
20VA 4V~
10VA
t 40°C/B
a
F
TM30/24
811
2 5
24V~
~ 50Hz 230V
10
30VA
12V~
15VA 12V~
15VA
t 40°C/B
a
F
TS16/24
5 8
1 4
~ 50Hz 230V
24V~ 16VA
t 40°C/B
a
TS24/4-8-12
8
11
2 5
~ 50Hz 230V
10
9
12V~ 24VA
8V~ 16VA
4V~ 8VA
t 40°C/B
a
TS16/12
5 8
1 4
~ 50Hz 230V
12V~ 16VA
t 40°C/B
a
TM15/24
5 8
1 4
24V~
~ 50Hz 230V
7
15VA
12V~
7,5VA 12V~
7,5VA
t 40°C/B
a
F
TM15/12
5 8
1 4
12V~
~ 50Hz 230V
7
15VA
8V~
10VA 4V~
5VA
t 40°C/B
a
F
TM10/12
5 8
1 4
12V~
~ 50Hz 230V
7
10VA
8V~
6.66VA
4V~
3.33VA
t 40°C/B
a
F
TM10/24
5 8
1 4
24V~
~ 50Hz 230V
7
10VA
12V~
5VA 12V~
5VA
t 40°C/B
a
F
TS16/8
5 8
1 4
~ 50Hz 230V
8V~ 16VA
t 40°C/B
a
TS24/8-12-24
8
11
2 5
~ 50Hz 230V
10
9
24V~ 24VA
12V~ 12VA
8V~ 8VA
t 40°C/B
a
TS8/8 SW
5 8
1 4
~ 50Hz 230V
8V~ 8VA
t 40°C/B
a
TS8/12 SW
5 8
1 4
~ 50Hz 230V
12V~ 8VA
t 40°C/B
a
TS8/24 SW
5 8
1 4
~ 50Hz 230V
24V~ 8VA
t 40°C/B
a
TS8/8
5 8
1 4
~ 8V
~ 50Hz 230V
t 40°C/B
a
8VA
TS8/12
5 8
1 4
~ 12V
~ 50Hz 230V
t 40°C/B
a
8VA
8VA
TS8/24
5 8
1 4
~ 24V
~ 50Hz 230V
t 40°C/B
a
OEPM080
Wiring diagram and marking information
8/4
8
ABB SACE
Other modular functions
Bells and buzzers
Overall dimensions ...................................... pg. 11/38
Characterized by discontinuous use through one or more pushbuttons, bells and buzzers are suitable
for public and tertiary acustic signalling.
Code Type Description
SM 1 electro-mechanical bells
EA 425 7 SM1/12 modular bell in 1 module - 12V a.c.
EA 426 5 SM1/230 modular bell in 1 module - 230V a.c.
RM1 buzzers
EA 427 3 RM1/12 modular buzzer in 1 module - 12V a.c.
EA 428 1 RM1/230 modular buzzer in 1 module - 230V a.c.
Electronic bell + TSM transformer (two-tones)
EA 414 1 TSM modular bell in 2 modules 12V a.c. (with built-in
10VA transformer)
Bell + buzzer + TSR transformer
EA 429 9 TSR transformer with built-in bell and buzzer 24V a.c. (2 modules)
Technical characteristics
Rated voltage Un[V] 12, 230
Rated frequency [Hz] 50
Power consumption [W] 3.6 (12V) ; 5.5 (230V); 6 (24V)
Modules [No] 1, 2
TEPM0317
TEPM0316
5678
TSM
1234
230V
N
L
5678
TSR
1234
230V
N
L
24V 24V
OEPM0081
TEPM0451
8/5
8
ABB SACE
Other modular functions
Modular sockets
Overall dimensions ...................................... pg. 11/38
Code Type Description
Bipolar socket + T with protected alveolous
EA 944 7 M 1173 10/16A 250V (Italian & Unel standard)
EA 945 4 M 1174 16A 250V (French standard)
EA 943 9 E 1175 10/16A 250V (German standard)
EA 942 1 E 1175-C 10/16A 250V (German standard) with cover
TEPM0319
Technical characteristics
Rated voltage Un[V] a.c. up to 250
Reted current In[A] 10/16
Rated frequency [Hz] 50/60
Power consumption [W] 0.6
Modules [No] 2.5
Standards IEC 60884-1
TEPM0452
8/6
8
ABB SACE
Other modular functions
M 9100 modular housing for CBK pushbuttons
Overall dimensions ...................................... pg. 11/39
Through an appropriate kit, this housing makes control and signalling units Ø22 CBK series for
industrial use (pushbuttons, indicators, selectors, etc.) uniform to modular devices according to DIN
rail.
Code Type Descriptiion
EA 947 0 M 9100 kit for modular housing (2 modules)
For detailed description of the industrial devices that can be installed using this kit, see Technical
catalogue 603356.
TEPM0320
9/1
ABB SACE
9
Unifix cabling system
Contents
Introduction ...........................................................................................................................9/2
Unifix H ...................................................................................................................................9/4
Unifix L ...................................................................................................................................9/5
Unifix SL .................................................................................................................................9/6
Unifix H system components ...............................................................................................9/7
Unifix L system components ............................................................................................... 9/9
Unifix SL system components ...........................................................................................9/11
9/2 ABB SACE
9
Unifix cabling system
Introduction
Unifix cabling system:
the ideal complement for the System pro M
range
Unifix is the ABB cabling system which makes the work of installers
and switchboard builders easier: with its standard connectors,
Unifix effects simple, quick and safe wiring of System pro M mo-
dular devices and SACE Isomax S1 and S2 and Tmax T1…T3
moulded-case circuit-breakers in ArTu® switchboards and ABB
consumer units.
For this reason, it is the ideal solution for using pro M modular
products to best advantage and exploiting the fact that ABB
products for low voltage applications can be perfectly integrated
whilst at the same time guaranteeing safety and full compliance
with Standards.
The system consists of three series H, L and SL. Each one is
suitable for specific applications both for the installation of devices
and installation in switchboards. In detail:
-the H series, intended for more demanding applications, is used
for wiring SACE Isomax S1 and S2 and Tmax T1…T3 moulded-
case circuit-breakers and System pro M modular devices in
ArTu® switchboards (rated currents up to 400A and short-circuit
currents up to 50kA);
-the L series is the universal solution for wiring System pro M
modular devices in ArTu® switchboards and polycarbonate
consumer units (rated currents up to 100A and short-circuit
currents up to 25kA);
-the SL series is the ideal easy and cheap solution for wiring
bipolar modular devices in consumer units (rated currents up to
40A and short-circuit currents up to 10kA).
Special features
The main feature of Unifix lies with the possibility of combining
different types of circuits (one-phase/three-phase/auxiliary) in a
single module. Pre-wiring can be effected at the workbench and
installed in the switchboard subsequently, with no limits to the type
or combination of devices which can be installed.
Unifix has adjustable pitch which replaces traditional wiring
harnesses which means that circuit-breakers with different polarities
can be placed in the same row as well as auxiliary modular devices.
The fact that Unifix integrates perfectly with the different ABB low
voltage products, both modular and moulded-case devices,
switchboards or insulating consumer units, ensures that all devices
and accessories can be quickly selected and installed.
N.B. The Unifix cabling system can be used with ABB SACE
devices only.
9/3
ABB SACE
9
ONE SYSTEM, MANY ADVANTAGES
Considerable reduction in wiring times: by using rigid lock con-
nectors which are standardized for the different types of device,
each device does not have to be connected using cables
Greater standardization of low voltage switchboards: the rigid
connectors enable the results of the type tests (overheating and
short-circuit) effected by ABB to be extended also on input wiring
of devices.
A more advanced and, at the same time, cheaper technical
solution compared with traditional wiring. This is made possible
by cutting down on materials (wires and wire terminals) and space
required, thus affecting operating times
Can be used on all ABB standard devices, without modifying or
adding accessories and without using special equipment
Adjustable pitch: Unifix uses adjustable pitch unlike traditional
wiring harnesses; in this way, circuit-breakers with different polar-
ity can be placed in the same row as well as auxiliary devices
Unifix cabling system
Introduction
1
2
3
4
5
9/4 ABB SACE
9
Unifix cabling system
Unifix H
Unifix H: for more demanding applications
The Unifix H version is for wiring moulded-case circuit-breakers
ranging from the innovative Tmax T1, T2 and T3 to the traditional
Isomax S1 and S2, and the System pro M modular devices in ArTu®
switchboards, with rated currents up to 250A (400A in input on the
busbars) and short-circuit currents up to 50kA.
The system enables moulded-case circuit-breakers (different sizes,
with residual current release and/or solenoid operator alongside) and
modular devices, with relative accessories, to be installed in the same
row by using standard base modules to connect each device.
TECHNICAL CHARACTERISTICS
Tetrapole frames
The frames consist of a system of busbars (25x5mm section ED2183,
ED2191) with 400A capacity and 50kA short-circuit current. The
basic modules used to connect the devices are fixed to this structure
and, with the power supply module, enable:
- direct supply of the bases using the supply module (ED2209)
- supply with main circuit-breaker in the row using a special base
module.
The frames, which can be installed in the 600 and 800mm wide
ArTu switchboards, are available in 24 and 36 module widths. They
are fixed to the structure with a special kit AD1060 for the module
H=200mm or AD1061 for the module H=300mm.
Power supply module
The 400A power supply module (L1-L2-L3-N) is attached to the
rear side of the frames without using space required for mounting
the devices on the front. The supply module can be directly
connected (using the drivescrew AD1064) to the 400/
800A busbar system installed on the bottom of the
cabinet.
Base modules for devices
The modules mechanically support the devices and electrically
connect them with the distribution busbars in the frames. The
modules for the System pro M modular devices are all one-pole
sized (ie. they take up only one DIN module); to connect one-pole,
two-pole, three-pole or four-pole circuit breakers, one, two, three or
four one-pole bases alongside are used respectively.
Each module connects a phase and is identified by the corresponding
letter (L1, L2, L3, N) or, for 1P+N circuit-breakers (1 module), by
L1+N, L2+N, L3+N. The modules for connecting the moulded-case
circuit-breakers Tmax T1, T2, T3 and Isomax S1, S2 are available in
one-pole versions, and together can be used to obtain three-pole or
four-pole versions or as a false pole for installing the residual current
release alongside. The modules are available in versions with a
capacity of up to 40 and 63A with top-down or bottom-up supply
systems and in versions with cable (L1+N o L1+L2) for connecting
auxiliary elements. For Tmax circuit-breakers equipped with solenoid
operator, the relative false module is necessary.
Completion accessories
The system is complemented with “false pole” modules which cover
the modules which are not occupied by devices or are placed
alongside devices which are wired in the traditional manner. There is
also a protective cover, which guarantees IP20 protection on the
horizontal distribution busbars in the sections where devices are not
installed.
9/5
ABB SACE
9
Unifix L: the universal solution for
switchboards and consumer units
With its special features, the Unifix L version is extremely versatile
in its use and meets the demands of installations which vary a
great deal with regard to function and size.
Unifix L is suitable for wiring System pro M modular devices in
ArTu® switchboards and ABB polycarbonate consumer units, for
rated currents up to 100A and short-circuit currents up to 25kA.
The devices are supplied top-down by way of special standard
rigid connectors.
TECHNICAL CHARACTERISTICS
Busbars
The busbars consist of a support which contains a system of 100A
capacity conductors (central supply) and 25kA short-circuit current
(conditioned). They are available in two-pole and four-pole versions
for widths of 12, 18, 24 or 36 modules which can be installed in
the ArTu switchboards with widths of 400, 600 and 800mm
respectively (18 modules excluded). Fixing is carried out by dove-
tailing on the rear of the DIN rail (GD4002 - GD6002 and GD8002),
and installation is in two modules with H=200mm.
The busbar system is structured in such a way that it is possible
to attach AD1009 special supports for ducts with max. dimensions
60x80mm on the rear.
Power supply module with cable
The 63A power supply module can be inserted directly in the busbar
conductors in the two-pole and four-pole versions. Its dimensions
are equivalent to two base modules (17.5 mm) and direct supply
the busbars when there is no main circuit-breaker in the row.
The four-pole version, with a cross-section of 16mm2, is supplied
with the following cable lengths:
- 250mm (ED3090);
- 400mm (ED3405);
- 800mm (ED3413);
- 1500mm (ED3439).
Power supply module without cable
The one-pole 100A supplier module in the L1, L2, L3, N versions
(ED3101-ED3102-ED3103-ED3104) is directly inserted in the
busbar conductors. Its dimensions are equivalent to a base module
(17.5 mm) and it directly supplies the busbars when there is no
main circuit-breaker in the row. It is equipped with a terminal which
enables connection of a conductor with a cross-section of 35mm2.
Power supply terminals
The one-pole 100A supply terminal (ED3100) is directly connected
to the front terminals of any ABB SACE modular circuit-breaker so
that the busbars can be supplied by way of the main row breaker.
It is equipped with a terminal which enables connection of a
conductor with a cross-section of 35mm2.
The one-pole 63A supply terminal (ED3140) has the same features
as the other terminal and is equipped with a terminal which enables
connection of a conductor with a cross-section of 25mm2.
Connections for devices
The connections consist of insulated copper busbars, cut and bent
to size. They supply each terminal of the System pro M modular
devices and the busbar system. The connections are supplied
according to the polarity of the device which must be wired
(connectors are available for L1, L2, L3, N and in the version for
1P + N devices in a DIN module). Supports with a cable are also
available for supplying auxiliary devices so that devices on the same
row can be wired to the modular circuit-breakers.
Unifix cabling system
Unifix L
9
9/6 ABB SACE
9
Unifix SL: simple and cheap, ideal for small
applications
Unifix SL is a simplified cheaper version of the L version for wiring
System pro M bipolar modular devices in all ABB consumer units
with rated currents up to 40A and short-circuit currents up to 10kA.
Unifix SL, which has all the advantages of the L version (adjustable
pitch, standard connectors etc.), is the ideal solution for domestic
consumer units and other similar consumer units. Its structure is
extremely compact since the bases are only bipolar. As a result, it
takes up very little space and is easily installed even in the smallest
of consumer units. The devices are always supplied top-down.
The three elements in the SL version system, like the L version,
are the busbars, the supply terminals and the rigid connectors
and supports with cables for the system pro M modular devices.
A simple DIN rail which is supplied with the consumer units must
be used.
TECHNICAL CHARACTERISTICS
Busbars
The busbars consist of a support, containing a system of horizontal
copper ducts. They are only available in the bipolar version (L1+N)
and lengths of 8, 12 and 18 modules. They are mounted in the
special housing supplied in all ABB consumer units for the wall-
mounting type and with the relative supports for the flush-mounting
version.
Power supply terminals
These are used when there is no main circuit-breaker in the row
with bottom-up supply. They can be directly connected to the front
terminals of any System pro M circuit-breaker in the row.
The terminal must have IP20 protection during wiring.
Standard connections for supplying devices
The connections consist of insulated copper busbars, cut and bent
to size. They supply each terminal of the System pro M modular
circuit-breakers and the system of ducts in the busbars. One
end is dove-tailed on the ducts in the busbar whereas the
other end is attached to the circuit-breaker terminal. The
connections are supplied in L1, N polarity and in the versio-
n for 1P + N devices in a DIN module. Supports with a
cable are also available to supply auxiliary devices and
connect these devices on the same row with the modular
circuit-breakers.
Unifix cabling system
Unifix SL
9/7
ABB SACE
9
Unifix cabling system
Unifix H system components
Code Description Pck./pieces
Unifix H
Frames for Tmax and Isomax
ED2183 Frame with busbars 24 DIN modules (W=600mm) 1/1
ED2191 Frame with busbars 36 DIN modules (W=800mm) 1/1
Frames for Isomax only
ED2506 Frame with busbars 24 DIN modules (W=600mm) 1/1
ED2514 Frame with busbars 36 DIN modules (W=800mm) 1/1
Power supply modules
ED2209 Supply module 4P 400A (for ED2183-ED2191) 1/1
ED2522 Supply module 4P 400A (for ED2506-ED2514) 1/1
Base modules In 16A
ED2894 Auxiliary base modules DIN L1-N top-down 16A 1/12
ED2902 Auxiliary base modules DIN L1-L2 top-down 16A 1/12
ED2910 Auxiliary base modules DIN L1-N bottom-up 16A 1/12
ED2928 Auxiliary base modules DIN L1-L2 bottom-up 16A 1/12
Base modules In 40A
ED2613 Base modules L1 top-down 40A 1/12
ED2621 Base modules L2 top-down 40A 1/12
ED2639 Base modules L3 top-down 40A 1/12
ED2647 Base modules neutral top-down 40A 1/12
ED2654 Base modules L1/neutral top-down 40A 1/12
ED2662 Base modules L2/neutral top-down 40A 1/12
ED2670 Base modules L3/neutral top-down 40A 1/12
ED2688 Base modules L1 bottom-up 40A 1/12
ED2696 Base modules L2 bottom-up 40A 1/12
ED2704 Base modules L3 bottom-up 40A 1/12
ED2712 Base modules neutral bottom-up 40A 1/12
Base modules In 63A
ED2530 Base modules L1 top-down 63A 1/12
ED2548 Base modules L2 top-down 63A 1/12
ED2555 Base modules L3 top-down 63A 1/12
ED2563 Base modules neutral top-down 63A 1/12
ED2571 Base modules L1 bottom-up 63A 1/12
ED2589 Base modules L2 bottom-up 63A 1/12
ED2597 Base modules L3 bottom-up 63A 1/12
ED2605 Base modules neutral bottom-up 63A 1/12
Base modules In 100A
ED2720 Base modules with cable L1 top-down 100A 1/12
ED2738 Base modules with cable L2 top-down 100A 1/12
ED2746 Base modules with cable L3 top-down 100A 1/12
ED2753 Base modules with cable neutral top-down 100A 1/12
ED2507
ED2506
ED2515
ED2514
ED2209
ED....
ED....
ED27..
VTQD0136
9/8 ABB SACE
9
Unifix cabling system
Unifix H system components
Code Description Pck./Pieces
Unifix H
Base modules In 160A Tmax T1
ED2217 Base modules L1 top-down L2 bottom-up 1/12
ED2225 Base modules L2 top-down L1 bottom-up 1/12
ED2233 Base modules L3 top-down neutral bottom-up 1/12
ED2241 Base modules Neutral top-down L3 bottom-up 1/12
ED2373 Base modules false pole for residual releaser 1/1
ED2381 Base modules false pole for solenoid control 1/3
Base modules In 125A Isomax S1
ED2761 Base modules L1 top-down L2 bottom-up 1/12
ED2779 Base modules L2 top-down L1 bottom-up 1/12
ED2787 Base modules L3 top-down neutral bottom-up 1/12
ED2795 Base modules Neutral top-down L3 bottom-up 1/12
ED2860 Base modules false pole for residual releaser Isomax RC 1/3
Base modules In 160A Tmax T2
ED2258 Base modules L1 top-down L2 bottom-up 1/12
ED2266 Base modules L2 top-down L1 bottom-up 1/12
ED2274 Base modules L3 top-down N bottom-up 1/12
ED2282 Base modules N top-down L3 bottom-up 1/12
ED2373 Base modules false pole for residual releaser 1/1
ED2399 Base modules false pole for solenoid control 1/3
Base modules In 160A Isomax S2
ED2803 Base modules L1 top-down L2 bottom-up 1/12
ED2811 Base modules L2 top-down L1 bottom-up 1/12
ED2829 Base modules L3 top-down N bottom-up 1/12
ED2837 Base modules N top-down L3 bottom-up 1/12
ED2878 Base modules false pole for residual releaser Isomax RC 1/3
Base modules In 250A Tmax T3
ED2290 Base modules L1 top-down 1/12
ED2308 Base modules L2 top-down 1/12
ED2316 Base modules L3 top-down 1/12
ED2324 Base modules N top-down 1/12
ED2332 Base modules L1 bottom-up 1/12
ED2340 Base modules L2 bottom-up 1/12
ED2357 Base modules L3 bottom-up 1/12
ED2365 Base modules N bottom-up 1/12
ED2373 Base modules false pole for residual releaser 1/1
Accessories
ED2845 Base modules false pole for DDA 1/12
ED2852 Base modules false pole for MDRCs 1/12
ED2407 N°2 IP20 covers (for ED2183-ED2191) W=173 mm (10 mod.DIN) 1/6
ED2886 N°2 IP20 covers (for ED2506-ED2514) W=173 mm (10 mod.DIN) 1/6
ED2936 N°6 duct supports 1/6
AD1060 Kit for ArTu without segregation width 600/800mm 1/1
with front modular panel H=200mm
AD1061 Kit for ArTu without segregation width 600/800mm 1/1
with front modular panel H=300mm
PM2624 Front modular panel 200x600mm (hxw) 1/1
PM3624 Front modular panel 300x600mm (hxw) 1/1
PM2836 Front modular panel 200x800mm (hxw) 1/1
PM3886 Front modular panel 300x800mm (hxw) 1/1
ED2407
ED2860
ED2878
PM....
AD....
In125A
In160A
ED2899
ED2825
ED2775
In250A
VTQD0137
9/9
ABB SACE
9
Unifix cabling system
Unifix L system components
Code Description Pck./Pieces
Unifix L
2-pole busbars
ED2993 Busbars 100A 2P 12 modules (W=400mm) 1/6
ED3017 Busbars 100A 2P 24 modules (W=600mm) 1/6
ED3025 Busbars 100A 2P 36 modules (W=800mm) 1/6
4-pole busbars
ED2944 Busbars 100A 4P 12 modules (W=400mm) 1/6
ED2969 Busbars 100A 4P 24 modules (W=600mm) 1/6
ED2977 Busbars 100A 4P 36 modules (W=800mm) 1/6
Busbars for ABB consumer units
ED2985 8 module busbars 100A 2P 1/6
ED3009 18 module busbars 100A 2P 1/6
ED2951 18 module busbars 100A 4P 1/6
Connections for different devices
ED3108 Supports with 2 cables 16A 1/6
ED3116 Supports with 3 cables 16A 1/6
ED3124 Supports with 4 cables 16A 1/6
Connections for devices
ED3355 Connections with 2 cables 40A 1/6
ED3363 Connections with 3 cables 40A 1/6
ED3371 Connections with 4 cables 40A 1/6
ED3074 Connections 1p+N 40A for DS121 1 mod. 1/10
ED3272 Connections L1-N 40 A for S9..1N neutral on right 1/10
ED3280 Connections L2-N 40 A for S9..1N neutral on right 1/10
ED3298 Connections L3-N 40 A for S9..1N neutral on right 1/10
ED3033 Connections L 1 100A 1/10
ED3041 Connections L 2 100A 1/10
ED3058 Connections L 3 100A 1/10
ED3066 Connections N 100A 1/10
ED3132 Power supplies with cable 4P 100A for disconnector 1/6
Power supply modules with cable In 63A
ED3082 Supply modules 2P 63A with cable W=250mm 1/6
ED3090 Supply modules 4P 63A with cable W=250mm 1/6
ED3405 Supply modules 4P 63A with cable W=400mm 1/6
ED3413 Supply modules 4P 63A with cable W=800mm 1/6
ED3439 Supply modules 4P 63A with cable W=1500mm 1/6
Power supply without cable In 100A
ED3101 One-pole supply modules L 1 1/10
ED3102 One-pole supply modules L 2 1/10
ED3103 One-pole supply modules L 3 1/10
ED3104 One-pole supply modules N 1/10
N L
N L3 L2 L1
2 poli
4 poli
ED....
ED3124
ED3066
ED3041
ED3033
ED3058
ED3104
ED3103
ED3102
ED3101
ED3090
VTQD0138
2 poles
2 poles
9/10 ABB SACE
9
Code Description Pck./Pieces
Unifix L
Accessories
ED3100 Supply terminals 100A for 35mm2 cable 1/10
ED3140 Supply terminals 63A for 25mm2 cable 1/10
GD6001 DIN rail kit and wall-mounting ArTu M W=600mm 1/1
GD8003 DIN rail kit and wall-mounting ArTu M W=800mm 1/1
GD4002 DIN rail kit and ArTu K without segregation supports W=400mm 1/1
GD6002 DIN rail kit and supports for wall-mounting ArTu M floor and
ArTu K without segregation W=600mm 1/1
GD8002 DIN rail kit and supports for wall-mounting ArTu M floor and
ArTu K without segregation W=800mm 1/1
PM2424 Front modular panel 200x400mm (hxw) 1/1
PM2624 Front modular panel 200x600mm (hxw) 1/1
PM2836 Front modular panel 200x800mm (hxw) 1/1
ED3100
GD....
PM....
VTQD0149
Unifix cabling system
Unifix L system components
9/11
ABB SACE
9
BUSBAR
CONNECTIONS
Code Type Description Pck./Pieces
Unifix SL
ED 315 7 XUSLT08 USL busbar 2P 8 modules 6
ED 316 5 XUSLT12 USL busbar 2P 12 modules 6
ED 317 3 XUSLT18 USL busbar 2P 18 modules 6
ED 324 9 XUSLT08+1 USL busbar 2P 8+1 modules 6
ED 325 6 XUSLT12+1 USL busbar 2P 12+1 modules 6
ED 326 4 XUSLT18+1 USL busbar 2P 18+1 modules 6
ED 318 1 XUSL1V USL set connections L1 (10 pieces) 6
ED 319 9 XUSLNV USL set connections N (10 pieces) 6
ED 320 7 XUSL1NT USL set connections L1N (10 pieces) 6
ED 333 0 XUSLP1NR USL set connections L1N for S9..1N (10 pieces) 6
ED 321 5 XUSLPP Parallel supplier 2P 40A 6
ED 322 3 XUSLX Support with 2 cables 16A for aux. 6
ED 314 0 XULM Supply terminal (10 pieces) 6
Unifix cabling system
Unifix SL system components
10/1
10
ABB SACE
Technical details
Contents
MCBs ....................................................................................................................................10/3
RCDs ..................................................................................................................................10/39
Other protection devices ..................................................................................................10/47
Command devices ............................................................................................................10/63
Load management devices ..............................................................................................10/73
Measurement devices ......................................................................................................10/81
Other modular functions ..................................................................................................10/89
10/2 ABB SACE
10/3
10
ABB SACE
Technical details
MCBs
Contents
Tripping characteristics ......................................................................................................10/4
Limitation of specific let-through energy .........................................................................10/7
Ip peak current ..................................................................................................................10/11
Selectivity between ABB circuit-breakers tables ..........................................................10/21
Internal resistances and dissipated power tables .........................................................10/33
Influence of ambient temperature on effective capacity and rated current ................10/35
Variation in alarm thresholds according to network frequency ...................................10/37
Applications in d.c. of standard circuit-breakers ...........................................................10/37
Examples of maximum voltages allowed between terminals according to
number of poles and wiring .............................................................................................10/38
Examples of high voltages between terminals and earth
with equal voltage between terminals ............................................................................10/38
10/4
10
ABB SACE
Technical details
MCBs
Description of product and codes ................. pg. 2/1
Tripping characteristics
According to the specific uses of the different types of circuit-breakers, the respective thermal and
electromagnetic relays are designed and regulated to effect the most widely requested current/time
tripping characteristics.
The following table shows the main general and specific tripping characteristics, with reference to the
circuit-breakers supplied by ABB SACE, as indicated in the table.
Series Characteristic
B C D K Z E sel.
S 941 N In=6…40A In=2...40A - - - -
S 951 N In=6…40A In=2...40A - - - -
S 971 N In=6…40A In=2...40A - - - -
S 240 - In=6...40A - - - -
S 250 In=6...63A In=0.5...63A - In=0.5...63A - -
S 270 In=6...63A In=0.5...63A In=0.5...63A In=0.5...63A - -
S 280 In=6...63A In=6...63A In=6...63A In=6...63A In=0.5...63A -
S 280 UC In=6...63A In=0.5...63A - In=0.5...63A In=0.5...63A -
S 290 - In=80...125A In=80…100A - - -
S 500 In=6...63A In=6...63A In=6...63A In=0.1...45A - -
S 500 UC In=6...63A - - In=0.1...45A - -
S 700 - - - - - In=25...100A
Versions without magnetic release are available on request.
Characteristics B-C-D
Tripping characteristics according to IEC/EN 60898 Standard. Rated currents from 6 to 63A in 10
different values (char. B) and from 0.5 to 63A in 16 different values (char. C, D).
These characteristics enable direct coordination of the circuit-breaker in relation to the capacity of
the cables Iz, according to IEC 60364.
The following coordination conditions apply:
Ib < In < Iz; If < 1.45 Iz, where:
Ib = circuit operating current
In = circuit-breaker rated current
Iz = capacity of cables
If = circuit-breaker operating current within conventional time.
MCBs with characteristic B are supplied for protecting resistive loads and long lines; MCBs with
characteristic C are used to protect circuits with resistive loads and small inductive loads; MCBs with
characteristic D are used for highly inductive loads or loads with high start currents.
10/5
10
ABB SACE
Description of product and codes ................. pg. 2/1
Technical details
MCBs
Tripping characteristic BCD
Standard IEC/EN 60898 IEC/EN 60898 IEC/EN 60898
Rated current In 6…63A 0.5…125A 0.5…100A
Thermal trip
Test currents:
non-tripping current Inf 1.13In 1.13In 1.13In
non-tripping time >1h >1h (up to 63A) > 2h (> 63A)
tripping current If 1.45 In 1.45 In 1.45 In
tripping time < 1h < 1h (up to 63A) < 2h (> 63A)
Electro-magnetic trip
Test currents:
non-tripping current Im1 3In 5In 10In
non-tripping time > 0.1s > 0.1s > 0.15s
tripping current Im2 5In 10In 20In
tripping time < 0.1s < 0.1s < 0.15s
multiples of rated current
Seconds Minutes
1 1.5 2 3 4 5 6 8 10 15 20 30
0.01
0.02
0.04
0.06
0.1
0.2
0.4
0.6
1
2
4
6
10
20
40
1
2
4
6
10
20
40
60
120
1.13
c.a. (a.c.)
c.c. (d.c.)
7.553
1.45
multiples of rated current
Seconds Minutes
1 1.5 2 3 4 5 6 8 10 15 20 30
0.01
0.02
0.04
0.06
0.1
0.2
0.4
0.6
1
2
4
6
10
20
40
1
2
4
6
10
20
40
60
120
1.13
510
c.a (a.c.)
c.c. (d.c.)
1.45
15
multiples of rated current
Seconds Minutes
1 1.5 2 3 4 5 6 8 10
0.01
0.02
0.04
0.06
0.1
0.2
0.4
0.6
1
2
4
6
10
20
40
1
2
4
6
10
20
40
60
120
1.13
15 20 30 40 50
c.a. (a.c.)
c.c. (d.c.)
1.45
10 20 30
Characteristic B Characteristic C Characteristic D
OEPM0086
OEPM0087
OEPM0088
10/6
10
ABB SACE
Technical details
MCBs
Description of product and codes ................. pg. 2/1
Characteristics K-Z-E selective
Tripping characteristics according to DINVDE 0660. Rated currents from 0.5 to 63A, in 16 different
values.
They are used to control and protect inductive circuits, power suppliers for semi-conductor electronic
circuits and secondary measurement circuits, in the commercial and industrial sectors.
Tripping characteristic K Z E selective
Standard DIN VDE 0660 DIN VDE 0660 DIN VDE 0660
9.82 part 1 9.82 part 1
Rated current In 0.5…63A 0.5…63A 25…100A
Thermal trip
Test currents:
non-tripping current Inf 1.05In 1.05In 1.05In
non-tripping time >2h >2h >2h
tripping current If 1.2In 1.2In 1.2In
tripping time < 2h < 2h < 2h
Electro-magnetic trip
non-tripping current Im1 8In 2In 5In
non-tripping time > 0.2s > 0.2s > 0.3s
tripping current Im2 14In 3In 6.25In
tripping time < 0.2s < 0.2s < 0.3s
multiples of rated current
Seconds Minutes
1 1.5 2 3 4 5 6 8 10 15 20 30
0.01
0.02
0.04
0.06
0.1
0.2
0.4
0.6
1
2
4
6
10
20
40
1
2
4
6
10
20
40
60
1201.05
c.a. (a.c.)
c.c. (d.c.)
1.2
2 3 4.5
Seconds Minutes
100
60
40
20
10
6
4
2
1
40
20
10
6
4
2
1
0
.
6
0
.
4
0
.
2
0
.
1
0
.
06
0
.
04
0
.
02
0
.
01 2 3 4 5 6 8 10 20 30 4050
Tripping time delay
multiples of rated current
1
1.05
1.2
Characteristic K Characteristic Z Characteristic E
selective
multiples of rated current
Seconds Minutes
1 1.5 2 3 4 5 6 8 10 15 20 30
0.01
0.02
0.04
0.06
0.1
0.2
0.4
0.6
1
2
4
6
10
20
40
1
2
4
6
10
20
40
60
120
1.05
c.a. (a.c.)
c.c. (d.c.)
1.2
818
12
OEPM0089
OEPM0090
OEPM0091
10/7
10
ABB SACE
Description of product and codes ................. pg. 2/1
Technical details
MCBs
Limitation of specific let-through energy
Tripping of an installation circuit by circuit-breaker when there is a short-circuit requires a certain
amount of time depending on the characteristics of the circuit-breaker and the entity of the short-
circuit current. During this period of time, some or all of the short-circuit current flows into the installation;
the parameter I2t defines the “specific let-through energy”, ie. the specific energy that the breaker
allows through when there is a short-circuit current Icc during the tripping time t.
In this way, we can determine the capacity of a circuit-breaker to limit, ie. break high currents up to
the rated breaking power of the device, by reducing the peak value of the above-mentioned currents
to a value which is considerably lower than the estimated current.
This can be achieved using mechanisms which open very rapidly and have the following advantages:
- they limit the thermal and dynamic effects both on the circuit-breaker and on the protected circuit;
- they reduce the dimensions of the current-limiting circuit-breaker without reducing breaking capacity;
- they considerably reduce ionized gases and sparklers emitted during the short-circuit and therefore
they avoid the danger of ignition and fires.
I
U
I
2
tv
KM
i
iK
uM
uB
t = 0
2
Current limiting circuit-breaker
KM
t
t
t
t = 0
tv
I
U
I
2
1
iK
uM
uB
Non-current limiting circuit-breaker
OEPM0092
Oscillogram of short-circuit
breaks on two circuit-breakers:
1 = traditional non-current limiting circuit-
breaker
2 = current limiting circuit-breaker
uB = arc voltage (red)
uM = rest voltage (blue)
Short-circuit current
red = effective short-circuit current squared
blue = estimated short-circuit current squared
(shunted circuit-breaker)
iKM = maximum values of symmetrical
component of short-circuit current
squared
shaded in
red = specific let-through energy in two cases
10/8
10
ABB SACE
Technical details
MCBs
Description of product and codes ................. pg. 2/1
I2t diagrams - Specific let-through energy value I2t
The I2t curves give the values of the specific let-through energy expressed in A2s (A=amps; s=seconds)
in relation to the estimated short-circuit current (amp).
Specific let-through energy I
2
t (A
2
s)
10
2
10
3
10
4
10
5
10
6
10
7
10
Perspective short-circuit current (A)
2A
1.6A
1A
3A
4A
6A
10A
13/16A
20/25A
50/63A 32/40A
10
5
10
4
10
2
10
3
Specific let-through energy I
2
t (A
2
s)
10
2
10
3
10
4
10
5
10
6
10
7
10
Perspective short-circuit current (A)
2A
1.6A
1A
3A
4A
6/8A
10A
13/16A
20A
50/63A 28/32A
40A
10
5
10
4
10
2
10
3
S 941 N characteristic B
S 240…280 characteristics B and C S 240…280 characteristics K and D
OEPM0095
OEPM0096
OEPM0093
OEPM0094
S 941 N characteristic C
Specific let-through energy
I
2
t (A
2
s)
103
104
105
102
Perspective short-circuit current (kA)
10A
0,511,522,533,544,5
6A
20A
16A
32A
25A
40A
Specific let-through energy I
2
t (A
2
s)
10
3
10
4
10
5
10
2
Perspective short-circuit current (kA)
4A
2A
10A
0,5 1 1,5 2 2,5 3 3,5 4 4,5
6A
20A
16A
32A
25A
40A
10/9
10
ABB SACE
Description of product and codes ................. pg. 2/1
Technical details
MCBs
10
5
Specific let-through energy I
2
t (A
2
s)
10
4
10
2
10
2
10
3
10
4
10
5
10
6
10
7
10
Perspective short-circuit current (A)
10
3
2A
1.6A
1A
3A
4A
6A
10A
13/16A
50/63A 32/40A 20/25A
Specific let-through energy
I
2
t (A
2
s)
Perspective short-circuit current
(A)
10
4
10
3
10
3
10
4
10
5
10
6
10
7
1.5 10
4
100/125A
80A
S 280 characteristic Z S 290 characteristic C, D
S 500 characteristics B, C and D
Specific let-through energy I
2
t (A
2
s)
10
4
10
5
10
6
10
3
Perspective short-circuit current (A)
40A
25A 16A
10
5
10
4
10
2
10
3
13A
Specific let-through energy I
2
t (A
2
s)
10
4
10
5
10
6
10
3
Perspective short-circuit current (A)
63A
50A
10
5
10
4
10
2
10
3
OEPM0099
OEPM0100
OEPM0097
OEPM0098
10/10
10
ABB SACE
Technical details
MCBs
Description of product and codes ................. pg. 2/1
25A
35A
50A
63A
80A
100A
10
1
234 6810
2
2346810
3
2346810
4
23
10
3
2
3
4
6
10
4
8
2
3
4
6
2
10
5
3
4
6
8
10
6
2
8
I =
n
I =
n
25 A
35 A
50 A
63 A ... 100 A
100
80
63
50
35
25
5 SEC.
Perspective short-circuit current
Icc (A)
Specific let-through energy
I t (A s.)
22
S 700 characteristic E selective
Specific let-through energy I
2
t (A
2
s)
10-1
100
101
10-2
Perspective short-circuit current (A)
104
103
10 102105
102
0.1…0.15A
0.14…0.21A
0.2…0.3A
0.28…0.42A
0.38…0.58A
0.53…0.80A
0.73…1.1A
Specific let-through energy I
2
t (A
2
s)
102
103
104
101
Perspective short-circuit current (A)
104
103
10 102105
105
1…1.5A
2.8…4.2A
1.4…2.1A
2…3A
3.8…5.8A
5.3…8A
7.3…11A
S 500 K - S 500 KM
S 500 K - S 500 KM
Specific let-through energy I
2
t (A
2
s)
103
104
105
102
Perspective short-circuit current (A)
10…15A
105
104
102103
18…26A
29…37A
OEPM0103
OEPM0104
OEPM0102
OEPM0101
10/11
10
ABB SACE
Ip peak current
With reference to the IEC/EN 60439-1 Standards, relative to the short-circuit withstand test, the
limited peak current values corresponding to the ultimate breaking capacity Icu (EN 60947-2) are
shown below.
Series In [A] Icu [kA] Ip [kA]
S 941 N 2...40 6 3.5
S 951 N 2...40 10 6
S 971 N 2...40 15 9
S 240 6...40 6 4
S 250 0.5...63 10 6
S 270 0.5...63 15 9
S 280 6...63 25/15 10
S 290 80...125 15 11
S 500 6...63 50 9.5
6,000
9,000
10,000
11,000
15,000 IEC/EN 60439-1 limit
S 250
S 270
S 280
S 290
In: 63A In: 63A In: 6...63A In:
80…125A
Ip [A]
Icu: 10 kA Icu: 15 kA Icu: 25/15 kA Icu: 15 kA
S 500
Icu: 50 kA
IEC/EN 60947-2
S 240
Icu: 6 kA
4,000
In: 40A In: 63A
S 951 N
S 971 N
In: 40A In: 40A
Icu: 10 kA Icu: 15 kA
S 941 N
Icu: 6 kA
In: 40A
OEPM0105
Technical details
MCBs
Description of product and codes ................. pg. 2/1
10/12
10
ABB SACE
S 941 N characteristic C - 230V
Description of product and codes ................. pg. 2/1
Technical details
MCBs
S 941 N characteristic B - 230V
Limitation curves
Ip [kA]
10
0
20
50
0.2
0.5
100
0Is [kA]
0.2 0.5 1 2 5 10 20 50 100
1
2
5
10A
32A
40A
25A
20A
16A
Ip [kA]
10
0
20
50
0,2
0,5
100
0Is [kA]
0,2 0,5 1 2 5 10 20 50 100
1
2
5
10A
6A
4A
2A
32A
40A
25A
20A
16A
10/13
10
ABB SACE
S 240 characteristic C - 3P, 4P 400V
Description of product and codes ................. pg. 2/1
Technical details
MCBs
S 250 characteristic B - 3P, 4P 400V
Ip [kA]
10
0
20
50
0,2
0,5
100
0Is [kA]
0,2 0,5 1 2 5 10 20 50 100
1
2
5
13A
6A
8A
10A
32A
40A
25A
20A
16A
Ip [kA]
10
0
20
50
0,2
0,5
100
0Is [kA]
0,2 0,5 1 2 5 10 20 50 100
1
2
5
13A
6A
8A
10A
50A
63A
32A
40A
25A
20A
16A
10/14
10
ABB SACE
S 250 characteristic C - 3P, 4P 400V
Description of product and codes ................. pg. 2/1
Technical details
MCBs
S 250 characteristic K - 3P, 4P 400V
Ip [kA]
10
0
20
50
0,2
0,5
100
0Is [kA]
0,2 0,5 1 2 5 10 20 50 100
1
2
5
4A
3A
2A
1,6A
1A
0,5A
13A
6A
10A
50A
63A
8A
32A
40A
25A
20A
16A
Ip [kA]
10
0
20
50
0,2
0,5
100
0Is [kA]
0,2 0,5 1 2 5 10 20 50 100
1
2
5
4A
3A
2A
1,6A
1A
0,5A
6A
10A
50A
63A
8A
32A
40A
25A
16A
10/15
10
ABB SACE
S 270 characteristic B - 3P, 4P 400V
Description of product and codes ................. pg. 2/1
Technical details
MCBs
S 270 characteristic C - 3P, 4P 400V
Ip [kA]
10
0
20
50
0,2
0,5
100
0Is [kA]
0,2 0,5 1 2 5 10 20 50 100
1
2
5
13A
6A
8A
10A
50A
63A
32A
40A
25A
20A
16A
Ip [kA]
10
0
20
50
0,2
0,5
100
0Is [kA]
0,2 0,5 1 2 5 10 20 50 100
1
2
5
4A
3A
2A
1,6A
1A
0,5A
13A
6A
10A
50A
63A
8A
32A
40A
25A
20A
16A
10/16
10
ABB SACE
S 270 characteristic D - 3P, 4P 400V
Description of product and codes ................. pg. 2/1
Technical details
MCBs
S 270 characteristic K - 3P, 4P 400V
Ip [kA]
10
0
20
50
0,2
0,5
100
0Is [kA]
0,2 0,5 1 2 5 10 20 50 100
1
2
5
4A
3A
2A
1,6A
1A
0,5A
6A
10A
50A
63A
8A
32A
40A
25A
16A
Ip [kA]
10
0
20
50
0,2
0,5
100
0Is [kA]
0,2 0,5 1 2 5 10 20 50 100
1
2
5
4A
3A
2A
1,6A
1A 0,5A
6A
10A
50A
63A
8A
32A
40A
25A
16A
10/17
10
ABB SACE
S 280 characteristic B - 3P, 4P 400V
Description of product and codes ................. pg. 2/1
Technical details
MCBs
S 280 characteristic C - 3P, 4P 400V
Ip [kA]
10
0
20
50
0,2
0,5
100
0Is [kA]
0,2 0,5 1 2 5 10 20 50 100
1
2
5
10A
6A
8A
40A
20A
25A
50A
63A
16A
32A
13A
Ip [kA]
10
0
20
50
0,2
0,5
100
0Is [kA]
0,2 0,5 1 2 5 10 20 50 100
1
2
5
4A
3A
2A
1,6A
1A
0,5A
8A
6A
13A
10A
50A
63A
40A
25A
32A
20A
16A
10/18
10
ABB SACE
S 280 characteristic D - 3P, 4P 400V
Description of product and codes ................. pg. 2/1
Technical details
MCBs
S 280 characteristic K - 3P, 4P 400V
Ip [kA]
10
0
20
50
0,2
0,5
100
0Is [kA]
0,2 0,5 1 2 5 10 20 50 100
1
2
5
4A
3A
2A
1,6A
1A 0,5A
8A
6A
50A
63A
32A
40A
16A
25A
10A
Ip [kA]
10
0
20
50
0,2
0,5
100
0Is [kA]
0,2 0,5 1 2 5 10 20 50 100
1
2
5
4A
3A
2A
1,6A
1A
0,5A
8A
6A
8A
6A
50A
63A
40A
25A
32A
16A
10A
10/19
10
ABB SACE
S 500 characteristics B-C-D - 3P, 4P 400V
Description of product and codes ................. pg. 2/1
Technical details
MCBs
Ip [kA]
10
0
20
50
0,2
0,5
100
0Is [kA]
0,2 0,5 1 2 5 10 20 50 100
1
2
5
13A
10A
50A
63A
32A
40A
25A
20A
16A
10/20
10
ABB SACE
Description of product and codes ................. pg. 2/1
Technical details
MCBs
Protective coordination between ABB circuit-breakers (back up table with Ue= 400 V a.c.)
upstream circuit-breaker
S 250 S 270 S 280/20 S 280/25 S 290 S 500 LNA S1B S2B S1N S2N S3N S4N S2S S6S S3H S4H S3L S4L S3X S3X S4X Fuses
gL/aM
In [A] <
32/63/100
125 160 125 160 250 250 160 800 250 250 250 250 125 200 250 125A
Icu [kA] 10 15 20 25 15 50 50 16 16 25 35 35 35 50 50 65 65 85 100 200 200 200 100
downstream circuit-breaker
Icu [kA]
6S 941 N
S 240
10 S 951 N S 240 S 240 S 240 S 240 S 240 S 240
15 S 240 S 240
S 250 S 250
16 S 250 S 250 S 250 S 250 S 250 S 250 S 250 S 250
20 S 240 S 250 S 250 S 270 S 250 S1B S 270 S 270 S 250 S 250 S 250
S 250 S2B
S 270
25 S 240 S 270 S 270 S 270 S 280/20 S 270 S 270 S 280/20 S 270 S 280/20 S 270 S 270 S 270
S 250 S 280/20 S 280/20 S1B S 280/20 S 280/20 S 280/20 S 280/20
S 270 S 280/25 S2B
S1B
30 S 240 S 240 S 280/20 S 280/25 S 280/25 S 280/20 S 280/25 S 280/25 S 280/25 S 280/25 S 280/20 S 280/25
S1B
35 S 280/25 S1B S1N S 280/25 S2B S 280/25 S 280/25
S1B S1N
S1N S2B
S2B
40 S 250 S 250 S1N S1B S1B
S2B S2B
50 S 270 S 270 S1B S2N S1N S2B
S 280/20 S 280/20 S1N S3N S1B
S 280/25 S 280/25 S2B S4N
S1B S1B S2N S5N
S1N S1N
100 S2N S1B S 240
S2S S 250
S3N S 270
S3H S 280
S3L S 700
200 S 500 S 500 LNA
LNA LNA S2N
S2N S2N S2S
S2S S2S S3N
S3N S3H
S3H S3L
S3L
When the same conditions in the table apply to several types of circuit-breaker, only one has been indicated so that the table can be easily
consulted; you must therefore read the indications as shown in the key:
S 250: S 250, DS 650
S 270: S 270 (B-C-D-K), S 280 (In= 3…8A and In= 50…63A), S 290, DS 670
S 280/20: S 280 (In= 32…40A)
S 280/25: S 280 (In= 10…25A)
10/21
10
ABB SACE
Technical details
MCBs
Description of product and codes ................. pg. 2/1
Upstream
breaker
S 290
D.strm In 80 100
breaker Im D D
S 240 6C T T
8C T T
10 C 5 T
13 C 4.5 7
16 C 4.5 7
20 C 3.5 5
25 C 3.5 5
32 C 4.5
40 C
S 250 < 2 C T T
3C T T
4C T T
6 B-C T T
8 B-C T T
10 B-C 5 8
13 B-C 4.5 7
16 B-C 4.5 7
20 B-C 3.5 5
25 B-C 3.5 5
32 B-C 4.5
40 B-C
50 B-C
63 B-C
S 250 < 2 K T T
3K T T
4K T T
6K T T
8K T T
10 K 5 8
16 K 3 5
20 K 3 7
25 K 4
32 K
40 K
50 K
63 K
Selectivity between ABB circuit-breakers tables
The tables below show the selectivity values (referring to the breaking capacity according to IEC
947-2 / EN 60947.2) between ABB SACE modular circuit-breakers and moulded-case circuit-breakers.
Selectivity is expressed in kA at a voltage of 380-415V a.c. according to the Icu of the IEC 947-2
Standards.
Letter “T” corresponds to the total selectivity which is compatible with the minimum breaking capacity
relative to the two circuit-breakers (upstream and downstream).
D.strm In 80 100
breaker Im D D
S 270 < 2 C T T
3C T T
4C T T
6 B-C 10.5 T
8 B-C 10.5 T
S 270 10 B-C 5 8
13 B-C 4.5 7
16 B-C 4.5 7
20 B-C 3.5 5
25 B-C 3.5 5
32 B-C 4.5
40 B-C
50 B-C
63 B-C
S 270 < 2 K T T
3K T T
4K T T
6 K 10.5 T
8 K 10.5 T
10 K 5 8
16 K 3 5
20 K 3 5
25 K 4
32 K
40 K
50 K
63 K
S 270 < 2 D T T
3D T T
4D T T
6 D 10.5 T
8 D 10.5 T
10 D 5 8
16 D 3 5
20 D 3 5
25 D 2.5 4
32 D 4
40 D
50 D
63 D
Upstream breaker
D.strm In 80 100
breaker Im D D
S 280 10 B-C 5 8
13 B-C 4.5 7
16 B-C 4.5 7
20 B-C 3.5 5
25 B-C 3.5 5
32 B-C 4.5
40 B-C
50 B-C
63 B-C
S 280 10 D 5 8
16 D 3 5
20 D 3 5
25 D 2.5 4
32 D 4
40 D
50 D
63 D
S 280 10 K 5 8
13 K 3 5
16 K 3 5
20 K 3 5
25 K 4
32 K
40 K
50 K
63 K
S 280 < 2 Z T T
3Z T T
4Z T T
6 Z 10.5 T
8 Z 10.5 T
10 Z 5 8
13 Z 4.5 7
16 Z 4.5 7
20 Z 3.5 5
25 Z 3.5 5
32 Z 3 4.5
40 Z 3 4.5
50 Z 3
63 Z
Upstream breaker
D.strm In 80 100
breaker Im D D
S 500 < 16 B-C-D 6 10
20 B-C-D 6 7.5
25 B-C-D 4.5 6
32 B-C-D 6
40 B-C-D
50 B-C-D
S 500 <5.8 K T T
8K 10 T
11 K 7.5 T
15 K 4.5 10
20 K 4.5 6
26 K 4.5
32 K
37 K
Upstream breaker
10/22
10
ABB SACE
Technical details
MCBs
Upstream circuit-breaker S 500
D.strm In 32 40 50 63
breaker ImDDDD
S 240 6 C 1.5 2 3 5.5
8 C 1.5 2 3 5.5
10 C 1 1.5 2 3
13 C 1.5 2 3
16 C 2 3
20 C 2.5
25 C
32 C
40 C
S 250 < 2CTTTT
3C36TT
4C236T
6 B-C 1.5 2 3 5.5
8 B-C 1.5 2 3 5.5
10 B-C 1 1.5 2 3
13 B-C 1.5 2 3
16 B-C 2 3
20 B-C 2.5
25 B-C
32 B-C
40 B-C
50 B-C
63 B-C
S 250 < 2KTTTT
3K36TT
4K236T
6 K 1.5 2 3 5.5
8 K 1.5 2 3 5.5
10 K 1.5 2 3
16 K 2
20 K
25 K
32 K
40 K
50 K
63 K
S 270 < 2CTTTT
3C36TT
4C236T
6 B-C 1.5 2 3 5.5
8 B-C 1.5 2 3 5.5
10 B-C 1 1.5 2 3
13 B-C 1.5 2 3
16 B-C 2 3
20 B-C 2.5
25 B-C
32 B-C
40 B-C
50 B-C
63 B-C
S 270 < 2KTTTT
3K36TT
4K236T
6 K 1.5 2 3 5.5
8 K 1.5 2 3 5.5
10 K 1.5 2 3
(cont.) 16 K 2
Upstream circuit-breaker
D.strm In 32 40 50 63
breaker ImDDDD
S 270 20 K
(cont.) 25 K
32 K
40 K
50 K
63 K
S 270 < 2DTTTT
3D36TT
4D236T
6 D 1.5 2 3 5.5
8 D 1.5 2 3 5.5
10 D 1 1.5 2 3
16 D 1.5 2
20 D 2
25 D
32 D
40 D
50 D
63 D
S 280 10 B-C 1 1.5 2 3
13 B-C 1.5 2 3
16 B-C 2 3
20 B-C 2.5
25 B-C
32 B-C
40 B-C
50 B-C
63 B-C
S 280 10 D 1 1.5 2 3
16 D 1.5 2
20 D 2
25 D
32 D
40 D
50 D
63 D
S 280 10 K 1.5 2 3
13 K 1.5 2
16 K 2
20 K
25 K
32 K
40 K
50 K
63 K
S 280 < 2ZTTTT
3Z36TT
4Z236T
6 Z 1.5 2 3 5.5
8 Z 1.5 2 3 5.5
10 Z 1 1.5 2 3
13 Z 1 1.5 2 3
16 Z 1 1.5 2 3
20 Z 1.5 2 2.5
25 Z 2 2.5
32 Z 2
40 Z
50 Z
63 Z
10/23
10
ABB SACE
Technical details
MCBs
Upstream circuit-breaker LNA32/63/100
D.strm In 32 39 47 54 63 80 100
breaker Im 450 550 650 650 650 800 800
S 240 6 C 1.5 2 3.5 3.5 3.5 5.5 5.5
8 C 1.5 2 3.5 3.5 3.5 5.5 5.5
10C1.51.522233
13C 1.522233
16C 22233
20 C 2 2 2.5 2.5
25 C 2.5 2.5
32 C 2.5
40 C
S 250 2CTTTTTTT
3C4TTTTTT
4C2.54777TT
6 B-C 1.5 2 3.5 3.5 3.5 5.5 5.5
8 B-C 1.5 2 3.5 3.5 3.5 5.5 5.5
10B-C1.51.522233
13B-C 1.522233
16B-C 22233
20 B-C 2 2 2.5 2.5
25 B-C 2.5 2.5
32 B-C 2.5
40 B-C
50 B-C
63 B-C
S 250 2KTTTTTTT
3K4TTTTTT
4K2.54777TT
6 K 1.5 2 3.5 3.5 3.5 5.5 5.5
8 K 1.5 2 3.5 3.5 3.5 5.5 5.5
10K 1.522233
16 K 1.5 2 2
20 K 2 2
25 K 2
32 K
40 K
50 K
63 K
S 270 2CTTTTTTT
3 C 4 10.5 TTTTT
4C2.54777TT
6 B-C 1.5 2 3.5 3.5 3.5 5.5 5.5
8 B-C 1.5 2 3.5 3.5 3.5 5.5 5.5
10B-C1.51.522233
13B-C 1.522233
16B-C 22233
20 B-C 2 2 2.5 2.5
25 B-C 2.5 2.5
32 B-C 2.5
40 B-C
50 B-C
63 B-C
S 270 2KTTTTTTT
3 K 4 10.5 TTTTT
4K2.54777TT
6 K 1.5 2 3.5 3.5 3.5 5.5 5.5
8 K 1.5 2 3.5 3.5 3.5 5.5 5.5
10K 1.522233
16 K 1.5 2 2
20 K 2 2
25 K 2
32 K
40 K
50 K
63 K
10/24
10
ABB SACE
Technical details
MCBs
Upstream circuit-breaker LNA32/63/100
D.strm In 32 39 47 54 63 80 100
breaker Im 450 550 650 650 650 800 800
S 270 < 2DTTTTTTT
3 D 4 10.5 T T T T T
4D2.54777TT
6 D 1.5 2 3.5 3.5 3.5 5.5 5.5
8 D 1.5 2 3.5 3.5 3.5 5.5 5.5
10 D 1.5 1.5 2 2 2 3 3
16 D 1.5 1.5 1.5 2 2
20 D 1.5 1.5 2 2
25 D 2 2
32 D 2
40 D
50 D
63 D
S 280 10 B-C 1.5 1.5 2 2 2 3 3
13B-C 1.522233
16B-C 22233
20 B-C 2 2 2.5 2.5
25 B-C 2.5 2.5
32 B-C 2.5
40 B-C
50 B-C
63 B-C
S 280 10 D 1.5 1.5 2 2 2 3 3
16 D 1.5 1.5 1.5 2 2
20 D 1.5 1.5 2 2
25 D 2 2
32 D 2
40 D
50 D
63 D
S 280 10K 1.522233
13 K 1.5 1.5 1.5 2 2
16 K 1.5 2 2
20 K 2 2
25 K 2
32 K
40 K
50 K
63 K
S 280 < 2ZTTTTTTT
3 Z 4 10.5 T T T T T
4Z2.54777TT
6 Z 1.5 2 3.5 3.5 3.5 5.5 5.5
8 Z 1.5 2 3.5 3.5 3.5 5.5 5.5
10 Z 1.5 1.5 2 2 2 3 3
13Z11.522233
16Z 1.522233
20 Z 2 2 2 2.5 2.5
25 Z 2 2.5 2.5
32 Z 2.5 2.5
40 Z 2.5
50 Z
63 Z
S 500 6 B-C 4.5 4.5
10 B-C-D 4.5 4.5
13 B-C-D 4.5 4.5
16 B-C-D 4.5 4.5
20 B-C-D 4.5 4.5
25 B-C-D 3 3
32 B-C-D 3
40 B-C-D
50 B-C-D
S 500 < 5.8 K 35 35
8 K 4.5 4.5
11 K 4.5 4.5
15 K 3 3
20 K
26 K
32 K
37 K
10/25
10
ABB SACE
Technical details
MCBs
Upstream circuit-breaker S1B-N
D.strm In 10 12.5 16 20 25 32 40 50 63 80 100 125
breaker Im 500 500 500 500 500 500 500 500 630 800 1000 1250
S 240 6 C 5.5 5.5 5.5 5.5 5.5 5.5 T T T T
8 C 5.5 5.5 5.5 5.5 5.5 T T T T
10C 33335TTT
13C 334.5TTT
16C 334.5TTT
20 C 2.5 3.5 5.5 T T
25 C 3.5 5.5 T T
32 C 4.5 7 T
40 C
S 250 < 2C TTTTTTTTTT
3C TTTTTTTTTT
4C TTTTTTTTTT
6 B-C 5.5 5.5 5.5 5.5 5.5 5.5 T T T T
8 B-C 5.5 5.5 5.5 5.5 5.5 T T T T
10B-C 333358.5TT
13 B-C 3 3 4.5 7.5 T T
16 B-C 3 3 4.5 7.5 T T
20 B-C 2.5 3.5 5.5 8 T
25 B-C 3.5 5.5 8 T
32 B-C 4.5 7 T
40 B-C 7T
50 B-C 6
63 B-C
S 250 < 2KTTTTTTTTTTTT
3K TTTTTTTTTTT
4K TTTTTTTTTT
6 K 5.5 5.5 5.5 5.5 T T T T
8 K 5.5 5.5 5.5 T T T T
10K 3358.5TT
16K 358T
20 K 4.5 6.5 T
25 K 6 9.5
32 K 9.5
40 K
50 K
63 K
S 270 < 2C TTTTTTTTTT
3C TTTTTTTTTT
4C TTTTTTTTTT
6 B-C 5.5 5.5 5.5 5.5 5.5 5.5 10.5 T T T
8 B-C 5.5 5.5 5.5 5.5 5.5 10.5 T T T
10B-C 333358.5TT
13 B-C 3 3 4.5 7.5 12 T
16 B-C 3 3 4.5 7.5 12 T
20 B-C 2.5 3.5 5.5 8 13.5
25 B-C 3.5 5.5 8 13.5
32 B-C 4.5 7 12
40 B-C 712
50 B-C 6
63 B-C
S 270 < 2KTTTTTTTTTTTT
3K TTTTTTTTTTT
4K TTTTTTTTTT
6 K 5.5 5.5 5.5 5.5 10.5 T T T
8 K 5.5 5.5 5.5 10.5 T T T
10K 3358.5TT
16 K 3 5 8 13.5
20 K 4.5 6.5 11
25 K 6 9.5
32 K 9.5
40 K
50 K
63 K
10/26
10
ABB SACE
Technical details
MCBs
Upstream circuit-breaker S1 B-N
D.strm In 10 12.5 16 20 25 32 40 50 63 80 100 125
breaker Im 500 500 500 500 500 500 500 500 630 800 1000 1250
S 270 < 2D TTTTTTTTTT
3D TTTTTTTTTT
4D TTTTTTTTTT
6 D 5.5 5.5 5.5 5.5 5.5 5.5 10.5 T T T
8 D 5.5 5.5 5.5 5.5 5.5 10.5 T T T
10D 333358.5TT
16D 2235813.5
20 D 2 3 4.5 6.5 11
25 D 2.5 4 6 9.5
32 D 4 6 9.5
40 D 58
50 D
63 D
S 280 10B-C 333358.517*T
13 B-C 3 3 4.5 7.5 12 20*
16 B-C 3 3 4.5 7.5 12 20*
20 B-C 2.5 3.5 5.5 8 13.5
25 B-C 3.5 5.5 8 13.5
32 B-C 4.5 7 12
40 B-C 4.5 7 12
50 B-C 6
63 B-C
S 280 10D 333358.517*T
16D 2235813.5
20 D 2 3 4.5 6.5 11
25 D 2.5 4 6 9.5
32 D 4 6 9.5
40 D 58
50 D
63 D
S 280 10K 3358.517*T
13K 235813.5
16 K 3 5 8 13.5
20 K 4.5 6.5 11
25 K 6 9.5
32 K 9.5
40 K
50 K
63 K
S 280 < 2ZTTTTTTTTTTTT
3ZTTTTTTTTTTTT
4ZTTTTTTTTTTTT
6 Z 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 10.5 T T T
8 Z 5.5 5.5 5.5 5.5 5.5 5.5 5.5 10.5 T T T
10Z 33333358.517*T
13 Z 3 3 3 3 3 4.5 7.5 12 20*
16 Z 3 3 3 3 4.5 7.5 12 20*
20 Z 2.5 2.5 2.5 3.5 5.5 8 13.5
25 Z 2.5 2.5 3.5 5.5 8 13.5
32Z 234.5712
40 Z 3 4.5 7 12
50 Z 3 4.5 6
63 Z 4.5 6
S 500 6 B-C 4.5 4.5 4.5 4.5 4.5 4.5 6 10 15 T
10 B-C-D 4.5 4.5 4.5 4.5 6 10 15 T
13 B-C-D 4.5 4.5 6 10 15 T
16 B-C-D 4.5 4.5 6 10 15 T
20 B-C-D 4.5 6 7.5 15 T
25 B-C-D 4.5 7.5 10 20*
32 B-C-D 6 10 20*
40 B-C-D 7.5 15
50 B-C-D 10
S 500 < 5.8K TTTTTTTT
8 K 4.5 4.5 4.5 10 T T T
11K 337.5TTT
15 K 4.5 10 15 T
20 K 6 10 20*
26 K 7.5 15
32 K 15
37 K
*consider the lower value between the breaking capacity of the upstream circuit-breaker and the value indicated
10/27
10
ABB SACE
Technical details
MCBs
Upstream circuit-breaker S1N
D.strm In 63 80 100 125
breaker ImDDDD
S 240 6CTTTT
8CTTTT
10CTTTT
13CTTTT
16CTTTT
20CTTTT
25CTTTT
32C TTT
40 C T T
S 250 < 2CTTTT
3CTTTT
4CTTTT
6B-CTTTT
8B-CTTTT
10B-CTTTT
13B-CTTTT
16B-CTTTT
20 B-C 7.5 9 T T
25 B-C 7.5 9 T T
32 B-C 8 T T
40 B-C T T
50 B-C T
63 B-C
S 250 < 2KTTTT
3KTTTT
4KTTTT
6KTTTT
8KTTTT
10KTTTT
16 K 7 8.5 T T
20K 7TT
25 K 9.5 T
32 K T
40 K
50 K
63 K
S 270 < 2CTTTT
3CTTTT
4CTTTT
6B-CTTTT
8B-CTTTT
10B-CTTTT
13 B-C 11 13 T T
16 B-C 11 13 T T
20 B-C 7.5 9 13.5 T
25 B-C 7.5 9 13.5 T
32 B-C 8 12 T
40 B-C 12 T
50 B-C 10.5
63 B-C
S 270 < 2KTTTT
3KTTTT
4KTTTT
6KTTTT
8KTTTT
10KTTTT
16 K 7 8.5 13.5 T
20 K 7 11.5 T
25 K 9.5 T
32 K T
40 K
50 K
63 K
Upstream circuit-breaker S1N
D.strm In 63 80 100 125
breaker ImDDDD
S 270 < 2DTTTT
3DTTTT
4DTTTT
6DTTTT
8DTTTT
10DTTTT
16 D 7 8.5 13.5 T
20 D 6 7 11.5 T
25 D 5.5 6.5 9.5 T
32 D 6.5 9.5 T
40 D 8.5 14.5
50 D
63 D
S 280 10 B-C 15 19.5 T T
13 B-C 11 13 20 T
16 B-C 11 13 20 T
20 B-C 7.5 9 13.5 T
25 B-C 7.5 9 13.5 T
32 B-C 8 12 T
40 B-C 12 T
50 B-C 10.5
63 B-C
S 280 10 D 15 19.5 T T
16 D 7 8.5 13.5 24.5
20 D 6 7 11.5 22
25 D 5.5 6.5 9.5 16
32 D 6.5 9.5 16
40 D 8.5 16
50 D
63 D
S 280 10 K 15 19.5 T T
13 K 7 8.5 13.5 24.5
16 K 7 8.5 13.5 24.5
20 K 7 11.5 22
25 K 9.5 16
32 K 16
40 K
50 K
63 K
S 280 < 2ZTTTT
3ZTTTT
4ZTTTT
6ZTTTT
8ZTTTT
10 Z 15 19.5 T T
13Z 111320T
16Z 111320T
20 Z 7.5 9 13.5 T
25 Z 7.5 9 13.5 T
32 Z 6.5 8 12 T
40 Z 6.5 8 12 T
50 Z 5 6.5 10.5
63 Z 6.5 10.5
S 500 6 B-C 15 20 T T
10 B-C-D 15 20 T T
13 B-C-D 15 20 T T
16 B-C-D 15 20 T T
20 B-C-D 10 15 T T
25 B-C-D 10 10 T T
32 B-C-D 10 20 T
40 B-C-D 15 T
50 B-C-D T
S 500 < 5.8KTTTT
8KTTTT
11KTTTT
15K 1520T T
20K 1520T
26 K 15 T
32 K T
37 K
10/28
10
ABB SACE
Technical details
MCBs
Upstream circuit-breaker S2B-N-S
D.strm In 12.5 16 20 25 32 40 50 63 80 100 125 160
breaker Im 500 500 500 500 500 500 500 630 800 1000 1250 1600
S 240 6C 5.55.55.55.55.55.5TTTTT
8C 5.55.55.55.55.5TTTTT
10C 33335TTTT
13C 334.5TTTT
16C 334.5TTTT
20 C 2.5 3.5 5.5 T T T
25 C 3.5 5.5 T T T
32 C 4.5 7 T T
40 C 7TT
S 250 < 2C TTTTTTTTTTT
3C TTTTTTTTTTT
4C TTTTTTTTTTT
6B-C 5.55.55.55.55.55.5TTTTT
8B-C 5.55.55.55.55.5TTTTT
10B-C 333358.5TTT
13 B-C 3 3 4.5 7.5 T T T
16 B-C 3 3 4.5 7.5 T T T
20 B-C 2.5 3.5 5.5 8 T T
25 B-C 3.5 5.5 8 T T
32 B-C 4.5 7 T T
40 B-C 7TT
50 B-C 6T
63 B-C T
S 250 < 2KTTTTTTTTTTTT
3KTTTTTTTTTTTT
4K TTTTTTTTTTT
6K 5.55.55.55.5TTTTT
8K 5.55.55.5TTTTT
10K 3358.5TTT
16K 358TT
20 K 4.5 6.5 T T
25 K 6 9.5 T
32 K 9.5 T
40 K T
50 K
63 K
S 270 < 2C TTTTTTTTTTT
3C TTTTTTTTTTT
4C TTTTTTTTTTT
6 B-C 5.5 5.5 5.5 5.5 5.5 5.5 10.5 TTTT
8 B-C 5.5 5.5 5.5 5.5 5.5 10.5 TTTT
10B-C 333358.5TTT
13 B-C 3 3 4.5 7.5 12 T T
16 B-C 3 3 4.5 7.5 12 T T
20 B-C 2.5 3.5 5.5 8 13.5 T
25 B-C 3.5 5.5 8 13.5 T
32 B-C 4.5 7 12 T
40 B-C 712T
50 B-C 6 10.5
63 B-C 10.5
S 270 < 2KTTTTTTTTTTTT
3KTTTTTTTTTTTT
4K TTTTTTTTTTT
6 K 5.5 5.5 5.5 5.5 10.5 TTTT
8 K 5.5 5.5 5.5 10.5 TTTT
10K 3358.5TTT
16 K 3 5 8 13.5 T
20 K 4.5 6.5 11 T
25 K 6 9.5 T
32 K 9.5 T
40 K T
50 K
63 K
10/29
10
ABB SACE
Technical details
MCBs
Upstream circuit-breaker S2B-N-S
D.strm In 12.5 16 20 25 32 40 50 63 80 100 125 160
breaker Im 500 500 500 500 500 500 500 630 800 1000 1250 1600
S 270 < 2D TTTTTTTTTTT
3D TTTTTTTTTTT
4D TTTTTTTTTTT
6 D 5.5 5.5 5.5 5.5 5.5 5.5 10.5 T T T T
8 D 5.5 5.5 5.5 5.5 5.5 10.5 T T T T
10D 333358.5TTT
16D 2235813.5 T
20 D 2 3 4.5 6.5 11 T
25 D 2.5 4 6 9.5 T
32 D 4 6 9.5 T
40 D 58T
50 D 9.5
63 D 9.5
S 280 10B-C 333358.517*TT
13 B-C 3 3 4.5 7.5 12 20* T
16 B-C 3 3 4.5 7.5 12 20* T
20 B-C 2.5 3.5 5.5 8 13.5 T
25 B-C 3.5 5.5 8 13.5 T
32 B-C 4.5 7 12 T
40 B-C 712T
50 B-C 6 10.5
63 B-C 10.5
S 280 10D 333358.517*TT
16D 2235813.5 24.5*
20 D 2 3 4.5 6.5 11 22*
25 D 2.5 4 6 9.5 16.5*
32 D 4 6 9.5 16.5*
40 D 58T
50 D 9.5
63 D 9.5
S 280 10K 3358.517*TT
13 K 2 3 5 8 13.5 24.5*
16 K 3 5 8 13.5 24.5*
20 K 4.5 6.5 11 22*
25 K 6 9.5 16.5*
32 K 9.5 16.5*
40 K 15
50 K
63 K
S 280 < 2ZTTTTTTTTTTTT
3ZTTTTTTTTTTTT
4ZTTTTTTTTTTTT
6 Z 5.5 5.5 5.5 5.5 5.5 5.5 5.5 10.5 T T T T
8 Z 5.5 5.5 5.5 5.5 5.5 5.5 5.5 10.5 T T T T
10Z 33333358.517*TT
13Z 333334.57.51220*T
16Z 33334.57.51220*T
20 Z 2.5 2.5 2.5 3.5 5.5 8 13.5 T
25 Z 2.5 2.5 3.5 5.5 8 13.5 T
32Z 234.5712T
40 Z 3 4.5 7 12 T
50 Z 3 4.5 6 10.5
63 Z 4.5 6 10.5
S 500 6 B-C 4.5 4.5 4.5 4.5 4.5 4.5 6 10 15 35* 35*
10 B-C-D 4.5 4.5 4.5 4.5 6 10 15 35* 35*
13 B-C-D 4.5 4.5 6 10 15 35* 35*
16 B-C-D 4.5 4.5 6 10 15 35* 35*
20 B-C-D 4.5 6 7.5 15 35* 35*
25 B-C-D 4.5 7.5 10 20* 35*
32 B-C-D 6 10 20* 35*
40 B-C-D 7.5 15 35*
50 B-C-D 10 35*
S 500 < 5.8 K 35* 35* 35* 35* 35* 35* 35* 35* T
8 K 4.5 4.5 4.5 10 35* 35* 35* T
11 K 3 3 7.5 25* 35* 35* T
15 K 4.5 10 15 30* T
20 K 6 10 20* T
26 K 7.5 15 T
32 K 15 T
37 K 20*
*consider the lower value between the breaking capacity of the upstream circuit-breaker and the value indicated
10/30
10
ABB SACE
Technical details
MCBs
Upstream circuit-breaker S3N-H-L
D.strm In 32 50 80 100 125 160 200 250
breaker Im 500 500 800 1000 1250 1600 2000 2500
S 240 6C5.55.5TTTTTT
8C5.55.5TTTTTT
10C33TTTTTT
13C 3TTTTTT
16C 3TTTTTT
20 C 2.5 5.5 T T T T T
25C 5.5TTTTT
32C 4.57TTTT
40C 7TTTT
S 250 < 2CTTTTTTTT
3CTTTTTTTT
4CTTTTTTTT
6B-C5.55.5TTTTTT
8B-C5.55.5TTTTTT
10B-C338.5TTTTT
13B-C 37.5TTTTT
16B-C 37.5TTTTT
20 B-C 2.5 5.5 8 T T T T
25B-C 5.58TTTT
32B-C 4.57TTTT
40B-C 7TTTT
50B-C 6TTT
63 B-C T T T
S 250 < 2KTTTTTTTT
3KTTTTTTTT
4KTTTTTTTT
6K5.55.5TTTTTT
8K5.55.5TTTTTT
10K 38.5TTTTT
16K 58TTTT
20 K 4.5 6.5 T T T T
25 K 6 9.5 T T T
32 K 9.5 T T T
40 K T T T
50 K T T
63 K T
S 270 < 2CTTTTTTTT
3CTTTTTTTT
4CTTTTTTTT
6B-C5.55.5TTTTTT
8B-C5.55.5TTTTTT
10B-C338.5TTTTT
13B-C 37.512TTTT
16B-C 37.512TTTT
20 B-C 2.5 5.5 8 13.5 T T T
25 B-C 5.5 8 13.5 T T T
32B-C 4.5712TTT
40B-C 712TTT
50 B-C 6 10.5 T T
63 B-C 10.5 T T
S 270 < 2KTTTTTTTT
3KTTTTTTTT
4KTTTTTTTT
6K5.55.5TTTTTT
8K5.55.5TTTTTT
10K 38.5TTTTT
16 K 5 8 13.5 T T T
20 K 4.5 6.5 11 T T T
25 K 6 9.5 T T T
32 K 9.5 T T T
40 K T T T
50 K T T
63 K T
10/31
10
ABB SACE
Technical details
MCBs
Upstream circuit-breaker S3N-H-L
D.strm In 32 50 80 100 125 160 200 250
breaker Im 500 500 800 1000 1250 1600 2000 2500
S 270 < 2DTTTTTTTT
3DTTTTTTTT
4DTTTTTTTT
6D5.55.5TTTTTT
8D5.55.5TTTTTT
10D338.5TTTTT
16 D 2 5 8 13.5 T T T
20 D 2 4.5 6.5 11 T T T
25 D 4 6 9.5 T T T
32 D 4 6 9.5 T T T
40D 58TTT
50 D 9.5 T T
63 D 9.5 T T
S 280 10B-C338.517TTTT
13 B-C 3 7.5 12 20 T T T
16 B-C 3 7.5 12 20 T T T
20 B-C 2.5 5.5 8 13.5 T T T
25 B-C 5.5 8 13.5 T T T
32B-C 4.5712TTT
40B-C 712TTT
50 B-C 6 10.5 T T
63 B-C 10.5 T T
S 280 10D338.517TTTT
16 D 2 5 8 13.5 24.5 T T
20 D 2 4.5 6.5 11 22 T T
25 D 4 6 9.5 16.5 T T
32 D 4 6 9.5 16.5 T T
40D 58TTT
50 D 9.5 T T
63 D 9.5 T T
S 280 10 K 3 8.5 17 T T T T
13 K 2 5 8 13.5 24.5 T T
16 K 5 8 13.5 24.5 T T
20 K 4.5 6.5 11 22 T T
25 K 6 9.5 16.5 T T
32 K 9.5 16.5 T T
40 K 15 T T
50 K T T
63 K T
S 280 < 2ZTTTTTTTT
3ZTTTTTTTT
4ZTTTTTTTT
6Z5.55.5TTTTTT
8Z5.55.5TTTTTT
10Z338.517TTTT
13 Z 3 3 7.5 12 20 T T T
16 Z 3 3 7.5 12 20 T T T
20 Z 2.5 2.5 5.5 8 13.5 T T T
25 Z 2.5 5.5 8 13.5 T T T
32Z 24.5712TTT
40Z 4.5712TTT
50 Z 3 4.5 6 10.5 T T
63 Z 4.5 6 10.5 T T
S 290 80 C-D 9.5 T
100 C-D 14
125 C
S 500 6 B-C 4.5 4.5 10 15 35 35 35 35
10 B-C-D 4.5 4.5 10 15 35 35 35 35
13 B-C-D 4.5 10 15 35 35 35 35
16 B-C-D 4.5 10 15 35 35 35 35
20 B-C-D 4.5 7.5 15 35 35 35 35
25 B-C-D 7.5 10 20 35 35 35
32 B-C-D 6 10 20 35 35 35
40 B-C-D 7.5 15 35 35 35
50 B-C-D 10 35 35 35
63 B-C-D 35 35 35
S 500 < 5.8K 3535353535T T T
8 K 4.5 4.5 35 35 35 T T T
11 K 3 25 35 35 T T T
15K 101530T T T
20 K 6 10 20 T T T
26 K 7.5 15 T T T
32 K 15 T T T
37 K 20 T T
41 K 20 T T
45 K 20 T T
10/32
10
ABB SACE
Technical details
MCBs
Upstream circuit-breaker S4N-H-L
D.strm In 100 160 250
breaker Im OFF OFF OFF
S 240 6CTTT
8CTTT
10CTTT
13CTTT
16CTTT
20CTTT
25CTTT
32CTTT
40CTTT
S 250 < 2CTTT
3CTTT
4CTTT
6B-CTTT
8B-CTTT
10 B-C T T T
13 B-C T T T
16 B-C T T T
20 B-C T T T
25 B-C T T T
32 B-C T T T
40 B-C T T T
50 B-C T T T
63 B-C T T T
S 250 < 2KTTT
3KTTT
4KTTT
6KTTT
8KTTT
10KTTT
16KTTT
20KTTT
25KTTT
32KTTT
40KTTT
50KTTT
63KTTT
S 270 < 2CTTT
3CTTT
4CTTT
6B-CTTT
8B-CTTT
10 B-C T T T
13 B-C T T T
16 B-C T T T
20 B-C T T T
25 B-C T T T
32 B-C T T T
40 B-C T T T
50 B-C T T T
63 B-C T T T
S 270 < 2KTTT
3KTTT
4KTTT
6KTTT
8KTTT
10KTTT
16KTTT
20KTTT
25KTTT
32KTTT
40KTTT
50KTTT
63KTTT
S 270 < 2DTTT
3DTTT
4DTTT
6DTTT
8DTTT
10DTTT
Upstream circuit-breaker
D.strm In 100 160 250
breaker Im OFF OFF OFF
S 270 16DTTT
20DTTT
25DTTT
32DTTT
40DTTT
50DTTT
63DTTT
S 280 10 B-C T T T
13 B-C T T T
16 B-C T T T
20 B-C T T T
25 B-C T T T
32 B-C T T T
40 B-C T T T
50 B-C T T T
63 B-C T T T
S 280 10DTTT
16DTTT
20DTTT
25DTTT
32DTTT
40DTTT
50DTTT
63DTTT
S 280 10KTTT
13KTTT
16KTTT
20KTTT
25KTTT
32KTTT
40KTTT
50KTTT
63KTTT
S 280 < 2ZTTT
3ZTTT
4ZTTT
6ZTTT
8ZTTT
10ZTTT
13ZTTT
16ZTTT
20ZTTT
25ZTTT
32ZTTT
40ZTTT
50ZTTT
63ZTTT
S 290 80 C-D 14 T
100 C-D 10.5 T
125 C T
S 500 6 B-C 40 40 40
10 B-C-D 40 40 40
13 B-C-D 40 40 40
16 B-C-D 40 40 40
20 B-C-D 40 40 40
25 B-C-D 40 40 40
32 B-C-D 40 40 40
40 B-C-D 40 40 40
50 B-C-D 40 40 40
63 B-C-D 40 40 40
S 500 < 5.8 K T T T
8KTTT
11KTTT
15KTTT
20KTTT
26KTTT
32KTTT
37KTTT
41KTTT
45KTTT
10/33
10
ABB SACE
Technical details
MCBs
Description of product and codes ................. pg. 2/1
S 91.. series
Characteristics B-C
In Resistance Diss. pwr.*
[A] [m] [W]
660.5 2.2
10 16.3 1.6
16 10.2 2.6
20 8.1 3.2
25 6.2 3.9
32 4.1 4.2
* total dissipated power of device
S 240 series
Characteristic C
In Resistance*Diss. pwr.*
[A] [m] [W]
648 1.7
815 1
10 13.3 1.3
13 13.3 2.3
16 9 2.3
20 6.25 2.5
25 5 3.2
32 3.6 3.7
40 2.5 4
* internal resistance and dissipated power per pole
S 250 series
Characteristics B, C ** Characteristic K
In Resistance* Diss. pwr.* Resistance* Diss. pwr.*
[A] [m] [W] [m ] [W]
0.5 5500 1.4 5020 1.26
11440 1.4 1390 1.39
1.6 630 1.6 612 1.56
2460 1.8 450 1.79
3150 1.3 147 1.32
4110 1.8 112 1.79
648 1.7 54.1 1.95
815 1 33.8 2.16
10 13.5 1.35 15.1 1.51
13 13.3 2.3 12.6 1.26
16 9 2.3 8.1 2.07
20 4.5 2.5 5.27 2.11
25 3.8 2.4 3.97 2.48
32 3.2 3.3 2.65 2.71
40 2.5 4 2.44 3.9
50 1.2 3 1.15 2.9
63 1.4 5.6 0.7 5.2
* internal resistance and dissipated power per pole
**the rated currents 0.5...4A only apply to characteristic C
Serie S 270
Characteristics B, C ** Characteristic K
In Resistance*Diss. pwr.* Resistance* Diss. pwr.
[A] [m] [W] [m] [W]
0.5 5500 1.4 5020 1.26
11440 1.4 1390 1.39
1.6 630 1.6 612 1.56
2460 1.8 450 1.79
3150 1.3 147 1.32
4110 1.8 112 1.79
648 1.7 54.1 1.95
815 1 33.8 2.16
10 13.5 1.35 15.1 1.51
13 13.3 2.3 13.3 2.3
16 9 2.3 8.1 2.07
20 6.25 2.5 5.27 2.11
25 3 1.9 3.97 2.48
32 2.9 3.7 2.65 2.71
40 2 4.8 2.44 3.9
50 1.2 3 1.15 2.9
63 1.4 5.6 0.7 5.2
* internal resistance and dissipated power per pole
**the rated currents 0.5...4A only apply to characteristic C
Internal resistances and dissipated power tables
Serie S 941 N - S 951 N - S 971 N
Characteristics B-C
In Resistance*Diss. pwr.*
[A] [m] [W]
2520 2.1
4147.5 2.4
664 2.3
10 19 1.9
16 14 3.6
20 12 4.8
25 7.1 4.4
32 6.5 6.7
40 4.7 7.5
* total dissipated power of device
10/34
10
ABB SACE
Technical details
MCBs
S 280 - S 280 UC series
Characteristics B, C (1) Characteristic Z (1) Characteristics K (1), D
In Resistance* Diss. pwr.* Resistance* Diss. pwr.* Resistance* Diss. pwr.*
[A] [m] [W] [m] [W] [m] [W]
0.5 5500 1.37 10100 2.52 5020 1.26
11440 1.44 2270 2.27 1390 1.39
1.6 630 1.61 1100 2.81 612 1.56
2460 1.84 619 2.47 450 1.79
3150 1.35 202 1.82 147 1.32
4110 1.76 149 2.38 112 1.79
648 1.73 104 3.74 54.1 1.95
815 1 53.9 3.45 33.8 2.16
10 13.5 1.35 17.5 1.75 15.1 1.51
13 13.3 2.3 - - 13.3 2.3
16 9 2.3 10.9 2.8 8.1 2.07
20 6.25 2.5 6 2.4 5.27 2.11
25 3 1.9 4.1 2.56 3.97 2.48
32 2.9 3.7 2.81 2.88 2.65 2.71
40 2 4.8 2.55 4.09 2.44 3.9
50 1.2 3 1.77 4.43 1.15 2.9
63 1.4 5.6 1.31 5.2 0.7 5.2
* internal resistance and dissipated power per pole (1) values also apply to UC version
S 290 series
Characteristics C, D
In Resistance*Diss. pwr.*
[A] [m] [W]
80 1.0 6.4
100 0.8 8.0
125 0.7 10.9
* internal resistance and dissipated power per pole
S 500 series
Characteristics B, C, UCB Characteristic D
In Resistance*
Diss. pwr.
* Resistance*
Diss. pwr.
*
[A] [m] [W] [m] [W]
655 1.98 - -
10 15.2 1.52 - -
13 12.0 2.03 10.0 1.69
16 8.4 2.15 7.1 1.82
20 6.5 2.60 5.0 2.00
25 4.5 2.81 3.5 2.19
32 3.5 3.58 3.0 3.07
40 2.1 3.36 1.9 3.04
50 1.7 4.25 1.7 4.25
63 1.7 6.75 1.7 6.75
* internal resistance and dissipated power per pole
S 500 series
Characteristics K adjustable, UC-K, KM
In Resistance* Diss. pwr.*
[A] [m] [W]
0.1...0.15 84000 1.89
0.14...0.21 51000 2.25
0.2...0.3 25500 2.30
0.28...0.42 12800 2.26
0.28...0.58 7000 2.35
0.53...0.8 3600 2.30
0.73...1.1 2000 2.42
1...1.5 1050 2.36
1.4...2.1 680 3.00
2...3.0 350 3.15
2.8...4.2 175 3.09
3.8...5.8 95 3.20
5.3...8.0 55 3.52
7.3...11.0 35 4.24
10...15.0 23 5.18
14...20.0 12 4.80
18...26.0 8 5.41
23...32.0 5 5.12
29...37.0 3.5 4.79
34...41.0 2.5 4.20
38...45.0 1.7 3.44
* internal resistance and dissipated power per pole
S 700 series
Characteristic E sel
In Resistance* Diss. pwr. In Resistance* Diss. pwr.*
[A] [m] [W] [A] [m] [W]
25 4.1 2.6
35 2.85 3.5
50 1.65 4.1
63 1.3 5.2
80 1.1 7.0
100 110
* internal resistance and dissipated power per pole
10/35
10
ABB SACE
Technical details
MCBs
Description of product and codes ................. pg. 2/1
Influence of ambient temperature on
effective capacity and rated current
The rated value of the current of a miniature circuit-breaker refers
to a temperature of 20°C for circuit-breakers with characteristics
K and Z and 30°C for characteristics B, C and D.
For other temperatures, consider a factor (Fc) multiplied by the
rated current of the device to obtain the non-tripping current (Inf)
for the new temperature.
The change in the Fc factor depending on ambient temparature,
rated current of the circuit-breaker and the characteristic type is
shown in the two graphs below. The rated current (equivalent) for
the new temperature is obtained by dividing the non-tripping current
by the factor of 1.13 for circuit-breakers with characteristics B, C
or D and by the factor of 1.05 for circuit-breakers with
Influence of ambient temperature
Inf= In • Fc (NON-tripping current)
Influence of ambient temperature
Inf= In • Fc (NON-tripping current)
Influence of adjacent devices
Fm factor
Devices number
12345678 9
0.6
0.7
0.8
0.9
1.0
Fc factor
Ambient temperature °C
13…32A
10 A
0.5…8A
and
40…63A
25 10 0 10 20 30 40 55
0.8
0.9
1
1.1
1.2
1.3
1.4
1.5
Rated current
S280
S270
S250
B - C - D
S240
Fc factor
K and Z
Ambient temperature °C
13…32A
10 A
0.5…8A
and
40…63A
25 10 0 10 20 30 40 55
0.8
0.9
1
1.1
1.2
1.3
1.4
1.5
Rated current
S280
S270
S250
OEPM0106
OEPM0107
OEPM0108
Influence of adjacent devices
Correction factor Fm
No. of adjacent devices Fm
11
2 0.95
3 0.9
4 0.86
5 0.82
6 0.795
7 0.78
8 0.77
9 0.76
>9 0.76
characteristics K or Z.
The following page contains two tables in which this calculation
has been effected for temperatures from
-25°C to +55°C for the curves B, C, D, K and Z.
This derating is sufficient for loads which last for less than an hour;
for loads which last for more than an hour, multiply the rated current
(equivalent) referring to the new temperature by another factor of
0.9.
A variation in the tripping current is also caused by the presence
of several devices installed alongside each other; in this case,
consider the factor Fm according to the number of adjacent devices
(see table).
10/36
10
ABB SACE
Example: S 252 C 16 with T=35°C
Type of use Values to use Formula Calculation Result
Load less In (amb. t°)
than an hour (see tables) In= 15.43A
Load more In (amb. t°)
than an hour (see tables), 0.9 In (amb. t°) x 0.9 15.43 x 0.9 In= 13.9A
Load over an hour In (amb. t°)
with 8 adj.devices (see tables), 0.9, Fm (0.77) In (amb. t°) x 0.9 x 0.77 15.43 x 0.9 x 0.77 In= 10.7A
Equivalent rated current according to ambient temperature
MINIATURE CIRCUIT-BREAKERS S 240 - S 250 - S 270 - S 280 SERIES - CHARACTERISTICS B-C-D
In
In temp. -25°C -20°C -15°C -10°C -5°C 0°C 5°C 10°C 15°C 20°C 25°C 30°C 35°C 40°C 45°C 50°C 55°C
0.5 0.64 0.63 0.62 0.60 0.59 0.58 0.57 0.55 0.54 0.53 0.51 0.5 0.48 0.46 0.45 0.43 0.41
11.28 1.26 1.23 1.20 1.18 1.15 1.13 1.10 1.08 1.05 1.03 1 0.96 0.93 0.89 0.86 0.82
1.6 2.05 2.01 1.97 1.93 1.88 1.84 1.81 1.77 1.73 1.68 1.64 1.6 1.54 1.49 1.43 1.37 1.32
22.57 2.51 2.46 2.41 2.35 2.30 2.27 2.21 2.16 2.11 2.05 2 1.93 1.86 1.79 1.72 1.65
33.85 3.77 3.69 3.61 3.53 3.45 3.40 3.31 3.24 3.16 3.08 3 2.89 2.79 2.68 2.58 2.47
45.13 5.03 4.92 4.81 4.71 4.60 4.53 4.42 4.32 4.21 4.11 4 3.86 3.72 3.58 3.43 3.29
67.06 6.98 6.88 6.77 6.72 6.64 6.53 6.42 6.37 6.27 6.11 6 5.79 5.68 5.58 5.47 5.31
89.42 9.31 9.17 9.03 8.96 8.85 8.71 8.57 8.50 8.35 8.14 8 7.72 7.58 7.43 7.29 7.08
10 12.83 12.57 12.30 12.04 11.77 11.50 11.33 11.04 10.80 10.53 10.27 10 9.65 9.29 8.94 8.58 8.23
13 16.11 15.82 15.53 15.19 14.96 14.61 14.38 14.15 13.81 13.58 13.23 13 12.54 12.37 11.96 11.50 11.16
16 19.82 19.47 19.12 18.69 18.41 17.98 17.70 17.42 16.99 16.71 16.28 16 15.43 15.22 14.73 14.16 13.73
20 24.78 24.34 23.89 23.36 23.01 22.48 22.12 21.77 21.24 20.88 20.35 20 19.29 19.03 18.41 17.70 17.17
25 30.97 30.42 29.87 29.20 28.76 28.10 27.65 27.21 26.55 26.11 25.44 25 24.12 23.78 23.01 22.12 21.46
32 39.65 38.94 38.23 37.38 36.81 35.96 35.40 34.83 33.98 33.42 32.57 32 30.87 30.44 29.45 28.32 27.47
40 47.08 46.55 45.84 45.13 44.78 44.25 43.54 42.83 42.48 41.77 40.71 40 38.58 37.88 37.17 36.46 35.40
50 58.85 58.19 57.30 56.42 55.97 55.31 54.42 53.54 53.10 52.21 50.88 50 48.23 47.35 46.46 45.58 44.25
63 74.15 73.31 72.20 71.08 70.53 69.69 68.58 67.46 66.90 65.79 64.12 63 60.77 59.65 58.54 57.42 55.75
MINIATURE CIRCUIT-BREAKERS S 240 - S 250 - S 270 - S 280 SERIES - CHARACTERISTICS K-Z
In
In temp. -25°C -20°C -15°C -10°C -5°C 0°C 5°C 10°C 15°C 20°C 25°C 30°C 35°C 40°C 45°C 50°C 55°C
0.5 0.55 0.55 0.54 0.54 0.53 0.52 0.52 0.51 0.51 0.5 0.49 0.49 0.48 0.47 0.45 0.44 0.43
11.10 1.10 1.09 1.08 1.07 1.05 1.04 1.02 1.01 1 0.98 0.97 0.95 0.93 0.90 0.89 0.87
1.6 1.77 1.75 1.74 1.72 1.71 1.68 1.66 1.64 1.62 1.6 1.57 1.55 1.52 1.49 1.45 1.42 1.39
22.21 2.19 2.17 2.15 2.13 2.10 2.08 2.05 2.03 2 1.96 1.94 1.90 1.87 1.81 1.77 1.73
33.31 3.29 3.26 3.23 3.20 3.14 3.11 3.07 3.04 3 2.94 2.91 2.86 2.80 2.71 2.66 2.60
44.42 4.38 4.34 4.30 4.27 4.19 4.15 4.10 4.06 4 3.92 3.89 3.81 3.73 3.62 3.54 3.47
66.63 6.57 6.51 6.46 6.40 6.29 6.23 6.14 6.09 6 5.89 5.83 5.71 5.60 5.43 5.31 5.20
88.84 8.76 8.69 8.61 8.53 8.38 8.30 8.19 8.11 8 7.85 7.77 7.62 7.47 7.24 7.09 6.93
10 12.38 12.19 11.90 11.52 11.33 11.05 10.76 10.48 10.29 10 9.81 9.33 9.05 8.57 8.29 7.81 7.52
13 15.35 15.17 14.98 14.73 14.49 14.11 13.87 13.62 13.25 13 12.75 12.38 12.13 11.76 11.39 10.77 10.52
16 18.90 18.67 18.44 18.13 17.83 17.37 17.07 16.76 16.30 16 15.70 15.24 14.93 14.48 14.02 13.26 12.95
20 23.62 23.33 23.05 22.67 22.29 21.71 21.33 20.95 20.38 20 19.62 19.05 18.67 18.10 17.52 16.57 16.19
25 29.52 29.17 28.81 28.33 27.86 27.14 26.67 26.19 25.48 25 24.52 23.81 23.33 22.62 21.90 20.71 20.24
32 37.79 37.33 36.88 36.27 35.66 34.74 34.13 33.52 32.61 32 31.39 30.48 29.87 28.95 28.04 26.51 25.90
40 44.19 43.81 43.43 43.05 42.67 41.90 41.52 40.95 40.57 40 39.24 38.86 38.10 37.33 36.19 35.43 34.67
50 55.24 54.76 54.29 53.81 53.33 52.38 51.90 51.19 50.71 50 49.05 48.57 47.62 46.67 45.24 44.29 43.33
63 69.60 69.00 68.40 67.80 67.20 66.00 65.40 64.50 63.90 63 61.80 61.20 60.00 58.80 57.00 55.80 54.60
Description of product and codes ................. pg. 2/1
Technical details
MCBs
10/37
10
ABB SACE
Variation in alarm thresholds according to network frequency
The circuit-breakers are calibrated for a current with a frequency range between 50 and 60Hz.
For other frequency values, the electro-magnetic tripping current varies according to the multiplication
factor H.
100 Hz 200Hz 400Hz d.c.
H 1.1 1.2 1.5 1.5
For the thermal trip, on the other hand, there is no variation because it is independent of the network
frequency.
Applications in d.c. of standard circuit-breakers
Direct current is used because of the need for a source of energy which is able to power essential
services such as protection systems, emergency lighting, alarm systems, uninterruptible power
supplies with extreme reliability even in the absence of normal energy sources.
Storage batteries, buffer-powered from the network and installed near the users, are the safest
source of energy for powering these services.
In most cases, the rated voltage of these installations lies between 24 and 220V; higher voltages are
not, however, excluded (even up to 1000V).
When selecting circuit-breakers, it is important to bear in mind that leakage currents are very high
near power sources due to the low internal resistance of the batteries.
The main applications of circuit-breakers used in circuits in d.c. include:
- electric traction
- industrial plants with electrolithic processes
- units for rapid drop-out of synchronous machines.
For use in d.c., most standard circuit-breakers can be used, as long as the relevant voltage limits are
respected, as well as the special versions.
It is important to remember that the electro-magnetic trip value in d.c. is approx. 1.5-1.6 times the
corresponding value in a.c.
Standard circuit-breakers
Series Max. permitted voltage
S 240, S 250, S 270, S 280 60 V d.c. for one-pole circuit-breakers
125 V d.c. for two-pole circuit-breakers
S 290 60 V d.c. for one-pole circuit-breakers
125 V d.c. for two-pole circuit-breakers
S 500 250 V d.c. for two-pole circuit-breakers
Special UC (Universal Current) circuit-breakers
Series Max. permitted voltage
S 280 UC 440 V d.c. for two-pole circuit-breakers
S 500 UC 750 V d.c. for three-pole circuit-breakers
Technical details
MCBs
Description of product and codes ................. pg. 2/1
10/38
10
ABB SACE
Examples of high voltages between terminals and earth with equal voltage
between terminals
Max. voltage 250 V .... 440 V .... 440 V .... 440 V .... 440 V ....
between terminals voltage reversal
Max. voltage between 250 V .... 250 V .... 440 V .... (1) 250 V .... 250 V ....
terminals and earth
Modular circuit- One-pole Two-pole Two-pole Two-pole Four-pole (2)
breaker S 281 UC S 282 UC S 282 UC S 282 UC S 284 UC
Power supply
from bottom
Power supply
from top
Max. voltage 440 V .... 440 V .... 440 V ....
between terminals interruption of both poles interruption of 1 pole interruption of both poles
Max. voltage between 250 V 440 V 440 V
terminals and earth power supply with unearthed network or with unearthed network or with
symmetrical earthing asymmetrical earthing asymmetrical earthing
Modular Two-pole Two-pole Four-pole (2)
circuit-breaker S 282 UC S 282 UC S 284 UC
(1) In the interruption example, the negative pole is earthed
(2) Version with 4 protected poles available on request
1
2
L+
+
L–
1
2
L+
+
L–
3
4
1
2
L+ L–
3
4
+
1
2
L+ L–
3
4
+
M
+
1
2
L+ L–
3
4
5 7
68
(L–) (L+)
2
1
L– L+
4
3
6
5
8
7
(L+) (L–)
2
1
L– L+
4
3
+
+
M
2
1
L– L+
4
3
+
2
1
L– L+
+
4
3
+
2
1
L– L+
2
1
4
3
+
+
2
1
4
3
+
+
2
1
4
3
6
5
8
7
+
+
OEPM0110
OEPM0111
Examples of maximum voltages allowed between terminals according to
number of poles and wiring
Description of product and codes ................. pg. 2/1
Technical details
MCBs
10/39
10
ABB SACE
Technical details
RCDs
Contents
Classification criteria for RCDs .......................................................................................10/40
Influence on RCDs of currents with d.c. components ..................................................10/41
Comparison tables: current, impedance, dissipated power .........................................10/42
Coordinated protection for RCCBs .................................................................................10/42
Selectivity ..........................................................................................................................10/43
Varimat DS 850 ..................................................................................................................10/44
Emergency stop using DDA AE series RCD blocks ......................................................10/45
10/40
10
ABB SACE
Classification criteria for RCDs
RCDs are classified according to:
- presence or absence of protections against overcurrents;
- intrinsic or conditioned breaking capacity;
- detectable wave forms (AC type, A type);
- tripping time (instantaneous or selective);
- differential sensitivity.
According to the wave form of the earth leakage which they are sensitive to, they can be
divided into two groups:
- AC type RCDs(for alternating current only): suitable for all installations where users have sinusoidal
earth current;
- A type RCDs: suitable for installations with user devices which are equipped with electronic devices
which rectify the current or regulate size with the phase break.
According to their tripping time, they can be divided into:
- general RCDs;
- selective RCDs: time-dependent but equipped with tripping delay, they are installed upstream of
other general type RCDs to ensure their selectivity. In this way, the only part of the installation to be
out of service will be the part affected by the fault.
According to tripping sensitivity, they can be divided into:
- low-sensitivity RCDs (In>30mA): they are coordinated with the resistance of the earth system
according to the formula IA<50/R to provide protection against indirect contacts, that is, to avoid
an accessible metal mass, which is normally insulated, becomes live (over 50V) because of an
insulation fault;
- high-sensitivity RCDs (In<30mA): used to provide protection against direct contacts. They are
also called physiological-sensitivity RCDs because the user who inadvertently touches a live part
opposes the resistance of his own body to the flow of the current to earth; the circuit-breaker must
therefore break the power supply as soon as this current exceeds safety levels.
Technical details
RCDs
Description of product and codes ................. pg. 3/1
10/41
10
ABB SACE
Influence on RCDs of currents with d.c. components
For many years the manufacturers of electrical appliances and other electrical equipment have been
using electronic components to improve the performance of their products, increase comfort and
save energy.
Loads such as washing machines with variations in spin speed, variable-speed tools, thermostats
and dimmers operate at currents with varying wave shapes (pulsating currents with d.c. components,
inverted currents, levelled currents).
There are three different types of current (fig. A):
Type I Inverted current with d.c. components,
with value continuously greater then zero, caused
by:
- three-phase current - median point and three-
phase current - jumper connection
- unidirectional rectification with inductive and
capacitive levelling
- Villard type voltage doubling
Type II Pulsating current with d.c. components
sometimes with zero value, caused by ohmic
load with:
- unidirectional rectification without levelling
- single-phase jumper connection with or without
levelling
- regulation of the symmetrical and asymmetrical
phase operating angle (dimmers, RPM meters)
Type III Pulsating current with d.c. components
passing through zero caused by inductive loads
with:
- unidirectional rectification without levelling
- single-phase jumper connection with or without
levelling
- symmetrical and asymmetrical regulation of the
phase operating angle (dimmers, RPM meters)
If there is a fault current to earth after an insulation fault on live parts supplied with rectified current,
the contact voltages are the same size as in alternating current.
Standard RCDs, which are designed to operate with alternating current at 50-60Hz, are insensitive
to fault currents with d.c. components.
Non-tripping of a RCD when there are fault currents with d.c. components may have two
consequences:
- it is dangerous for people and equipment (electrocution or fire)
- it causes desensitivation of RCD due to excessive polarization of the transformer core that is no
longer able to send the necessary power supply to the releaser (figure B - hysteresis cycle no. 1).
To avoid this inconveniences, RCDs type A have to be used. Thanks to the specific technology of the
toroidal cores, the supply level is increased at a value sufficient to trigger the switching mechanism
(figure B - hysteresis cycle nr. 2). The sensitivity of the switching mechanism is further increased by its
coupling with an electronic circuit sensitive to the wave shape of the current. In this way the tripping
of the RCD is assured for any unidirectional pulsating wave shape even in case of overlapping of a
DC component up to 6mA.
OEPM0116
Description of product and codes ................. pg. 3/1
Technical details
RCDs
I
t
Type I
I
t
Type III
I
t
Type II
Figure A
H1 H2 A/cm
H
B1
B2
B
12
Figure B
OEPM0115
10/42
10
ABB SACE
DS.. series
Rated Two-pole RCBOs Three/four-pole RCBOs
current Resistance* Diss. pwr.* Resistance* Diss. pwr.*
In [A] [m] [W] [m] [W]
650 1.8 54.5 2.0
10 16 1.6 16.5 1.65
16 10.5 2.7 11 2.8
20 6.2 2.2 6.7 2.7
25 5.5 3.5 6 3.75
32 4 4.1 4.1 4.2
40 3.5 5.6 3.6 5.8
50 1.6 3.9 1.8 4.5
63 1.9 7.5 2 7.8
* internal resistance and dissipated power per pole
Total dissipated power of F.. series RCCBs
Type Rated Total
current Diss. pwr.
In [A] [W]
F362-F372 25 2
F362-F372-F392 40 4.1
F362-F372-F392 63 5.6
F362-F372 80 8.5
F364-F374 25 4
F364-F374-F394 40 8.2
F364-F374-F394 63 12.6
F664-F674 80 12
F664-F674 100 17
F664-F674 125 27
Comparison tables: current, impedance, dissipated power
Coordinated protection for RCCBs
When installing RCCBs, it is important to check that these devices are properly protected against overload and short-circuit; this check
varies according to whether RCCBs without releasers are used or RCBOs.
In the first case, the devices must be protected using special miniature circuit-breakers or fuses; using both devices leads to two short-
circuit current values: conditional residual short-circuit current (Ic) and conditional short-circuit current (Inc).
ABB SACE RCCBs have a breaking capacity of 0.5-1.5 kA for earth fault in accordance with the test cycle specified in IEC 1008 / EN
61008 Standard.
When the value of the earth fault current exceeds the Im value (residual current breaking capacity), the device inserted to protect
against short-circuits must be able to protect the installation and the RCCB by limiting Ip and I2t to the maximum values indicated in the
table below.
The table indicates the breaking capacities of some protective combinations of RCCBs effected using miniature circuit-breakers or
fuses.
RCCB rated current In [A] 16 25 40 63 125
Rated breaking capacity Im [A] 500 500 1500 1500 1500
Max. withstanding I2tI2t [A2s] 28,000 28,000 40,000 60,000 90,000
Max. withstanding peak current Ip [A] 5,000 5,000 6,000 6,000 10,000
The RCBOs do not have a protection problem since they are designed to be self-protecting up to the breaking capacity value indicated
on the block.
In the event of a short-circuit through earth, the devices have a residual current breaking capacity which is equal to the breaking
capacity for service insulated short-circuits indicated on the label.
Total dissipated power DDA blocks
class “AC - A” In=30
Rated Two-pole RCD blocks Three/four-pole RCD blocks
current Resistance Diss. pwr. Resistance Diss. pwr.
Ib [A] [m] [W] [m] [W]
25 4.0 2.5 4.8 3
40 2.8 4.5 3.5 5.5
63 0.7 3 0.9 3.5
The dissipated power shown in the table refers to Ib. For use with
circuit-breakers with lower rated current In the dissipated power
in W must be determined using the formula:
I2
W = (–––) • WIB
Ib
Technical details
RCDs
10/43
10
ABB SACE
Selectivity
When using RCDs, problems linked to tripping times are very important. In actual fact, protection
against contact voltages is only effective if the maximum tripping times established in the safety
curve are not exceeded.
Bearing in mind that when going up from the peripheral branches of the installation to the main
switchboards it is less likely that unskilled persons come into contact with dangerous parts, we can
envisage a first level of high sensitivity (0.01 and 0.03A) RCDs, installed to protect all the parts of the
installation which are accessed by unskilled persons and a second level upstream with sensitivity
which is not more than a third of that of the downstream circuit-breaker.
Table of RCD tripping times for general AC-A types
Sensitivity Times acc. to
IEC 1008 / EN 61008 - IEC 1009 / EN 61009
InIn2 In5 In 500A
All 0.3s 0.15s 0.04s 0.04s
Table of RCD tripping times for selective AC-A (S) types
Sensitivity Times acc. to
IEC 1008 / EN 61008 - IEC 1009 / EN 61009
InIn2 In5 In 500A
> 0.03A
0.13...0.5s 0.06...0.2s 0.05...0.15s 0.04...0.15s
N.B. High sensitivity selective RCDs are not allowed
12345678910
x I
n
25
50
75
100
150
200
T (ms)
300 ms.
1.4 2.8 4.2 5.6 7 8.4 9.8 11.2 12.6 14
x I
n
500A
240
Limits acc. to IEC/EN 61008 -
IEC/EN 61009
OEPM0117
Description of product and codes ................. pg. 3/1
Technical details
RCDs
10/44
10
ABB SACE
VARIMAT DS 850
Function
The VARIMAT RCBO carries out the same
functions as the out-dated circuit-breakers
with manual sensitivity change, but
automatically.
VARIMAT RCBOs not only measure the
current in the live conductors but also in
the protection conductor (PE) and are
therefore able to distinguish direct contact
(without current in the PE) from indirect
contact.
The VARIMAT RCBO is sized so that
sensitivity is 30mA for direct contacts and
200mA for indirect contacts.
Advantages
The VARIMAT RCBO enables high
sensitivity protection to be used also in
installations where the earth leakage is so
high that it would prevent the use of normal
30mA RCBOs.
In other words, with VARIMAT it is possible
to add protection against direct contacts
in situations where this would not be
possible with traditional devices because
of nuisance tripping.
kWh
Earth
system Rt
PE Energy
meter
Varimat
DS 850
T
T'
PE
L
N~
To
other
loads
OEPM0120
Technical details
RCDs
Description of product and codes ................. pg. 3/1
12345678910
x I
n
200
500
T (ms)
500 A
150
130
60 50 I
n = 1A I
n=1A
100
250
100
40
I
n=0,3 A
I
n=0,5 A
Limits acc.to CEI EN 61008 -
CEI EN 61009
1 2 3 4 5 6 7 8 9 10 x I
n
50
100
200
250
350
T (ms)
150
300
10x1.4 X
I
n
~
1.4 2x1.4 5x1.4 500 A
2
500
I
n = 0.5
I
n = 0.3 A
A
Limiti rilevabili dalla tabella dei tempi
Key
Selectivie
General type
Limits acc. to CEI EN 61008,
CEI EN 61009
OEPM0118
OEPM0119
10/45
10
ABB SACE
Emergency stop using DDA AE series RCD blocks
The AE series RCD block combines the protection supplied by the RCBOs with a positive safety
emergency stop function for remote tripping.
In the AE version, the DDA AE series RCD blocks are available.
Operating principle (patented)
Two additional primary circuits powered with the same voltage and equipped with the same resistance
have been added to the transformer; under normal conditions the same current would flow through,
but since they are wound by the same number of coils in opposite directions they cancel each other
out and do not produce any flow.
One of these two windings acts as the remote control circuit: the emergency stop is obtained by
interrupting the current flow in this circuit.
The positive safety is therefore obvious: an accidental breakage in the circuit is equivalent to operating
an emergency control button.
Advantages
Compared with the devices which are normally used in emergency circuits, DDA AE blocks have the
following advantages:
- positive safety
- no undesirable tripping if there is a temporary reduction or interruption of the mains voltage
- efficient immediate operating even after long off-service periods of the installation.
Use
Application of the DDA AE blocks complies with the requirements of IEC/EN 60364 Standard they
are therefore suitable for escalators, lifts, hoists, electrically operated gates, machine tools, car washes
and conveyor belts and everywhere the positive command is required.
R R/2
R/2
1
5
2
34
1Polarized relay
2Sensor winding
3Induction toroid
4Supplementary
primary windings
5Single or multiple
push-button unit
Push-buttons
(normally
closed)
OEPM0121
OEPM0122
Description of product and codes ................. pg. 3/1
Technical details
RCDs
10/47
10
ABB SACE
Technical details
Other protection devices
Contents
RD2 residual current monitors ........................................................................................10/48
OVR surge protective devices .........................................................................................10/49
MS 225 manual motor starters ........................................................................................10/56
E 930 fuse holders .............................................................................................................10/60
M2160 - M2060 fuse switches .........................................................................................10/61
10/48
10
ABB SACE
RD2 RESIDUAL CURRENT MONITORS
They operate in connection to appropriate toroidal transformers (in 6 different diameters) which perform
the summation of line currents; any potential current leakage in the managed circuit causes, in the
secondary of the toroidal transformer, an indication detected by the relay which intervenes.
The relay can control the tripping of the protection circuit-breaker release, thus breaking the circuit.
According to the EN 61008 Standard, these relays are sensitive to leakage sinusoidal currents and to
leakage pulsating currents with direct components. Thus they can be defined as “A type”.
Some electric circuits allow to adjust sensitivity and time; the values can be selected through
appropriate minidips.
They are fully in compliance with EN 62020.
Technical details
Other protection devices
Description of product and codes ................. pg. 4/2
10/49
10
ABB SACE
Technical details
Other protection devices
Description of product and codes ................. pg. 4/3
OVR SURGE PROTECTIVE DEVICES (SPDs)
Power lines often experience disturbances due to very short, high amplitude transient overvoltages
(from ten µs to few ms) that can reach a high value of kV.
For atmospheric phenomena overvoltages due to lightning can occurr either on overhead lines and
underground cables (increase of the potential to the earth).
In addition, loads themselves can introduce into the network parasitic interferences, originating i.e.
from lamps switch-on, welding devices, thyristor operation, contactor operations, etc. These
disturbances have a low energetic content, but the sudden front and crest value make them hurtful
for an appropriate operation of appliances; inserting some types of lamps can i.e. cause overvoltages
to the network frequency with crest values of 5-6kV, that can be repetitive in case of incorrect operation.
In general the disturbances wave form is defined by the following three parameters:
• crest value (amplitude)
• impulse rise time (t90) up to 90% of amplitude
• duration, measured from the fall time (t50) to half wave amplitude.
The numerous experimental surveys allow to detect the
trends statistically more frequent for overvoltage and
overcurrent waves.
Examples of voltage normalized waves:
•t90 = 1.2µs t50 = 50µs (1.2/50 µs)
•t90 = 0.5µs t50 = 700µs
Examples of current normalized waves:
•t90 = 8µs t50 = 20µs (8/20 µs)
•t90 = 10µs t50 = 1000µs
In order to fix the problems caused by transient overvoltages it is useful to install a protection system
such as OVERSTOP, which includes protection devices for low voltage power lines (main and
secondary), telephone lines, and data transmission lines.
The main characteristic of OVERSTOP devices is the use appropriately combined of surge arresters
and varistors, with the possibility of taking advantage of both.
In addition to the response speed (< 25 ns) typical of varistors, these devices are able to guarantee
also the restriction of residual voltage and electric load power consumption as well as the prolongation
of varistor average life.
OEPM0125
0
t10 TIME
[µs]
WAVE
AMPLITUDE
10%
30%
50%
90%
t30 t90 t50
10/50
10
ABB SACE
Description of product and codes ................. pg. 4/3
Technical details
Other protection devices
OVR/365, OVR/165, OVR/365P and OVR/165P
These SPDs are particularly suitable for three-phase and single-phase main power lines protection in
TT or TN-S circuits mainly in industrial/tertiary sectors located in high lightning risk zones. If on the
building i.e. or nearby (within a radius of 50m) it is installed a lightning conductor, the surge arrester
must be Imax=65kA.
More technical characteristics
OVR/365, OVR/365P OVR/165, OVR/165P
OVR protection
- fuse holder 22x58-80A
- C curve circuit-breaker 25A
Terminals F/N [mm2] 16 (flexible) 25 (rigid)
Earth [mm2] 35 (flexible) 50 (rigid)
Operating temperature [°C] -20…+40
Storage temperature [°C] -40…+70
End of life indication
On the front of the device there is and indicator which signals the surge arrester status:
operating;
warning (replace as soon as possible);
in this status OVR electric performance are reduced and it is possible that,
in case of overvoltages, the device does not perform its protection function causing
unexpected trippings of system residual protections;
failing.
Using OVERSTOP protections against line overvoltages, it is possible to avoid damages to sensitive
elements in load devices, the precocious aging of these elements or other possible consequences
on the correct device operation (i.e. the uncontrolled machine starting or stopping, incorrect data
display or transmission, disturbances in the software procedures, uncorrect switching of alarms).
The SPDs used depends on the network structure, with a difference between the two types of
protection against transient overvoltages:
- common protection between active conductors and earth (phase/earth; neutral/earth)
- residual protection between active conductors (phase/phase; phase/neutral; phase/earth; neutral/
earth) and between active conductors and earth. In TT and TN-S systems in particular differential
protection is required (as provided by OVR series).
OVERSTOP devices guarantee load protection both against atmospheric discharges (lightning) and
overvoltages in some plants (switch operations, parasitic interferences etc).
10/51
10
ABB SACE
Technical details
Other protection devices
Description of product and codes ................. pg. 4/3
OVR/340, OVR/140, OVR/315, OVR/115
OVR/340P, OVR/140P, OVR/315P, OVR/115P
These SPDs are particularly suitable for three-phase and single-phase main/secondary power lines
protection in TT or TN-S circuits in tertiary/residential sectors.
More technical characteristics
OVR/340, OVR/140 OVR/315, OVR/115
OVR/340P, OVR/140P OVR/315P, OVR/115P
OVR protection
- fuse holder 14x51-50A 10,3x38-25A
- curve C circuit-breaker C 25A 10A
Terminals F/N [mm2] 16 (flexible); 25 (rigid)
Earth [mm2] 35 (flexible); 50 (rigid)
Operating temperature [°C] -20…+40
Storage temperature [°C] -40…+70
End of life indication
On the front of the device there is an indicator which signals the surge arrester status:
operating;
failure; to be replaced immediately.
OVR/TEL
OVR/TEL surge arrester is intended for the protection of loads connected to a telephone line or to a
data transmission line at 48V d.c. up to 200V d.c.
More technical information
OVR/TEL
Terminals [mm2] from 0.5 to 2.5
Operating temperature [°C] -20…+40
Storage temperature [°C] -40…+70
End of life indication
On the front of the device there is an indicator which signals the surge arrester status:
operating;
failure, to be replaced immediately.
10/52
10
ABB SACE
Description of product and codes ................. pg. 4/3
Technical details
Other protection devices
L1
N
E
R
OEPM0126
OVR/SIGN
OVR/SIGN is an accessory complementary to OVR surge arresters (monobloc and withdrawable-
cartridge versions) which allows signalling the operating status (standard operation or local/remote
alarm) of one or more OVR surge arresters, up to a maximum of 15 modules.
More technical characteristics
Terminals [mm2] 2.5 rigid
Operating temperature [°C] -20…+40
Storage temperature [°C] -40…+70
This accessory is made up by an E emitter module, which must
be installed on the left of the devices to be managed and by an R
receiver module installed on the right. The receiver module enables
(through the switching contact) the triggering of a remote optical
or acoustic alarm.
Parameter to choose OVR
When choosing the appropriate protection for each application, the following parameters must be
considered:
type and electric characteristics of system devices
specific electric parameters for protection
maximum discharge current Imax and line residual voltage Up
(maximum voltage still applied to appliances when the protection operates)
dangerousness of a geographic zone in connection with the lightning risk level
economical value of the devices to be protected.
For a correct evaluation these parameters must be analysed in a correlated way; this allows to
choose a single protection and also to define the advisability of a multiple level protection system
(cascaded protection).
Example: two or more level protection through OVR monobloc surge arresters
For a practical example consider two types of protection with a maximum discharge current of 65kA
(2kV residual voltage) and 15kA (1.2kV residual voltage) respectively. These values indicate the OVR
protection operating capability before ending its life and be replaced: each protection, in fact, can
withstand only one discharge of maximum current (65kA or 15kA) or 20 discharges at rated transient
discharge current (20 or 5kA respectively).
If the devices installed on the secondary line to be protected have an insulation voltage lower than
2kV, a 15kA protection must be used (1.2kV residual voltage). As previously explained, this protection
can have a too short operation life if it is installed in a high risk zone or with a high number of
Bases with signal contact
BASE1N and BASE3N are equipped with an auxiliary remote
contact signalling the product end of life. Through a switching
contact, it also enables the triggering of a remote alarm related to
the failure of a specific OVR release.
OEPM0166
141112
L
Note:
L1, connection to
terminal 1
N, connection to
terminal 5
10/53
10
ABB SACE
Technical details
Other protection devices
Description of product and codes ................. pg. 4/3
N.B.
For installing the appliances, the diagram considers approximate device insulation voltage values to
be related to the line residual voltages of each OVR UP res. level. In the reality it is necessary to refer to
the specific marking (insulation voltage) of each device to be protected.
OVR/TEL
Telephone
Telephone appliances and data transmission
voltage
of
appliances
Up:
2.5kV
OVR/365
OVR/165
OVR/340
OVR/140
OVR/315
OVR/115
Motors
command
appliances
Others
Numerical
control
machines
Residual
voltage
provided
by OVR
Up res:
2kV
Level 1 - Electro-mechanical appliances
High-risk zone
Livello 3 - Electronic and electro-mechanical appliances with electronic components
Low-risk zone
Others
PCs
printers Televisions
Hi-fis
Line 230V/ 400Va.c.
Max.
discharge
current
I max:
65kA
Up res:
1,2kV
..8kV
I max:
40kA
Telephone line 48…200V d.c.
Numerical
control
machines
Level 2 - Electronic and electro-mechanical appliances with electronic components
Medium-risk zone
Alarm
Up res:
1.2kV
1.8kV
I max:
15kA
PCs
printers
Televisions
Hi-fis
Alarm Others
Up:
1.2-2kV
Up:
1.2-2kV
Up res:
0.3kV
I max:
10kA
Appliances
Example
OVR
OVR
Appliances
Appliances
OVR
OVR
Others
Fax
Control line
Residual
voltage
provided
by OVR
Residual
voltage
provided
by OVR
Residual
voltage
provided
by OVR
Max.
discharge
current
Max.
discharge
current
Max.
discharge
current
Max.
discharge
current
Insulation
voltage
of
appliances
Insulation
voltage
of
appliances
Insulation
voltage
of
appliances
Insulation
overvoltages (i.e. high lightning risk level zones).
This also causes a problem to appliances: in case of high energy content overvoltage the 15kA
protection could end its life immediately, without avoiding damages to electric loads to be protected.
A two level protection system can be, in these cases, the best solution which can be achieved
applying the 65kA protection on the main power line upstream the secondary line.
For a finer and more effective protection cascaded systems on more levels can be useful, i.e. using
65kA, 40kA and 15kA protections.
The diagram shows a general example of cascaded protection on three levels; it is also indicated a
specific level for telephone and data transmission devices. Each level can be applied individually
based on the actual system needs and on the dangerousness of the zone: i.e. the levels 2 and/or 3
are sufficient in residential and small tertiary applications in medium/low risk zones.
10/54
10
ABB SACE
Description of product and codes ................. pg. 4/3
Technical details
Other protection devices
Defining the zone dangerousness
The lightning risk level is determined by the number of lightnings per km2 a year. This level can be
provided by the local meteorologic offices. In Europe the average level, equal to 2.50Ng, can exceed
10Ng in some areas (Alps and other mountainous zones).
The atmospheric risk level, determined based on the geographic zone, must be evaluated according
to other parameters, i.e. the presence of a lightning conductor nearby (in this case a 65kA protection
must be installed) or of appliances causing transient overcurrents.
It must also be observed that an underground power supply network is less sensitive to overcurrents;
anyway, in case of lightning conductors or large objects connected to earth, a higher risk level must
be considered.
In conclusion, the higher is the zone dangerousness, the higher must be the OVR Imax at the first
level.
10/55
10
ABB SACE
Technical details
Other protection devices
Description of product and codes ................. pg. 4/3
By way of indication, the table shows the importance of an appropriate protection system against
overvoltages based on the type of the appliances to be protected, their value, and on the zone risk
level.
The choice of a system on one or more levels, including protections with higher technical characteristics
(i.e. 65kA), is explained by the cost of the appliances compared to the cost of these protections; in
many cases, in fact, using only protections with lower characteristics (i.e. 15kA) could damage the
protections themselves in short times and decrease the safety for the device integrity.
Low risk zones
Type of device Value of the device to be protected (in Euros)
>500 1000…5000 5000
Electro-mechanical Optional Optional Recommended
Electro-mechanical/electronic Optional Recommended Recommended
Electronic Recommended Recommended Recommended
Medium risk zones
Type of device Value of the device to be protected (in Euros)
>500 1000…5000 5000
Electro-mechanical Optional Recommended Recommended
Electro-mechanical/electronic Optional Recommended Highly recommended
Electronic Recommended Highly recommended Highly recommended
High risk zones
Type of device Value of the device to be protected (in Euros)
>500 1000…5000 5000
Electro-mechanical Recommended Recommended Recommended
Electro-mechanical/electronic Recommended Highly recommended Highly recommended
Electronic Highly recommended Highly recommended Highly recommended
10/56
10
ABB SACE
Description of product and codes ................. pg. 4/7
Technical details
Other protection devices
MS 225 MANUAL MOTOR STARTERS
MS 225 series manual motor starters with modular structure are included in a supply containing
systems and devices for protecting and controlling motors.
Because of their characteristics MS 225 switches are general application devices; their compact
structure and the possibility of being installed on DIN rail make them the perfect solution even outside
the industrial environment.
The number of accessories available allow to satisfy every installation need.
More technical characteristics
Storage temperature -50...+80°C
Protection degree IP20
Max. rated current in DC
60V 110V 220V 440V
in DC1 8 8 3 0.4
in DC3 7 7 2 0.3
in DC5 5 3 1 0.2
Max. rated power in AC3
three-phase motors 220V: 7kW
380V: 12.5kW
500V: 16kW
660V: 22kW
Max. altitude 3000m
Weight 390g
Tropicalization IEC 68-2-2Bb/-2-1Ab,
IEC 68-2-30Db
Resistance and dissipation values per pole
Type Resistance Dissipation
[m] [W]
MS 225/0.16 71100 1.82
MS 225/0.25 27100 1.69
MS 225/0.4 12300 1.97
MS 225/0.63 5170 2.05
MS 225/1 2090 2.09
MS 225/1.6 805 2.06
MS 225/2.5 340 2.13
MS 225/4 141 2.25
MS 225/6.3 51 2.02
MS 225/9 22.4 1.81
MS 225/12.5 12.2 1.90
MS 225/16 8.1 2.07
MS 225/20 4.8 1.92
MS 225/25 3.5 2.18
Magnetothermic tripping characteristics
Overload cut-out tripping time according to the overload or short-
circuit generated on the protected line. The values refer to an
ambient temperature of 20°C.
0.01
0.004
0.04
0.1
0.4
1
4
10
40
1
4
10
40
1
12 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
x In adjusted rated current
Tripping time - sec.
3 poles
2 poles
OEPM0129
10/57
10
ABB SACE
Technical details
Other protection devices
Description of product and codes ................. pg. 4/7
Test voltage
420V, 50Hz
cosϕIk
1 500A
0.92 1500A
0.87 3000A
0.75 4500A
0.68 6000A
0.55 10000A
0.32 20000A
0.22 30000A
0.18 50000A
Test voltage
420V, 50Hz
cosϕIk
1 500A
0.92 1500A
Restriction of the specific let-through energy on short-circuit
100 1000 10000 50000
10
1
10
2
10
3
10
4
Estimated short-circuit current Icc
Specific let-through energy
i
2
dt) in A
2
s
20-25A
16-20A
12.5-16A
9-12.5A
6.3-9A
4-6.3A
2.5-4A
1.6-2.5A
1-1.6A
A
(
10 100 1000
0.001
0.01
1
10
100
0.1
1000
10000
20 30 40 50 200 300 500 2000
Estimated short-circuit current Icc
Specific let-through energy (I
2
dt) in A
2
s
0.63-1A
0.4-0.63A
0.25-0.4A
0.16-0.25A
0.1-0.16A
A
OEPM0131 OEPM0130
10/58
10
ABB SACE
Description of product and codes ................. pg. 4/7
Technical details
Other protection devices
Electric diagrams for special applications
Load insertion in direct current
I > I > I >
I > I > I >
1
3
5
2
4
6
+-
LOAD
1/L1
3/L2
5/L3
2/T1
4/T2
6/T3
Direct starter
I > I > I >
I > I > I >
M
3 ~
L3
L2
L1
U1 V1 W1
I > I > I >
I > I > I >
1/L1
3/L2
5/L3
2/T1
4/T2
6/T3
1
3
5
1
3
5
1
3
5
2
4
6
2
4
6
2
4
6
U1
V1
W1
U2
V2
W2
Star-delta starter
L3
L2
L1
M
3 ~
I > I > I > I > I > I >
I > I > I >
1/L1
3/L2
5/L3
2/T1
4/T2
6/T3
1
3
5
2
4
6
U1
V1
W1
I > I > I >
1/L1
3/L2
5/L3
1
3
5
2
4
6
2-speed motor, 2 different windings
L3
L2
L1
2/T1
4/T2
6/T3
U2
V2
W2
M
3 ~
OEPM0134
OEPM0135 OEPM0133
OEPM0132
10/59
10
ABB SACE
Technical details
Other protection devices
Description of product and codes ................. pg. 4/7
Accessory installation
0
I
MS 225
~ 690V
0,80,90
1,0A
0,7
1,63
HK
21
13
22
14
-1 1
SK
33
34
-1 0
TT
AS HK.. SK..
UA
MS 225
0
I
MS 3 25
~ 690V
0,8 0,90
1,0A
0,7
1,63
MP
0
I
MS 3 25
~ 690V
0,8 0,90
1,0A
0,7
1,63
CUST IP65-RG
2 HK 1 HK + 1 SK 1 HK 1 SK MS 225 MS 225 + 1 NO + 1 NC
OEPM0141
OEPM0140
OEPM0137
OEPM0136
10/60
10
ABB SACE
Description of product and codes ............... pg. 4/10
Technical details
Other protection devices
Power consumption in watt
at rated current
Of the fuse Fuses Fuses Fuses
In [A] 10.3x38 14x51 22x58
aM aM aM
1 0.08
2 0.12
4 0.17 0.25 0.30
6 0.30 0.30 0.45
8 0.35 0.40 0.55
1 0.40 0.50 0.60
12 0.45 0.65 0.75
16 0.70 0.90 0.90
20 1.00 1.00 1.10
25 1.20 1.20 1.35
32 1.50 1.55 1.60
40 2.10 1.90
45 2.15 2.20
50 2.50 3.00
63 4.10
80 5.20
100 6.50
125 7.80
E 930 FUSE HOLDERS
More technical characteristics
Protection degree IP20
Self-extinguishing degree V0 acc. UL94
Resistance to UV rays 60h
Terminals 10mm2 (up to 32A);
25mm2 (from 50A);
35mm2 (from 125A)
Screws galvanized steel
Colour RAL 7035 grey
Power consumption in watt at rated current
Of the fuse Fuses Fuses Fuses
In [A] 10.3x38 14x51 22x58
gL gL gL
10.272 0.50 0.80
41.05 0.95 1.45
61.10 1.30 1.60
81.20 1.60 2.15
10 1.30 1.90 2.50
12 1.50 2.10 2.70
16 1.80 2.20 2.75
20 2.00 2.30 2.90
25 2.30 3.00 3.40
32 2.60 3.30 3.60
40 3.60 4.50
45 4.10 4.80
50 5.00 5.50
63 6.35
80 7.35
100 8.75
125 12.50
10/61
10
ABB SACE
Technical details
Other protection devices
Description of product and codes ............... pg. 4/12
2 3 4 0.5 1 2 5
4
10
-2
2
4
345 10 2 3 4 50 100 2 3 4 500 1000 2 34
10
-1
2
4
10
0
2
4
10
1
2
4
10
2
2
4
10
3
2
4
10
4
B
A
Blow-out time in seconds
Current intensity
0.16
0.25
0.5
0.6
1
2
4
6
8
10
12
16
20
25
32
40
50
63
80
100
125
2345 10 2 5
4
10
-2
2
4
3 4 50 100 2 3 4 500 1000 2 3 4 5000 10000 2 34
10
-1
2
4
10
0
2
4
10
1
2
4
10
2
2
4
10
3
2
4
10
4
B
A
Blow-out time in seconds
Current intensity
1
2
4
6
8
10
12
16
20
25
32
40
50
63
80
100
125
Maximum values of specific
let-throug energy in A2s
In [A] aM fuses
Pre-arc Total
110 20
235 60
4110 270
6200 600
8400 1100
10 800 2000
12 1000 2800
16 1200 4500
20 1700 7000
25 2700 11000
32 5000 19000
40 9000 28000
45 14000 37000
50 19000 45000
63 30000 70000
80 50000 110000
100 80000 170000
125 100000 185000
Maximum values of specific
let-through energy in A2s
In [A] gL fuses
Pre-arc Total
1315
2530
415 110
660 200
880 330
10 130 400
12 250 700
16 450 1500
20 800 2700
25 1400 4500
32 2200 7000
40 3500 11000
45 4000 15000
50 4500 17000
63 9300 27000
80 20000 65000
100 40000 100000
125 70000 160000
gL type cylindrical fuses
Type aM cylindrical fuses
A: max. time for protection against short-circuits
B: max. time for protection against indirect contact for m=1
A
B
A
B
OEPM0142
OEPM0142
M2160 - M2060 FUSE SWITCHES
More technical characteristics
Type Power
consumption
[W]
M 2161 3.18
M 2161 Na 4.38
M 2162 6.38
Type Power
consumption
[W]
M 2163 9.54
M 2163 Na 16.00
M 2061 3.18
Type Power
consumption
[W]
M 2061 Na 4.38
M 2062 6.38
Type Power
consumption
[W]
M 2063 9.54
M 2063 Na 16.00
10/63
10
ABB SACE
Technical details
Command devices
Contents
E 240 - E 270 switch disconnectors ................................................................................10/64
RS 370 rotary switch disconnectors ...............................................................................10/65
E 220 switches ..................................................................................................................10/65
ESB - EN contactors .........................................................................................................10/66
Latching relays ..................................................................................................................10/70
10/64
10
ABB SACE
Technical details
Command devices
Description of product and codes ................. pg. 5/2
E 240 - E 270 SWITCH DISCONNECTORS
More technical characteristics
E 240 E 270
Rated closing capacity 1.25In - 1.1Vn - cosϕ = 0.3 1.25In - 1.1Vn - cosϕ = 0.3
Rated short-circuit capacity 15In 15In
Short-circuit conditional back up resistance to back up resistance to
current device short-cirtuit device short-circuit
S 250 5KA S 250 10KA
S 260 5KA S 260 10KA
S270 5KA S 270 10KA
S 280 8KA S 280 16KA
S 290 3KA S 290 6KA
S 700 50A MCB 10 KA S700 100A MCB 25 KA
NH00 50A fuse 10 KA NH00 100A fuse 25 KA
BS88 50A fuse 25 KA BS88 160A fuse 50 KA
Rated application uninterrupted uninterrupted
Rated thermal
current in housing Ithe = 45A Ithe = 100A Ithe = 125A
Utilization category AC22B AC23A AC22A
Minimum insulation distance 5mm, is kept on opening position
Contact indication control lever used to indicate contact position
Terminals 25mm250mm2
Installation on DIN profile 35mm, according to EN 50022
Colour housing: gray, RAL 7035; lever: gray, RAL 7000
Type Power
consumption
[W]
E 241/16 0.3
E 242/16 0.6
E 243/16 0.9
E 244/16 1.2
E 241/32 0.7
E 242/32 1.4
E 243/32 2.1
E 244/32 2.8
Type Power
consumption
[W]
E 241/45 1.92
E 242/45 3.83
E 243/45 5.76
E 244/45 7.68
E 271/63 2.5
E 272/63 5.0
E 273/63 7.5
E 274/63 10
Type Power
consumption
[W]
E 272/80 8
E 273/80 12
E 274/80 16
E 272/100 13
E 273/100 19.5
E 274/100 26
Type Power
consumption
[W]
E 272/125 16
E 273/125 24
E 274/125 32
50
250
200
100
12345671020 30 40 70 100
I (A)
DC
63
U (V)
DC
τ = 4 ms
τ = 15 ms
50
250
200
100
12345671020 30 40 70 100
80
50
250
200
100
12345671020 30 40 70 100
τ = 15 ms
τ = 4 ms
U (V)
I (A)
DC
DC
U (V)
DC
I (A)
DC
τ = 4 ms
τ = 15 ms
Direct current operation (2000 cycles)
OEPM0144
E 270 - 63A E 270 - 80A
E 270 - 100A
10/65
10
ABB SACE
Description of product and codes ................. pg. 5/4
Technical details
Command devices
RS 370 ROTARY SWITCH DISCONNECTORS
E 220 SWITCHES
More technical characteristics
Terminals 10mm2 protected
Resistance to corrosion constant atmosphere: 40/92
variable atmosphere: SFW DIN50077
Insulation voltage 3000V a.c.
Closing capacity 1.25In; 1.1Un cosϕ = 0.6
Resistance to short-circuit 3KA 400V; cosϕ = 0.8 in series with gL 35A fuse
or S2 circuit-breaker, B curve, 32A
Short-time current 960A per 1s (according to IEC 408 rating AC22)
Minimum current 4mA
Screws with slot for flat-blade and cruciform screwdriver
Depth 68mm
More technical characteristics
Disconnector 45A 63A 80A 100A
Power consumption per pole 1.4W 2.8W 3.2W 3.6W
Insulation voltage 750V 750V 750V 750V
Maximum voltage in AC20 and DC20 690V 690V 690V 690V
Short-time voltage impulse 8kV 8kV 8kV 8kV
Thermal current Ith 40°C at day 45A 63A 80A 100A
AC20 and DC20 40°C in housing 45A 63A 80A 100A
60°C in housing 45A 63A 80A 100A
Rated current
AC21A <500V 45 63 80 100
690V 45 63 80 100
AC22A <500V 45 63 80 100
690V 45 63 80 100
AC23A <415V 30 38 50 60
500V 30 32 32 50
690V 20 20 20 35
Rated output 230V 7.5kW 11kW 15kW 18.5kW
AC23A 400/415V 15kW 18.5kW 30kW 30kW
500V 15 18.5 18.5 30
690V 15 15 15 30
Short-circuit rated current 25 KA 50KA 50KA 50KA 50KA
rms with protection fuses 50A 63A 80A 100A
Electric endurance 3,000 3,000 3,000 3,000
Mechanical endurance 20,000 20,000 20,000 20,000
Weight 3P 0.27kg 0.27kg 0.31kg 0.36kg
4P 0.35kg 0.35kg 0.45kg 0.50kg
Operation strenght 1.2Nm 1.2Nm 1.2Nm 1.2Nm
Copper cable section 1.525mm21.525mm21.550mm21070mm2
10/66
10
ABB SACE
Technical details
Command devices
Description of product and codes ............... pg. 5/10
1000
500
400
300
200
100
70
60
50
40
30
20
10 12345671016 20 30
32
OPENING (NC)
CLOSING (NO)
OPENING (NC)
CLOSING (NO)
TIME COSTANT τ = 4 ms (resistive load)
UDC (V)
I
DC
(A)
TIME COSTANT
τ = 15 ms
(inductive load)
Direct current operation
OEPM0145
Type Power
consumption
[W]
E 221-10 0.48
E 221-10x 0.50
E 221-20 0.96
E 221-20x 1.00
E 221-30 1.44
E 221-40 1.92
E 221-11 0.96
E 221-22 1.92
E 221-31 1.92
E 221-30x 1.44
E 221-6 0.48
E 221-6/2 0.96
E 221-4 0.48
E 221-4/2 0.96
E 222-10x 1.15
E 222-20x 2.30
E 222-10 1.13
E 222-20 2.26
E 222-30 3.29
E 222-40 4.52
E 222-11 2.30
E 222-30x 3.45
E 222-6 1.13
E 222-4 1.13
E 223-10 1.78
E 223-20 3.56
E 223-30 5.34
ESB 20 ESB 24 ESB 40 ESB 63
Ieff insertion capability (IEC 947 -4-1)
cosϕ 0.65 at 380-400V three-phase - 85A 220A 300A
cosϕ 0.95 at 220-230V single-phase 100 - - -
Ieff disinsertion capability (IEC 947 -4-1)
cosϕ 0.65 at 380-400V three-phase - 68A 176A 240A
cosϕ 0.95 at 220-230V single-phase 80A - - -
Coordination for automatic short-circuit
(B-C) - fuse (gL) Inom 20A 35A 63A 80A
Short-time current max. 10 s at ambient temperature 40°C, in cold open air
76A 68A 176A 240A
Type Power
consumption
[W]
E 223-40 7.12
E 225-11B 0.96
E 225-11C 0.96
E 225-11D 0.96
E 225-11E 0.96
E 225-11F 0.96
E 225-11G 0.96
E 225-11Z 0.96
E 227-10B 1.50
E 227-10C 1.50
E 227-10D 1.50
E 227-10E 1.50
E 227-10G 1.50
E 227-10Z 1.50
E 229-B 1.03
E 229-C 1.03
E 229-D 1.03
E 229-E 1.03
E 229-G 1.03
E 229-Z 1.03
E 220/L/Z 1.03
E 220-B 1.03
E 220-C 1.03
E 220-D 1.03
E 220-E 1.03
ESB-EN CONTACTORS
10/67
10
ABB SACE
Description of product and codes ............... pg. 5/10
Technical details
Command devices
1 1,5 2 3 4 5 6 8 10 16 20 24 30 40 50 63 80
00,1
00,2
00,3
00,4
00,5
00,6
00,8
0,1
0,2
0,3
0,4
0,5
0,6
0,8
1
2
ESB 20
ESB 24
ESB 40
ESB 63
millions of operations
contact capacity (A)
ESB/EN 20: at 230V, AC1 single-phase
ESB/EN 24, 40, 63: at 400V, AC1 three-
phase
ESB/EN 24, 40, 63: at 400V, AC3 three-
phase
OEPM0147
OEPM0146
1 1,5 2 3 4 5 6 8 10 16 24 30 40 50 63 80
00,1
00,2
00,3
00,4
00,5
00,6
00,8
0,1
0,2
0,3
0,4
0,5
0,6
0,8
1
2
1,1 2,2 3 4 7,5 11 15
ESB 24
ESB 40
ESB 63
millions of operations
contact capacity (A)
power (kW)
More technical characteristics
ESB 20 ESB 24 ESB 40 ESB 63
EN 20 EN 24 EN 40
Rated output in AC1
230V [kW] 4 9 16 24
400V - 16 26 40
Rated output in AC3
230V [kW] 1.3 2.2 5.5 8.5
400V - 4 11 15
Capacity in direct current
Type Operating DC1 (IEC 947 - 4) DC13 (L/R 50ms) (IEC 947- 4)
voltage Rated current Current path
path
1 pole 2 poles in series 3 poles in series 1 pole 2 poles in series 3 poles
in series
ESB/EN 24 24V 15A 20A 20A 6A 10A 10A
230V 0.3A 1A 2A 0.2A 0.35A 0.5A
ESB/EN 40 24V 30A 40A 40A 6A 10A 10A
230V 0.3A 1A 2A 0.2A 0.35A 0.5A
ESB 63 24V 40A 63A 63A 6A 10A 10A
230V 0.5A 1.5A 4 0.2A 0.35A 0.5A
Characteristics of control magnetic circuit
Operating field Vc, 220V, 0.85...1.1Un AC (40...450Hz) or DC
of coil Vc, 230V, 0.8...1.06Un (except for ESB 20 / EN 20)
ESB 20 / EN 20 ESB 24 / EN 24 ESB 40 / EN 40 ESB 63
Coil consumption
at 230V- pick up 8VA 3.7VA 4.4VA 7VA
5W 3.7W 4.4W 7W
- holding 3.2VA 3.7VA 4.4VA 4.2VA
1.2W 3.7W 4.4W 4.2W
at 24V- pick up 8VA 3.7VA 4.4VA 7VA
- holding 2.95VA 3.7VA 4.4VA 4.2VA
3.7W 4.4W 4.2W
Operating time (ms)
- pick up 9...12 23...30 32...40 18...23
- drop-out 10...12 25...30 25...32 16...21
Power consumption 1W 1.2W 3W 6W
per Ith AC1 pole
Operating temperature -25...+55°C -25...+55°C -25...+55°C -25...+55°C
10/68
10
ABB SACE
Technical details
Command devices
Description of product and codes ............... pg. 5/10
Information about lamp insertion between phase and neutral
Power Cond. cap.
[W] Number of lamps allowed at 220V/50Hz [µF]
ESB/EN 20 ESB/EN 24 ESB/EN 40 ESB 63
Incandescent lamps
60 21 25 54 83
100 13 15 32 50
200 7 7 16 25
300 4 5 11 16
500 3 3 6 10
1000 1 1 3 5
POWER FACTOR UNCORRECTED/CORRECTED IN SERIES
fluorescent lamps
15 25 30 100 155
20 22 26 85 140
40 17 20 65 105
42 13 16 52 85
65 10 12 40 60
115 4 5 18 28
140 4 5 18 28
POWER FACTOR CORRECTED IN PARALLEL
fluorescent lamps
156815674.5
205714605
406815674.5
424612506
654510437
115 1 2 4 17 18
140 1 2 4 17 18
POWER FACTOR UNCORRECTED
twin-lamps
2x20 22 26 85 140
2x40 17 20 65 105
2x42 13 16 52 85
2x65 10 12 40 60
2x115 4 5 18 28
2x140 4 5 18 28
POWER FACTOR UNCORRECTED
Metal iodide lamps (HQI type)
35 - 10 28 38
70 - 5 14 20
150 - 3 8 11
250 - 2 5 7
400 - 1 4 6
1000 - - 1 2
2000 - - 1 1
2000 at 380V - - 2 2
3500 at 380V - - 1 1
POWER FACTOR CORRECTED IN PARALLEL
metal iodide lamps (HQI type)
35 - 5 11 30 6
70 - 3 5 18 12
150 - 1 3 9 20
250 - 1 2 7 33
400 - 1 2 6 35
1000 - - - 2 95
2000 - - - 1 148
2000 at 380V - - 1 2 58
3500 at 380V - - - 1 100
POWER FACTOR UNCORRECTED
low pressure sodium
vapour lamps (Sox type)
35582230
55582230
90351319
135 2 3 10 13
150 2 3 10 14
180 2 3 10 14
200 3 5 14 20
10/69
10
ABB SACE
Description of product and codes ............... pg. 5/10
Technical details
Command devices
Power Cond. cap.
[W] Number of lamps allowed at 220V/50Hz [µF]
ESB/EN 20 ESB/EN 24 ESB/EN 40 ESB 63
POWER FACTOR CORRECTED IN PARALLEL
low pressure sodium
vapour lamps (Sox type)
35 - 1 4 15 20
55 - 1 4 15 20
90 - 1 3 10 30
135 - - 2 7 45
150 - - 2 8 40
180 - - 2 8 40
200 - 1 3 12 25
POWER FACTOR UNCORRECTED
High pressure sodium
vapour lamps (NAV type)
150 - 4 15 20
250 - 3 9 15
330 - 2 8 10
400 - 1 6 8
1000 - - 3 4
POWER FACTOR CORRECTED IN PARALLEL
high pressure sodium
vapour lamps (NAV type)
150 - 1 3 15 20
250 - 1 2 9 33
330 - - 2 7 40
400 - - 1 6 48
1000 - - - 2 106
POWER FACTOR UNCORRECTED
high pressure mercury
vapour lamps (HQL type)
50 12 14 36 50
80 7 10 27 38
125 5 7 19 26
250 3 4 10 14
40012710
700 - 1 4 6
1000 - 1 3 4
2000 at 380V - 1 3 4
POWER FACTOR CORRECTED IN PARALLEL
high pressure mercury
vapour lamps (HQL type)
50 4 5 10 43 7
80348378
1252362610
2501231518
4001131025
700 - - 1 5 45
1000 - - 1 4 60
2000 at 380V - 1 2 3 35
Lamps with electronic reactor
1x1815245576
2x18 8 18 34 48
1x3612163447
2x36 7 11 20 29
1x5811143246
2x58 6 8 17 24
Very low voltage
halogen lamps - 12V
20 40 52 110 174
50 20 24 50 80
75 13 16 35 54
100 10 12 27 43
150 7 9 19 29
200 5 6 14 23
30034914
10/70
10
ABB SACE
Technical details
Command devices
Description product and codes ................... pg. 5/14
LATCHING RELAYS
E 250 electro-mechanical
More technical characteristics
Power consumption 1P = 7W
with continuous pick up 2P = 10W
at rated voltage 4P = 20W
Minimum impulse endurance 50ms
Service factor 100% * (command indication can be kept)
Contact material sintered silver + cadmium oxide
Distance between contacts < 3 mm
Movement endurance 3ms
Dielectric strenght < 2000V between contacts
< 4000V between contacts and coils
Operation frequency 103/h
Switching reliability 99%
Protection against short-circuit by S2 series circuit-breaker, characteristic B, 16A
Operating temperature -5...+50°C
Terminal section coil power supply: 6mm2, command: 4mm2
* if the coil is picked up for long periods, it is recommended to use heatsinks. In case of the command
signal is not impulsive, use E 259 series installation relay, where applicable.
Information about lamp insertion between phase and neutral
Power Number of
lamps
allowed
[W] at 220V/50Hz
INCANDESCENT
lamps
15 150
25 90
40 57
60 38
75 30
100 22
150 15
200 11
300 7
500 4
1000 2
Power Number of
lamps
allowed
[W] at 220V/50Hz
POWER FACTOR UNCORRECTED
fluorescent lamps
15 16
18 14
20 14
36 12
40 12
58 8
65 8
115 4
140 3
10/71
10
ABB SACE
Description of product and codes ............... pg. 5/14
Technical details
Command devices
Power Number of
lamps
allowed
[W] at 220V/50Hz
POWER FACTOR CORRECTED IN PARALLEL
fluorescent lamps
15 12
18 10
20 10
36 9
40 9
58 6
65 6
115 3
140 2
POWER FACTOR UNCORRECTED
twin-lamps
2x18 33
2x20 33
2x36 16
2x40 16
2x58 10
2x65 10
2x115 5
2x140 4
POWER FACTOR UNCORRECTED
metal vapour halogen
lamps (HQI type)
35 10
70 5
150 2
250 1
400 1
POWER FACTOR UNCORRECTED
low pressure sodium
vapour lamps (Sox type)
18 15
37 9
56 8
91 5
135 5
185 5
Power Number of
lamps
allowed
[W] at 220V/50Hz
POWER FACTOR UNCORRECTED
high pressure
sodium vapour lamps
(NAV type)
50 6
70 5
150 2
250 1
POWER FACTOR UNCORRECTED
high pressure mercury
vapour lamps
(HQL type)
50 8
80 6
125 4
250 2
400 1
Lamps with
electronic reactor
1x18 150
2x18 70
1x36 70
2x36 35
1x58 45
2x58 20
Very low voltage
halogen lamps
- 12V
20 32
50 16
75 10
100 8
150 5
200 4
300 2
Information about lamp insertion between phase and neutral
10/72
10
ABB SACE
Technical details
Command devices
Description product and codes ................... pg. 5/16
E 260 electronic
More technical characteristics
Power consumption with continuous
pick up at rated voltage 1P = 2W; 2P = 3W
Service factor 100% *
Contact material silver Ag Cd O 10
Distance between contacts 0.5mm
Movement endurance 3ms
Minimum contact capacity 4V a.c. /10mA
Operation frequency 103/h
Max. capacity in parallel > 2mF (about 6000m)
Max. current on the lighted pushbutton
(for incandescent lamps) 30mA
Switching reliability 99.9%
Operating temperature -20...+50°C
Terminal section switching circuit: 6mm2; control circuit: 4mm2
Protection against short-circuit with S2 series circuit-breaker, characteristic B, 16A
* if the coil is picked for long periods, it is recommended to use heatsinks.
10/73
10
ABB SACE
Technical details
Load management devices
Contents
Time delay relays ..............................................................................................................10/74
LSS1/2 load shedding switches ......................................................................................10/76
CRT programmable thermostats .....................................................................................10/77
Max./min. current/voltage ammetric and voltmetric relays ..........................................10/77
STD universal dimmers ....................................................................................................10/79
10/74
10
ABB SACE
Technical details
Load management devices
Description of product and codes ................. pg. 6/2
TIME DELAY RELAYS
More technical characteristics
Min. contact capacity 4V a.c. /10mA
Service factor 100%
Operation frequency 103/h
Repetition accuracy at 25°C ± 0.1%
OFF time in case of network
power failure 0.2s
Control current
(for all control voltages) 6-25mA ± 20%
t
1815
ARV
RV
AV
OFF
ON
IA
EW
AW
TI
TP
F
2s
0,5s
0.1s
4h
2h
5s
1m
2m
5m
1h
T
3
2
1
10
8
5
6
7
xT
*
*only for MFR multifunction version
4
9
Time base Set through T switch.
Adjustment range:
0.1-0.5-2-5 seconds
1-2-5 minutes
1-2-4 hours
Multiplier Set between 1 and 10 through XT switch.
The time base x the multiplier determines the adjustment range(t).
OEPM0148
10/75
10
ABB SACE
Technical details
Load management devices
AV
Delayed
at pick up
Supply voltage
When the control voltage is applied
the process through which the contact 15-16
becomes the contact 15-18 starts.
RVDelayed
at drop-out
Supply voltage
When the control voltage is applied
the contact 15-16 becomes 15-18.
When the control voltage is broken the process starts.
Once the process is finished, the contact returns to the initizal
position 15-16.
TI
Generating
impulse
timer
Supply voltage
Until the control voltage is applied
the contacts change from 15-16 to 15-18 according to the set time.
AW
On
energization
timer
Supply voltage
Breaking the control voltage
the contact passes from 15-16 to 15-18 and returns to 15-16 when
the energization time expires.
EW
On
de-energization
timer
Supply voltage
When applying the control voltage
the contact passes from 15-16 to 15-18 and returns to 15-16 when
the de-energization time expires.
TPGenerating
impulse
timer with starting
delay
Supply voltage
When applying the control voltage
during the set time, the contact stays in the position
15-16. Then it passes from 15-16 to 15-18 according to the set
time.
ARV
Delay at
pick up
and dropout
Supply voltage
When applying the control voltage the process through which the
contact passes from 15-16 to 15-18 starts. At the end of the
process, after the control voltage breaking, the contact passes
from 15-18 to 15-16.
AV Delay at pick up
RV Delay at drop-out
TI Impulse generating timer
Description of functions
OEPM0149
t
B
1
A
2
A
1
A
2
15/18
15/16
t
B
1
A
2
A
1
A
2
15/18
15/16
t t t t t
B
1
A
2
A
1
A
2
15/18
15/16
t
B
1
A
2
A
1
A
2
15/18
15/16
t
B
1
A
2
A
1
A
2
15/18
15/16
t tt t tt
B
1
A
2
A
1
A
2
15/18
15/16
t t
B
1
A
2
A
1
A
2
15/18
15/16
1 sec
A
1
B
2
A
1
A
2
15/18
15/16 t
20ms
t t1 t t1 t
B
1
A
2
A
1
A
2
15/18
15/16
TI2
Generating
impulse
timer
Supply voltage
When the command voltage is applied the contact 15-16 passes
alternately to 15-18 and t and t1 times can be set to different values.
IA
Delayed at
drop-out and
controlled by impulse
timer
Supply voltage
Controlled by 20ms impulse, the contact 15-16 passes to 15-18
(for one second) after the set time.
TP Impulse generating timer
with delayed starting
AW On energization timer
10/76
10
ABB SACE
Technical details
Load management devices
Description of product and codes ................. pg. 6/9
LSS1/2 LOAD SHEDDING SWITCHES
The LSS1/2 switch intervenes when the total power consumption exceeds the threshold set through
the switch placed on the front of the device. After a preset time the switch verifies the possibility to
reset disabled not primary loads; the attempt is repeated until a standard situation is established
again.
Particularly suitable in applications where load total power is higher than the one indicated in the
contract and the average power consumption in a long time interval (dozen minutes) is lower, the
LSS1/2 switch can be used in public and industrial single-phase networks and for three-phase
networks if they are symmetrical and balanced.
LOAD
1 3 5 7 9 11 13 15
2 4 6 8 10 12 14 16
NL
230V~
PL
NPL1
NPL2
Possible
remote
signalling
Possible
forced NPL 1
and NPL 2
switch-off
Single-phase electric
diagram
The device must be
inserted into the network
downstream of main
circuit-breaker. The E not
primary load OFF contact
must be without voltage.
PL = Primary load
NPL= Not primary load
1 3 5 7 9 11 13 15
2 4 6 8 10 12 14 16
L1
PL
L2
L3 TA/5A
380V
NPL1 NPL2
Le2Le1
E
220V
Three-phase electric diagram
OEPM0151 OEPM0150
10/77
10
ABB SACE
Description of product and codes ............... pg. 6/13
Technical details
Load management devices
MIN./MAX. CURRENT/VOLTAGE AMMETRIC AND VOLTMETRIC RELAYS
Testing a load with the following marking:
In= 7A (standard operation rated current)
Vn= 230V a.c. (standard operation rated voltage)
Imin = 6A (RLI relay intervention)
1. Connect according to the diagram (as Imin = 6A).
2. Set the “Current %” trimmer to 60%, as:
l% = x 100 = 60%
being the terminals 7-12 wired.
3. Set the “Hysteresis %” trimmer; choosing 10% you get an intervention
range from 6 to 6.6A (6A + 10% = 6.6A).
The relay intervention will be 6A and the return to the standard
operation 6.6A.
4. Set the “Delay” trimmer. This allows to delay the relay intervention
time (1…30 sec).
During the delay the “Power ON” LED blinks; at the end of the delay
the “Alarm” LED is permanently lighted and the relay intervenes.
A
12 5643
78 1112109
Alarm
Supply voltage
230Vc.a.
F
N
LOAD
RLI
Network to be measured I
min
6A
C
I
n
=7A
6.6A
I
min
=6A
Alarm on
Alarm on as within of the
hysteresis window
Alarm off as out of the
hysteresis window
Selected
hysteresis
window
= 10%
Regular
operation
6 (lmin.)
10 (lset)
N.B. Generally connect terminals:
7-10 if lmin is 2A
7-11 if lmin is > 2A and 5A
7-12 if lmin is > 5A and 10A
Example of MINIMUM CURRENT relay (RLI) operating principle
Testing a load with the following marking:
In= 5A (standard operation rated current)
Vn= 230V a.c. (standard operation rated voltage)
Imax = 6A (RHI relay intervention)
1. Connect according to the diagram (as Imax = 6A).
2. Set the “Current %” trimmer to 60% as:
l% = x 100 = 60%
being the terminal 7-12 wired.
3. Set the “Hysteresis %” trimmer; choosing 10% you get an intervention
range from 5.4 to 6A (6A - 10% = 5.4A).
The relay intervention will be 6A and the return to the standard
operation 5.4A.
4. Set the “Delay” trimmer. This allows to delay the relay intervention
time (1…30 sec).
During the delay the “Power ON” LED blinks; at the end of the delay
the “Alarm” LED is permanently lighted and the relay intervenes.
N.B. Generally connect terminals:
7-10 if lmax is 2A
7-11 if lmax is > 2A and 5A
7-12 if lmax is > 5A and 10A
Example of MAXIMUM CURRENT relay (RHI) operating principle
A
12 5643
78 1112109
Alarm
Supply voltage
230Vc.a.
F
N
LOAD
RHI
Network to be measured Imax 6A
C
I
max
=6A
5.4A
I
n
=5A
Regular
operation
Alarm on
Alarm on as within of the
hysteresis window
Alarm off as out of the
hysteresis window
Selected
hysteresis
window
= 10%
6 (lmax)
10 (lset)
10/78
10
ABB SACE
Technical details
Load management devices
Description of product and codes ............... pg. 6/13
Managing a load with the following marking:
In= 5A (standard operation rated current)
Vn= 230V a.c. (standard operation rated voltage)
Vmin = 200V a.c. (RLV relay intervention)
1. Connect according to the diagram (as Vmin = 200V).
2. Set the “Voltage %” trimmer to 66.7%, as:
V% = x 100 = 66,7%
being the terminal 7-11 wired.
3. Set the “Hysteresis %” trimmer; choosing 10% you get an intervention
range from 200 to 220V (200 + 10% = 220V).
The relay intervention will be 200V and the return to the standard
operation 220V.
4. Set the “Delay” trimmer. This allows to delay the relay intervention
time (1…30 sec).
During the delay the “Power ON” LED blinks. At the end of the delay
the “Alarm” LED is permanently lighted and the relay intervenes.
200 (Vmin.)
300 (Vset)
N.B. Generally connect terminals:
7-10 if Vmin is 100V
7-11 if Vmin is > 100V and 300V
7-12 if Vmin is > 300V and 500V
Example of MINIMUM VOLTAGE relay (RLV) operating principle
A
12 5643
78 1112109
Alarm
Supply voltage
230Vc.a.
F
N
LOAD
RLV
Network to be measured V
min
200V c.a.
C
V
n
=230V
220V
V
min
=200V
Normale
funzionamento
Alarm on
Alarm on as within of the
hysteresis window
Alarm off as out of the
hysteresis window
Selected
hysteresis
window
= 10%
Managing a load with the following marking:
In= 5A (standard operation rated current)
Vn= 230V a.c. (standard operation rated voltage)
Vmax = 250V a.c. (RHV relay intervention)
1. Connect according to the diagram (as Vmax = 250V).
2. Set the “Voltage%” trimmer to 83.33%, as:
V% = x 100 = 83.33%
being terminal 7-11 wired.
3. Set the “Hysteresis %” trimmer; choosing 5% you get an intervention
range from 237.5 to 250V (250 -5% = 237.5V).
The relay intervention will be 250V and the return to the standard
operation 237.5V.
4. Set the “Delay” trimmer. This allows to delay the relay intervention
time (1…30 sec).
During the delay the “Power ON” LED blinks; at the end of the delay
the “Alarm” LED is permanently lighted and the relay intervenes.
250 (Vmax)
300 (Vset)
N.B. Generally connect terminals:
7-10 if Vmax is 100V
7-11 if Vmax is > 100V and 300V
7-12 if Vmax is > 300V and 500V
Example of MAXIMUM VOLTAGE relay (RHV) operating principle
A
12 5643
78 1112109
Alarm
Supply voltage
230Vc.a.
F
N
LOAD
RHV
Network to be measured V
max
250V c.a.
C
V
max
=250V
237.5V
V
n
=230V
Regular
operation
Alarm on
Alarm on as within of the
hysteresis window
Alarm off as out of the
hysteresis window
Selected
hysteresis
window
= 5%
10/79
10
ABB SACE
Description of product and codes ............... pg. 6/14
Technical details
Load management devices
STD UNIVERSAL DIMMERS
The models available are appropriate for residential, but also for tertiary installation (conference
rooms, restaurants, churches, schools, hotels, etc).
The STD-500MA model in particular can be connected in parallel to a maximum of 5 STD-420LS
modules, reaching a 3000W/VA power on existing load lines, without contrasting with CE regulations
that define a 1000W/VA power limit for each device.
With STD-1000U dimmers it is possible to manage even 18000W/VA by simply connecting in parallel
up to 18 devices, that separately guarantee a maximum adjustment of 1000W/VA.
D2 D1 2 1 N L
L
N
PSB/S 1.1
or
SB/S 1.1 (i-bus EIB)
SG1DNL
STD-500MA
SG1DNL
STD-500MA
D2 D1 2 1 N L
L1
L2
L3
N
PSB/S 1.1
or
SB/S 1.1 (i-bus EIB)
SG1DNL
STD-500MA
SG1DNL
STD-500MA
SG1DNL
STD-500MA
SGL
STD-420SL
SGL
STD-420SL
SGL
STD-420SL
Connection examples
A) Connection of 2 STD-500MA
dimmers and one SB/S 1.1
(ABB i-bus EIB system)
Note: this connection enables
using a maximum of 8 STD-
500MA dimmers.
B) Connection of 3 STD-
500MA dimmers, 3 STD-
420SL power modules and a
SB/S 1.1 (ABB i-bus EIB
system).
Note: this connection enables
using a maximum of 6 STD-
500MA dimmers and 5 STD-
420SL power modules.
A
B
10/80
10
ABB SACE
Technical details
Load management devices
Description of product and codes ............... pg. 6/14
Operating principle
STD dimmers operate based on the delay of phase principle, a solution of the switching tecnique
with semiconductor components where the triac is controlled by the release diode, working as an
electric fuse. The phase voltage cut off is performed according to a delay of phase angle both in the
positive and negative sinusoidal voltage half waves at 50 Hz which decreases or increases voltage.
Each dimmer control cycles of about a hundred switch on and switch off operations based on
interval depending on the lighting parameters set for each controlled lamp (incandescent, halogen
incandescent at 230V, low voltage halogen with common wound transformers).
LGNDN1
L1
L2
L3
N
STD-1000U
5G–+
LGNDN1
STD-1000U
5G–+
LGNDN1
STD-1000U
5G–+
LGNDN1
L1
L2
L3
N
STD-1000U
5G
–+
LGNDN1
STD-1000U
5G
–+
LGNDN1
STD-1000U
5G
–+
K1 K1 K1 K1
STD
MTS
NG1–+
L
N
N
+
-
LEVG
STD
MTS
NG1–+ N
+
-
LEVG
Connection of 3 STD-1000U
dimmers in parallel.
Note: this connection enables
using a maximum of 18 STD-
1000U dimmers.
Connection of 3 STD-1000U
dimmers in parallel controlled
by a remote control switch (K1).
Note: this connection enables
using a maximum of 18 STD-
1000U dimmers.
Connection of 2 STD-MTS
dimmers in series to control
fluorescent lamps.
10/81
10
ABB SACE
Technical details
Measurement devices
Contents
MTM multimeters ..............................................................................................................10/82
Accessories for analogue and digital instruments ........................................................10/83
DELTA METER series electronic single-phase and three-phase energy meters ........10/84
EE MINI METER single-phase energy meters ................................................................10/86
EMT 3 single-phase energy meters ................................................................................10/86
Insulation monitors ...........................................................................................................10/88
10/82
10
ABB SACE
Technical details
Measurement devices
Description of product and codes ................. pg. 7/5
MTM MULTIMETERS
APushbutton for three-phase system (L) quantities and peak
values (PEAK) displaying:
• pressing A pushbutton for less than 3 seconds you access to
three-phase values (L) displaying of the measurement selected
by B pushbutton;
• pressing A pushbutton for more than 3 seconds you access
to peak values displaying on the F display, while viewing “PEAK”
on the G display.
BPushbutton for selecting the measure to view on the F display.
CPushbutton for selecting the measure to view on the G display.
DLED bar to indicate the measure viewed on F displays.
ELED bar to indicate the measure viewed on the G display.
F3 displays for viewing measurements divided by phases.
GDisplay for viewing the measurement indicated by the LED E bar. The voltage value refers to
three-phase system.
The selection of elements to be measured and the transformation ratio setting are performed through
the 3 keys A, B and C. The measurements are shown on F and G 3-digit and 8-segment red LED
displays.
To set the transformation ratio (A.T.):
press A and C pushbutton simultaneously until viewing “SET” on the G display and “CT 001” on
the F display;
replace the “001” value by setting the appropriate A.T. transformation ratio (i.e.: A.T. 800/5A =
160);
press B or C pushbutton to increase or decrease respectively the transformation ratio values to
be set;
press A pushbutton to confirm the datum.
Measurable quantities
Quantity View
Voltages between lines [V, kV] VL1-VL2, VL2-VL3, VL3-VL1
Phase voltage [V, kV] VL1-N, VL2-N, VL3-N
Phase currents [A, kA] I1, I2, I3
Active phase
power [W, kW] P1, P2, P3
Reactive phase
power [VAr, kVAr] QL1, QL2, QL3
Apparent phase
power [VA, kVA] S1, S2, S3
Phase power
factors [ψ] PF1, PF2, PF3
Temperature [°C] from 0 to 60
Average value
summation [] VL-L, VL-N, I, P, Q
Peak value
summation [] I, P
D
F
G E C AB
L1 L2 L3
V
L-N
A
cosϕ
W VAr VA V
L-L
V
L-N
V
L-L
Hz °C
ΣL
OEPM0264
10/83
10
ABB SACE
Technical details
Measurement devices
ACCESSORIES FOR ANALOGUE AND DIGITAL INSTRUMENTS
Current transformers
The following terms refer to transformers construction and operating characteristics.
In particular:
- the thermal current is the maximum primary current (effective value) that C.T. can withstand for 1s
with short-circuited secondary without generating damages due to excessive overloads;
- the dynamic current is the maximum primary current (crest value) that C.T. can withstand for 1s
with short-circuited secondary without generating damages due to electromagnetic stress;
- the maximum operating voltage is the maximum voltage (effective value) that C.T. can withstand;
- the test voltage is, for insulation purposes, the industrial frequency voltage the C.T. withstands for
1min with the primary and the secondary;
- the safety factor (m) or saturation factor (Fs) is the ratio between primary current value (causing
the core saturation) and rated primary current value ( 10%). The lower is the value, the higher the
instrument protection.
More technical characteristics
Mounting CTR 0, 1, 3, 4: panel, wall or DIN rail mounting
CTR 6, 8: panel, bar or cable mounting
Housing self-extinguishing thermoplastic material (V0 rating according to UL94)
Maximum operating voltage 0.72kV
Test voltage 3kV for 1’ at 50Hz
Permanent overcurrent 1.2In
Short-circuit with wound primary: 60 In
thermal current (Ith) with through primary: limited to the bar section
Short-circuit dynamic current (Idin) 2.5 times Ith
Utilization temperature -25°C...+50°C
Storage temperature -40°C…+80°C
Safety factor 5
Electronic transducers
TCS1 TRANSDUCER FOR ONE-PHASE POWER FACTOR METER
Direct insertion (5A) Insertion through A.T. (.../5A)
* Rated voltages (100 V, 220 V, 380 V) and rated current (5A) already preset
* Standard scale 0,5 - 1 - 0,5
- With 100V power supply, connect terminal 3 ( )
- With 230V power supply, connect terminal 4 ( )
- With 400V power supply, connect terminal 5 ( )
INSTRUMENT
910111213141516
13
K L1 l
A
!
OUT
–+
No.12,5
!
TCS 1
100V 5A
230V 5A
400V 5A
50 Hz
UI
0,5 Lead....I....0,5 Lag
1234 5678
+
11 2
100V 220V 380V
NL1
V
0 ... 1mA R < = 1k
!
In case of different voltages, use voltage transformer (…100V) and connect the secondaries to terminals 3 and 1
INSTRUMENT
910111213141516
13
K L1 l
A
!
OUT
–+
No.12,5
!
TCS 1
100V 5A
230V 5A
400V 5A
50 Hz
UI
0,5 Lead....I....0,5 Lag
1234 5678
+
11 2
100V 220V 380V
NL1
V
0 ... 1mA R < = 1k
!
kl
KL
L1
N
L1
N
Direct insertion (5A) Insertion through A.T. (.../5A)
In case of different voltages, use voltage transformer (
.../ 100V)
and connect the secondaries to terminals 3 and 6
TCS2 TRANSDUCER FOR BALANCED THREE-PHASE POWER FACTOR METER WITHOUT NEUTRAL
* Rated voltages (100 V, 220 V, 380 V) and rated current (5A) already preset
* Standard scale 0,5 - 1 - 0,5
- With 100V power supply, connect terminal 3 and 6 ( )
- With 230V power supply, connect terminal 4 and 7 ( )
- With 400V power supply, connect terminal 5 and 8 ( )
910111213141516
13
K L1 l
A
!
OUT
–+
No.12,5
!
TCS 2
100V 5A
230V 5A
400V 5A
50 Hz
UI
0,5 Lead....I....0,5 Lag
1234 5678
+
11 2
100V 220V 380V
L2
V
0 ... 1mA R < = 1k
!
100V 220V 380V
L3
8
3~ 1E
910111213141516
13
K L1 l
A
!
OUT
–+
No.12,5
!
TCS 2
100V 5A
230V 5A
400V 5A
50 Hz
UI
0,5 Lead....I....0,5 Lag
1234 5678
+
11 2
100V 220V 380V
L2
V
0 ... 1mA R < = 1k
!
100V 220V 380V
L3
8
3~ 1E
kl
KL
L1
L2
L3
L1
L2
L3
INSTRUMENT INSTRUMENT
10/84
10
ABB SACE
Technical details
Measurement devices
Description of product and codes ............... pg. 7/15
Microprocessor
It is the device main element. It
manages the counting functions and
is programmed for four different
operating modes that allow to view
parameters, counting and tests, to
define settings etc. The operating
modes can be set through SET and
SCROLL pushbuttons or by the
optical interface. The devices are
equipped with the “installation test”
function, which enables performing
the connection test and signalling
any failure or the correct installation
(“OK“) by a code. An EEPROM
memory allows to access storaged
data indipendentely from the power
supply.
Measurement system
It allows the direct measurement for currents up to 65A or the
secondary measurement from A.T. current transformers (5A
secondary) for higher currents, with on choice transformation
ratio. In special versions, DELTA METERs can also be connected
to voltage transformers.
SET and SCROLL pushbuttons
Placed on the upper front of DELTA METERs
(under the protection), they enable setting
changing and selecting the desired menus
and controls, to view all the available infor-
mation on the display.
Optical interface
It is made up by a phototransistor and is started by pointing a torch to
the meter allowing to select the parameters to be viewed on the
display. This function is useful if the meter is installed inside
switchboards protected by a glass door.
PC output
It makes available a frequency impulse signal propor-
tional to the detected consumption, which can be sent
to a PC for subsequent processing. The impulse speed
is of 100 imp./kWh in direct connection versions and
of 1000 imp./kWh in versions with connection by cur-
rent transformers. In special versions the impulse speed
can be adjusted.
Liquid crystal display
With its very large dimensions and legibility
degree it is an information source for the
functions performed by meters. Pressing
SET and SCROLL pushbuttons it is possible
to view easily the consumption and every
other information.
OEPM0171
DELTA METER SERIES ELECTRONIC SINGLE-PHASE AND
THREE-PHASE ENERGY METERS
The figure shows the main components making up DELTA METER meters.
10/85
10
ABB SACE
Technical details
Measurement devices
Description of product and codes ............... pg. 7/15
Standard mode
The Standard mode views the following information:
-active energy
-reactive energy
-connected phases
-load indications
-LCD impulse optical blinking
-“OK” symbol
-symbol for main registration (on meters connected to A.T. transformers)
Alternate mode
It can be accessed directly from the Standard mode or from the Menu mode and allows performing
the following functions:
-viewing one extra decimal for all values
-transformation ratio reading (on meters connected to A.T. transformers)
-viewing failure status
-testing display lighting segments
-viewing impulse frequency (option)
Menu mode
It contains the submenus allowing to:
-enter the meter Set mode;
-return to the Alternate mode
-enter the Error submenu to view any failure detected by the installation test or other failures
-choose the End control to return to the Standard mode
Set mode
It enable the following controls:
-Test, to start the installation test
-LCD, to start LCD display test
-Trafo, to set transformation ratios on external A.T. current transformers
-Pulse, to set the impulse speed (only in special versions)
-Reset, to reset energy registers (only in versions with reset)
-OpenC, to open IR communication (infrared rays) in order to perform meter calibration
-End, to return to the Menu mode
Operating modes
DELTA METER meters are programmed to work in the four following modes: Standard, Alternate,
Menu and Set (settings). SET and SCROLL pushbuttons allow selecting the desired operating mode.
Within Menu and Set you can choose submenus and controls.
10/86
10
ABB SACE
Technical details
Measurement devices
Description of product and codes ............... pg. 7/17
EE MINI METER SINGLE-PHASE ENERGY METERS
More electric characteristics
Starting current 0.1A
Protection from short-circuit
for direct connection MCB or fuse up to 32A
Protection from short-circuit
for connection to A.T. MCB or 10A fuse
Pulse output 10 imp/kWh
Impulse lenght 100ms
More functional characteristics
Local reset feature
Press SW1 pushbutton for more than 5s.
To recall the power consumption storaged in EEPROM, press the SW1 pushbutton for a time
ranging from 50ms to 5s, viewing the two decimals of the actual consumption and then the
consumption preceding the reset.
Remote reset feature
Apply to the device a voltage impulse of 10...40V d.c. with a minimum time of 5s.
Pulse output
The pulse output ratio is indicated on the meter. The time of the impulse is 100ms.
For counters measured through A.T. and with a set ratio, the impulse frequency is 10 imp/kWh.
10-40Vd.c.
26 25
10-40Vd.c./a.c.
21 20
Remote reset
Pulse output
OEPM0164
OEPM0164
10/87
10
ABB SACE
Technical details
Measurement devices
Description of product and codes ............... pg. 7/17
EMT 3 SINGLE-PHASE ENERGY METERS
With particularly reduced dimensions (3 modules) they are equipped with an internal microprocessor
with a 5 channels analogue/digital converter which allows to measure current and voltage.
Direct reading is possible up to 25A. For higher values it is necessary to use current transformers
with 5A secondary.
The energy value is storaged in 8 decimal digits, where the less important digit indicates volt-ampere/
hour; on the meter display only 4 digits are viewed. They refer to units, tens, hundreds and thousand.
In case of network voltage failure, saving values and other reference parameters into EEPROM memory
makes it possible to restart counting from the last value, whatever the time of power supply breaking.
Selecting one of 5 measurements (60/5; 100/5; 250/5; 400/5; 1000/5) through the appropriate
minidips, the meter reads the actual consumption without multiplying the consumption value by the
A.T. ratio.
A reset pushbutton enables resetting counting.
Minidip programming:
1* 2 3 4 TA.../5 Wh/kWh
OFF OFF OFF OFF Wh
ON/OFF OFF OFF ON kWh
ON/OFF OFF ON OFF 60/5 kWh
ON/OFF OFF ON ON 100/5 kWh
ON/OFF ON OFF OFF 250/5 kWh
ON/OFF ON OFF ON 600/5 kWh
ON/OFF ON ON OFF 800/5 kWh
ON/OFF ON ON ON 1000/5 kWh
*ON = 999.9
OFF = 9999
OFF
ON
1234
OEPM0165
10/88
10
ABB SACE
Technical details
Measurement devices
Description of product and codes ............... pg. 7/18
INSULATION MONITORS
The insulation transformers provide protection from indirect contacts without breaking the circuit at
the first indirect contact. They are used mostly in systems where miniature circuit-breaking is not
allowed because a sudden service breaking could cause serious inconveniences.
The Standards define strict safety rules; in particular, the active parts of the separate circuit must not
have shared parts, nor connections to earth. In addition, an appropriate device for the permanent
testing of the insulation status must be provided in order to detect, signal and remove the circuit first
fault.
Isoltester-C
This device operates generating a test voltage which is applied between the circuit leading to the
insulation transformer secondary and earth system. The current that is generated is made up by an
Ir (ohmic earth leakage) and an Ic (capacitive earth leakage) component. It closes between the
insulated system and the earth allowing to detect the leakage.
If passing through the sensing electronic device the ohmic/capacitive global leakage exceeds the
one preset, the alarm is activated and the device yellow lighted indicator switches on.
The alarm status is then reported on the appropriate QSD acoustic/lighted signalling panel, that can
be placed remotely from the switchboard.
Selvtester-C
Designed according to an operating principle similar to Isolterster-C with which can be coupled, this
device signals the first indirect contact in SELV circuits shunted from insulated network with transformer
(i.e. in systems for operating theatres where scialytic lamps are connected).
In addition to this insulatin control basic function, Selvtester-C enables to view through green and
yellow led respectively the operating status and any indirect contact.
A specific pushbutton enables to perform periodic self-test operations.
QSD 230/24 C panels for remote segnalling
Each panel is equipped with a green indicator to signal the standard operation and with a yellow
indicator reporting the alarms triggered by devices.
In case of alarm an appropriate acoustic signalling buzzer is also provided which can be switched off
by switching the silencing relay (green pushbutton). The lighted signal is active until the cause of the
alarm stops.
In order to perform periodic alarm test with simulation of indirect contact, press the red pushbutton.
The panels are provided along with the relative support, plate and flush-mounting box already
assembled.
10/89
10
ABB SACE
Technical details
Other modular functions
Contents
Bell transformers ..............................................................................................................10/89
10/90
10
ABB SACE
Technical details
Other modular functions
Description of product and codes ................. pg. 8/2
BELL TRANSFORMERS
The strict project criteria and the quality of materials used guarantee the high reliability of these
devices. In fact, the windings are completely separated and insulated in order to avoid dangerous
voltage tranfer on the secondary even if malfunctioning.
Furthermore, the variations from no-load to rated load are reduced to minimum levels allowing to use
these transformers also with low-consumption devices (electronic devices) which have particular
sensitivity to high voltage variations.
In particular, 4 series of safety transformers are available.
- TM failure-proof series:
in case of uncorrected use, they cannot work but they are not dangerous for users and for next
electric parts. The series includes 8 models with 10, 15, 30 and 40VA power and 4, 8, 12 and 24V
output voltages.
- TS8 short-circuit proof not by construction series:
also after short-circuit, they keep temperature below indicated limits and so they can work. TS 8
series includes 3 models with 8VA power and 8, 12, 24V output voltages;
- TS8/SW short-circuit proof not by construction series:
it is different from previous series because of a 0-1 switch on the front which enables transformer
insertion/disinsertion from line. The TS 8/SW series includes 5 models with 8VA power and 4, 6, 8,
12 and 24V output voltages;
- TS16/TS 24 short-circuit proof not by construction series:
also after short-circuit, they keep temperature below indicated limits. They are also equipped with
thermal breaking auto-closing device which automatically resets current when relative part of
transformer is cold enough or when the load has been removed. TS 16/TS 24 series includes 7
models with 16 and 24 VA power and 4, 6, 8, 12 and 24V output voltages.
11/1
11
ABB SACE
Overall dimensions
Contents
MCBs, RCDs, auxiliary elements and accessories ........................................................ 11/3
Other protection devices ................................................................................................ 11/13
Command devices .......................................................................................................... 11/17
Load management devices ............................................................................................ 11/21
Measurement devices .................................................................................................... 11/29
Other modular functions ................................................................................................ 11/37
11/2 ABB SACE
11/3
11
ABB SACE
Overall dimensions
MCBs, RCDs,
auxiliary elements and accessories
Contents
MCBs .................................................................................................................................. 11/4
RCDs .................................................................................................................................. 11/6
Auxiliary elements and accessories .............................................................................. 11/10
11/4
11
ABB SACE
90
45
70122,5122,5122,5122,526.25 52.5 78.75 105
1P 2P 3P 4P
1.5 module 3 modules 4.5 modules 6 modules
43.5
74
68
85
45
17.5
1P
35
1P+N
35
2P
52.5
3P
70
4P
1 module 2 2 3 4
44
74.7
68
83
45
17.8
1P+N
62
Overall dimensions
MCBs
Description of product and codes ................. pg. 2/1
S 931 N - S 941 N - S 951 N - S 971 N
S 240 - S 250 - S 270 - S 280 - M 280
S 290
11/5
11
ABB SACE
45
91
125
10.5
35 70 105 140
145
130
1P 2P 3P 4P
2 modules 4 modules 6 modules 8 modules
56.5
45
35
100755025
1P 2P 3P 4P
80
92
75
91
Overall dimensions
MCBs
S 500
S 700
Description of product and codes ................. pg. 2/1
11/6
11
ABB SACE
45
74
68
94
45
4P (8 modules)
DS 654 50 ÷63 A
DS 674 50 ÷63 A
T
4P
DS 654 0,5 ÷25 A
DS 674 0,5 ÷25 A
6 modules
T
105
2P
DS 642 P 0,5 ÷32 A
DS 652 0,5 ÷ 63 A
DS 672 0,5 ÷ 63 A
4 modules
T
70
2P
DS 852 VARIMAT
10 - 15 - 20 A
5 modules
87.5
T
2 modules
43.5
74
68
97
45
35
1P+N DS 642-
DS 651-DS 751 6 ÷ 32 A DS 640-650-670-850
4P (7 modules)
DS 654 32 ÷40 A
DS 674 32 ÷40 A
123
7 modules
140
8 modules
T
36
83
44
76.7
83
45
62
70
Overall dimensions
RCDs
Description of product and codes ................. pg. 3/1
DS 941 - DS 951 - DS 971
DS 642 - DS 650 - DS 670 - DS 751
11/7
11
ABB SACE
45
87
107
87.5
7.8
35.5
85
80
60
5 modules
4P
F 664 - F 674
45
45
45
6
68
43.5
2P
T
35
4P
T
70
2 modules 4 modules
56.5
45
180
92.5
56.5
45
150
92.5
125
75
50A
63A
40A
2P4P
Overall dimensions
RCDs
F 360 - F 370 - F 390 - F 660 In = 80…100A
F 660 - F 670 In = 125A
Description of product and codes ................. pg. 3/1
F 500
11/8
11
ABB SACE
45
45
45
6
79
43.5
2P
T
105
6 modules
4P
T
140
8 modules
10 10
4P
144
T
87.5
61
.
5
55
44
Overall dimensions
RCDs
Description of product and codes ................. pg. 3/1
F 360 AR - F 370 AR - F 390 AR
F 800
11/9
11
ABB SACE
45
65
90
122,5
90
4P 100 A
DDA 64DDA 62
90
61
2P 100 A
4P 25 A 4P 40 A 4P 63 A
35 52.5 70
TT T
2 modules 3 modules 4 modules
DDA 64
DDA 74
DDA 94
DDA 64 AE
DDA 64 AP
3P 63 A
70
3P 40 A
52.5
3P 25 A
35
TT T
2 modules 3 modules 4 modules
DDA 63
DDA 73
DDA 93
DDA 63 AE
2P 25 A - 40 A - 63 A
35
T
45
74
68
94
45
2 modules
DDA 62
DDA 72
DDA 92
DDA 62 AE
DDA 62 AP
Overall dimensions
RCDs
DDA 60 - DDA 70 - DDA 90 - DDA 60 AE - DDA 60 AP
Description of product and codes ................. pg. 3/1
11/10
11
ABB SACE
56.5
45
92
.
5
92.5
Installable on left Installable on right
2525 12,512.512.5
NAUA/AL NHS
85
17.5
44
68
45
8.75
1/2 mod. 1 module
S2-H..
S2-S
S2-S/H
S9-X
S9-S
S2-A..
S2-BM.
S2-BP
S2-BPS
45
73
17.5
1 module
S 290 A1
S 290 A2
S 290 BM
8.75
1/2 module
S 290 H11
S 290 S
90
17.8
S9-T..
S9-V..
83
83
18945
78
92,5
45
92,5
45
70
2 POLES = 17
3 POLES = 34
4 POLES = 52
Overall dimensions
Auxiliary elements and accessories
Description of product and codes ................. pg. 2/1
Auxiliary elements for range S9../DS9..
Auxiliary elements for range S2..
Auxiliary elements for S 500 - F 500
Motor operating device
11/11
11
ABB SACE
61.5
33
9.5
75
F 6-HF 3-H11
1 module
45
45
45
6
68
43.5
17.5
75
CODE A B C
ME 1 - 1 module
ME 2 - 2 modules
ME 3 - 3 modules
ME 4 - 4 modules
18
36
54
72
40
57
75
93
50
67
85
103
ME 6 - 6 modules 108 129 139
ME 8 - 8 modules 130 157 167
DEPTH D:
57 mm for S 240-S 250-
S 270-S 280 circuit-breakers
72 mm for S 210
circuit-breakers
80
D
6
72
C
B
47
A
Ø 3.5+4
C
B
A
45
D
E
F
CODE A B C D E F
PCD/2
PCD/4
PCD/6
PCD/8
40
75
109
144
29
64
99
134
135
135
135
135
42
77
112
146
154
154
154
154
82
82
82
82
Overall dimensions
Auxiliary elements and accessories
Auxiliary elements for F 3.. - F 6..
PCD terminal covers
ME flange for rear board mounting
Description of product and codes ................. pg. 2/1
11/12 ABB SACE
74.5
6
.
5
150
45
33
79
.
5
95
.
5
(1 pole = 90,5)
141
150
34
33
130
10
.
5
4.5
40
4040
40
12
46.4
8.5 104.5
175
66
18.5
N
L1
L2
L3
PE
16
35 35
30
78.5
45
83.5
99.5 ( 1 pole = 94.5)
4040
40
40
12
175
46.4
23.5
125
EST 2
157
117
115
157
EST 1
NH base
25.5 34
10
41.5
Ø 40
M22x1
65
24.5
22.5
3.2
36
48
36
Ø 4
48
40.7 min. 30 - max. 15080
Overall dimensions
Auxiliary elements and accessories
Description of product and codes ................. pg. 2/1
Rotary handle for S 500 - F 500
Accessories for S 700
SA flange for S 700
BT1 plate EST
11/13
11
ABB SACE
Overall dimensions
Other protection devices
Contents
RD2 residual current monitors ...................................................................................... 11/14
OVR surge protective devices ....................................................................................... 11/15
MS 225 manual motor starters ...................................................................................... 11/15
E 930 fuse holders .......................................................................................................... 11/16
M2160 - 2060 fuse switches ........................................................................................... 11/16
11/14
11
ABB SACE
50
64.8
85
35
45
2 modules
ON TEST TRIP
43.5
58
85
52.5
45
35
3 modules
CODE ABCD EG
TR 35
TR 60
TR 80
TR 110
35
60
80
110
83
112
132
158
73
98
115
148
92
116
136
188
100
125
146
178
40
55
65
78
H
6
6
6
6
I
28
28
28
28
TR 210 210 315 305 310 325 155 8.5 45
TR 210A 210 315 305 310 325 155 8.5 45+30
C
B
A
G
39
H
I
E
D
Overall dimensions
Other protection devices
Description of product and codes ................. pg. 4/1
RD2 residual current monitors and toroidal transformers
11/15
11
ABB SACE
17.5 35 70 69
87
OVR/TEL,
OVR/SIGN OVR 165, OVR 140,
OVR 115 OVR 365, OVR 340,
OVR 315
1 module 2 modules 4 modules
HK, SK, AS
66.5
86
44
9
54 70
86
44
OVR surge protective devices
MS 225 manual motor starters
Overall dimensions
Other protection devices
Description of product and codes ................. pg. 4/1
11/16
11
ABB SACE
1 module 2 modules 3 modules 4 modules
1P 1P+N
2P 3P 3P+N
68
45
3817.5 35 52.5 70
A
D
B
F
E
D
A
B
F
E
C
1 module 2 modules 3 modules
1P - 1P+N 2P
17
.
535 52
.
5
45
61
Up to 32A
50A
107
125A
Overall dimensions
Other protection devices
Description of product and codes ................. pg. 4/1
E 930 fuse holders
M2160 - M2060 fuse switches
Type No. poles Dimens. of fuse A B/B open C D E/E open F
E 931/20-32 1 8.5 x 31.5 (32A: 10.3 x 38) 83 72/107 17.5 45 65/102 44
E 931N/20-32 1+N 8.5 x 31.5 (32A: 10.3 x 38) 83 72/107 17.5 45 65/102 44
E 932/20-32 2 8.5 x 31.5 (32A: 10.3 x 38) 83 72/107 35 45 65/102 44
E 933/20-32 3 8.5 x 31.5 (32A: 10.3 x 38) 83 72/107 52.5 45 65/102 44
E 933N/20-32 3+N 8.5 x 31.5 (32A: 10.3 x 38) 83 72/107 52.5 45 65/102 44
E 931/50 1 14 x 51 107 76/104 21 45 60 50
E 931N/50 1+N 14 x 51 107 76/104 42 45 60 50
E 932/50 2 14 x 51 107 76/104 42 45 60 50
E 933/50 3 14 x 51 107 76/104 63 45 60 50
E 933N/50 3+N 14 x 51 107 76/104 84 45 60 50
E 931/125 1 22 x 58 124 76/104 35 45 60 50
E 931N/125 1+N 22 x 58 124 76/104 70 45 60 50
E 932/125 2 22 x 58 124 76/104 70 45 60 50
E 933/125 3 22 x 58 124 76/104 105 45 60 50
E 933N/125 3+N 22 x 58 124 76/104 140 45 60 50
11/17
11
ABB SACE
Overall dimensions
Command devices
Contents
E 240 - E 270 switch disconnectors .............................................................................. 11/18
RS 370 rotary switch disconnectors ............................................................................. 11/18
E 220 switches ................................................................................................................ 11/18
E 220 pushbuttons and indicator lamps ....................................................................... 11/19
ESB contactors ............................................................................................................... 11/19
EN contactors ................................................................................................................. 11/19
E 259 installation relays .................................................................................................. 11/20
E 250 electro-mechanical latching relays ..................................................................... 11/20
E 260 electronic latching relays ..................................................................................... 11/20
11/18
11
ABB SACE
17.5 44
68
45
90
52.5 7035
1 module
1P
2 modules 3 modules 4 modules
2P 3P 4P
1 module
1P, 2P, 3P, 4P
85
17.5 44
68
45
8.5 43.5
68
45
90
52.5 70
RS 370/11
RS 370/20
RS 370/02
3 modules 4 modules
RS 373 RS 374
Overall dimensions
Command devices
E 240 - E 270 switch disconnectors
RS 370 rotary switch disconnectors
E 220 switches
Description of product and codes ................. pg. 5/1
11/19
11
ABB SACE
1 module
17.5
85
68
45
44
45
58
44
17.5
85
35 54 9
1 module 2 modules 3 modules
ESB 20 ESB 24 ESB 40 - ESB 63 ESB 04
45
58
44
17.5
85
35 54
1 module 2 modules 3 modules
EN 20 EN 24 EN 40
Overall dimensions
Command devices
Description of product and codes ................. pg. 5/1
E 220 pushbuttons and indicator lamps
ESB contactors
EN contactors
11/20 ABB SACE
45
58
44
17.5
85
1 module 2 modules
E 251
E 252
E 253
E 254
45
58
44
85
35
17.5
1 module
17.5
85
45
58
44
1 module
Overall dimensions
Command devices
E 259 installation relays
E 250 electro-mechanical latching relays
E 260 electronic latching relays
Description of product and codes ................. pg. 5/1
11/21
11
ABB SACE
Overall dimensions
Load management devices
Contents
E 234 time delay relays ................................................................................................... 11/22
ETS electro-mechanical time switches ........................................................................ 11/22
DTS digital time switches ............................................................................................... 11/22
E 232 staircase timers .................................................................................................... 11/23
SWD staircase switch-off warning devices .................................................................. 11/23
TWS-1 twilight switches + sensor ................................................................................. 11/23
RAL overload alarms ...................................................................................................... 11/24
LSS1/2 load shedding switches .................................................................................... 11/24
SQZ3 phase and sequence relays ................................................................................. 11/25
LE power failure signalling lamps ..................................................................................11/25
E 228 WM alarm indicators ............................................................................................ 11/26
Min./max. current/voltage ammetric and voltmetric relays ........................................ 11/26
STD universal dimmers .................................................................................................. 11/27
11/22
11
ABB SACE
1 module
45
58
44
85
17.5
3 modules
52.4
88.5
45
58
2 modules 6 modules
DTS 1/1 - DTS 7/1
DTS 7/2 - DTS 7/2 I DTS 7/3
45
58
85
35
105
45
82
53
38
1 module
85
17.5
ETS1M - 1RM ETS1 - 1R - 7R
Overall dimensions
Load management devices
Description of product and codes ................. pg. 6/1
E 234 time delay relays
ETS electro-mechanical time switches
DTS digital time switches
11/23
11
ABB SACE
1 module
85
17.5
45
58
44
1 module
58
45
17.5
85
82
35 60
lux.
45
15
84
33
20
33
32
17
Ø 5
Overall dimensions
Load management devices
E 232 staircase timers
SWD staircase switch-off warning devices
TWS-1 twilight switches + sensor
Description of product and codes ................. pg. 6/1
11/24
11
ABB SACE
5 modules
2 modules
45
85
35
1
2
3
58
44
87.5
45
58
Overall dimensions
Load management devices
Description of product and codes ................. pg. 6/1
RAL overload alarms
LSS1/2 load shedding switches
11/25
11
ABB SACE
2 modules
58
44
45
85
35
3 modules
65
50
45
85
52.5
Phases Sequence
400V 50Hz
OK
OK
OK
Three phases
Min Voltage
Min Voltage
Delay (s)
70% 100%
220
Overall dimensions
Load management devices
SQZ3 phase and sequence relays
LE power failure signalling lamps
Description of product and codes ................. pg. 6/1
11/26
11
ABB SACE
1 module
17.5
85
58
45
3 modules
45
58
52.5
85
Overall dimensions
Load management devices
Description of product and codes ................. pg. 6/1
E 228 WM alarm indicators
Min./max. current/voltage ammetric and voltmetric relays
11/27
11
ABB SACE
2 modules
35
85
58
45
4 modules
70
85
2 modules
35
85
52.5
85
70
45
3 modules
Overall dimensions
Load management devices
STD universal dimmers
Description of product and codes ................. pg. 6/1
11/28 ABB SACE
11/29
11
ABB SACE
Overall dimensions
Measurement devices
Contents
Analogue measurement instruments ............................................................................ 11/30
Digital measurement instruments VLM-D, AMT-D ....................................................... 11/30
MTM multimeters ............................................................................................................ 11/31
MCV - MCA voltmetric and ammetric switches ........................................................... 11/31
Current transformers ...................................................................................................... 11/32
TCS electronic transducers ........................................................................................... 11/33
DC shunts ........................................................................................................................ 11/33
HTM - E 233 electro-mechanical hour meters ............................................................. 11/34
DELTA METER energy meters ....................................................................................... 11/35
EE MINI-METER energy meters .................................................................................... 11/35
EMT 3 energy meters ...................................................................................................... 11/35
Isoltester-C ...................................................................................................................... 11/36
Selvtester-C ..................................................................................................................... 11/36
QSD panels for remote signalling .................................................................................. 11/36
11/30
11
ABB SACE
3 modules
52.5
85
58
45
V
200
400
3 modules
A
52.5
85
58
45
Overall dimensions
Measurement devices
Description of product and codes ................. pg. 7/1
Analogue measurement instruments
Digital measurement instruments VLM-D, AMT-D
11/31
11
ABB SACE
72
52.5
56÷58
45
75
43
3 modules
58
45
6 modules
105
90
Overall dimensions
Measurement devices
MTM multimeters
MCV - MCA voltmetric and ammetric switches
Description of product and codes ................. pg. 7/1
11/32
11
ABB SACE
124
150
82
12.5
65
37
40
55
3 modules
52.5 58
45
85
TRFM
45
127
100
33
64
80
33
50
10.5
73
102
48
63 41
34
25
20
12
10
41
34
25
20
12
10
60
92
48 60
92
60
92
48
63
33
12
22
13
48
Overall dimensions
Measurement devices
Description of product and codes ................. pg. 7/1
Current transformers
11/33
11
ABB SACE
130
115
70
Voltage drop
mV Dimensions 61015 5
25 40
100 60
150 250 400 600 1000 1500 2500
Current [A]
A type B type
a
a
b
b
b
c
c
e
h
90
28
78
20
8
100
33
80
30
15
145
55
105
40
20
10
10
30
60
30
165
65
90
21
48
115
120
30
60
60
1
2
1
2
3
1
2
a
c
30
9
135
115
e
a
b1
b1
b3
a
1
e
a
2
c
2
h
c1
15 1
1
b2
Insulanting base only ut to
25A
A
type
B
type
2
Overall dimensions
Measurement devices
TCS electronic transducers
DC shunts
Description of product and codes ................. pg. 7/1
11/34
11
ABB SACE
2 modules 1 module
HMT E 233
58
44
45
85
35
58
45
90 (monofase)
126 (trifase)
Overall dimensions
Measurement devices
Description of product and codes ................. pg. 7/1
HMT - E 233 electro-mechanical hour meters
11/35
11
ABB SACE
3 modules
45
58
52.5
85
10
20 50
3 modules
52.5
45
58
122.5
45
64.8
96
7 modules
Overall dimensions
Measurement devices
DELTA METER energy meters
EE MINI-METER energy meters
EMT 3 energy meters
Description of product and codes ................. pg. 7/1
11/36 ABB SACE
17
55
121
78
QSD
Quadro segnalazione / Insulation check panel
Controllo rete / Check network
TACITAZIONE
SILENCE
PROVA
TEST RETE
ON
GUASTO
FAULT
CE
I
64.4
TEST PERIODICO
TEST PERIODICALLY
230 V ~ 24 V ~
6 modules
68
85
45
105
Isoltester-C
2 modules
68
85
45
34
Selvtester-C
Overall dimensions
Measurement devices
Description of product and codes ................. pg. 7/1
Isoltester-C
Selvtester-C
QSD panels for remote signalling
11/37
11
ABB SACE
Overall dimensions
Other modular functions
Contents
TM/TS bell transformers ................................................................................................ 11/38
Bells and buzzers ............................................................................................................ 11/38
Modular sockets ............................................................................................................. 11/38
M 9100 modular housings for CBK pushbuttons ......................................................... 11/39
11/38
11
ABB SACE
44
85
60
45
44
2 modules
TM10…TM15,
TSM,
TS8/8…TS8/24,
TS8/4-8-12,
TS16/8…TS16/24,
TS16/4-6-8,
TS16/4-8-12
TM30…TM40,
TS8/4-6-8,
TS24/4-8-12,
TS24/8-12-24
3 modules
45
58
52.5
35
85
1 module
45
58
44
17.5
85
2 modules
35
SM1
RM1 TSM
2 modules
35
TSR
45
68
44
SM1 - RM1 - TSM TSR
Overall dimensions
Other modular functions
TM/TS bell transformers
Bells and buzzers
Modular sockets
Description of product and codes ................. pg. 8/1
11/39
11
ABB SACE
2 modules
58
44
45
85
35
Overall dimensions
Other modular functions
M 9100 modular housings for CBK pushbuttons
Description of product and codes ................. pg. 8/1
Examples of applications
Residential buildings
Public buildings
Commercial buildings
Industry
Handycraft
Contents
E 259 installation relay ................................................................................................12/4
E 255 latching relay with sequential contacts ........................................................... 12/5
E 262 C electronic latching relay ............................................................................... 12/6
E 234 EW time delay relay ....................................................................................... 12/7-8
E 234 RW time delay relay ....................................................................................... 12/7-8
ETS electro-mechanical time switch ..........................................................................12/9
DTS two-channel digital time switch ........................................................................12/10
E 232 staircase timer and SWD switch-off warning device .....................................12/11
TWS-1 twilight switch and DTS 7/1 time switch ................................................. 12/12-13
TWS-1 twilight switch and ETS 7/R time switch .................................................12/12-13
RAL overload alarm .................................................................................................. 12/14
LSS1/2 load shedding switch ................................................................................... 12/15
SQZ3 phase and sequence presence relay ..............................................................12/16
MTME-I multimeter ................................................................................................... 12/18
Application sheets
Description of product and codes........................ pg. 5/13
ABB SACE
12/4
12
Application sheets
E 259 installation relay
Operating principle
The E 259 installation relay, suitable for
residential and commercial applications,
is available in three versions: with NO
contact, with NO and NC contacts, and
with two NO contacts.
Application environments
The E 259 installation relay is
particularly indicated in any environment
and situation where it is necessary to
control considerable power loads
(i.e. lighting systems).
Example of installation
As shown in the diagrams, one of
the possible applications is to
mount the E 259 installation relay
with a NO and a NC contact inside
the electric system of an hospital
ward. The first control sent through
pushbutton to the lighting circuit
will switch off the ceiling lights and
switch on the corridor lamps, while
the second impulse returns to the
previous state.
E 259-R11
1
LIGHT UNIT
N
2
1
C
AUXILIARY
L1
4
3
C
A2
A1
S1
01
LIGHT UNIT
2
C
E259
AUXILIARY L1 N
ABB SACE 12/5
12
Application sheets
E 255 latching relay
with sequential contacts
Operating principle
The two contacts of the E 255 latching
relay switch the position (open/closed)
at each impulse according to a
sequence programmed by the control
pushbutton circuit.
Application environments
The E 255 latching relay is particularly
indicated in environments and situations
requiring the load sequential control
through a single pushbutton circuit
(offices, restaurants, etc.)
Example of installation
As shown in the diagrams, one of
the possible applications is to
mount the E 255 latching relay
inside the lighting system of an art
gallery. The first pushbutton
impulse will switch on the ceiling
lights, the second triggers the wall
lamps, the third switches off the
ceiling lights and the fourth
switches off the wall lamps.
E255
L1 NAUXILIARY
A2
PP
A1
PP/A
2
1
PP/B
4
3
L1
N
AUXILIARY
WALL LAMPS CEILING
LIGHT
A
A+B
B
O
A = diffused light
B = intensive light
max lightingA+B =
E 225 relay switching cycles
E 255
Description of product and codes........................ pg. 5/14
ABB SACE
12/6
12
Application sheets
E 262 C electronic latching relay
Operating principle
The E 262 C electronic latching relay is
controlled by two circuits. Acting on the
first circuit through a pushbutton you
cause the switching (open/closed) in a
single way. The second circuit switches
the relay on the open or closed position
regardless to the contact status.
Application environments
The E 262 C electronic latching relay is
particularly indicated in environments
and situations where it is necessary to
send a single switch-on/switch-off
control to multiple loads regardless
to the open/closed circuit status (office
districts, hotels, museums, theatres, etc.).
Example of installation
As shown in the diagrams, one of
the possible applications is to
mount the E 262 C electronic
latching relay inside the electric
system of an office district. The
lights in the various offices can be
switched on or off by pressing the
pushbuttons placed in the different
rooms or by tripping all the circuits
simultaneously from the porter’s
office or from another central
position.
A2
PP1
A1
LIGHTING –
OFFICE 1
N
E 262-C
2
1
PP2
2
1
PP1
P1
L1
E 262-C
P2
A2
PP2
A1
B1 C1 C1
ON OFF
B1
ON
CENTRAL OFF
CENTRAL LIGHTING –
OFFICE 2
AUXILIARY
E262C
AUXILIARY NL1
ON OFF
Description of product and codes........................ pg. 5/16
ABB SACE 12/7
12
E234 ETS MS225
ESB
E234
AUXILIARY
PUMP
K
L3L2L1
FOT O
Operating principle
The operation of the E 234 EW relay
implies the alternate activation of
electric loads according to adjustable
time intervals in order to plan
operation/pause sequences.
Application environments
By allowing the automatic control of the
electric loads based on alternate time
intervals, the E 234 EW time delay relay
is particularly indicated to trigger
ventilation systems (offices, restaurants,
dressing-room, etc.), solenoid valves
and pump controls (garden irrigation,
carwashes, fountains, etc.).
Example of installation
As shown in the diagrams, one of
the possible applications is to
mount the E 234 EW time delay
relay inside a pump power supply
circuit in order to control it
according to an adjustable
operation/pause sequence (i.e.
acting on a fountain pump to set
the water jet and recycling
activation sequence in one or more
tanks).
Application sheets
E 234 EW time delay relay
A1
A2
T1
OPERATION
TIME DELAY
E 234-EW
AUXILIARY
T2
16
15
T1
161818
15
A1
A2
T2
12
10
ETS-7R
4
6
ETS-7R
E 234-EW
B1 B1
K
A2
A1
PUMP PAUSE
TIME DELAY
4
3
6
5
8
7
L1 L2 L3
MS 225
K
PUMP
ESB
Description of product and codes........................ pg. 6/2
ABB SACE
12/8
12
Application sheets
E 234 RV time delay relay
Operating principle
The delayed at drop-out E 234 RV time
delay relay operation is performed by
impulsive control through a pushbutton.
The time can be set multiplying the
adjustment range from 0.1 seconds to
2 hours by 1 to 10 values.
Application environments
By allowing the automatic control of the
electric loads based on the time,
E 234 RV time delay relay is particularly
indicated to trigger alarms (public
areas, baths for disabled persons, etc.)
and to signal the opening of
unsupervised entrances (shops,
workrooms, etc.).
Example of installation
As shown in the diagrams, one of
the possible applications is to
mount the E 234 RV time delay relay
inside the power supply circuit of a
bath for disabled persons. In this
case, by pressing the appropriate
pushbutton it is possible to activate
an acoustic alarm for a preset time.
Description of product and codes........................ pg. 6/2
12
ABB SACE 12/9
Application sheets
ETS electro-mechanical time switch
Operating principle
The ETS electro-mechanical time switch
enables to control the circuit
opening/closing according to a daily or
weekly program or to manually set
permanent ON/OFF operation.
Application environments
The ETS electro-mechanical time switch
is particularly indicated in any
environment and situation where it is
necessary to program system load
operation according to a daily or weekly
frequency (shop lighting system, public
buildings, heating systems, irrigation
systems, etc.).
Example of installation
As shown in the diagrams, one of
the possible applications is to
mount the ETS electro-mechanical
time switch inside the power supply
circuit of a golf field. In this case
the device programming enables
the daily activation of the irrigation
system at a preset time.
Description of product and codes........................ pg. 6/3
AUXILIARY L1 N
S1
1O
ETS
ETS-1R
IRRIGATION
SOLENOID VALVE
N
4
6
ETS-1R
L1
12
10
S1
1O
EV
E 221-10
AUXILIARY
ABB SACE
12/10
12
DTS
AUXILIARY L1 N
Application sheets
DTS two-channel digital time switch
SUN
Operating principle
The DTS two-channel digital time switch
enables to open and close circuits
according to a daily or weekly program,
controlling single loads or group of
loads even when they require different
time controls with a common time
reference. The EEPROM memory of
these devices enables to save settings
even in case of power failure and
regardless to the event length.
Application environments
The DTS two-channel digital time switch
is particularly indicated in environments
and situations requiring the
management of multiple loads
according to a time program flexible
enough to include or exclude their
application based on the day of the
week (offices, schools, public areas, etc.).
Example of installation
As shown in the diagrams, one of
the possible applications is to
mount the DTS two-channel digital
time switch inside the power supply
circuit of a church, where in the
days when no service is performed
only the heating system is activated
(programmed on one of the two
channels) at a preset time, while on
Sundays and when services are
performed the lighting system is
also switched on (through a
program on the second channel).
According to the controlled system
power, the activation is performed
by an ESB contactor.
4
2
N
DTS7/2
DTS7/2
6
8
L1
LIGHTING SYSTEM HEATING SYSTEM
1
3
DTS7/2
AUXILIARY
Description of product and codes........................ pg. 6/4
ABB SACE 12/11
12
Application sheets
E 232 staircase timer and SWD
switch-off warning device
Operating principle
The E 232 staircase timer operation is
determined by impulsive control through
a pushbutton. This staircase timer
enables to turn on the plant lights for a
preset time T1. Through a connection in
parallel to the SWD switch-off warning
device module it is possible to delay the
time while decreasing the lighting level
of 50%.
Application environment
The installation of the E 232 staircase
timer combined to the SWD switch-off
warning device module is suitable for
any environment and situation needing
the lighting time delay (staircases,
offices and public passage areas,
basements, garages, etc.).
Example of installation
As shown in the diagrams, one of
the possible applications is the
installation of the E 232 staircase
timer coupled to the SWD switch-
off warning device module in the
staircase lighting system of a block
of flats. Pressing a pushbutton, the
time delay switch picks up and
switches on the lights for T1 time,
that can be set. At the end of the
time delay, the SWD switch-off
warning device module reduces the
lighting level of 50% per T2 time.
During this time it is possible to
control light switch-on again.
SWD
E232-230
AUXILIARY L1 N
LIGHTING LOAD
E 232-230
N
4
3
T
L1
A1
A2
T
PUSHBUTTON
LOCATION LIGHT
SWD
2
3
AUXILIARY
Description of product and codes....................... pg. 6/5
ABB SACE
12/12
12
AUXILIARY
Operating principle
TWS-1 twilight switch and DTS 7/1 time
switch coupling in the same system
enables to control lighting system
switch-on according to ambient lighting
level and to specific time programming
(daily or weekly).
Application environments
The installation of TWS-1 twilight switch
combined to DTS 7/1 time switch is
suitable for any environment and
situation needing the rationalization
of power consumption (shops, offices
and public passage areas, parking,
parks, etc.).
Example of installation
As shown in the diagrams, one of
the possible applications is the
installation of the TWS-1 twilight
switch coupled to the DTS 7/1 time
switch in the lighting system of a
chemist’s. When the external light
decreases below a certain level (i.e.
shop opening during evening
hours), the twilight switch controls
the lighting of windows, sign and
cross sign. The last one can have
an intermittent switch-on/off
because of time delay relay
installation. When the chemist’s is
opened during the night, the
switch-on of all lights (using the
twilight switch) is set through date
and time programming using time
switch. When the chemist’s is
closed, the time switch
programming switches off the
windows and cross sign lights
independently from twilight switch
(sign ON).
Application sheets
TWS-1 twilight switch
and DTS 7/1 time switch
SUN
AUXILIARY
SIGN WINDOW
LIGHTING
LOGO
SIGN
Description of product and codes........................ pg. 6/7
12
ABB SACE 12/13
Application sheets
TWS-1 twilight switch and
ETS 7/R time switch
SUN
SUN
MON TUE WED
THUR
FRI SAT
MON TUE WED
THUR
FRI SAT
TWS-1
SENS.
ETS7R
6
7
AUXILIARY L1 N
6
7
TWS-1
TWS-1
LIGHTING
LOAD
N
L1
ETS-7R
ETS-7R
SENSOR
1
2
10
3
4
6
4
12
AUXILIARY
Operating principle
TWS-1 twilight switch and ETS 7/R time
switch coupling in the same system
enables to control lighting system
switch-on according to ambient lighting
level and to specific time programming
(daily or weekly).
Application environments
The installation of the TWS-1 twilight
switch combined to the ETS 7/R time
switch is suitable for any environment
and situation needing the rationalization
of power consumption (shops, offices
and public passage areas, parking,
parks, etc.).
Example of installation
As shown in the diagrams, one of
the possible applications is the
installation of the TWS-1 twilight
switch coupled to the ETS 7/R time
switch in the office district system.
The external light switch-on
depends on ambient lighting level
during working days; otherwise, no
lighting element control is
programmed during non-working
days.
Description of product and codes........................ pg. 6/7
ABB SACE
12/14
12
Application sheets
RAL overload alar m
Operating principle
The RAL overload alarm constantly
compares the maximum preset power
consumption value to effective system
power consumption.
Approaching allowed threshold, it
signals to disconnect one of the loads
through acoustic alarm avoiding the
main circuit-breaker tripping.
Connecting the S 9-T415 undervoltage
release to the appropriate contact, the
RAL overload alarm provides an
acoustic alarm and simultaneously
opens the circuit-breaker protecting one
or more not primary loads.
Application environments
The installation of the RAL overload
alarm is suitable for any environment
and situation in order to avoid power
consumption which could trip the
limiting circuit-breaker of the system.
Example of installation
As shown in the diagrams, one of
the possible applications is the
installation of the RAL overload
alarm in the domestic system where
the electric oven and washing
machine are simultaneously
switched on increasing the power
consumption. When the power
consumption approaches the preset
threshold values, an acoustic alarm
is activated and the washing
machine switches off automatically
through an undervoltage release.
3
1
u.r.
NOT PRIMARY
LOADS
NL1
Id
RAL
BUILT-IN BELL
u.r.
RAL
AUXILIARY
NOT PRIMARY
LOADS
PRIMARY
LOADS
u.r.
AUXILIARY
PRIMARY
LOADS NOT PRIMARY
LOADS
Id
NL1
u.r.
RAL
Description of product and codes........................ pg. 6/8
12
ABB SACE 12/15
Application sheets
LSS1/2 load shedding switch
Operating principle
LSS1/2 load shedding switch is used in
case of exceeding of consumption
threshold allowed in the system by
switching off in sequence one or two
loads, if necessary. At preset intervals
and until current consumption is not
below the reference level, the switch tries
to reset the disconnected loads.
Application environments
The installation of the LSS1/2 load
shedding switch is suitable for any
environment and situation where it is
necessary to control electric energy
consumption within consumption limits
allowed in the system.
Example of installation
As shown in the diagrams, one of
the possible applications is the
installation of the LSS1/2 load
shedding switch in a printing office
system, where the conditioning
switch-on causes the exceeding of
the energy consumption threshold
defined with the supplying company
by contract. The LSS1/2 load
shedding switch preserves printing
machines operation by switching
off one or two primary loads
automatically (i.e. night
conditioning and lighting), where
ON red leds indicate temporary
OFF. After a preset interval, the
switch checks that current
consumption values fall within the
limits again trying to reset the
previously disconnected loads.
SOCKETS
LSS1/2
L1
357
4 8 12 11 14 13
LIGHT CONDITIONING BOILER
PRIMARY LOADS NOT PRIMARY LOADS
MAX 16A
FIXED OFF NOT PRIMARY LOADS
MAX 16A
SOCKETS
LSS1/2
PRIMARY LOADS
L1 N
NOT PRIMARY
LOADS NOT PRIMARY
LOADS
Description of product and codes........................ pg. 6/9
ABB SACE
12/16
12
SQZ3
ESB
MS225
K
FOTO
MOTOR
K
L3L2L1
M
3
AUXILIARY
Application sheets
SQZ3 phase and sequence presence relay
Operating principle
Through an output relay with contact
in safety switching, the SQZ3 phase
and sequence presence device for
400 V a.c. three-phase networks
enables the phase and sequence
presence management monitoring also
the minimum voltage (adjustable up to
70% of Vn). In case of any defect, the
device operates within a range from 2 to
20 seconds, with the opportunity to
control the appropriate acoustic signals,
motor controlling contactors or circuit-
breakers.
Application environments
The installation of the SQZ3 phase and
sequence presence relay is particularly
suitable for any environment and
situation where it is necessary to control
the three-phase network operation
promptly signalling any defect.
Example of installation
As shown in the diagrams, one of
the possible applications is the
installation of the SQZ3 phase and
sequence presence relay in a
department store, where the
escalator supply circuit has a phase
variation determining the SQZ3
relay intervention on the ESB
contactor and causing the motor
block and the alarm lighting
indication.
4
5
MOTOR
AUXILIARY
8
7
6
5
4
31197
K
A2
A1
MOTOR
K
MS 225
L3L2L1
ESB
SQZ3
HG
SQZ3
M
L1
L2
L3
3
Description of product and codes........................ pg. 6/10
ABB SACE 12/17
12
Application sheets
MTME-I multimeter
Example of installation
As shown in the diagrams, one of
the possible applications is the
installation of two MTME-I
multimeters in a camping system,
where the first multimeter
measures the consumption of the
three-phase network supplying
the area reserved for ship
docking, while the second one
measures the energy
consumption of the one-phase
network supplying the camper
area. The computer placed at the
reception collects data from both
multimeters and reckons them
through the special software.
Application environments
The installation of the MTME-I
multimeter is particularly suitable for any
environment and situation where it is
necessary to combine voltage, current,
power and temperature measurements
with energy consumption
measurements, remote management
and reckoning in electric three-phase
networks (business centres, industry
departments, harbours, etc.).
Operating principle
The MTME-I multimeter provides for the
main electric quantities measurement as
well as the active and reactive energy
calculation in three-phase networks or
through pulse output. Along with the
CDI impulse concentrator and the CUS
serial output converter from RS485 to
RS232, the pulse output also enables
the remote reading of the energy
consumption measured by the
multimeter and by any meter if
connected. This consumption can be
turned into costs to be divided among
each user through the SWD1 software.
(+8 of MTME I and energy meters
must be connected to A + E - of CDIS)
HARBOUR CAMPING AREA
Description of product and codes........................ pg. 7/5
13/1
ABB SACE
13
Product by product
general contents
Product Order Technical Overall Application
information details dimensions sheet
MCBs
S 9.. MCBs
S 931 N series .....................................................................................................2/10 ....................... 10/4 .......................11/4 ...........................
S 941 N series .....................................................................................................2/11 ....................... 10/4 .......................11/4 ...........................
S 951 N series .....................................................................................................2/12 ....................... 10/4 .......................11/4 ...........................
S 971 N series .....................................................................................................2/13 ....................... 10/4 .......................11/4 ...........................
Auxiliary elements
Shunt trips ............................................................................................................2/15 .....................................................11/10 ...........................
Auxiliary/signal contacts.......................................................................................2/16 .....................................................11/10 ...........................
Undervoltage releases .........................................................................................2/17 .....................................................11/10 ...........................
S 2.. MCBs
S 240 series .........................................................................................................2/22 ....................... 10/4 .......................11/4 ...........................
S 250 series .........................................................................................................2/24 ....................... 10/4 .......................11/4 ...........................
S 270 series .........................................................................................................2/27 ....................... 10/4 .......................11/4 ...........................
S 280 B-C-D series ..............................................................................................2/30 ....................... 10/4 .......................11/4 ...........................
S 280 K-Z series ..................................................................................................2/32 ....................... 10/4 .......................11/4 ...........................
S 280 UC series ...................................................................................................2/34 ....................... 10/4 .......................11/4 ...........................
M 280 magnetic only series .................................................................................2/36 ....................... 10/4 .......................11/4 ...........................
Auxiliary elements
Shunt trips ............................................................................................................2/39 .....................................................11/10 ...........................
Auxiliary/signal contacts.......................................................................................2/40 .....................................................11/10 ...........................
Undervoltage releases .........................................................................................2/41 .....................................................11/10 ...........................
Mechanical interlocks...........................................................................................2/42 .....................................................11/10 ...........................
Mechanical interlocks with signal contact ............................................................2/43 .....................................................11/10 ...........................
Accessories
S 2.. range accessories .......................................................................................2/45 .....................................................11/10 ...........................
S 290 MCBs
S 290 series .........................................................................................................2/51 ....................... 10/4 .......................11/4 ...........................
Auxiliary elements
Shunt trips ............................................................................................................2/53 .....................................................11/10 ...........................
Auxiliary/signal contacts.......................................................................................2/54 .....................................................11/10 ...........................
Undervoltage releases .........................................................................................2/55 .....................................................11/10 ...........................
S 500 MCBs
S 500 B-C-D series ..............................................................................................2/60 ....................... 10/4 .......................11/5 ...........................
S 500 UC series (especially for d.c.)....................................................................2/62 ....................... 10/4 ....................... 11/5 ...........................
S 500-K motor protection series with adjustable thermal release,
S 500-KM magnetic only ........................................................................................2/64 ....................... 10/4 .......................11/5 ...........................
Auxiliary elements and accessories
Auxiliary/signal contacts.......................................................................................2/66 .....................................................11/10 ...........................
Shunt trips ............................................................................................................2/67 .....................................................11/10 ...........................
Undervoltage releases .........................................................................................2/67 .....................................................11/10 ...........................
Accessories..........................................................................................................2/68 .....................................................11/10 ...........................
S 700 MCBs
S 700 series .........................................................................................................2/71 ....................... 10/4 .......................11/5 ...........................
13/2 ABB SACE
13
Product by product
general contents
Product Order Technical Overall Application
information details dimensions sheet
RCDs
DS 9.. RCBOs
DS 941 series .......................................................................................................3/6 ..................... 10/40 ....................... 11/6 ...........................
DS 951 series .....................................................................................................3/10 ..................... 10/40 ....................... 11/6 ...........................
DS 971 series .....................................................................................................3/14 ..................... 10/40 ....................... 11/6 ...........................
Auxiliary elements
Shunt trips ............................................................................................................3/19 .....................................................11/10 ...........................
Auxiliary/signal contacts.......................................................................................3/20 .....................................................11/10 ...........................
Undervoltage releases .........................................................................................3/21 .....................................................11/10 ...........................
DS 6.., DS 751, DS 850, F 500 RCBOs
Elettrostop DS 640 ...............................................................................................3/26 ..................... 10/40 .......................11/6 ...........................
Elettrostop DS 650 ...............................................................................................3/27 ..................... 10/40 .......................11/6 ...........................
Elettrostop DS 670 ...............................................................................................3/29 ..................... 10/40 .......................11/6 ...........................
Varistop DS 751 ...................................................................................................3/31 ..................... 10/40 ....................... 11/6 ...........................
Varimat DS 850 .................................................................................................... 3/32 ..................... 10/40 .......................11/6 ...........................
F 500 ....................................................................................................................3/33 ..................... 10/44 .......................11/7 ...........................
RCCBs
Elettrostop F 360..................................................................................................3/38 ..................... 10/40 .......................11/7 ...........................
Elettrostop F 660..................................................................................................3/39 ..................... 10/40 .......................11/7 ...........................
Varistop F 370 ...................................................................................................... 3/40 ..................... 10/40 .......................11/7 ...........................
Varistop F 670 ...................................................................................................... 3/41 ..................... 10/40 .......................11/7 ...........................
Selective Var istop F 390 ......................................................................................3/42 ..................... 10/40 .......................11/7 ...........................
F 360 AR, F 370 AR, F 390 AR with automatic reclosing device.........................3/43 ..................... 10/40 .......................11/8 ...........................
F 370 for high frequencies (400 Hz) ....................................................................3/44 ..................... 10/40 .......................11/7 ...........................
F 800 for leakage current with continuous components ......................................3/45 ..................... 10/40 .......................11/8 ...........................
Auxiliary elements and accessories
Auxiliary elements ................................................................................................3/46 .....................................................11/10 ...........................
Accessories..........................................................................................................3/46 .....................................................11/10 ...........................
RCD blocks
DDA 60.................................................................................................................3/51 ..................... 10/40 .......................11/9 ...........................
DDA 70.................................................................................................................3/52 ..................... 10/40 .......................11/9 ...........................
Selective DDA 90 .................................................................................................3/53 ..................... 10/40 .......................11/9 ...........................
DD A 60 AE for emergency stop ........................................................................... 3/54 ..................... 10/45 .......................11/9 ...........................
Anti-disturbance DD A 60 AP ................................................................................3/55 ..................... 10/40 .......................11/9 ...........................
D 60 .....................................................................................................................3/58 ..................... 10/40 .......................11/9 ...........................
D 70 .....................................................................................................................3/59 ..................... 10/40 .......................11/9 ...........................
Selective D 90 ......................................................................................................3/60 ..................... 10/40 .......................11/9 ...........................
Other protection devices
RD2 residual current monitors ........................................................................... 4/2 ..................... 10/48 .....................11/14 ...........................
OVR surge protective devices
Monobloc surge protective devices........................................................................ 4/3 ..................... 10/49 .....................11/15 ...........................
Withdrawable-cartridge surge protective devices ..................................................4/5 ..................... 10/49 ..................... 11/15 ...........................
MS 225 manual motor starters ........................................................................... 4/7 ..................... 10/56 .....................11/15 ...........................
E 930 fuse holders ..............................................................................................4/10 ..................... 10/60 .....................11/16 ...........................
13/3
ABB SACE
13
M2160 - M2060 fuse-switches ..........................................................................4/12 ..................... 10/61 .....................11/16 ...........................
Command devices
E 240 - E 270 switch disconnectors ................................................................... 5/2 ..................... 10/64 .....................11/18 ...........................
RS 370 rotary switch disconnectors .................................................................. 5/4 ..................... 10/65 .....................11/18 ...........................
E 220 switches .....................................................................................................5/6 ..................... 10/65 .....................11/18 ...........................
E 220 pushbuttons and indicator lamps ............................................................ 5/8 .....................................................11/19 ...........................
Contactors and installation relays
ESB series contactors..........................................................................................5/10 ..................... 10/66 .....................11/19 ...........................
EN series contactors ............................................................................................5/12 ..................... 10/66 ..................... 11/19 ...........................
E 259 installation relays .......................................................................................5/13 ..................... 10/66 ..................... 11/20 ...................... 12/4
Latching relays
E 250 electro-mechanical ....................................................................................5/14 ..................... 10/70 ..................... 11/20 ...................... 12/5
E 260 electronic ...................................................................................................5/16 ..................... 10/70 .....................11/20 ...................... 12/6
Load management devices
E 234 time delay relays ........................................................................................6/2 ..................... 10/74 .....................11/22 ...................12/7-8
Time switches
ETS electro-mechanical .........................................................................................6/3 .....................................................11/22 ...................... 12/9
DTS digital .............................................................................................................6/4 .....................................................11/22 .................... 12/10
E 232 electro-mechanical and E 232 E electronic staircase timers ................6/5 .....................................................11/23 .................... 12/11
SWD staircase switch-off warning devices ....................................................... 6/6 .....................................................11/23 ...........................
TWS-1 twilight switches ......................................................................................6/7 .....................................................11/23 ............... 12/12-13
RAL overload alarms ...........................................................................................6/8 .....................................................11/24 .................... 12/14
LSS1/2 load shedding switches .........................................................................6/9 ..................... 10/76 .....................11/24 .................... 12/15
SQZ3 phase and sequence relays ....................................................................6/10 .....................................................11/25 .................... 12/16
LE power failure signalling lamps .................................................................... 6/11 .....................................................11/25 ...........................
E 228 WM alarm indicators ...............................................................................6/12 .....................................................11/26 ...........................
Min./max. current/voltage ammetric and voltmetric relays ........................... 6/13 ..................... 10/77 .....................11/26 ...........................
STD universal dimmers ..................................................................................... 6/14 ..................... 10/79 .....................11/27 ...........................
Product by product
general contents
Product Order Technical Overall Application
information details dimensions sheet
13/4 ABB SACE
13
Product Order Technical Overall Application
information details dimensions sheet
Measurement devices
Measurement instruments
Analogic instruments..............................................................................................7/2 ............................ ..................... 11/30 ...........................
Digital instruments .................................................................................................7/4 ............................ .....................11/30 ...........................
MTM multimeters ...................................................................................................7/5 ..................... 10/82 .....................11/31 .................... 12/18
Accessories for analogue and digital instruments
MCV - MCA voltmetric and ammetric switches ......................................................7/6 ............................ ..................... 11/31 ...........................
Interchangeable scales for analogue instruments..................................................7/7 ............................ ............................ ...........................
Current transformers .............................................................................................. 7/9 ..................... 10/83 .....................11/32 ...........................
Electronic transducers .........................................................................................7/12 ............................ .....................11/33 ...........................
Shunts .................................................................................................................. 7/13 ............................ ..................... 11/33 ...........................
HMT and E 233 electro-mechanical hour meters ........................................... 7/14 .....................................................11/34 ...........................
Electronic single-phase and three-phase energy meters
Three-phase DELTA METER series with digital display on LCD.......................... 7/15 ..................... 10/84 .....................11/35 ...........................
EE MINI-METER and EMT 3 series.....................................................................7/17 ..................... 10/86 .....................11/35 ...........................
Insulation testers
Isoltester-C...........................................................................................................7/18 ..................... 10/88 .....................11/36 ...........................
Selvtester-C .........................................................................................................7/19 ..................... 10/88 .....................11/36 ...........................
QSD panels for remote signalling ........................................................................7/19 ..................... 10/88 .....................11/36 ...........................
Other modular functions
TM/TS bell transformers ..................................................................................... 8/2 ..................... 10/89 .....................11/38 ...........................
Bells and buzzers .................................................................................................8/4 .....................................................11/38 ...........................
Modular sockets .................................................................................................. 8/5 .....................................................11/38 ...........................
M9100 modular housing for CBK pushbuttons .................................................8/6 .....................................................11/39 ...........................
Unifix rapid cabling system
Unifix H system components ..............................................................................9/7 ............................ ............................ ...........................
Unifix L system components .............................................................................. 9/9 ............................ ............................ ...........................
Unifix SL system components .......................................................................... 9/11 ............................ ............................ ...........................
Product by product
general contents
14/1
ABB SACE
Code list
Elc code
Elc code Order code Type Pg. Elc code Order code Type Pg. Elc code Order code Type Pg.
14
11176144 11176144 D74 32A 30mA (0015) 3/59
11176145 11176145 D74 63A 30mA (0015) 3/59
11176148 11176148 D74 32A 300mA (0015) 3/59
11176149 11176149 D74 63A 300mA (0015) 3/59
11176233 11176233 D92 63A 300mA (0015) 3/60
11176249 11176249 D94 63A 300mA (0015) 3/60
11176252 11176252 D94 63A 1A (0015) 3/60
11178108 11178108 S 251 D 0,5 2/24
11178109 11178109 S 251 D 1 2/24
11178110 11178110 S 251 D 1,6 2/24
11178111 11178111 S 251 D 2 2/24
11178112 11178112 S 251 D 3 2/24
11178113 11178113 S 251 D 4 2/24
11178114 11178114 S 251 D 6 2/24
11178115 11178115 S 251 D 10 2/24
11178117 11178117 S 251 D 20 2/24
11178118 11178118 S 251 D 25 2/24
11178119 11178119 S 251 D 32 2/24
11178120 11178120 S 251 D 40 2/24
11178121 11178121 S 251 D 50 2/24
11178122 11178122 S 251 D 63 2/24
11178123 11178123 S 252 D 0,5 2/26
11178124 11178124 S 252 D 1 2/26
11178125 11178125 S 252 D 1,6 2/26
11178126 11178126 S 252 D 2 2/26
11178127 11178127 S 252 D 3 2/26
11178128 11178128 S 252 D 4 2/26
11178129 11178129 S 252 D 6 2/26
11178130 11178130 S 252 D 10 2/26
11178131 11178131 S 252 D 16 2/26
11178132 11178132 S 252 D 20 2/26
11178133 11178133 S 252 D 25 2/26
11178134 11178134 S 252 D 32 2/26
11178135 11178135 S 252 D 40 2/26
11178136 11178136 S 252 D 50 2/26
11178137 11178137 S 252 D 63 2/26
11178138 11178138 S 253 D 0,5 2/26
11178139 11178139 S 253 D 1 2/26
11178140 11178140 S 253 D 1,6 2/26
11178141 11178141 S 253 D 2 2/26
11178142 11178142 S 253 D 3 2/26
11178143 11178143 S 253 D 4 2/26
11178144 11178144 S 253 D 6 2/26
11178146 11178146 S 253 D 16 2/26
11178147 11178147 S 253 D 20 2/26
11178148 11178148 S 253 D 25 2/26
11178149 11178149 S 253 D 32 2/26
11178150 11178150 S 253 D 40 2/26
11178151 11178151 S 253 D 50 2/26
11178152 11178152 S 253 D 63 2/26
11178153 11178153 S 254 D 0,5 2/26
11178154 11178154 S 254 D 1 2/26
11178155 11178155 S 254 D 1,6 2/26
11178156 11178156 S 254 D 2 2/26
11178157 11178157 S 254 D 3 2/26
11178158 11178158 S 254 D 4 2/26
11178159 11178159 S 254 D 6 2/26
11178160 11178160 S 254 D 10 2/26
11178161 11178161 S 254 D 16 2/26
11178162 11178162 S 254 D 20 2/26
11178163 11178163 S 254 D 25 2/26
11178164 11178164 S 254 D 32 2/26
11178165 11178165 S 254 D 40 2/26
11178166 11178166 S 254 D 50 2/26
11178167 11178167 S 254 D 63 2/26
11812281 11812281 DS671 C 6 30mA 3/29
11812282 11812282 DS671 C10 30mA 3/29
11812283 11812283 DS671 C16 30mA 3/29
11812284 11812284 DS671 C20 30mA 3/29
11812285 11812285 DS671 C25 30mA 3/29
11812286 11812286 DS671 C32 30mA 3/29
11861114 11861114 S931N C 2 R 2/10
11861115 11861115 S931N C 4 R 2/10
11861116 11861116 S931N C 6 R 2/10
11861117 11861117 S931N C10 R 2/10
11861118 11861118 S931N C16 R 2/10
11861119 11861119 S931N C20 R 2/10
11861120 11861120 S931N C25 R 2/10
11861121 11861121 S931N C32 R 2/10
11861122 11861122 S931N C40 R 2/10
EA 051 1 16010511 E 931/50 4/11
EA 052 9 16010529 E 931N/50 4/11
EA 053 7 16010537 E 932/50 4/11
EA 054 5 16010545 E 933/50 4/11
EA 055 2 16010552 E 933N/50 4/11
EA 058 6 16010586 E 931/125 4/11
EA 059 4 16010594 E 931N/125 4/11
EA 060 2 16010602 E 932/125 4/11
EA 061 0 16010610 E 933/125 4/11
EA 062 8 16010628 E 933N/125 4/11
EA 065 1 16010651 E 930/MCR1P50 4/11
EA 066 9 16010669 E 930/MCR3P50 4/11
EA 067 7 16010677 E 930/MCR1P125 4/11
EA 068 5 16010685 E 930/MCR3P125 4/11
EA 069 3 16010693 E 930/ACP50 4/11
EA 070 1 16010701 E 930/ACP125 4/11
EA 109 7 16011097 4E 1905 2/47
EA 120 4 36011204 RS 373/45 5/4
EA 121 2 36011212 RS 373/63 5/4
EA 122 0 36011220 RS 373/80 5/4
EA 123 8 36011238 RS 373/100 5/4
EA 124 6 36011246 RS 374/45 5/4
EA 125 3 36011253 RS 374/63 5/4
EA 126 1 36011261 RS 374/80 5/4
EA 127 9 36011279 RS 374/100 5/4
EA 128 7 36011287 RS 370/4P 5/5
EA 129 5 36011295 RS 370/11 5/5
EA 132 9 36011329 RS 370/SH 5/5
EA 133 7 36011337 RS 370/1S 5/5
EA 134 5 36011345 RS 370/3S 5/5
EA 140 2 16011402 MTME 7/5
EA 141 0 16011410 MTME-I 7/5
EA 142 8 16011428 MTME-485 7/5
EA 143 6 16011436 CDI 7/5
EA 144 4 16011444 CUS 7/5
EA 145 1 16011451 SW01 7/5
EA 150 1 16011501 E 221-30X 5/6
EA 151 9 16011519 E 221-11 5/6
EA 152 7 16011527 E 221-22 5/6
EA 153 5 16011535 E 221-31 5/6
EA 154 3 16011543 E 222-10 5/7
EA 155 0 16011550 E 222-20 5/7
EA 156 8 16011568 E 222-30 5/7
EA 157 6 16011576 E 222-40 5/7
EA 158 4 16011584 E 222-30X 5/7
EA 159 2 16011592 E 222-11 5/7
EA 160 0 16011600 E225-11F 5/8
EA 161 8 16011618 E225-11G 5/8
EA 162 6 16011626 E225-11Z 5/8
EA 163 4 16011634 E227-11G 5/8
EA 164 2 16011642 E227-11Z 5/8
EA 165 9 16011659 E229-G 5/8
EA 166 7 16011667 E229-Z 5/8
EA 167 5 16011675 E220-B1 5/9
EA 168 3 16011683 E220-C1 5/9
EA 169 1 16011691 E220-D1 5/9
EA 170 9 16011709 E220-E1 5/9
EA 171 7 16011717 E220-G1 5/9
EA 172 5 16011725 E 220-G 5/9
EA 173 3 16011733 E10/12 5/9
EA 174 1 16011741 E10/24 5/9
EA 175 8 16011758 E10/48 5/9
EA 176 6 16011766 E10/60 5/9
EA 177 4 16011774 E10/110 5/9
EA 191 5 16011915 E 931/20 4/10
EA 193 1 16011931 E 932/20 4/10
EA 194 9 16011949 E 933/20 4/10
EA 201 2 16012012 E 931/32 4/10
EA 203 8 16012038 E 932/32 4/10
EA 204 6 16012046 E 933/32 4/10
EA 211 1 16012111 E 930/KIT 4/11
EA 213 7 16012137 BSA 2 2/45
EA 214 5 36012145 BSA 1 2/45
EA 215 2 36012152 FERMO END 2/45
EA 260 8 16012608 TM10/12 8/2
EA 261 6 16012616 TM10/24 8/2
EA 262 4 16012624 TM15/12 8/2
EA 263 2 16012632 TM15/24 8/2
EA 264 0 16012640 TM30/12 8/2
EA 265 7 16012657 TM30/24 8/2
EA 266 5 16012665 TM40/12 8/2
EA 267 3 16012673 TM40/24 8/2
EA 269 9 16012699 TS8/8 8/2
EA 270 7 16012707 TS8/12 8/2
EA 271 5 16012715 TS8/24 8/2
EA 272 3 16012723 TS8/8SW 8/2
To make order procedures easier, the
following pages supply the list of
correspondences between ELC codes
(identifying each product) and order codes
(to specify in the order form).
The list is based on two research keys: by
ELC codes and by type.
Elc code Order code Type Pg.
11170564 11170564 DS651 C16 100 mA 3/27
11170565 11170565 DS651 C20 100 mA 3/27
11178116 11178116 S 251 D 16 2/24
11178145 11178145 S 253 D 10 2/26
11865333 11865333 S 282 C 0,5 2/30
11865334 11865334 S 282 C 1 2/30
11865335 11865335 S 282 C 1,6 2/30
11865336 11865336 S 282 C 2 2/30
11865337 11865337 S 282 C 3 2/30
11865338 11865338 S 282 C 4 2/30
11865375 11865375 S 282 K 0,5 2/32
11865376 11865376 S 282 K 1 2/32
11865377 11865377 S 282 K 1,6 2/32
11865378 11865378 S 282 K 2 2/32
11865379 11865379 S 282 K 3 2/32
11865380 11865380 S 282 K 4 2/32
11866313 11866313 S 283 C 0,5 2/31
11866314 11866314 S 283 C 1 2/31
11866315 11866315 S 283 C 1,6 2/31
11866316 11866316 S 283 C 2 2/31
11866317 11866317 S 283 C 3 2/31
11866318 11866318 S 283 C 4 2/31
11866329 11866329 S 283 K 0,5 2/33
11866330 11866330 S 283 K 1 2/33
11866331 11866331 S 283 K 1,6 2/33
11866332 11866332 S 283 K 2 2/33
11866333 11866333 S 283 K 3 2/33
11866334 11866334 S 283 K 4 2/33
11170387 11170387 DS751 C10 10mA (0008) 3/31
11170388 11170388 DS751 C13 10mA (0008) (CH)3/31
11170389 11170389 DS751 C16 10mA (0008) 3/31
11170771 11170771 DS651 K 6 30mA (0020) 3/27
11170773 11170773 DS651 K10 30mA (0020) 3/27
11170774 11170774 DS651 K16 30mA (0020) 3/27
11170775 11170775 DS651 K20 30mA (0020) 3/27
11170776 11170776 DS651 K25 30mA (0020) 3/27
11170777 11170777 DS651 K32 30mA (0020) 3/27
11170787 11170787 DS651 K 6 300mA (0020) 3/27
11170789 11170789 DS651 K10 300mA (0020) 3/27
11170790 11170790 DS651 K16 300mA (0020) 3/27
11170791 11170791 DS651 K20 300mA (0020) 3/27
11176027 11176027 D62 16A 10mA (0015) 3/58
11176028 11176028 D62 32A 30mA (0015) 3/58
11176029 11176029 D62 63A 30mA (0015) 3/58
11176032 11176032 D62 32A 300mA (0015) 3/58
11176033 11176033 D62 63A 300mA (0015) 3/58
11176034 11176034 D62 32A 500mA (0015) 3/58
11176035 11176035 D62 63A 500mA (0015) 3/58
11176036 11176036 D63 32A 30mA (0015) 3/58
11176037 11176037 D63 63A 30mA (0015) 3/58
11176040 11176040 D63 32A 300mA (0015) 3/58
11176041 11176041 D63 63A 300mA (0015) 3/58
11176044 11176044 D64 32A 30mA (0015) 3/58
11176045 11176045 D64 63A 30mA (0015) 3/58
11176048 11176048 D64 32A 300mA (0015) 3/58
11176049 11176049 D64 63A 300mA (0015) 3/58
11176050 11176050 D64 32A 500mA (0015) 3/58
11176051 11176051 D64 63A 500mA (0015) 3/58
11176127 11176127 D72 16A 10mA (0015) 3/59
11176128 11176128 D72 32A 30mA (0015) 3/59
11176129 11176129 D72 63A 30mA (0015) 3/59
11176132 11176132 D72 32A 300mA (0015) 3/59
11176133 11176133 D72 63A 300mA (0015) 3/59
11176136 11176136 D73 32A 30mA (0015) 3/59
11176137 11176137 D73 63A 30mA (0015) 3/59
11176140 11176140 D73 32A 300mA (0015) 3/59
11176141 11176141 D73 63A 300mA (0015) 3/59
14/2 ABB SACE
Code list
Elc code
Elc code Order code Type Pg. Elc code Order code Type Pg. Elc code Order code Type Pg.
14
EA 273 1 16012731 TS8/12SW 8/2
EA 274 9 16012749 TS8/24SW 8/2
EA 275 6 16012756 TS8/4-6-8SW 8/2
EA 276 4 16012764 TS8/4-8-12SW 8/2
EA 277 2 16012772 TS16/8 8/2
EA 278 0 16012780 TS16/12 8/2
EA 279 8 16012798 TS16/24 8/2
EA 280 6 16012806 TS16/4-6-8 8/2
EA 281 4 16012814 TS16/4-8-12 8/2
EA 282 2 16012822 TS24/4-8-12 8/2
EA 283 0 16012830 TS24/8-12-24 8/2
EA 291 3 16012913 E 931N/20 4/10
EA 292 1 16012921 E 933N/20 4/10
EA 293 9 16012939 E 931N/32 4/10
EA 294 7 16012947 E 933N/32 4/10
EA 380 4 36013804 E 251-8V 5/14
EA 381 2 36013812 E 251-24 V 5/14
EA 382 0 36013820 E 251-230 V 5/14
EA 383 8 36013838 E 252-8 V 5/14
EA 384 6 36013846 E 252-24 V 5/14
EA 385 3 36013853 E 252-230 V 5/14
EA 386 1 36013861 E 254-8 V 5/14
EA 387 9 36013879 E 254-24 V 5/14
EA 388 7 36013887 E 254-230 V 5/14
EA 389 5 36013895 E 256-8 V 5/14
EA 390 3 36013903 E 256-24 V 5/14
EA 391 1 36013911 E 256-230 V 5/14
EA 414 1 16014141 TSM 8/4
EA 425 7 16014257 SM1/12 8/4
EA 426 5 16014265 SM1/230 8/4
EA 427 3 16014273 RM1/12 8/4
EA 428 1 16014281 RM1/230 8/4
EA 429 9 16014299 TSR [NEW] 8/4
EA 502 3 16015023 ETS-1M 6/3
EA 503 1 16015031 ETS-1RM 6/3
EA 510 6 16015106 ETS-KIT 6/3
EA 511 4 16015114 ETS 1 6/3
EA 512 2 16015122 ETS 1/R 6/3
EA 513 0 16015130 ETS 7/R 6/3
EA 519 7 36015197 E 232-230 6/5
EA 520 5 36015205 E 232E-230 6/5
EA 523 9 36015239 E 232E-8/230 6/5
EA 524 7 16015247 BCP 2/N 2/47
EA 525 4 16015254 BCP 3/N 2/47
EA 526 2 16015262 BCP 4/N 2/47
EA 546 0 16015460 MR/35 S 2/47
EA 549 4 16015494 EK - B 2/47
EA 550 2 16015502 EK - M 2/47
EA 554 4 16015544 DTS 1/1 6/4
EA 555 1 16015551 DTS 7/1 6/4
EA 556 9 16015569 DTS 7/2 6/4
EA 557 7 16015577 DTS 7/2 I 6/4
EA 558 5 16015585 DTS 7/3 6/4
EA 580 9 36015809 E 255-8 V 5/14
EA 581 7 36015817 E 255-12 V 5/14
EA 582 5 36015825 E 255-24 V 5/14
EA 583 3 36015833 E 255-230 V 5/14
EA 584 1 36015841 E 251-12 V 5/14
EA 585 8 36015858 E 252-12 V 5/14
EA 586 6 36015866 E 254-12 V 5/14
EA 587 4 36015874 E 256-12V 5/14
EA 588 2 36015882 E 259 R10-8V 5/13
EA 589 0 36015890 E 259 R10-12V 5/13
EA 590 8 36015908 E 259 R10-24V 5/13
EA 591 6 36015916 E 259 R10-230V 5/13
EA 592 4 36015924 E 259 R11-8V 5/13
EA 593 2 36015932 E 259 R11-12V 5/13
EA 594 0 36015940 E 259 R11-24V 5/13
EA 595 7 36015957 E 259 R11-230V 5/13
EA 596 5 36015965 E 259 R20-8V 5/13
EA 597 3 36015973 E 259 R20-12V 5/13
EA 598 1 36015981 E 259 R20-24V 5/13
EA 599 9 36015999 E 259 R20-230V 5/13
EA 610 4 36016104 E 261-24 V 5/16
EA 611 2 36016112 E 261-230 V 5/16
EA 613 8 36016138 E 262-24 V 5/16
EA 614 6 36016146 E 262-230 V 5/16
EA 616 1 36016161 E 266-24 V 5/16
EA 617 9 36016179 E 266-230 V 5/16
EA 618 7 36016187 E 261 C-12 V 5/17
EA 619 5 36016195 E 261 C-24 V 5/17
EA 620 3 36016203 E 261 C-230 V 5/17
EA 621 1 36016211 E 262 C-12 V 5/17
EA 622 9 36016229 E 262 C-24 V 5/17
EA 623 7 36016237 E 262 C-230 V 5/17
EA 624 5 36016245 E 266 C-12 V 5/17
EA 625 2 36016252 E 266 C-24 V 5/17
EA 626 0 36016260 E 266 C-230 V 5/17
EA 634 4 36016344 E 234-MFR 6/2
EA 635 1 36016351 E 234-AV 6/2
EA 636 9 36016369 E 234-RV 6/2
EA 638 5 36016385 E 234-AW 6/2
EA 639 3 36016393 E 234-EW 6/2
EA 642 7 36016427 E 234-TI2 6/2
EA 643 5 16016435 BCF 1/100 2/47
EA 644 3 16016443 BCF 1H/100 2/47
EA 645 0 16016450 BCF 2/100 2/47
EA 646 8 16016468 BCF 3/100 2/47
EA 647 6 16016476 BCF 4/100 2/47
EA 648 4 16016484 EK - C 2/47
EA 649 2 16016492 EK - C4 2/47
EA 650 0 16016500 BCP 1/100 2/47
EA 715 1 16017151 E 225-11C 5/8
EA 716 9 16017169 E 225-11D 5/8
EA 717 7 16017177 E 225-11E 5/8
EA 718 5 16017185 E 227-11B 5/8
EA 719 3 16017193 E 227-11E 5/8
EA 720 1 16017201 E 229-B 5/8
EA 721 9 16017219 E 229-D 5/8
EA 722 7 16017227 E 229-E 5/8
EA 723 5 16017235 E 220-E 5/9
EA 724 3 16017243 E 220-E3 5/9
EA 836 5 16018365 OVR /115P 4/6
EA 837 3 16018373 OVR /315P 4/6
EA 838 1 16018381 OVR /140P 4/5
EA 839 9 16018399 OVR /340P 4/5
EA 840 7 16018407 OVR /165P 4/5
EA 841 5 16018415 OVR /365P 4/5
EA 858 9 16018589 OVR /BASE1N 4/6
EA 859 7 16018597 OVR /BASE3N 4/6
EA 860 5 16018605 OVR /15P 4/6
EA 861 3 16018613 OVR /40P 4/6
EA 862 1 16018621 OVR /65P 4/6
EA 863 9 16018639 OVR /N 4/6
EA 876 1 16018761 OVR/115 4/4
EA 877 9 16018779 OVR/140 4/3
EA 878 7 16018787 OVR/165 4/3
EA 879 5 16018795 OVR/315 4/4
EA 880 3 16018803 OVR/340 4/3
EA 881 1 16018811 OVR/365 4/3
EA 882 9 16018829 OVR/TEL 4/4
EA 883 7 16018837 OVR/SIGN 4/4
EA 942 1 16019421 E 1175-C 8/5
EA 943 9 16019439 E 1175 8/5
EA 944 7 16019447 M 1173 8/5
EA 945 4 16019454 M 1174 8/5
EA 947 0 16019470 M 9100 8/6
EA 948 8 16019488 M 2061 4/12
EA 949 6 16019496 M 2061 Na 4/12
EA 950 4 16019504 M 2062 4/12
EA 951 2 16019512 M 2063 4/12
EA 952 0 16019520 M 2063 Na 4/12
EA 953 8 16019538 M 2161 4/12
EA 954 6 16019546 M 2161 Na 4/12
EA 955 3 16019553 M 2162 4/12
EA 956 1 16019561 M 2163 4/12
EA 957 9 16019579 M 2163 Na 4/12
EB 000 7 16020007 DS941 B6-30MA/AC 3/6
EB 001 5 16020015 DS941 B10-30MA/AC 3/6
EB 002 3 16020023 DS941 B16-30MA/AC 3/6
EB 003 1 16020031 DS941 B20-30MA/AC 3/6
EB 004 9 16020049 DS941 B25-30MA/AC 3/6
EB 005 6 16020056 DS941 B32-30MA/AC 3/6
EB 006 4 16020064 DS941 B40-30MA/AC 3/6
EB 007 2 16020072 DS941 B6-100MA/AC 3/6
EB 008 0 16020080 DS941 B10-100MA/AC 3/6
EB 009 8 16020098 DS941 B16-1000MA/AC 3/6
EB 010 6 16020106 DS941 B20-100MA/AC 3/6
EB 011 4 16020114 DS941 B25-100MA/AC 3/6
EB 012 2 16020122 DS941 B32-100MA/AC 3/6
EB 013 0 16020130 DS941 B40-100MA/AC 3/6
EB 014 8 16020148 DS941 B6-300MA/AC 3/7
EB 015 5 16020155 DS941 B10-300MA/AC 3/7
EB 016 3 16020163 DS941 B16-3000MA/AC 3/7
EB 017 1 16020171 DS941 B20-300MA/AC 3/7
EB 018 9 16020189 DS941 B25-300MA/AC 3/7
EB 019 7 16020197 DS941 B32-300MA/AC 3/7
EB 020 5 16020205 DS941 B40-300MA/AC 3/7
EB 021 3 16020213 DS941 B6-500MA/AC 3/7
EB 022 1 16020221 DS941 B10-500MA/AC 3/7
EB 023 9 16020239 DS941 B16-5000MA/AC 3/7
EB 024 7 16020247 DS941 B20-500MA/AC 3/7
EB 025 4 16020254 DS941 B25-500MA/AC 3/7
EB 026 2 16020262 DS941 B32-500MA/AC 3/7
EB 027 0 16020270 DS941 B40-500MA/AC 3/7
EB 028 8 16020288 DS941 B6-1000MA/AC 3/7
EB 029 6 16020296 DS941 B10-1000MA/AC 3/7
EB 030 4 16020304 DS941 B16-10000MA/AC 3/7
EB 031 2 16020312 DS941 B20-1000MA/AC 3/7
EB 032 0 16020320 DS941 B25-1000MA/AC 3/7
EB 033 8 16020338 DS941 B32-1000MA/AC 3/7
EB 034 6 16020346 DS941 B40-1000MA/AC 3/7
EB 039 5 16020395 DS941 C6-30MA/AC 3/6
EB 040 3 16020403 DS941 C10-30MA/AC 3/6
EB 041 1 16020411 DS941 C16-30MA/AC 3/6
EB 042 9 16020429 DS941 C20-30MA/AC 3/6
EB 043 7 16020437 DS941 C25-30MA/AC 3/6
EB 044 5 16020445 DS941 C32-30MA/AC 3/6
EB 045 2 16020452 DS941 C40-30MA/AC 3/6
EB 046 0 16020460 DS941 C6-100MA/AC 3/6
EB 047 8 16020478 DS941 C10-100MA/AC 3/6
EB 048 6 16020486 DS941 C16-100MA/AC 3/6
EB 049 4 16020494 DS941 C20-100MA/AC 3/6
EB 050 2 16020502 DS941 C25-100MA/AC 3/6
EB 051 0 16020510 DS941 C32-100MA/AC 3/6
EB 052 8 16020528 DS941 C40-100MA/AC 3/6
EB 053 6 16020536 DS941 C6-300MA/AC 3/7
EB 054 4 16020544 DS941 C10-300MA/AC 3/7
EB 055 1 16020551 DS941 C16-300MA/AC 3/7
EB 056 9 16020569 DS941 C20-300MA/AC 3/7
EB 057 7 16020577 DS941 C25-300MA/AC 3/7
EB 058 5 16020585 DS941 C32-300MA/AC 3/7
EB 059 3 16020593 DS941 C40-300MA/AC 3/7
EB 060 1 16020601 DS941 C6-500MA/AC 3/7
EB 061 9 16020619 DS941 C10-500MA/AC 3/7
EB 062 7 16020627 DS941 C16-500MA/AC 3/7
EB 063 5 16020635 DS941 C20-500MA/AC 3/7
EB 064 3 16020643 DS941 C25-500MA/AC 3/7
EB 065 0 16020650 DS941 C32-500MA/AC 3/7
EB 066 8 16020668 DS941 C40-500MA/AC 3/7
EB 082 5 16020825 DS941 C6-1000MA/AC 3/7
EB 083 3 16020833 DS941 C10-1000MA/AC 3/7
EB 084 1 16020841 DS941 C16-1000MA/AC 3/7
EB 085 8 16020858 DS941 C20-1000MA/AC 3/7
EB 086 6 16020866 DS941 C25-1000MA/AC 3/7
EB 087 4 16020874 DS941 C32-1000MA/AC 3/7
EB 088 2 16020882 DS941 C40-1000MA/AC 3/7
EB 100 5 16021005 DS951 B6-30MA/AC 3/10
EB 101 3 16021013 DS951 B10-30MA/AC 3/10
EB 102 1 16021021 DS951 B16-30MA/AC 3/10
EB 103 9 16021039 DS951 B20-30MA/AC 3/10
EB 104 7 16021047 DS951 B25-30MA/AC 3/10
EB 105 4 16021054 DS951 B32-30MA/AC 3/10
EB 106 2 16021062 DS951 B40-30MA/AC 3/10
EB 107 0 16021070 DS951 B6-100MA/AC 3/10
EB 108 8 16021088 DS951 B10-100MA/AC 3/10
EB 109 6 16021096 DS951 B16-1000MA/AC 3/10
EB 110 4 16021104 DS951 B20-100MA/AC 3/10
EB 111 2 16021112 DS951 B25-100MA/AC 3/10
EB 112 0 16021120 DS951 B32-100MA/AC 3/10
EB 113 8 16021138 DS951 B40-100MA/AC 3/10
EB 114 6 16021146 DS951 B6-300MA/AC 3/11
EB 115 3 16021153 DS951 B10-300MA/AC 3/11
EB 116 1 16021161 DS951 B16-3000MA/AC 3/11
EB 117 9 16021179 DS951 B20-300MA/AC 3/11
EB 118 7 16021187 DS951 B25-300MA/AC 3/11
EB 119 5 16021195 DS951 B32-300MA/AC 3/11
EB 120 3 16021203 DS951 B40-300MA/AC 3/11
EB 121 1 16021211 DS951 B6-500MA/AC 3/11
EB 122 9 16021229 DS951 B10-500MA/AC 3/11
EB 123 7 16021237 DS951 B16-5000MA/AC 3/11
EB 124 5 16021245 DS951 B20-500MA/AC 3/11
EB 125 2 16021252 DS951 B25-500MA/AC 3/11
EB 126 0 16021260 DS951 B32-500MA/AC 3/11
EB 127 8 16021278 DS951 B40-500MA/AC 3/11
EB 128 6 16021286 DS951 B6-1000MA/AC 3/11
EB 129 4 16021294 DS951 B10-1000MA/AC 3/11
EB 130 2 16021302 DS951 B16-10000MA/AC 3/11
EB 131 0 16021310 DS951 B20-1000MA/AC 3/11
EB 132 8 16021328 DS951 B25-1000MA/AC 3/11
14/3
ABB SACE
Code list
Elc code
Elc code Order code Type Pg. Elc code Order code Type Pg. Elc code Order code Type Pg.
14
EB 133 6 16021336 DS951 B32-1000MA/AC 3/11
EB 134 4 16021344 DS951 B40-1000MA/AC 3/11
EB 135 1 16021351 DS951 C6-30MA/AC 3/10
EB 136 9 16021369 DS951 C10-30MA/AC 3/10
EB 137 7 16021377 DS951 C16-30MA/AC 3/10
EB 138 5 16021385 DS951 C20-30MA/AC 3/10
EB 139 3 16021393 DS951 C25-30MA/AC 3/10
EB 140 1 16021401 DS951 C32-30MA/AC 3/10
EB 141 9 16021419 DS951 C40-30MA/AC 3/10
EB 142 7 16021427 DS951 C6-100MA/AC 3/10
EB 143 5 16021435 DS951 C10-100MA/AC 3/10
EB 144 3 16021443 DS951 C16-100MA/AC 3/10
EB 145 0 16021450 DS951 C20-100MA/AC 3/10
EB 146 8 16021468 DS951 C25-100MA/AC 3/10
EB 147 6 16021476 DS951 C32-100MA/AC 3/10
EB 148 4 16021484 DS951 C40-100MA/AC 3/10
EB 149 2 16021492 DS951 C6-300MA/AC 3/11
EB 150 0 16021500 DS951 C10-300MA/AC 3/11
EB 151 8 16021518 DS951 C16-300MA/AC 3/11
EB 152 6 16021526 DS951 C20-300MA/AC 3/11
EB 153 4 16021534 DS951 C25-300MA/AC 3/11
EB 154 2 16021542 DS951 C32-300MA/AC 3/11
EB 155 9 16021559 DS951 C40-300MA/AC 3/11
EB 156 7 16021567 DS951 C6-500MA/AC 3/11
EB 157 5 16021575 DS951 C10-500MA/AC 3/11
EB 158 3 16021583 DS951 C16-500MA/AC 3/11
EB 159 1 16021591 DS951 C20-500MA/AC 3/11
EB 160 9 16021609 DS951 C25-500MA/AC 3/11
EB 161 7 16021617 DS951 C32-500MA/AC 3/11
EB 162 5 16021625 DS951 C40-500MA/AC 3/11
EB 163 3 16021633 DS951 C6-1000MA/AC 3/11
EB 164 1 16021641 DS951 C10-1000MA/AC 3/11
EB 165 8 16021658 DS951 C16-1000MA/AC 3/11
EB 166 6 16021666 DS951 C20-1000MA/AC 3/11
EB 167 4 16021674 DS951 C25-1000MA/AC 3/11
EB 168 2 16021682 DS951 C32-1000MA/AC 3/11
EB 169 0 16021690 DS951 C40-1000MA/AC 3/11
EB 176 5 16021765 FP 1 2/45
EB 177 3 16021773 FP 2 2/45
EB 178 1 16021781 FP 4 2/45
EB 179 9 16021799 FP 6 2/45
EB 183 1 16021831 SFP 2/45
EB 185 6 36021856 PCD/N2 2/45
EB 186 4 36021864 PCD/N4 2/45
EB 187 2 36021872 PCD/N6 2/45
EB 188 0 36021880 PCD/N8 2/45
EB 195 5 16021955 DS971 B6-30MA/AC 3/14
EB 196 3 16021963 DS971 B10-30MA/AC 3/14
EB 197 1 16021971 DS971 B16-30MA/AC 3/14
EB 198 9 16021989 DS971 B20-30MA/AC 3/14
EB 199 7 16021997 DS971 B25-30MA/AC 3/14
EB 200 3 16022003 DS971 B32-30MA/AC 3/14
EB 201 1 16022011 DS971 B40-30MA/AC 3/14
EB 202 9 16022029 DS971 B6-100MA/AC 3/14
EB 203 7 16022037 DS971 B10-100MA/AC 3/14
EB 204 5 16022045 DS971 B16-1000MA/AC 3/14
EB 205 2 16022052 DS971 B20-100MA/AC 3/14
EB 206 0 16022060 DS971 B25-100MA/AC 3/14
EB 207 8 16022078 DS971 B32-100MA/AC 3/14
EB 208 6 16022086 DS971 B40-100MA/AC 3/14
EB 209 4 16022094 DS971 B6-300MA/AC 3/15
EB 210 2 16022102 DS971 B10-300MA/AC 3/15
EB 211 0 16022110 DS971 B16-3000MA/AC 3/15
EB 212 8 16022128 DS971 B20-300MA/AC 3/15
EB 213 6 16022136 DS971 B25-300MA/AC 3/15
EB 214 4 16022144 DS971 B32-300MA/AC 3/15
EB 215 1 16022151 DS971 B40-300MA/AC 3/15
EB 216 9 16022169 DS971 B6-500MA/AC 3/15
EB 217 7 16022177 DS971 B10-500MA/AC 3/15
EB 218 5 16022185 DS971 B16-5000MA/AC 3/15
EB 219 3 16022193 DS971 B20-500MA/AC 3/15
EB 220 1 16022201 DS971 B25-500MA/AC 3/15
EB 221 9 16022219 DS971 B32-500MA/AC 3/15
EB 222 7 16022227 DS971 B40-500MA/AC 3/15
EB 223 5 16022235 DS971 B6-1000MA/AC 3/15
EB 224 3 16022243 DS971 B10-1000MA/AC 3/15
EB 225 0 16022250 DS971 B16-10000MA/AC 3/15
EB 226 8 16022268 DS971 B20-1000MA/AC 3/15
EB 227 6 16022276 DS971 B25-1000MA/AC 3/15
EB 228 4 16022284 DS971 B32-1000MA/AC 3/15
EB 229 2 16022292 DS971 B40-1000MA/AC 3/15
EB 246 6 16022466 ISOLTESTER-C [NEW] 7/18
EB 247 4 16022474 SELVTESTER-C [NEW] 7/19
EB 248 2 16022482 QSD230/24-C [NEW] 7/19
EB 315 9 16023159 DS971 C6-30MA/AC 3/14
EB 316 7 16023167 DS971 C10-30MA/AC 3/14
EB 317 5 16023175 DS971 C16-30MA/AC 3/14
EB 318 3 16023183 DS971 C20-30MA/AC 3/14
EB 319 1 16023191 DS971 C25-30MA/AC 3/14
EB 320 9 16023209 DS971 C32-30MA/AC 3/14
EB 321 7 16023217 DS971 C40-30MA/AC 3/14
EB 322 5 16023225 DS971 C6-100MA/AC 3/14
EB 323 3 16023233 DS971 C10-100MA/AC 3/14
EB 324 1 16023241 DS971 C16-100MA/AC 3/14
EB 325 8 16023258 DS971 C20-100MA/AC 3/14
EB 326 6 16023266 DS971 C25-100MA/AC 3/14
EB 327 4 16023274 DS971 C32-100MA/AC 3/14
EB 328 2 16023282 DS971 C40-100MA/AC 3/14
EB 329 0 16023290 DS971 C6-300MA/AC 3/15
EB 330 8 16023308 DS971 C10-300MA/AC 3/15
EB 331 6 16023316 DS971 C16-300MA/AC 3/15
EB 332 4 16023324 DS971 C20-300MA/AC 3/15
EB 333 2 16023332 DS971 C25-300MA/AC 3/15
EB 334 0 16023340 DS971 C32-300MA/AC 3/15
EB 335 7 16023357 DS971 C40-300MA/AC 3/15
EB 336 5 16023365 DS971 C6-500MA/AC 3/15
EB 337 3 16023373 DS971 C10-500MA/AC 3/15
EB 338 1 16023381 DS971 C16-500MA/AC 3/15
EB 339 9 16023399 DS971 C20-500MA/AC 3/15
EB 340 7 16023407 DS971 C25-500MA/AC 3/15
EB 341 5 16023415 DS971 C32-500MA/AC 3/15
EB 342 3 16023423 DS971 C40-500MA/AC 3/15
EB 343 1 16023431 DS971 C6-1000MA/AC 3/15
EB 344 9 16023449 DS971 C10-1000MA/AC 3/15
EB 345 6 16023456 DS971 C16-1000MA/AC 3/15
EB 346 4 16023464 DS971 C20-1000MA/AC 3/15
EB 347 2 16023472 DS971 C25-1000MA/AC 3/15
EB 348 0 16023480 DS971 C32-1000MA/AC 3/15
EB 349 8 16023498 DS971 C40-1000MA/AC 3/15
EB 355 5 16023555 DS941 B6-10MA/A 3/8
EB 356 3 16023563 DS941 B10-10MA/A 3/8
EB 357 1 16023571 DS941 B16-10MA/A 3/8
EB 375 3 16023753 DS941 B6-30MA/A 3/8
EB 376 1 16023761 DS941 B10-30MA/A 3/8
EB 377 9 16023779 DS941 B16-30MA/A 3/8
EB 378 7 16023787 DS941 B20-30MA/A 3/8
EB 379 5 16023795 DS941 B25-30MA/A 3/8
EB 380 3 16023803 DS941 B32-30MA/A 3/8
EB 381 1 16023811 DS941 B40-30MA/A 3/8
EB 382 9 16023829 DS941 B6-100MA/A 3/8
EB 383 7 16023837 DS941 B10-100MA/A 3/8
EB 384 5 16023845 DS941 B16-1000MA/A 3/8
EB 385 2 16023852 DS941 B20-100MA/A 3/8
EB 386 0 16023860 DS941 B25-100MA/A 3/8
EB 387 8 16023878 DS941 B32-100MA/A 3/8
EB 388 6 16023886 DS941 B40-100MA/A 3/8
EB 389 4 16023894 DS941 B6-300MA/A 3/9
EB 390 2 16023902 DS941 B10-300MA/A 3/9
EB 391 0 16023910 DS941 B16-3000MA/A 3/9
EB 392 8 16023928 DS941 B20-300MA/A 3/9
EB 393 6 16023936 DS941 B25-300MA/A 3/9
EB 394 4 16023944 DS941 B32-300MA/A 3/9
EB 395 1 16023951 DS941 B40-300MA/A 3/9
EB 396 9 16023969 DS941 B6-500MA/A 3/9
EB 397 7 16023977 DS941 B10-500MA/A 3/9
EB 398 5 16023985 DS941 B16-5000MA/A 3/9
EB 399 3 16023993 DS941 B20-500MA/A 3/9
EB 400 9 16024009 DS941 B25-500MA/A 3/9
EB 401 7 16024017 DS941 B32-500MA/A 3/9
EB 402 5 16024025 DS941 B40-500MA/A 3/9
EB 403 3 16024033 DS941 B6-1000MA/A 3/9
EB 404 1 16024041 DS941 B10-1000MA/A 3/9
EB 405 8 16024058 DS941 B16-1000MA/A 3/9
EB 406 6 16024066 DS941 B20-1000MA/A 3/9
EB 407 4 16024074 DS941 B25-1000MA/A 3/9
EB 408 2 16024082 DS941 B32-1000MA/A 3/9
EB 409 0 16024090 DS941 B40-1000MA/A 3/9
EB 410 8 16024108 DS941 C6-30MA/A 3/8
EB 411 6 16024116 DS941 C10-30MA/A 3/8
EB 412 4 16024124 DS941 C16-30MA/A 3/8
EB 413 2 16024132 DS941 C20-30MA/A 3/8
EB 414 0 16024140 DS941 C25-30MA/A 3/8
EB 415 7 16024157 DS941 C32-30MA/A 3/8
EB 416 5 16024165 DS941 C40-30MA/A 3/8
EB 417 3 16024173 DS941 C6-100MA/A 3/8
EB 418 1 16024181 DS941 C10-100MA/A 3/8
EB 419 9 16024199 DS941 C16-100MA/A 3/8
EB 420 7 16024207 DS941 C20-100MA/A 3/8
EB 421 5 16024215 DS941 C25-100MA/A 3/8
EB 422 3 16024223 DS941 C32-100MA/A 3/8
EB 423 1 16024231 DS941 C40-100MA/A 3/8
EB 424 9 16024249 DS941 C6-300MA/A 3/9
EB 425 6 16024256 DS941 C10-300MA/A 3/9
EB 426 4 16024264 DS941 C16-300MA/A 3/9
EB 427 2 16024272 DS941 C20-300MA/A 3/9
EB 428 0 16024280 DS941 C25-300MA/A 3/9
EB 429 8 16024298 DS941 C32-300MA/A 3/9
EB 430 6 16024306 DS941 C40-300MA/A 3/9
EB 431 4 16024314 DS941 C6-500MA/A 3/9
EB 432 2 16024322 DS941 C10-500MA/A 3/9
EB 433 0 16024330 DS941 C16-500MA/A 3/9
EB 434 8 16024348 DS941 C20-500MA/A 3/9
EB 435 5 16024355 DS941 C25-500MA/A 3/9
EB 436 3 16024363 DS941 C32-500MA/A 3/9
EB 437 1 16024371 DS941 C40-500MA/A 3/9
EB 438 9 16024389 DS941 C6-1000MA/A 3/9
EB 439 7 16024397 DS941 C10-1000MA/A 3/9
EB 440 5 16024405 DS941 C16-1000MA/A 3/9
EB 441 3 16024413 DS941 C20-1000MA/A 3/9
EB 442 1 16024421 DS941 C25-1000MA/A 3/9
EB 443 9 16024439 DS941 C32-1000MA/A 3/9
EB 444 7 16024447 DS941 C40-1000MA/A 3/9
EB 475 1 16024751 DS951 B6-30MA/A 3/12
EB 476 9 16024769 DS951 B10-30MA/A 3/12
EB 477 7 16024777 DS951 B16-30MA/A 3/12
EB 478 5 16024785 DS951 B20-30MA/A 3/12
EB 479 3 16024793 DS951 B25-30MA/A 3/12
EB 480 1 16024801 DS951 B32-30MA/A 3/12
EB 481 9 16024819 DS951 B40-30MA/A 3/12
EB 482 7 16024827 DS951 B6-100MA/A 3/12
EB 483 5 16024835 DS951 B10-100MA/A 3/12
EB 484 3 16024843 DS951 B16-1000MA/A 3/12
EB 485 0 16024850 DS951 B20-100MA/A 3/12
EB 486 8 16024868 DS951 B25-100MA/A 3/12
EB 487 6 16024876 DS951 B32-100MA/A 3/12
EB 488 4 16024884 DS951 B40-100MA/A 3/12
EB 489 2 16024892 DS951 B6-300MA/A 3/13
EB 490 0 16024900 DS951 B10-300MA/A 3/13
EB 491 8 16024918 DS951 B16-3000MA/A 3/13
EB 492 6 16024926 DS951 B20-300MA/A 3/13
EB 493 4 16024934 DS951 B25-300MA/A 3/13
EB 494 2 16024942 DS951 B32-300MA/A 3/13
EB 495 9 16024959 DS951 B40-300MA/A 3/13
EB 496 7 16024967 DS951 B6-500MA/A 3/13
EB 497 5 16024975 DS951 B10-500MA/A 3/13
EB 498 3 16024983 DS951 B16-5000MA/A 3/13
EB 499 1 16024991 DS951 B20-500MA/A 3/13
EB 500 6 16025006 DS951 B25-500MA/A 3/13
EB 501 4 16025014 DS951 B32-500MA/A 3/13
EB 502 2 16025022 DS951 B40-500MA/A 3/13
EB 503 0 16025030 DS951 B6-1000MA/A 3/13
EB 504 8 16025048 DS951 B10-1000MA/A 3/13
EB 505 5 16025055 DS951 B16-10000MA/A 3/13
EB 506 3 16025063 DS951 B20-1000MA/A 3/13
EB 507 1 16025071 DS951 B25-1000MA/A 3/13
EB 508 9 16025089 DS951 B32-1000MA/A 3/13
EB 509 7 16025097 DS951 B40-1000MA/A 3/13
EB 515 4 16025154 DS951 C6-30MA/A 3/12
EB 516 2 16025162 DS951 C10-30MA/A 3/12
EB 517 0 16025170 DS951 C16-30MA/A 3/12
EB 518 8 16025188 DS951 C20-30MA/A 3/12
EB 519 6 16025196 DS951 C25-30MA/A 3/12
EB 520 4 16025204 DS951 C32-30MA/A 3/12
EB 521 2 16025212 DS951 C40-30MA/A 3/12
EB 522 0 16025220 DS951 C6-100MA/A 3/12
EB 523 8 16025238 DS951 C10-100MA/A 3/12
EB 524 6 16025246 DS951 C16-100MA/A 3/12
EB 525 3 16025253 DS951 C20-100MA/A 3/12
EB 526 1 16025261 DS951 C25-100MA/A 3/12
EB 527 9 16025279 DS951 C32-100MA/A 3/12
EB 528 7 16025287 DS951 C40-100MA/A 3/12
EB 529 5 16025295 DS951 C6-300MA/A 3/13
EB 530 3 16025303 DS951 C10-300MA/A 3/13
EB 531 1 16025311 DS951 C16-300MA/A 3/13
EB 532 9 16025329 DS951 C20-300MA/A 3/13
EB 533 7 16025337 DS951 C25-300MA/A 3/13
EB 534 5 16025345 DS951 C32-300MA/A 3/13
EB 535 2 16025352 DS951 C40-300MA/A 3/13
EB 536 0 16025360 DS951 C6-500MA/A 3/13
EB 537 8 16025378 DS951 C10-500MA/A 3/13
EB 538 6 16025386 DS951 C16-500MA/A 3/13
EB 539 4 16025394 DS951 C20-500MA/A 3/13
14/4 ABB SACE
Code list
Elc code
Elc code Order code Type Pg. Elc code Order code Type Pg. Elc code Order code Type Pg.
14
EB 540 2 16025402 DS951 C25-500MA/A 3/13
EB 541 0 16025410 DS951 C32-500MA/A 3/13
EB 542 8 16025428 DS951 C40-500MA/A 3/13
EB 543 6 16025436 DS951 C6-1000MA/A 3/13
EB 544 4 16025444 DS951 C10-1000MA/A 3/13
EB 545 1 16025451 DS951 C16-1000MA/A 3/13
EB 546 9 16025469 DS951 C20-1000MA/A 3/13
EB 547 7 16025477 DS951 C25-1000MA/A 3/13
EB 548 5 16025485 DS951 C32-1000MA/A 3/13
EB 549 3 16025493 DS951 C40-1000MA/A 3/13
EB 575 8 16025758 DS971 B6-30MA/A 3/16
EB 576 6 16025766 DS971 B10-30MA/A 3/16
EB 577 4 16025774 DS971 B16-30MA/A 3/16
EB 578 2 16025782 DS971 B20-30MA/A 3/16
EB 579 0 16025790 DS971 B25-30MA/A 3/16
EB 580 8 16025808 DS971 B32-30MA/A 3/16
EB 581 6 16025816 DS971 B40-30MA/A 3/16
EB 582 4 16025824 DS971 B6-100MA/A 3/16
EB 583 2 16025832 DS971 B10-100MA/A 3/16
EB 584 0 16025840 DS971 B16-1000MA/A 3/16
EB 585 7 16025857 DS971 B20-100MA/A 3/16
EB 586 5 16025865 DS971 B25-100MA/A 3/16
EB 587 3 16025873 DS971 B32-100MA/A 3/16
EB 588 1 16025881 DS971 B40-100MA/A 3/16
EB 589 9 16025899 DS971 B6-300MA/A 3/17
EB 590 7 16025907 DS971 B10-300MA/A 3/17
EB 591 5 16025915 DS971 B16-3000MA/A 3/17
EB 592 3 16025923 DS971 B20-300MA/A 3/17
EB 593 1 16025931 DS971 B25-300MA/A 3/17
EB 594 9 16025949 DS971 B32-300MA/A 3/17
EB 595 6 16025956 DS971 B40-300MA/A 3/17
EB 596 4 16025964 DS971 B6-500MA/A 3/17
EB 597 2 16025972 DS971 B10-500MA/A 3/17
EB 598 0 16025980 DS971 B16-5000MA/A 3/17
EB 599 8 16025998 DS971 B20-500MA/A 3/17
EB 600 4 16026004 DS971 B25-500MA/A 3/17
EB 601 2 16026012 DS971 B32-500MA/A 3/17
EB 602 0 16026020 DS971 B40-500MA/A 3/17
EB 603 8 16026038 DS971 B6-1000MA/A 3/17
EB 604 6 16026046 DS971 B10-1000MA/A 3/17
EB 605 3 16026053 DS971 B16-10000MA/A 3/17
EB 606 1 16026061 DS971 B20-1000MA/A 3/17
EB 607 9 16026079 DS971 B25-1000MA/A 3/17
EB 608 7 16026087 DS971 B32-1000MA/A 3/17
EB 609 5 16026095 DS971 B40-1000MA/A 3/17
EB 665 7 16026657 DS971 C6-30MA/A 3/16
EB 666 5 16026665 DS971 C10-30MA/A 3/16
EB 667 3 16026673 DS971 C16-30MA/A 3/16
EB 668 1 16026681 DS971 C20-30MA/A 3/16
EB 669 9 16026699 DS971 C25-30MA/A 3/16
EB 670 7 16026707 DS971 C32-30MA/A 3/16
EB 671 5 16026715 DS971 C40-30MA/A 3/16
EB 672 3 16026723 DS971 C6-100MA/A 3/16
EB 673 1 16026731 DS971 C10-100MA/A 3/16
EB 674 9 16026749 DS971 C16-100MA/A 3/16
EB 675 6 16026756 DS971 C20-100MA/A 3/16
EB 676 4 16026764 DS971 C25-100MA/A 3/16
EB 677 2 16026772 DS971 C32-100MA/A 3/16
EB 678 0 16026780 DS971 C40-100MA/A 3/16
EB 679 8 16026798 DS971 C6-300MA/A 3/17
EB 680 6 16026806 DS971 C10-300MA/A 3/17
EB 681 4 16026814 DS971 C16-300MA/A 3/17
EB 682 2 16026822 DS971 C20-300MA/A 3/17
EB 683 0 16026830 DS971 C25-300MA/A 3/17
EB 684 8 16026848 DS971 C32-300MA/A 3/17
EB 685 5 16026855 DS971 C40-300MA/A 3/17
EB 686 3 16026863 DS971 C6-500MA/A 3/17
EB 687 1 16026871 DS971 C10-500MA/A 3/17
EB 688 9 16026889 DS971 C16-500MA/A 3/17
EB 689 7 16026897 DS971 C20-500MA/A 3/17
EB 690 5 16026905 DS971 C25-500MA/A 3/17
EB 691 3 16026913 DS971 C32-500MA/A 3/17
EB 692 1 16026921 DS971 C40-500MA/A 3/17
EB 693 9 16026939 DS971 C6-1000MA/A 3/17
EB 694 7 16026947 DS971 C10-1000MA/A 3/17
EB 695 4 16026954 DS971 C16-1000MA/A 3/17
EB 696 2 16026962 DS971 C20-1000MA/A 3/17
EB 697 0 16026970 DS971 C25-1000MA/A 3/17
EB 698 8 16026988 DS971 C32-1000MA/A 3/17
EB 699 6 16026996 DS971 C40-1000MA/A 3/17
EB 876 0 36028760 F662 80 30mA 3/39
EB 877 8 36028778 F662 100 30mA 3/39
EB 878 6 36028786 F662 80 300mA 3/39
EB 879 4 36028794 F662 100 300mA 3/39
EB 880 2 36028802 F664 80 30mA 3/39
EB 881 0 36028810 F664 100 30mA 3/39
EB 883 6 36028836 F664 80 300mA 3/39
EB 884 4 36028844 F664 100 300mA 3/39
EB 886 9 36028869 F674 80 30mA 3/41
EB 887 7 36028877 F674 100 30mA 3/41
EB 889 3 36028893 F674 80 300mA 3/41
EB 890 1 36028901 F674 100 300mA 3/41
EB 892 7 36028927 F672 80 30mA 3/41
EB 893 5 36028935 F672 100 30mA 3/41
EB 947 9 36029479 F664 125 30mA 3/39
EB 950 3 36029503 F674 125 30mA 3/41
EB 966 9 36029669 F664 125 300mA 3/39
EB 998 2 36029982 F674 125 300mA 3/41
EC 068 3 36030683 PB 2/45
EE 380 0 16053800 S 244 C 6 2/23
EE 381 8 16053818 S 244 C 8 2/23
EE 382 6 16053826 S 244 C 10 2/23
EE 383 4 16053834 S 244 C 13 2/23
EE 384 2 16053842 S 244 C 16 2/23
EE 385 9 16053859 S 244 C 20 2/23
EE 386 7 16053867 S 244 C 25 2/23
EE 387 5 16053875 S 244 C 32 2/23
EE 388 3 16053883 S 244 C 40 2/23
EE 390 9 16053909 S 254 K 0,5 2/26
EE 391 7 16053917 S 254 K 1 2/26
EE 392 5 16053925 S 254 K1,6 2/26
EE 393 3 16053933 S 254 K 2 2/26
EE 394 1 16053941 S 254 K 3 2/26
EE 395 8 16053958 S 254 K 4 2/26
EE 396 6 16053966 S 254 K 6 2/26
EE 397 4 16053974 S 254 K 8 2/26
EE 398 2 16053982 S 254 K 10 2/26
EE 399 0 16053990 S 254 K 16 2/26
EE 400 6 16054006 S 254 K 20 2/26
EE 401 4 16054014 S 254 K 25 2/26
EE 402 2 16054022 S 254 K 32 2/26
EE 403 0 16054030 S 254 K 40 2/26
EE 404 8 16054048 S 254 K 50 2/26
EE 405 5 16054055 S 254 K 63 2/26
EE 410 5 16054105 S 274 K 0,5 2/29
EE 411 3 16054113 S 274 K 1 2/29
EE 412 1 16054121 S 274 K 1,6 2/29
EE 413 9 16054139 S 274 K 2 2/29
EE 414 7 16054147 S 274 K 3 2/29
EE 415 4 16054154 S 274 K 4 2/29
EE 416 2 16054162 S 274 K 6 2/29
EE 417 0 16054170 S 274 K 8 2/29
EE 418 8 16054188 S 274 K 10 2/29
EE 419 6 16054196 S 274 K 16 2/29
EE 420 4 16054204 S 274 K 20 2/29
EE 421 2 16054212 S 274 K 25 2/29
EE 422 0 16054220 S 274 K 32 2/29
EE 423 8 16054238 S 274 K 40 2/29
EE 424 6 16054246 S 274 K 50 2/29
EE 425 3 16054253 S 274 K 63 2/29
EE 430 3 16054303 S 274 D 0,5 2/29
EE 431 1 16054311 S 274 D 1 2/29
EE 432 9 16054329 S 274 D 1,6 2/29
EE 433 7 16054337 S 274 D 2 2/29
EE 434 5 16054345 S 274 D 3 2/29
EE 435 2 16054352 S 274 D 4 2/29
EE 436 0 16054360 S 274 D 6 2/29
EE 437 8 16054378 S 274 D 8 2/29
EE 438 6 16054386 S 274 D 10 2/29
EE 439 4 16054394 S 274 D 16 2/29
EE 440 2 16054402 S 274 D 20 2/29
EE 441 0 16054410 S 274 D 25 2/29
EE 442 8 16054428 S 274 D 32 2/29
EE 443 6 16054436 S 274 D 40 2/29
EE 444 4 16054444 S 274 D 50 2/29
EE 445 1 16054451 S 274 D 63 2/29
EE 540 9 16055409 S 941N B 6 2/11
EE 541 7 16055417 S 941N B 10 2/11
EE 542 5 16055425 S 941N B 16 2/11
EE 543 3 16055433 S 941N B 20 2/11
EE 544 1 16055441 S 941N B 25 2/11
EE 545 8 16055458 S 941N B 32 2/11
EE 546 6 16055466 S 941N B 40 2/11
EE 550 8 16055508 S 941N C 2 2/11
EE 551 6 16055516 S 941N C 4 2/11
EE 552 4 16055524 S 941N C 6 2/11
EE 553 2 16055532 S 941N C 10 2/11
EE 554 0 16055540 S 941N C 16 2/11
EE 555 7 16055557 S 941N C 20 2/11
EE 556 5 16055565 S 941N C 25 2/11
EE 557 3 16055573 S 941N C 32 2/11
EE 558 1 16055581 S 941N C 40 2/11
EE 560 7 16055607 S 951N B 6 2/12
EE 561 5 16055615 S 951N B 10 2/12
EE 562 3 16055623 S 951N B 16 2/12
EE 563 1 16055631 S 951N B 20 2/12
EE 564 9 16055649 S 951N B 25 2/12
EE 565 6 16055656 S 951N B 32 2/12
EE 566 4 16055664 S 951N B 40 2/12
EE 570 6 16055706 S 951N C 2 2/12
EE 571 4 16055714 S 951N C 4 2/12
EE 572 2 16055722 S 951N C 6 2/12
EE 573 0 16055730 S 951N C 10 2/12
EE 574 8 16055748 S 951N C 16 2/12
EE 575 5 16055755 S 951N C 20 2/12
EE 576 3 16055763 S 951N C 25 2/12
EE 577 1 16055771 S 951N C 32 2/12
EE 578 9 16055789 S 951N C 40 2/12
EE 580 5 16055805 S 971N B 6 2/13
EE 581 3 16055813 S 971N B 10 2/13
EE 582 1 16055821 S 971N B 16 2/13
EE 583 9 16055839 S 971N B 20 2/13
EE 584 7 16055847 S 971N B 25 2/13
EE 585 4 16055854 S 971N B 32 2/13
EE 586 2 16055862 S 971N B 40 2/13
EE 590 4 16055904 S 971N C 2 2/13
EE 591 2 16055912 S 971N C 4 2/13
EE 592 0 16055920 S 971N C 6 2/13
EE 593 8 16055938 S 971N C 10 2/13
EE 594 6 16055946 S 971N C 16 2/13
EE 595 3 16055953 S 971N C 20 2/13
EE 596 1 16055961 S 971N C 25 2/13
EE 597 9 16055979 S 971N C 32 2/13
EE 598 7 16055987 S 971N C 40 2/13
EE 610 0 16056100 S9-X 2/16
EE 611 8 16056118 S9-S 2/16
EE 612 6 16056126 S9-V24CA 2/17
EE 613 4 16056134 S9-V24CC 2/17
EE 614 2 16056142 S9-V48CA 2/17
EE 615 9 16056159 S9-V48CC 2/17
EE 616 7 16056167 S9-V230CA 2/17
EE 619 1 16056191 S9-T24 2/15
EE 620 9 16056209 S9-T130 2/15
EE 621 7 16056217 S9-T415 2/15
EF 010 2 16060102 S 241 C 6 2/22
EF 011 0 16060110 S 241 C 10 2/22
EF 012 8 16060128 S 241 C 16 2/22
EF 013 6 16060136 S 241 C 20 2/22
EF 014 4 16060144 S 241 C 25 2/22
EF 015 1 16060151 S 241 C 32 2/22
EF 016 9 16060169 S 241 C 8 2/22
EF 017 7 16060177 S 241 C 13 2/22
EF 018 5 16060185 S 241 C 40 2/22
EF 020 1 16060201 S 241 Na C 6 2/22
EF 021 9 16060219 S 241 Na C 10 2/22
EF 022 7 16060227 S 241 Na C 16 2/22
EF 023 5 16060235 S 241 Na C 20 2/22
EF 024 3 16060243 S 241 Na C 25 2/22
EF 025 0 16060250 S 241 Na C 32 2/22
EF 026 8 16060268 S 241 Na C 8 2/22
EF 027 6 16060276 S 241 Na C 13 2/22
EF 028 4 16060284 S 241 Na C 40 2/22
EF 030 0 16060300 S 242 C 6 2/22
EF 031 8 16060318 S 242 C 10 2/22
EF 032 6 16060326 S 242 C 16 2/22
EF 033 4 16060334 S 242 C 20 2/22
EF 034 2 16060342 S 242 C 25 2/22
EF 035 9 16060359 S 242 C 32 2/22
EF 036 7 16060367 S 242 C 8 2/22
EF 037 5 16060375 S 242 C 13 2/22
EF 038 3 16060383 S 242 C 40 2/22
EF 040 9 16060409 S 243 C 6 2/23
EF 041 7 16060417 S 243 C 10 2/23
EF 042 5 16060425 S 243 C 16 2/23
EF 043 3 16060433 S 243 C 20 2/23
EF 044 1 16060441 S 243 C 25 2/23
14/5
ABB SACE
Code list
Elc code
Elc code Order code Type Pg. Elc code Order code Type Pg. Elc code Order code Type Pg.
14
EF 045 8 16060458 S 243 C 32 2/23
EF 046 6 16060466 S 243 C 8 2/23
EF 047 4 16060474 S 243 C 13 2/23
EF 048 2 16060482 S 243 C 40 2/23
EF 060 7 16060607 S 251 C 6 2/24
EF 061 5 16060615 S 251 C 8 2/24
EF 062 3 16060623 S 251 C 10 2/24
EF 063 1 16060631 S 251 C 16 2/24
EF 064 9 16060649 S 251 C 20 2/24
EF 065 6 16060656 S 251 C 25 2/24
EF 066 4 16060664 S 251 C 32 2/24
EF 067 2 16060672 S 251 C 40 2/24
EF 068 0 16060680 S 251 C 50 2/24
EF 069 8 16060698 S 251 C 63 2/24
EF 070 6 16060706 S 251 Na C 6 2/25
EF 071 4 16060714 S 251 Na C 8 2/25
EF 072 2 16060722 S 251 Na C 10 2/25
EF 073 0 16060730 S 251 Na C 16 2/25
EF 074 8 16060748 S 251 Na C 20 2/25
EF 075 5 16060755 S 251 Na C 25 2/25
EF 076 3 16060763 S 251 Na C 32 2/25
EF 077 1 16060771 S 251 Na C 40 2/25
EF 078 9 16060789 S 251 Na C 50 2/25
EF 079 7 16060797 S 251 Na C 63 2/25
EF 080 5 16060805 S 252 C 6 2/26
EF 081 3 16060813 S 252 C 8 2/26
EF 082 1 16060821 S 252 C 10 2/26
EF 083 9 16060839 S 252 C 16 2/26
EF 084 7 16060847 S 252 C 20 2/26
EF 085 4 16060854 S 252 C 25 2/26
EF 086 2 16060862 S 252 C 32 2/26
EF 087 0 16060870 S 252 C 40 2/26
EF 088 8 16060888 S 252 C 50 2/26
EF 089 6 16060896 S 252 C 63 2/26
EF 090 4 16060904 S 253 C 6 2/26
EF 091 2 16060912 S 253 C 8 2/26
EF 092 0 16060920 S 253 C 10 2/26
EF 093 8 16060938 S 253 C 16 2/26
EF 094 6 16060946 S 253 C 20 2/26
EF 095 3 16060953 S 253 C 25 2/26
EF 096 1 16060961 S 253 C 32 2/26
EF 097 9 16060979 S 253 C 40 2/26
EF 098 7 16060987 S 253 C 50 2/26
EF 099 5 16060995 S 253 C 63 2/26
EF 110 0 16061100 S 251 B 6 2/24
EF 111 8 16061118 S 251 B 8 2/24
EF 112 6 16061126 S 251 B 10 2/24
EF 113 4 16061134 S 251 B 16 2/24
EF 114 2 16061142 S 251 B 20 2/24
EF 115 9 16061159 S 251 B 25 2/24
EF 116 7 16061167 S 251 B 32 2/24
EF 117 5 16061175 S 251 B 40 2/24
EF 118 3 16061183 S 251 B 50 2/24
EF 119 1 16061191 S 251 B 63 2/24
EF 120 9 16061209 S 251 Na B 6 2/25
EF 121 7 16061217 S 251 Na B 8 2/25
EF 122 5 16061225 S 251 Na B 10 2/25
EF 123 3 16061233 S 251 Na B 16 2/25
EF 124 1 16061241 S 251 Na B 20 2/25
EF 125 8 16061258 S 251 Na B 25 2/25
EF 126 6 16061266 S 251 Na B 32 2/25
EF 127 4 16061274 S 251 Na B 40 2/25
EF 128 2 16061282 S 251 Na B 50 2/25
EF 129 0 16061290 S 251 Na B 63 2/25
EF 130 8 16061308 S 252 B 6 2/26
EF 131 6 16061316 S 252 B 8 2/26
EF 132 4 16061324 S 252 B 10 2/26
EF 133 2 16061332 S 252 B 16 2/26
EF 134 0 16061340 S 252 B 20 2/26
EF 135 7 16061357 S 252 B 25 2/26
EF 136 5 16061365 S 252 B 32 2/26
EF 137 3 16061373 S 252 B 40 2/26
EF 138 1 16061381 S 252 B 50 2/26
EF 139 9 16061399 S 252 B 63 2/26
EF 140 7 16061407 S 253 B 6 2/26
EF 141 5 16061415 S 253 B 8 2/26
EF 142 3 16061423 S 253 B 10 2/26
EF 143 1 16061431 S 253 B 16 2/26
EF 144 9 16061449 S 253 B 20 2/26
EF 145 6 16061456 S 253 B 25 2/26
EF 146 4 16061464 S 253 B 32 2/26
EF 147 2 16061472 S 253 B 40 2/26
EF 148 0 16061480 S 253 B 50 2/26
EF 149 8 16061498 S 253 B 63 2/26
EF 160 5 16061605 S 251 K 0,5 2/24
EF 161 3 16061613 S 251 K 1 2/24
EF 162 1 16061621 S 251 K 1,6 2/24
EF 163 9 16061639 S 251 K 2 2/24
EF 164 7 16061647 S 251 K 3 2/24
EF 165 4 16061654 S 251 K 4 2/24
EF 166 2 16061662 S 251 K 6 2/24
EF 167 0 16061670 S 251 K 8 2/24
EF 168 8 16061688 S 251 K 10 2/24
EF 169 6 16061696 S 251 K 16 2/24
EF 170 4 16061704 S 251 K 20 2/24
EF 171 2 16061712 S 251 K 25 2/24
EF 172 0 16061720 S 251 K 32 2/24
EF 173 8 16061738 S 251 K 40 2/24
EF 174 6 16061746 S 251 K 50 2/24
EF 175 3 16061753 S 251 K 63 2/24
EF 176 1 16061761 S 251 B 13 2/24
EF 177 9 16061779 S 251 C 13 2/24
EF 180 3 16061803 S 251 Na K 0,5 2/25
EF 181 1 16061811 S 251 Na K 1 2/25
EF 182 9 16061829 S 251 Na K 1,6 2/25
EF 183 7 16061837 S 251 Na K 2 2/25
EF 184 5 16061845 S 251 Na K 3 2/25
EF 185 2 16061852 S 251 Na K 4 2/25
EF 186 0 16061860 S 251 Na K 6 2/25
EF 187 8 16061878 S 251 Na K 8 2/25
EF 188 6 16061886 S 251 Na K 10 2/25
EF 189 4 16061894 S 251 Na K 16 2/25
EF 190 2 16061902 S 251 Na K 20 2/25
EF 191 0 16061910 S 251 Na K 25 2/25
EF 192 8 16061928 S 251 Na K 32 2/25
EF 193 6 16061936 S 251 Na K 40 2/25
EF 194 4 16061944 S 251 Na K 50 2/25
EF 195 1 16061951 S 251 Na K 63 2/25
EF 196 9 16061969 S 251 Na B 13 2/25
EF 197 7 16061977 S 251 Na C 13 2/25
EF 200 9 16062009 S 252 K 0,5 2/26
EF 201 7 16062017 S 252 K 1 2/26
EF 202 5 16062025 S 252 K 1,6 2/26
EF 203 3 16062033 S 252 K 2 2/26
EF 204 1 16062041 S 252 K 3 2/26
EF 205 8 16062058 S 252 K 4 2/26
EF 206 6 16062066 S 252 K 6 2/26
EF 207 4 16062074 S 252 K 8 2/26
EF 208 2 16062082 S 252 K 10 2/26
EF 209 0 16062090 S 252 K 16 2/26
EF 210 8 16062108 S 252 K 20 2/26
EF 211 6 16062116 S 252 K 25 2/26
EF 212 4 16062124 S 252 K 32 2/26
EF 213 2 16062132 S 252 K 40 2/26
EF 214 0 16062140 S 252 K 50 2/26
EF 215 7 16062157 S 252 K 63 2/26
EF 216 5 16062165 S 252 B 13 2/26
EF 217 3 16062173 S 252 C 13 2/26
EF 220 7 16062207 S 253 K 0,5 2/26
EF 221 5 16062215 S 253 K 1 2/26
EF 222 3 16062223 S 253 K 1,6 2/26
EF 223 1 16062231 S 253 K 2 2/26
EF 224 9 16062249 S 253 K 3 2/26
EF 225 6 16062256 S 253 K 4 2/26
EF 226 4 16062264 S 253 K 6 2/26
EF 227 2 16062272 S 253 K 8 2/26
EF 228 0 16062280 S 253 K 10 2/26
EF 229 8 16062298 S 253 K 16 2/26
EF 230 6 16062306 S 253 K 20 2/26
EF 231 4 16062314 S 253 K 25 2/26
EF 232 2 16062322 S 253 K 32 2/26
EF 233 0 16062330 S 253 K 40 2/26
EF 234 8 16062348 S 253 K 50 2/26
EF 235 5 16062355 S 253 K 63 2/26
EF 236 3 16062363 S 253 B 13 2/26
EF 237 1 16062371 S 253 C 13 2/26
EF 260 3 16062603 S 271 C 6 2/27
EF 261 1 16062611 S 271 C 8 2/27
EF 262 9 16062629 S 271 C 10 2/27
EF 263 7 16062637 S 271 C 16 2/27
EF 264 5 16062645 S 271 C 20 2/27
EF 265 2 16062652 S 271 C 25 2/27
EF 266 0 16062660 S 271 C 32 2/27
EF 267 8 16062678 S 271 C 40 2/27
EF 268 6 16062686 S 271 C 50 2/27
EF 269 4 16062694 S 271 C 63 2/27
EF 270 2 16062702 S 271 Na C 6 2/28
EF 271 0 16062710 S 271 Na C 8 2/28
EF 272 8 16062728 S 271 Na C 10 2/28
EF 273 6 16062736 S 271 Na C 16 2/28
EF 274 4 16062744 S 271 Na C 20 2/28
EF 275 1 16062751 S 271 Na C 25 2/28
EF 276 9 16062769 S 271 Na C 32 2/28
EF 277 7 16062777 S 271 Na C 40 2/28
EF 278 5 16062785 S 271 Na C 50 2/28
EF 279 3 16062793 S 271 Na C 63 2/28
EF 280 1 16062801 S 272 C 6 2/28
EF 281 9 16062819 S 272 C 8 2/28
EF 282 7 16062827 S 272 C 10 2/28
EF 283 5 16062835 S 272 C 16 2/28
EF 284 3 16062843 S 272 C 20 2/28
EF 285 0 16062850 S 272 C 25 2/28
EF 286 8 16062868 S 272 C 32 2/28
EF 287 6 16062876 S 272 C 40 2/28
EF 288 4 16062884 S 272 C 50 2/28
EF 289 2 16062892 S 272 C 63 2/28
EF 290 0 16062900 S 273 C 6 2/29
EF 291 8 16062918 S 273 C 8 2/29
EF 292 6 16062926 S 273 C 10 2/29
EF 293 4 16062934 S 273 C 16 2/29
EF 294 2 16062942 S 273 C 20 2/29
EF 295 9 16062959 S 273 C 25 2/29
EF 296 7 16062967 S 273 C 32 2/29
EF 297 5 16062975 S 273 C 40 2/29
EF 298 3 16062983 S 273 C 50 2/29
EF 299 1 16062991 S 273 C 63 2/29
EF 310 6 16063106 S 271 B 6 2/27
EF 311 4 16063114 S 271 B 8 2/27
EF 312 2 16063122 S 271 B 10 2/27
EF 313 0 16063130 S 271 B 16 2/27
EF 314 8 16063148 S 271 B 20 2/27
EF 315 5 16063155 S 271 B 25 2/27
EF 316 3 16063163 S 271 B 32 2/27
EF 317 1 16063171 S 271 B 40 2/27
EF 318 9 16063189 S 271 B 50 2/27
EF 319 7 16063197 S 271 B 63 2/27
EF 320 5 16063205 S 271 Na B 6 2/28
EF 321 3 16063213 S 271 Na B 8 2/28
EF 322 1 16063221 S 271 Na B 10 2/28
EF 323 9 16063239 S 271 Na B 16 2/28
EF 324 7 16063247 S 271 Na B 20 2/28
EF 325 4 16063254 S 271 Na B 25 2/28
EF 326 2 16063262 S 271 Na B 32 2/28
EF 327 0 16063270 S 271 Na B 40 2/28
EF 328 8 16063288 S 271 Na B 50 2/28
EF 329 6 16063296 S 271 Na B 63 2/28
EF 330 4 16063304 S 272 B 6 2/28
EF 331 2 16063312 S 272 B 8 2/28
EF 332 0 16063320 S 272 B 10 2/28
EF 333 8 16063338 S 272 B 16 2/28
EF 334 6 16063346 S 272 B 20 2/28
EF 335 3 16063353 S 272 B 25 2/28
EF 336 1 16063361 S 272 B 32 2/28
EF 337 9 16063379 S 272 B 40 2/28
EF 338 7 16063387 S 272 B 50 2/28
EF 339 5 16063395 S 272 B 63 2/28
EF 340 3 16063403 S 273 B 6 2/29
EF 341 1 16063411 S 273 B 8 2/29
EF 342 9 16063429 S 273 B 10 2/29
EF 343 7 16063437 S 273 B 16 2/29
EF 344 5 16063445 S 273 B 20 2/29
EF 345 2 16063452 S 273 B 25 2/29
EF 346 0 16063460 S 273 B 32 2/29
EF 347 8 16063478 S 273 B 40 2/29
EF 348 6 16063486 S 273 B 50 2/29
EF 349 4 16063494 S 273 B 63 2/29
EF 360 1 16063601 S 271 K 0,5 2/27
EF 361 9 16063619 S 271 K 1 2/27
EF 362 7 16063627 S 271 K 1,6 2/27
EF 363 5 16063635 S 271 K 2 2/27
EF 364 3 16063643 S 271 K 3 2/27
EF 365 0 16063650 S 271 K 4 2/27
EF 366 8 16063668 S 271 K 6 2/27
EF 367 6 16063676 S 271 K 8 2/27
EF 368 4 16063684 S 271 K 10 2/27
EF 369 2 16063692 S 271 K 16 2/27
EF 370 0 16063700 S 271 K 20 2/27
EF 371 8 16063718 S 271 K 25 2/27
EF 372 6 16063726 S 271 K 32 2/27
EF 373 4 16063734 S 271 K 40 2/27
EF 374 2 16063742 S 271 K 50 2/27
EF 375 9 16063759 S 271 K 63 2/27
14/6 ABB SACE
Code list
Elc code
Elc code Order code Type Pg. Elc code Order code Type Pg. Elc code Order code Type Pg.
14
EF 380 9 16063809 S 271 Na K 0,5 2/28
EF 381 7 16063817 S 271 Na K 1 2/28
EF 382 5 16063825 S 271 Na K 1,6 2/28
EF 383 3 16063833 S 271 Na K 2 2/28
EF 384 1 16063841 S 271 Na K 3 2/28
EF 385 8 16063858 S 271 Na K 4 2/28
EF 386 6 16063866 S 271 Na K 6 2/28
EF 387 4 16063874 S 271 Na K 8 2/28
EF 388 2 16063882 S 271 Na K 10 2/28
EF 389 0 16063890 S 271 Na K 16 2/28
EF 390 8 16063908 S 271 Na K 20 2/28
EF 391 6 16063916 S 271 Na K 25 2/28
EF 392 4 16063924 S 271 Na K 32 2/28
EF 393 2 16063932 S 271 Na K 40 2/28
EF 394 0 16063940 S 271 Na K 50 2/28
EF 395 7 16063957 S 271 Na K 63 2/28
EF 400 5 16064005 S 272 K 0,5 2/28
EF 401 3 16064013 S 272 K 1 2/28
EF 402 1 16064021 S 272 K 1,6 2/28
EF 403 9 16064039 S 272 K 2 2/28
EF 404 7 16064047 S 272 K 3 2/28
EF 405 4 16064054 S 272 K 4 2/28
EF 406 2 16064062 S 272 K 6 2/28
EF 407 0 16064070 S 272 K 8 2/28
EF 408 8 16064088 S 272 K 10 2/28
EF 409 6 16064096 S 272 K 16 2/28
EF 410 4 16064104 S 272 K 20 2/28
EF 411 2 16064112 S 272 K 25 2/28
EF 412 0 16064120 S 272 K 32 2/28
EF 413 8 16064138 S 272 K 40 2/28
EF 414 6 16064146 S 272 K 50 2/28
EF 415 3 16064153 S 272 K 63 2/28
EF 420 3 16064203 S 273 K 0,5 2/29
EF 421 1 16064211 S 273 K 1 2/29
EF 422 9 16064229 S 273 K 1,6 2/29
EF 423 7 16064237 S 273 K 2 2/29
EF 424 5 16064245 S 273 K 3 2/29
EF 425 2 16064252 S 273 K 4 2/29
EF 426 0 16064260 S 273 K 6 2/29
EF 427 8 16064278 S 273 K 8 2/29
EF 428 6 16064286 S 273 K 10 2/29
EF 429 4 16064294 S 273 K 16 2/29
EF 430 2 16064302 S 273 K 20 2/29
EF 431 0 16064310 S 273 K 25 2/29
EF 432 8 16064328 S 273 K 32 2/29
EF 433 6 16064336 S 273 K 40 2/29
EF 434 4 16064344 S 273 K 50 2/29
EF 435 1 16064351 S 273 K 63 2/29
EF 536 6 16065366 S 251 C 0,5 2/24
EF 537 4 16065374 S 251 C 1 2/24
EF 538 2 16065382 S 251 C 1,6 2/24
EF 539 0 16065390 S 251 C 2 2/24
EF 540 8 16065408 S 251 C 3 2/24
EF 541 6 16065416 S 251 C 4 2/24
EF 542 4 16065424 S 251 Na C 0,5 2/25
EF 543 2 16065432 S 251 Na C 1 2/25
EF 544 0 16065440 S 251 Na C 1,6 2/25
EF 545 7 16065457 S 251 Na C 2 2/25
EF 546 5 16065465 S 251 Na C 3 2/25
EF 547 3 16065473 S 251 Na C 4 2/25
EF 548 1 16065481 S 252 C 0,5 2/26
EF 549 9 16065499 S 252 C 1 2/26
EF 550 7 16065507 S 252 C 1,6 2/26
EF 551 5 16065515 S 252 C 2 2/26
EF 552 3 16065523 S 252 C 3 2/26
EF 553 1 16065531 S 252 C 4 2/26
EF 554 9 16065549 S 253 C 0,5 2/26
EF 555 6 16065556 S 253 C 1 2/26
EF 556 4 16065564 S 253 C 1,6 2/26
EF 557 2 16065572 S 253 C 2 2/26
EF 558 0 16065580 S 253 C 3 2/26
EF 559 8 16065598 S 253 C 4 2/26
EF 566 3 16065663 S 271 C 0,5 2/27
EF 567 1 16065671 S 271 C 1 2/27
EF 568 9 16065689 S 271 C 1,6 2/27
EF 569 7 16065697 S 271 C 2 2/27
EF 570 5 16065705 S 271 C 3 2/27
EF 571 3 16065713 S 271 C 4 2/27
EF 572 1 16065721 S 271 Na C 0,5 2/28
EF 573 9 16065739 S 271 Na C 1 2/28
EF 574 7 16065747 S 271 Na C 1,6 2/28
EF 575 4 16065754 S 271 Na C 2 2/28
EF 576 2 16065762 S 271 Na C 3 2/28
EF 577 0 16065770 S 271 Na C 4 2/28
EF 578 8 16065788 S 272 C 0,5 2/28
EF 579 6 16065796 S 272 C 1 2/28
EF 580 4 16065804 S 272 C 1,6 2/28
EF 581 2 16065812 S 272 C 2 2/28
EF 582 0 16065820 S 272 C 3 2/28
EF 583 8 16065838 S 272 C 4 2/28
EF 584 6 16065846 S 273 C 0,5 2/29
EF 585 3 16065853 S 273 C 1 2/29
EF 586 1 16065861 S 273 C 1,6 2/29
EF 587 9 16065879 S 273 C 2 2/29
EF 588 7 16065887 S 273 C 3 2/29
EF 589 5 16065895 S 273 C 4 2/29
EF 600 0 16066000 S 271 D 0,5 2/27
EF 601 8 16066018 S 271 D 1 2/27
EF 602 6 16066026 S 271 D 1,6 2/27
EF 603 4 16066034 S 271 D 2 2/27
EF 604 2 16066042 S 271 D 3 2/27
EF 605 9 16066059 S 271 D 4 2/27
EF 606 7 16066067 S 271 D 6 2/27
EF 607 5 16066075 S 271 D 8 2/27
EF 608 3 16066083 S 271 D 10 2/27
EF 609 1 16066091 S 271 D 16 2/27
EF 610 9 16066109 S 271 D 20 2/27
EF 611 7 16066117 S 271 D 25 2/27
EF 612 5 16066125 S 271 D 32 2/27
EF 613 3 16066133 S 271 D 40 2/27
EF 614 1 16066141 S 271 D 50 2/27
EF 615 8 16066158 S 271 D 63 2/27
EF 616 6 16066166 S 271 Na D 0,5 2/28
EF 617 4 16066174 S 271 Na D 1 2/28
EF 618 2 16066182 S 271 Na D 1,6 2/28
EF 619 0 16066190 S 271 Na D 2 2/28
EF 620 8 16066208 S 271 Na D 3 2/28
EF 621 6 16066216 S 271 Na D 4 2/28
EF 622 4 16066224 S 271 Na D 6 2/28
EF 623 2 16066232 S 271 Na D 8 2/28
EF 624 0 16066240 S 271 Na D 10 2/28
EF 625 7 16066257 S 271 Na D 16 2/28
EF 626 5 16066265 S 271 Na D 20 2/28
EF 627 3 16066273 S 271 Na D 25 2/28
EF 628 1 16066281 S 271 Na D 32 2/28
EF 629 9 16066299 S 271 Na D 40 2/28
EF 630 7 16066307 S 271 Na D 50 2/28
EF 631 5 16066315 S 271 Na D 63 2/28
EF 632 3 16066323 S 272 D 0,5 2/28
EF 633 1 16066331 S 272 D 1 2/28
EF 634 9 16066349 S 272 D 1,6 2/28
EF 635 6 16066356 S 272 D 2 2/28
EF 636 4 16066364 S 272 D 3 2/28
EF 637 2 16066372 S 272 D 4 2/28
EF 638 0 16066380 S 272 D 6 2/28
EF 639 8 16066398 S 272 D 8 2/28
EF 640 6 16066406 S 272 D 10 2/28
EF 641 4 16066414 S 272 D 16 2/28
EF 642 2 16066422 S 272 D 20 2/28
EF 643 0 16066430 S 272 D 25 2/28
EF 644 8 16066448 S 272 D 32 2/28
EF 645 5 16066455 S 272 D 40 2/28
EF 646 3 16066463 S 272 D 50 2/28
EF 647 1 16066471 S 272 D 63 2/28
EF 648 9 16066489 S 273 D 0,5 2/29
EF 649 7 16066497 S 273 D 1 2/29
EF 650 5 16066505 S 273 D 1,6 2/29
EF 651 3 16066513 S 273 D 2 2/29
EF 652 1 16066521 S 273 D 3 2/29
EF 653 9 16066539 S 273 D 4 2/29
EF 654 7 16066547 S 273 D 6 2/29
EF 655 4 16066554 S 273 D 8 2/29
EF 656 2 16066562 S 273 D 10 2/29
EF 657 0 16066570 S 273 D 16 2/29
EF 658 8 16066588 S 273 D 20 2/29
EF 659 6 16066596 S 273 D 25 2/29
EF 660 4 16066604 S 273 D 32 2/29
EF 661 2 16066612 S 273 D 40 2/29
EF 662 0 16066620 S 273 D 50 2/29
EF 663 8 16066638 S 273 D 63 2/29
EF 690 1 16066901 S 281 UC B 6 2/34
EF 691 9 16066919 S 281 UC B 8 2/34
EF 692 7 16066927 S 281 UC B 10 2/34
EF 693 5 16066935 S 281 UC B 16 2/34
EF 694 3 16066943 S 281 UC B 20 2/34
EF 695 0 16066950 S 281 UC B 25 2/34
EF 696 8 16066968 S 281 UC B 32 2/34
EF 697 6 16066976 S 281 UC B 40 2/34
EF 698 4 16066984 S 281 UC B 50 2/34
EF 699 2 16066992 S 281 UC B 63 2/34
EF 700 8 16067008 S 274 C0,5 2/29
EF 701 6 16067016 S 274 C 1 2/29
EF 702 4 16067024 S 274 C1,6 2/29
EF 703 2 16067032 S 274 C 2 2/29
EF 704 0 16067040 S 274 C 3 2/29
EF 706 5 16067065 S 274 C 4 2/29
EF 707 3 16067073 S 274 C 6 2/29
EF 708 1 16067081 S 274 C 8 2/29
EF 709 9 16067099 S 274 C 10 2/29
EF 710 7 16067107 S 282 UC B 6 2/35
EF 711 5 16067115 S 282 UC B 8 2/35
EF 712 3 16067123 S 282 UC B 10 2/35
EF 713 1 16067131 S 282 UC B 16 2/35
EF 714 9 16067149 S 282 UC B 20 2/35
EF 715 6 16067156 S 282 UC B 25 2/35
EF 716 4 16067164 S 282 UC B 32 2/35
EF 717 2 16067172 S 282 UC B 40 2/35
EF 718 0 16067180 S 282 UC B 50 2/35
EF 719 8 16067198 S 282 UC B 63 2/35
EF 720 6 16067206 S 281 UC C 0,5 2/34
EF 721 4 16067214 S 281 UC C 1 2/34
EF 722 2 16067222 S 281 UC C 1,6 2/34
EF 723 0 16067230 S 281 UC C 2 2/34
EF 724 8 16067248 S 281 UC C 3 2/34
EF 725 5 16067255 S 281 UC C 4 2/34
EF 726 3 16067263 S 281 UC C 6 2/34
EF 727 1 16067271 S 281 UC C 8 2/34
EF 728 9 16067289 S 281 UC C 10 2/34
EF 729 7 16067297 S 281 UC C 16 2/34
EF 730 5 16067305 S 281 UC C 20 2/34
EF 731 3 16067313 S 281 UC C 25 2/34
EF 732 1 16067321 S 281 UC C 32 2/34
EF 733 9 16067339 S 281 UC C 40 2/34
EF 734 7 16067347 S 281 UC C 50 2/34
EF 735 4 16067354 S 281 UC C 63 2/34
EF 736 2 16067362 S 282 UC C 0,5 2/35
EF 737 0 16067370 S 282 UC C 1 2/35
EF 738 8 16067388 S 282 UC C 1,6 2/35
EF 739 6 16067396 S 282 UC C 2 2/35
EF 740 4 16067404 S 282 UC C 3 2/35
EF 741 2 16067412 S 282 UC C 4 2/35
EF 742 0 16067420 S 282 UC C 6 2/35
EF 743 8 16067438 S 282 UC C 8 2/35
EF 744 6 16067446 S 282 UC C 10 2/35
EF 745 3 16067453 S 282 UC C 16 2/35
EF 746 1 16067461 S 282 UC C 20 2/35
EF 747 9 16067479 S 282 UC C 25 2/35
EF 748 7 16067487 S 282 UC C 32 2/35
EF 749 5 16067495 S 282 UC C 40 2/35
EF 750 3 16067503 S 282 UC C 50 2/35
EF 751 1 16067511 S 282 UC C 63 2/35
EF 752 9 16067529 S 281 UC K 0,5 2/34
EF 753 7 16067537 S 281 UC K 1 2/34
EF 754 5 16067545 S 281 UC K 1,6 2/34
EF 755 2 16067552 S 281 UC K 2 2/34
EF 756 0 16067560 S 281 UC K 3 2/34
EF 757 8 16067578 S 281 UC K 4 2/34
EF 758 6 16067586 S 281 UC K 6 2/34
EF 759 4 16067594 S 281 UC K 8 2/34
EF 760 2 16067602 S 281 UC K 10 2/34
EF 761 0 16067610 S 281 UC K 16 2/34
EF 762 8 16067628 S 281 UC K 20 2/34
EF 763 6 16067636 S 281 UC K 25 2/34
EF 764 4 16067644 S 281 UC K 32 2/34
EF 765 1 16067651 S 281 UC K 40 2/34
EF 766 9 16067669 S 281 UC K 50 2/34
EF 767 7 16067677 S 281 UC K 63 2/34
EF 768 5 16067685 S 282 UC K 0,5 2/35
EF 769 3 16067693 S 282 UC K 1 2/35
EF 770 1 16067701 S 282 UC K 1,6 2/35
EF 771 9 16067719 S 282 UC K 2 2/35
EF 772 7 16067727 S 282 UC K 3 2/35
EF 773 5 16067735 S 282 UC K 4 2/35
EF 774 3 16067743 S 282 UC K 6 2/35
EF 775 0 16067750 S 282 UC K 8 2/35
EF 776 8 16067768 S 282 UC K 10 2/35
EF 777 6 16067776 S 282 UC K 16 2/35
EF 778 4 16067784 S 282 UC K 20 2/35
EF 779 2 16067792 S 282 UC K 25 2/35
EF 780 0 16067800 S 282 UC K 32 2/35
EF 781 8 16067818 S 282 UC K 40 2/35
EF 782 6 16067826 S 282 UC K 50 2/35
14/7
ABB SACE
Code list
Elc code
Elc code Order code Type Pg. Elc code Order code Type Pg. Elc code Order code Type Pg.
14
EF 783 4 16067834 S 282 UC K 63 2/35
EF 784 2 16067842 S 281 UC Z 0,5 2/34
EF 785 9 16067859 S 281 UC Z 1 2/34
EF 786 7 16067867 S 281 UC Z 1,6 2/34
EF 787 5 16067875 S 281 UC Z 2 2/34
EF 788 3 16067883 S 281 UC Z 3 2/34
EF 789 1 16067891 S 281 UC Z 4 2/34
EF 790 9 16067909 S 281 UC Z 6 2/34
EF 791 7 16067917 S 281 UC Z 8 2/34
EF 792 5 16067925 S 281 UC Z 10 2/34
EF 793 3 16067933 S 281 UC Z 16 2/34
EF 794 1 16067941 S 281 UC Z 20 2/34
EF 795 8 16067958 S 281 UC Z 25 2/34
EF 796 6 16067966 S 281 UC Z 32 2/34
EF 797 4 16067974 S 281 UC Z 40 2/34
EF 798 2 16067982 S 281 UC Z 50 2/34
EF 799 0 16067990 S 281 UC Z 63 2/34
EF 800 6 16068006 S 274 C 13 2/29
EF 801 4 16068014 S 274 C 16 2/29
EF 804 8 16068048 S 274 C 20 2/29
EF 805 5 16068055 S 274 C 25 2/29
EF 806 3 16068063 S 274 C 32 2/29
EF 807 1 16068071 S 274 C 40 2/29
EF 808 9 16068089 S 274 C 50 2/29
EF 809 7 16068097 S 274 C 63 2/29
EF 810 5 16068105 S 282 UC Z 0,5 2/35
EF 811 3 16068113 S 282 UC Z 1 2/35
EF 812 1 16068121 S 282 UC Z 1,6 2/35
EF 813 9 16068139 S 282 UC Z 2 2/35
EF 814 7 16068147 S 282 UC Z 3 2/35
EF 815 4 16068154 S 282 UC Z 4 2/35
EF 816 2 16068162 S 282 UC Z 6 2/35
EF 817 0 16068170 S 282 UC Z 8 2/35
EF 818 8 16068188 S 282 UC Z 10 2/35
EF 819 6 16068196 S 282 UC Z 16 2/35
EF 820 4 16068204 S 282 UC Z 20 2/35
EF 821 2 16068212 S 282 UC Z 25 2/35
EF 822 0 16068220 S 282 UC Z 32 2/35
EF 823 8 16068238 S 282 UC Z 40 2/35
EF 824 6 16068246 S 282 UC Z 50 2/35
EF 825 3 16068253 S 282 UC Z 63 2/35
EF 830 3 16068303 S 271 B 13 2/27
EF 831 1 16068311 S 271 Na B 13 2/28
EF 832 9 16068329 S 272 B 13 2/28
EF 833 7 16068337 S 273 B 13 2/29
EF 835 2 16068352 S 271 C 13 2/27
EF 836 0 16068360 S 271 Na C 13 2/28
EF 837 8 16068378 S 272 C 13 2/28
EF 838 6 16068386 S 273 C 13 2/29
EF 840 2 16068402 S 254 C0,5 2/26
EF 841 0 16068410 S 254 C 1 2/26
EF 842 8 16068428 S 254 C1,6 2/26
EF 843 6 16068436 S 254 C 2 2/26
EF 844 4 16068444 S 254 C 3 2/26
EF 845 1 16068451 S 254 C 4 2/26
EF 846 9 16068469 S 254 C 6 2/26
EF 847 7 16068477 S 254 C 8 2/26
EF 848 5 16068485 S 254 C 10 2/26
EF 849 3 16068493 S 254 C 13 2/26
EF 850 1 16068501 S 254 C 16 2/26
EF 851 9 16068519 S 254 C 20 2/26
EF 852 7 16068527 S 254 C 25 2/26
EF 853 5 16068535 S 254 C 32 2/26
EF 854 3 16068543 S 254 C 40 2/26
EF 855 0 16068550 S 254 C 50 2/26
EF 856 8 16068568 S 254 C 63 2/26
EF 883 2 16068832 S 254 B 6 2/26
EF 884 0 16068840 S 254 B 8 2/26
EF 885 7 16068857 S 254 B 10 2/26
EF 886 5 16068865 S 254 B 13 2/26
EF 887 3 16068873 S 254 B 16 2/26
EF 888 1 16068881 S 254 B 20 2/26
EF 889 9 16068899 S 254 B 25 2/26
EF 890 7 16068907 S 254 B 32 2/26
EF 891 5 16068915 S 254 B 40 2/26
EF 892 3 16068923 S 254 B 50 2/26
EF 893 1 16068931 S 254 B 63 2/26
EF 901 2 16069012 E 221-10 5/6
EF 902 0 16069020 E 223-10 5/7
EF 903 8 16069038 E 221-20 5/6
EF 904 6 16069046 E 223-20 5/7
EF 905 3 16069053 E 221-30 5/6
EF 906 1 16069061 E 223-30 5/7
EF 907 9 16069079 E 221-40 5/6
EF 908 7 16069087 E 223-40 5/7
EF 909 5 16069095 E 221-10X 5/6
EF 910 3 16069103 E 221-20X 5/6
EF 911 1 16069111 E 221-6 5/6
EF 912 9 16069129 E 221-6/2 5/6
EF 913 7 16069137 E 221-4 5/6
EF 914 5 16069145 E 221-4/2 5/6
EF 915 2 16069152 E 10/230 5/9
EF 916 0 16069160 E 222-10X 5/7
EF 917 8 16069178 E 222-20X 5/7
EF 918 6 16069186 E 222-6 5/7
EF 919 4 16069194 E 222-4 5/7
EF 920 2 16069202 E 225-11B 5/8
EF 921 0 16069210 E 227-11C 5/8
EF 922 8 16069228 E 227-11D 5/8
EF 923 6 16069236 E 229-C 5/8
EF 924 4 16069244 E 220-C 5/9
EF 925 1 16069251 E 220-D 5/9
EF 926 9 16069269 E 220-B 5/9
EF 927 7 16069277 E 220-C3 5/9
EF 928 5 16069285 E 220-D3 5/9
EF 929 3 16069293 E 220-B3 5/9
EF 930 1 16069301 E 228-WM 6/12
EF 931 9 36069319 E 241/16 5/2
EF 932 7 36069327 E 242/16 5/2
EF 933 5 36069335 E 243/16 5/3
EF 934 3 36069343 E 244/16 5/3
EF 935 0 36069350 E 241/32 5/2
EF 936 8 36069368 E 242/32 5/2
EF 937 6 36069376 E 243/32 5/3
EF 938 4 36069384 E 244/32 5/3
EF 939 2 36069392 E 241/45 5/2
EF 940 0 36069400 E 242/45 5/2
EF 941 8 36069418 E 243/45 5/3
EF 942 6 36069426 E 244/45 5/3
EF 943 4 36069434 E 271/80 5/2
EF 944 2 36069442 E 271/100 5/2
EF 945 9 16069459 S 274 B 6 2/29
EF 946 7 16069467 S 274 B 8 2/29
EF 947 5 16069475 S 274 B 10 2/29
EF 948 3 16069483 S 274 B 13 2/29
EF 949 1 16069491 S 274 B 16 2/29
EF 950 9 36069509 E 271/63 5/2
EF 951 7 36069517 E 272/63 5/2
EF 952 5 36069525 E 273/63 5/2
EF 953 3 36069533 E 274/63 5/2
EF 954 1 36069541 E 272/80 5/2
EF 955 8 36069558 E 273/80 5/3
EF 956 6 36069566 E 274/80 5/3
EF 957 4 36069574 E 272/100 5/2
EF 958 2 36069582 E 273/100 5/3
EF 959 0 36069590 E 274/100 5/3
EF 960 8 36069608 E 272/125 5/2
EF 961 6 36069616 E 273/125 5/3
EF 962 4 36069624 E 274/125 5/3
EF 963 2 16069632 S 274 B 20 2/29
EF 964 0 16069640 S 274 B 25 2/29
EF 965 7 16069657 S 274 B 32 2/29
EF 966 5 16069665 S 274 B 40 2/29
EF 967 3 16069673 S 274 B 50 2/29
EF 968 1 16069681 S 274 B 63 2/29
EF 973 1 36069731 E 271/125 5/2
EF 998 8 16069988 S2-BP 2/42
EF 999 6 16069996 S2-BPS 2/43
EG 035 8 36070358 BT 1 2/71
EG 037 4 36070374 KA 1 2/71
EG 040 8 36070408 SA 2/71
EG 041 6 36070416 SPA 2/71
EG 042 4 36070424 SPB 1 2/71
EG 044 0 36070440 SPE 2/71
EG 046 5 36070465 EST 1 2/71
EG 047 3 36070473 EST 2 2/71
EG 048 1 16070481 SCL 1/250 7/7
EG 051 5 16070515 VLM 1/300 7/2
EG 052 3 16070523 VLM 1/500 7/2
EG 053 1 16070531 AMT 1/10 7/2
EG 054 9 16070549 AMT 1/15 7/2
EG 055 6 16070556 AMT 1/20 7/2
EG 056 4 16070564 AMT 1/25 7/2
EG 057 2 16070572 AMT 1/30 7/2
EG 058 0 16070580 AMT 1/A1 7/2
EG 059 8 16070598 AMT 1/5 7/2
EG 060 6 16070606 FRZ 1 7/2
EG 061 4 16070614 SCL 1/5 7/7
EG 062 2 16070622 SCL 1/10 7/7
EG 063 0 16070630 SCL 1/20 7/7
EG 064 8 16070648 SCL 1/30 7/7
EG 065 5 16070655 SCL 1/50 7/7
EG 066 3 16070663 SCL 1/80 7/7
EG 067 1 16070671 SCL 1/100 7/7
EG 068 9 16070689 SCL 1/150 7/7
EG 069 7 16070697 SCL 1/200 7/7
EG 070 5 16070705 SCL 1/300 7/7
EG 071 3 16070713 VLM 2/100 7/3
EG 072 1 16070721 VLM 2/300 7/3
EG 073 9 16070739 AMT 2/5 7/3
EG 074 7 16070747 AMT 2/10 7/3
EG 075 4 16070754 AMT 2/15 7/3
EG 076 2 16070762 AMT 2/20 7/3
EG 077 0 16070770 AMT 2/25 7/3
EG 078 8 16070788 AMT 2/30 7/3
EG 079 6 16070796 SCL 2/6 7/8
EG 080 4 16070804 SCL 2/10 7/8
EG 081 2 16070812 AMT 2 7/3
EG 082 0 16070820 SCL 2/5 7/8
EG 083 8 16070838 SCL 1/400 7/7
EG 084 6 16070846 SCL 1/500 7/7
EG 085 3 16070853 SCL 1/800 7/7
EG 086 1 16070861 SCL 1/1000 7/7
EG 087 9 16070879 SCL 1/A5/5 7/7
EG 088 7 16070887 SCL 1/A5/10 7/7
EG 089 5 16070895 SCL 1/A5/20 7/7
EG 090 3 16070903 SCL 1/A5/30 7/7
EG 102 6 16071026 SCL 2/400 7/8
EG 103 4 16071034 SCL 2/500 7/8
EG 106 7 16071067 SCL 1/75 7/7
EG 107 5 16071075 HMT 11 7/14
EG 108 3 16071083 AMT 1/A5 7/2
EG 109 1 16071091 SCL 1/A5/50 7/7
EG 110 9 16071109 SCL 1/A5/80 7/7
EG 119 0 16071190 SCL 1/A5/100 7/7
EG 120 8 16071208 SCL 1/A5/150 7/7
EG 125 7 16071257 SNT 1/15 7/13
EG 126 5 16071265 SNT 1/20 7/13
EG 127 3 16071273 SNT 1/25 7/13
EG 128 1 16071281 SNT 1/30 7/13
EG 129 9 16071299 SNT 1/40 7/13
EG 130 7 16071307 SNT 1/60 7/13
EG 131 5 16071315 SNT 1/80 7/13
EG 132 3 16071323 SNT 1/5 7/13
EG 135 6 16071356 SNT 1/6 7/13
EG 136 4 16071364 SNT 1/150 7/13
EG 138 0 16071380 AMT 2/0,01 7/3
EG 139 8 16071398 AMT 2/0,1 7/3
EG 140 6 16071406 AMT 2/1 7/3
EG 149 7 16071497 SCL 2/20 7/8
EG 150 5 16071505 SCL 2/30 7/8
EG 162 0 16071620 SNT 1/200 7/13
EG 171 1 16071711 SCL 1/25 7/7
EG 172 9 16071729 SCL 1/40 7/7
EG 173 7 16071737 SCL 1/60 7/7
EG 174 5 16071745 SCL 1/600 7/7
EG 181 0 16071810 SNT 1/10 7/13
EG 182 8 16071828 SNT 1/50 7/13
EG 183 6 16071836 SNT 1/100 7/13
EG 184 4 16071844 SNT 1/250 7/13
EG 185 1 16071851 SNT 1/400 7/13
EG 186 9 16071869 SNT 1/500 7/13
EG 187 7 16071877 SNT 1/600 7/13
EG 188 5 16071885 SNT 1/800 7/13
EG 189 3 16071893 SNT 1/1000 7/13
EG 190 1 16071901 SNT 1/1500 7/13
EG 191 9 16071919 SNT 1/2000 7/13
EG 192 7 16071927 SNT 1/2500 7/13
EG 193 5 16071935 SCL 2/50 7/8
EG 194 3 16071943 SCL 2/80 7/8
EG 195 0 16071950 SCL 2/100 7/8
EG 196 8 16071968 SCL 2/150 7/8
EG 197 6 16071976 SCL 2/200 7/8
EG 198 4 16071984 SCL 2/250 7/8
EG 199 2 16071992 SCL 2/300 7/8
EG 289 1 16072891 TRFM/40 7/11
EG 290 9 16072909 TRFM/60 7/11
EG 291 7 16072917 TRFM/100 7/11
EG 292 5 16072925 TRFM/150 7/11
EG 293 3 16072933 TRFM/250 7/11
14/8 ABB SACE
Code list
Elc code
Elc code Order code Type Pg. Elc code Order code Type Pg. Elc code Order code Type Pg.
14
EG 294 1 16072941 TRFM/400 7/11
EG 295 8 16072958 TRFM/600 7/11
EG 296 6 16072966 LE-230 6/11
EG 299 0 16072990 TRM 4/2
EG 309 7 16073097 TR 1 4/2
EG 310 5 16073105 TR 2 4/2
EG 311 3 16073113 TR 3 4/2
EG 312 1 16073121 TR 4 4/2
EG 313 9 16073139 CSF 1 7/3
EG 316 2 16073089 RD2 4/2
EG 401 2 16074012 HMT 1/24 7/14
EG 402 0 16074020 HMT 1/110 7/14
EG 403 8 16074038 HMT 1/220 7/14
EG 405 3 16074053 SWD 6/6
EG 406 1 16074061 AMT-D1 7/4
EG 407 9 16074079 AMT-D2 7/4
EG 408 7 16074087 VLM-D1 7/4
EG 409 5 16074095 VLM-D2 7/4
EG 410 3 16074103 FRZ-D1 7/4
EG 411 1 16074111 RAL3 6/8
EG 412 9 16074129 RAL6 6/8
EG 415 2 16074152 TR 5/A 4/2
EG 416 0 16074160 TR 5/C 4/2
EG 417 8 16074178 LSS1/2 6/9
EG 548 0 16075480 SCL 1/1500 7/7
EG 549 8 16075498 SCL 1/2000 7/7
EG 550 6 16075506 SCL 1/2500 7/7
EG 568 8 16075688 TCS 1 7/12
EG 569 6 16075696 TCS 2 7/12
EG 573 8 16075738 TWS-1 6/7
EG 574 6 16075746 LS-1 6/7
EG 578 7 16075787 EMT 3 7/17
EG 590 2 16075902 MCV 4 7/6
EG 591 0 16075910 MCV 7 7/6
EG 592 8 16075928 MCA 4 7/6
EG 593 6 36075936 E 233 12/48 7/14
EG 594 4 36075944 E 233-24 7/14
EG 595 1 36075951 E 233-230 7/14
EG 596 9 16075969 RLV 6/13
EG 597 7 16075977 RHV 6/13
EG 598 5 16075985 RLI 6/13
EG 599 3 16075993 RHI 6/13
EG 616 5 16076165 MTM 7/5
EG 617 3 16076173 SQZ3 6/10
EG 700 7 36077007 S 701 25 A ACCESS. 2/71
EG 701 5 36077015 S 701 35 A ACCESS. 2/71
EG 702 3 36077023 S 701 50 A ACCESS. 2/71
EG 703 1 36077031 S 701 63 A ACCESS. 2/71
EG 704 9 36077049 S 701 80 A ACCESS. 2/71
EG 705 6 36077056 S 701 100 A ACCESS. 2/71
EG 706 4 36077064 S 702 25 A ACCESS. 2/71
EG 707 2 36077072 S 702 35 A ACCESS. 2/71
EG 708 0 36077080 S 702 50 A ACCESS. 2/71
EG 709 8 36077098 S 702 63 A ACCESS. 2/71
EG 710 6 36077106 S 702 80 A ACCESS. 2/71
EG 711 4 36077114 S 702 100 A ACCESS. 2/71
EG 712 2 36077122 S 703 25 A ACCESS. 2/71
EG 713 0 36077130 S 703 35 A ACCESS. 2/71
EG 714 8 36077148 S 703 50 A ACCESS. 2/71
EG 715 5 36077155 S 703 63 A ACCESS. 2/71
EG 716 3 36077163 S 703 80 A ACCESS. 2/71
EG 717 1 36077171 S 703 100 A ACCESS. 2/71
EG 718 9 36077189 S 704 25 A ACCESS. 2/71
EG 719 7 36077197 S 704 35 A ACCESS. 2/71
EG 720 5 36077205 S 704 50 A ACCESS. 2/71
EG 721 3 36077213 S 704 63 A ACCESS. 2/71
EG 722 1 36077221 S 704 80 A ACCESS. 2/71
EG 723 9 36077239 S 704 100 A ACCESS. 2/71
EG 730 4 36077304 S 702 25 A NAVAL 2/71
EG 731 2 36077312 S 702 35 A NAVAL 2/71
EG 732 0 36077320 S 702 50 A NAVAL 2/71
EG 733 8 36077338 S 702 63 A NAVAL 2/71
EG 734 6 36077346 S 702 80 A NAVAL 2/71
EG 735 3 36077353 S 702 100 A NAVAL 2/71
EG 736 1 36077361 S 703 25 A NAVAL 2/71
EG 737 9 36077379 S 703 35 A NAVAL 2/71
EG 738 7 36077387 S 703 50 A NAVAL 2/71
EG 739 5 36077395 S 703 63 A NAVAL 2/71
EG 740 3 36077403 S 703 80 A NAVAL 2/71
EG 741 1 36077411 S 703 100 A NAVAL 2/71
EG 742 9 36077429 STD-500 MA 6/14
EG 743 7 36077437 STD-420 LS 6/14
EG 744 5 36077445 STD-1000 U 6/15
EG 745 2 36077452 STD 50-4 6/15
EG 746 0 36077460 STD-MTS 6/15
EG 750 2 16077502 CTR 0/1 7/9
EG 751 0 16077510 CTR 0/5 7/9
EG 752 8 16077528 CTR 0/10 7/9
EG 753 6 16077536 CTR 0/15 7/9
EG 754 4 16077544 CTR 0/20 7/9
EG 755 1 16077551 CTR 0/25 7/9
EG 756 9 16077569 CTR 0/40 7/9
EG 757 7 16077577 CTR 0/50 7/9
EG 758 5 16077585 CTR 0/60 7/9
EG 759 3 16077593 CTR 0/80 7/9
EG 760 1 16077601 CTR 0/100 7/9
EG 761 9 16077619 CTR 1/40 7/10
EG 762 7 16077627 CTR 1/50 7/10
EG 763 5 16077635 CTR 1/60 7/10
EG 764 3 16077643 CTR 1/80 7/10
EG 765 0 16077650 CTR 1/100 7/10
EG 766 8 16077668 CTR 1/150 7/10
EG 767 6 16077676 CTR 1/200 7/10
EG 768 4 16077684 CTR 1/250 7/10
EG 769 2 16077692 CTR 3/100 7/10
EG 770 0 16077700 CTR 3/150 7/10
EG 771 8 16077718 CTR 3/200 7/10
EG 772 6 16077726 CTR 3/250 7/10
EG 773 4 16077734 CTR 3/300 7/10
EG 774 2 16077742 CTR 3/400 7/10
EG 775 9 16077759 CTR 3/500 7/10
EG 776 7 16077767 CTR 3/600 7/10
EG 777 5 16077775 CTR 4/250 7/10
EG 778 3 16077783 CTR 4/300 7/10
EG 779 1 16077791 CTR 4/400 7/10
EG 780 9 16077809 CTR 4/500 7/10
EG 781 7 16077817 CTR 4/600 7/10
EG 782 5 16077825 CTR 4/800 7/10
EG 783 3 16077833 CTR 4/1000 7/10
EG 784 1 16077841 CTR 6/400 7/11
EG 785 8 16077858 CTR 6/500 7/11
EG 786 6 16077866 CTR 6/600 7/11
EG 787 4 16077874 CTR 6/800 7/11
EG 788 2 16077882 CTR 6/1000 7/11
EG 789 0 16077890 CTR 6/1200 7/11
EG 790 8 16077908 CTR 6/1500 7/11
EG 792 4 16077924 CTR 8/800 7/11
EG 793 2 16077932 CTR 8/1000 7/11
EG 794 0 16077940 CTR 8/1200 7/11
EG 795 7 16077957 CTR 8/1500 7/11
EG 796 5 16077965 CTR 8/2000 7/11
EG 797 3 16077973 CTR 8/2500 7/11
EI 060 4 36090604 S 501 B 6 2/60
EI 061 2 36090612 S 501 B 10 2/60
EI 062 0 36090620 S 501 B 13 2/60
EI 063 8 36090638 S 501 B 16 2/60
EI 064 6 36090646 S 501 B 20 2/60
EI 065 3 36090653 S 501 B 25 2/60
EI 066 1 36090661 S 501 B 32 2/60
EI 067 9 36090679 S 501 B 40 2/60
EI 068 7 36090687 S 501 B 50 2/60
EI 069 5 36090695 S 501 B 63 2/60
EI 070 3 36090703 S 502 B 6 2/60
EI 071 1 36090711 S 502 B 10 2/60
EI 072 9 36090729 S 502 B 13 2/60
EI 073 7 36090737 S 502 B 16 2/60
EI 074 5 36090745 S 502 B 20 2/60
EI 075 2 36090752 S 502 B 25 2/60
EI 076 0 36090760 S 502 B 32 2/60
EI 077 8 36090778 S 502 B 40 2/60
EI 078 6 36090786 S 502 B 50 2/60
EI 079 4 36090794 S 502 B 63 2/60
EI 080 2 36090802 S 503 B 6 2/61
EI 081 0 36090810 S 503 B 10 2/61
EI 082 8 36090828 S 503 B 13 2/61
EI 083 6 36090836 S 503 B 16 2/61
EI 084 4 36090844 S 503 B 20 2/61
EI 085 1 36090851 S 503 B 25 2/61
EI 086 9 36090869 S 503 B 32 2/61
EI 087 7 36090877 S 503 B 40 2/61
EI 088 5 36090885 S 503 B 50 2/61
EI 089 3 36090893 S 503 B 63 2/61
EI 090 1 36090901 S 504 B 6 2/61
EI 091 9 36090919 S 504 B 10 2/61
EI 092 7 36090927 S 504 B 13 2/61
EI 093 5 36090935 S 504 B 16 2/61
EI 094 3 36090943 S 504 B 20 2/61
EI 095 0 36090950 S 504 B 25 2/61
EI 096 8 36090968 S 504 B 32 2/61
EI 097 6 36090976 S 504 B 40 2/61
EI 098 4 36090984 S 504 B 50 2/61
EI 099 2 36090992 S 504 B 63 2/61
EI 100 8 36091008 S 501 C 6 2/60
EI 101 6 36091016 S 501 C 10 2/60
EI 102 4 36091024 S 501 C 13 2/60
EI 103 2 36091032 S 501 C 16 2/60
EI 104 0 36091040 S 501 C 20 2/60
EI 105 7 36091057 S 501 C 25 2/60
EI 106 5 36091065 S 501 C 32 2/60
EI 107 3 36091073 S 501 C 40 2/60
EI 108 1 36091081 S 501 C 50 2/60
EI 109 9 36091099 S 501 C 63 2/60
EI 110 7 36091107 S 502 C 6 2/60
EI 111 5 36091115 S 502 C 10 2/60
EI 112 3 36091123 S 502 C 13 2/60
EI 113 1 36091131 S 502 C 16 2/60
EI 114 9 36091149 S 502 C 20 2/60
EI 115 6 36091156 S 502 C 25 2/60
EI 116 4 36091164 S 502 C 32 2/60
EI 117 2 36091172 S 502 C 40 2/60
EI 118 0 36091180 S 502 C 50 2/60
EI 119 8 36091198 S 502 C 63 2/60
EI 120 6 36091206 S 503 C 6 2/61
EI 121 4 36091214 S 503 C 10 2/61
EI 122 2 36091222 S 503 C 13 2/61
EI 123 0 36091230 S 503 C 16 2/61
EI 124 8 36091248 S 503 C 20 2/61
EI 125 5 36091255 S 503 C 25 2/61
EI 126 3 36091263 S 503 C 32 2/61
EI 127 1 36091271 S 503 C 40 2/61
EI 128 9 36091289 S 503 C 50 2/61
EI 129 7 36091297 S 503 C 63 2/61
EI 130 5 36091305 S 504 C 6 2/61
EI 131 3 36091313 S 504 C 10 2/61
EI 132 1 36091321 S 504 C 13 2/61
EI 133 9 36091339 S 504 C 16 2/61
EI 134 7 36091347 S 504 C 20 2/61
EI 135 4 36091354 S 504 C 25 2/61
EI 136 2 36091362 S 504 C 32 2/61
EI 137 0 36091370 S 504 C 40 2/61
EI 138 8 36091388 S 504 C 50 2/61
EI 139 6 36091396 S 504 C 63 2/61
EI 315 2 36093152 S 501 UC B 6 2/62
EI 316 0 36093160 S 501 UC B 10 2/62
EI 317 8 36093178 S 501 UC B 13 2/62
EI 318 6 36093186 S 501 UC B 16 2/62
EI 319 4 36093194 S 501 UC B 20 2/62
EI 320 2 36093202 S 501 UC B 25 2/62
EI 321 0 36093210 S 501 UC B 32 2/62
EI 322 8 36093228 S 501 UC B 40 2/62
EI 323 6 36093236 S 501 UC B 50 2/62
EI 324 4 36093244 S 501 UC B 63 2/62
EI 325 1 36093251 S 502 UC B 6 2/62
EI 326 9 36093269 S 502 UC B 10 2/62
EI 327 7 36093277 S 502 UC B 13 2/62
EI 328 5 36093285 S 502 UC B 16 2/62
EI 329 3 36093293 S 502 UC B 20 2/62
EI 330 1 36093301 S 502 UC B 25 2/62
EI 331 9 36093319 S 502 UC B 32 2/62
EI 332 7 36093327 S 502 UC B 40 2/62
EI 333 5 36093335 S 502 UC B 50 2/62
EI 334 3 36093343 S 502 UC B 63 2/62
EI 335 0 36093350 S 503 UC B 6 2/63
EI 336 8 36093368 S 503 UC B 10 2/63
EI 337 6 36093376 S 503 UC B 13 2/63
EI 338 4 36093384 S 503 UC B 16 2/63
EI 339 2 36093392 S 503 UC B 20 2/63
EI 340 0 36093400 S 503 UC B 25 2/63
EI 341 8 36093418 S 503 UC B 32 2/63
EI 342 6 36093426 S 503 UC B 40 2/63
EI 343 4 36093434 S 503 UC B 50 2/63
EI 344 2 36093442 S 503 UC B 63 2/63
EI 345 9 36093459 S 503 K 0,1 - 0,15 2/64
EI 346 7 36093467 S 503 K 0,14 - 0,21 2/64
EI 347 5 36093475 S 503 K 0,2 - 0,3 2/64
EI 348 3 36093483 S 503 K 0,28 - 0,42 2/64
EI 349 1 36093491 S 503 K 0,38 - 0,58 2/64
EI 350 9 36093509 S 503 K 0,53 - 0,8 2/64
EI 351 7 36093517 S 503 K 0,73 - 1,1 2/64
EI 352 5 36093525 S 503 K 1 - 1,5 2/64
14/9
ABB SACE
Code list
Elc code
Elc code Order code Type Pg. Elc code Order code Type Pg. Elc code Order code Type Pg.
14
EI 353 3 36093533 S 503 K 1,4 - 2,1 2/64
EI 354 1 36093541 S 503 K 2-3 2/64
EI 355 8 36093558 S 503 K 2,8 - 4,2 2/64
EI 356 6 36093566 S 503 K 3,8 - 5,8 2/64
EI 357 4 36093574 S 503 K 5,3 - 8 2/64
EI 358 2 36093582 S 503 K 7,3 - 11 2/64
EI 359 0 36093590 S 503 K 10 - 15 2/64
EI 360 8 36093608 S 503 K 14 - 20 2/64
EI 361 6 36093616 S 503 K 18 - 26 2/64
EI 362 4 36093624 S 503 K 23 - 32 2/64
EI 363 2 36093632 S 503 K 29 - 37 2/64
EI 364 0 36093640 S 503 K 34 - 41 2/64
EI 365 7 36093657 S 503 K 38 - 45 2/64
EI 409 3 36094093 S500 RD3 2/68
EI 410 1 36094101 S5-H11 2/66
EI 411 9 36094119 S5-H20 2/66
EI 412 7 36094127 S5-S11 2/66
EI 413 5 36094135 S5-S20 2/66
EI 415 0 36094150 S500 S52 2/68
EI 416 8 36094168 S500 S51 2/68
EI 417 6 36094176 S 503 KM 1,6 2/64
EI 418 4 36094184 S 503 KM 2,5 2/64
EI 419 2 36094192 S 503 KM 4 2/64
EI 420 0 36094200 S 503 KM 6 2/64
EI 421 8 36094218 S 503 KM 9 2/64
EI 422 6 36094226 S 503 KM 20 2/64
EI 423 4 36094234 S 503 KM 32 2/64
EI 424 2 36094242 S 503 KM 52 2/64
EI 425 9 36094259 S 503 KM 63 2/64
EI 426 7 36094267 S500 RD4 2/68
EI 427 5 36094275 S500 H2B1 2/68
EI 428 3 36094283 S 503 KM 75 2/64
EI 437 4 36094374 S500 H2Y1 2/68
EI 438 2 36094382 S500 H2B2 2/68
EI 439 0 36094390 S500 H2Y2 2/68
EI 440 8 36094408 S500 H8B 2/68
EI 441 6 36094416 S500 H8Y 2/68
EI 442 4 36094424 S500 HP2B 2/68
EI 443 2 36094432 S500 HP2Y 2/68
EI 444 0 36094440 S500 S56 2/68
EI 450 7 36094507 S 501 K 0,1 - 0,15 2/64
EI 451 5 36094515 S 501 K 0,14 - 0,21 2/64
EI 452 3 36094523 S 501 K 0,2 - 0,3 2/64
EI 453 1 36094531 S 501 K 0,28 - 0,42 2/64
EI 454 9 36094549 S 501 K 0,38 - 0,58 2/64
EI 455 6 36094556 S 501 K 0,53 - 0,8 2/64
EI 456 4 36094564 S 501 K 0,73 - 1,1 2/64
EI 457 2 36094572 S 501 K 1 - 1,5 2/64
EI 458 0 36094580 S 501 K 1,4 - 2,1 2/64
EI 459 8 36094598 S 501 K 2-3 2/64
EI 460 6 36094606 S 501 K 2,8 - 4,2 2/64
EI 461 4 36094614 S 501 K 3,8 - 5,8 2/64
EI 462 2 36094622 S 501 K 5,3 - 8 2/64
EI 463 0 36094630 S 501 K 7,3 - 11 2/64
EI 464 8 36094648 S 501 K 10 - 15 2/64
EI 465 5 36094655 S 501 K 14 - 20 2/64
EI 466 3 36094663 S 501 K 18 - 26 2/64
EI 467 1 36094671 S 501 K 23 - 32 2/64
EI 468 9 36094689 S 501 K 29 - 37 2/64
EI 469 7 36094697 S 501 K 34 - 41 2/64
EI 470 5 36094705 S 501 K 38 - 45 2/64
EI 475 4 36094754 S 502 K 0,1 - 0,15 2/64
EI 476 2 36094762 S 502 K 0,14 - 0,21 2/64
EI 477 0 36094770 S 502 K 0,2 - 0,3 2/64
EI 478 8 36094788 S 502 K 0,28 - 0,42 2/64
EI 479 6 36094796 S 502 K 0,38 - 0,58 2/64
EI 480 4 36094804 S 502 K 0,53 - 0,8 2/64
EI 481 2 36094812 S 502 K 0,73 - 1,1 2/64
EI 482 0 36094820 S 502 K 1 - 1,5 2/64
EI 483 8 36094838 S 502 K 1,4 - 2,1 2/64
EI 484 6 36094846 S 502 K 2-3 2/64
EI 485 3 36094853 S 502 K 2,8 - 4,2 2/64
EI 486 1 36094861 S 502 K 3,8 - 5,8 2/64
EI 487 9 36094879 S 502 K 5,3 - 8 2/64
EI 488 7 36094887 S 502 K 7,3 - 11 2/64
EI 489 5 36094895 S 502 K 10 - 15 2/64
EI 490 3 36094903 S 502 K 14 - 20 2/64
EI 491 1 36094911 S 502 K 18 - 26 2/64
EI 492 9 36094929 S 502 K 23 - 32 2/64
EI 493 7 36094937 S 502 K 29 - 37 2/64
EI 494 5 36094945 S 502 K 34 - 41 2/64
EI 495 2 36094952 S 502 K 38 - 45 2/64
EL 175 6 16121756 BA 50 2/71
EL 820 7 36128207 EN 20-20/230 5/12
EL 821 5 36128215 EN 24-30/230 5/12
EL 822 3 36128223 EN 24-40/230 5/12
EL 823 1 36128231 EN 40-20/230 5/12
EL 824 9 36128249 EN 40-30/230 5/12
EL 825 6 36128256 EN 40-40/230 5/12
EL 869 4 36128694 ESB 20-11/12 5/10
EL 870 2 36128702 ESB 20-11/24 5/10
EL 871 0 36128710 ESB 20-11/48 5/10
EL 872 8 36128728 ESB 20-11/110 5/10
EL 873 6 36128736 ESB 20-11/230 5/10
EL 874 4 36128744 ESB 20-02/12 5/10
EL 875 1 36128751 ESB 20-02/24 5/10
EL 876 9 36128769 ESB 20-02/48 5/10
EL 877 7 36128777 ESB 20-02/110 5/10
EL 878 5 36128785 ESB 20-02/230 5/10
EL 879 3 36128793 ESB 20-20/12 5/10
EL 880 1 36128801 ESB 20-20/24 5/10
EL 881 9 36128819 ESB 20-20/48 5/10
EL 882 7 36128827 ESB 20-20/110 5/10
EL 883 5 36128835 ESB 20-20/230 5/10
EL 884 3 36128843 ESB 24-40/12 5/10
EL 885 0 36128850 ESB 24-40/24 5/10
EL 888 4 36128884 ESB 24-40/230 5/10
EL 890 0 36128900 ESB 40-40/24 5/11
EL 893 4 36128934 ESB 40-40/230 5/11
EL 895 9 36128959 ESB 63-40/24 5/11
EL 898 3 36128983 ESB 63-40/230 5/11
EL 900 7 36129007 EH 04-20 5/11
EL 901 5 36129015 EH 04-11 5/11
EL 902 3 36129023 ESB-DIS 5/11
EL 903 1 36129031 ESB-PLK 24 5/11
EL 904 9 36129049 ESB-PLK 40/63 5/11
EO 010 2 36150102 OHB 2AJ 2/46
EO 070 6 36150706 OXS 5X 330 2/46
EP 680 1 36166801 MS 225/0,16 4/7
EP 681 9 36166819 MS 225/0,25 4/7
EP 682 7 36166827 MS 225/0,4 4/7
EP 683 5 36166835 MS 225/0,63 4/7
EP 684 3 36166843 MS 225/1,0 4/7
EP 685 0 36166850 MS 225/1,6 4/7
EP 686 8 36166868 MS 225/2,5 4/7
EP 687 6 36166876 MS 225/4,0 4/7
EP 688 4 36166884 MS 225/6,3 4/7
EP 689 2 36166892 MS 225/9 4/7
EP 690 0 36166900 MS 225/12,5 4/7
EP 691 8 36166918 MS 225/16 4/7
EP 692 6 36166926 MS 225/20 4/7
EP 693 4 36166934 MS 225/25 4/7
EP 742 9 36167429 ST 2/46
EP 743 7 36167437 ST-E 2/46
EP 834 4 36168344 UA 415 Vc.a.. - S 4/8
EP 835 1 36168351 UA 24 Vc.a. 4/8
EP 836 9 36168369 UA 48 Vc.a. 4/8
EP 837 7 36168377 UA 60 Vc.a. 4/8
EP 838 5 36168385 UA 110 Vc.a. 4/8
EP 839 3 36168393 UA 230 Vc.a. 4/8
EP 840 1 36168401 UA 415 Vc.a. 4/8
EP 841 9 36168419 UA 500 Vc.a. 4/8
EP 842 7 36168427 HK 11 4/8
EP 843 5 36168435 HK 20 4/8
EP 844 3 36168443 HK 02 4/8
EP 845 0 36168450 SK 10 & 4/8
EP 846 8 36168468 SK 01 & 4/8
EP 847 6 36168476 AS 4/9
EP 849 2 36168492 COP-1 4/9
EP 850 0 36168500 TAR-1 4/9
EP 862 5 36168625 SA 1 4/9
EP 863 3 36168633 SA 3 4/9
EP 866 6 36168666 1 SA 12-2 4/9
EP 867 4 36168674 PS3-2-0 4/9
EP 868 2 36168682 PS3-2-1 4/9
EP 869 0 36168690 PS3-2-2 4/9
EP 870 8 36168708 PS3-4-0 4/9
EP 871 6 36168716 PS3-4-1 4/9
EP 872 4 36168724 PS3-4-2 4/9
EP 873 2 36168732 S3-M1 4/9
EP 874 0 36168740 S3-M2 4/9
EP 890 6 36168906 CONB6-7 4/9
EP 891 4 36168914 CONVB6-7 4/9
EP 892 2 36168922 BSA325 4/9
EP 893 0 36168930 GA 02 4/9
EP 894 8 36168948 ADAT 4/9
EP 915 1 36169151 1SAM101909R0001 4/9
EP 916 9 36169169 1SAM101909R0002 4/9
EP 977 1 36169771 HKF11 4/8
EP 978 9 36169789 HKF20 4/8
EP 979 7 36169797 SK 11 [NEW] 4/8
EP 981 3 36169813 OTPA325A1P1 [NEW] 4/9
EP 982 1 36169821 OTPA325B1P1 [NEW] 4/9
EP 983 9 36169839 OTPA325A2P1 [NEW] 4/9
EP 984 7 36169847 OTPA325B2P1 [NEW] 4/9
EY 006 9 16250069 DS651 C10 10mA (F) 3/27
EY 008 5 16250085 DS651 C16 10mA (F) 3/27
EY 011 9 16250119 DS 642 C 6 30mA 3/26
EY 012 7 16250127 DS 642 C 10 30mA 3/26
EY 013 5 16250135 DS 642 C 16 30mA 3/26
EY 014 3 16250143 DS 642 C 20 30mA 3/26
EY 015 0 16250150 DS 642 C 25 30mA 3/26
EY 016 8 16250168 DS 642 C 32 30mA 3/26
EY 017 6 16250176 DS 642 C 8 30mA 3/26
EY 018 4 16250184 DS 642 C 13 30mA 3/26
EY 021 8 16250218 DS 642 P C 6 30mA 3/26
EY 022 6 16250226 DS 642 P C 10 30mA 3/26
EY 023 4 16250234 DS 642 P C 16 30mA 3/26
EY 024 2 16250242 DS 642 P C 20 30mA 3/26
EY 025 9 16250259 DS 642 P C 25 30mA 3/26
EY 026 7 16250267 DS 642 P C 32 30mA 3/26
EY 027 5 16250275 DS 642 P C 8 30mA 3/26
EY 028 3 16250283 DS 642 P C 13 30mA 3/26
EY 031 7 16250317 DS 642 C 6 300mA 3/26
EY 032 5 16250325 DS 642 C 10 300mA 3/26
EY 033 3 16250333 DS 642 C 16 300mA 3/26
EY 034 1 16250341 DS 642 C 20 300mA 3/26
EY 035 8 16250358 DS 642 C 25 300mA 3/26
EY 036 6 16250366 DS 642 C 32 300mA 3/26
EY 037 4 16250374 DS 642 C 8 300mA 3/26
EY 038 2 16250382 DS 642 C 13 300mA 3/26
EY 040 8 16250408 DS 652 C 6 10mA 3/28
EY 041 6 16250416 DS 652 C 8 10mA 3/28
EY 042 4 16250424 DS 652 C 10 10mA 3/28
EY 043 2 16250432 DS 652 C 16 10mA 3/28
EY 044 0 16250440 DS 652 C 20 10mA 3/28
EY 050 7 16250507 DS 652 C 6 30mA 3/28
EY 051 5 16250515 DS 652 C 8 30mA 3/28
EY 052 3 16250523 DS 652 C 10 30mA 3/28
EY 053 1 16250531 DS 652 C 16 30mA 3/28
EY 054 9 16250549 DS 652 C 20 30mA 3/28
EY 055 6 16250556 DS 652 C 25 30mA 3/28
EY 056 4 16250564 DS 652 C 32 30mA 3/28
EY 057 2 16250572 DS 652 C 40 30mA 3/28
EY 058 0 16250580 DS 652 C 50 30mA 3/28
EY 059 8 16250598 DS 652 C 63 30mA 3/28
EY 060 6 16250606 DS 652 C 6 300mA 3/28
EY 061 4 16250614 DS 652 C 8 300mA 3/28
EY 062 2 16250622 DS 652 C 10 300mA 3/28
EY 063 0 16250630 DS 652 C 16 300mA 3/28
EY 064 8 16250648 DS 652 C 20 300mA 3/28
EY 065 5 16250655 DS 652 C 25 300mA 3/28
EY 066 3 16250663 DS 652 C 32 300mA 3/28
EY 067 1 16250671 DS 652 C 40 300mA 3/28
EY 068 9 16250689 DS 652 C 50 300mA 3/28
EY 069 7 16250697 DS 652 C 63 300mA 3/28
EY 110 9 16251109 DS 654 C 6 30mA 3/28
EY 111 7 16251117 DS 654 C 8 30mA 3/28
EY 112 5 16251125 DS 654 C 10 30mA 3/28
EY 113 3 16251133 DS 654 C 16 30mA 3/28
EY 114 1 16251141 DS 654 C 20 30mA 3/28
EY 115 8 16251158 DS 654 C 25 30mA 3/28
EY 118 2 16251182 DS 654 C 50 30mA 3/28
EY 119 0 16251190 DS 654 C 63 30mA 3/28
EY 120 8 16251208 DS 654 C 6 300mA 3/28
EY 121 6 16251216 DS 654 C 8 300mA 3/28
EY 122 4 16251224 DS 654 C 10 300mA 3/28
EY 123 2 16251232 DS 654 C 16 300mA 3/28
EY 124 0 16251240 DS 654 C 20 300mA 3/28
EY 125 7 16251257 DS 654 C 25 300mA 3/28
EY 128 1 16251281 DS 654 C 50 300mA 3/28
EY 129 9 16251299 DS 654 C 63 300mA 3/28
EY 188 5 16251885 DS 852 C 10 3/32
EY 189 3 16251893 DS 852 C 16 3/32
14/10 ABB SACE
Code list
Elc code
Elc code Order code Type Pg. Elc code Order code Type Pg. Elc code Order code Type Pg.
14
EY 190 1 16251901 DS 852 C 20 3/32
EY 191 9 16251919 DS 654 C 32 30mA 3/28
EY 192 7 16251927 DS 654 C 40 30mA 3/28
EY 193 5 16251935 DS 654 C 32 300mA 3/28
EY 194 3 16251943 DS 654 C 40 300mA 3/28
EY 200 8 16252008 DS 672 C 6 30mA 3/29
EY 201 6 16252016 DS 672 C 8 30mA 3/29
EY 202 4 16252024 DS 672 C 10 30mA 3/29
EY 203 2 16252032 DS 672 C 16 30mA 3/29
EY 204 0 16252040 DS 672 C 20 30mA 3/29
EY 205 7 16252057 DS 672 C 25 30mA 3/29
EY 206 5 16252065 DS 672 C 32 30mA 3/29
EY 207 3 16252073 DS 672 C 40 30mA 3/29
EY 208 1 16252081 DS 672 C 50 30mA 3/29
EY 209 9 16252099 DS 672 C 63 30mA 3/29
EY 260 2 16252602 DS 674 C 6 30mA 3/30
EY 261 0 16252610 DS 674 C 8 30mA 3/30
EY 262 8 16252628 DS 674 C 10 30mA 3/30
EY 263 6 16252636 DS 674 C 16 30mA 3/30
EY 264 4 16252644 DS 674 C 20 30mA 3/30
EY 265 1 16252651 DS 674 C 25 30mA 3/30
EY 268 5 16252685 DS 674 C 50 30mA 3/30
EY 269 3 16252693 DS 674 C 63 30mA 3/30
EY 270 1 16252701 DS 674 C 6 300mA 3/30
EY 271 9 16252719 DS 674 C 8 300mA 3/30
EY 272 7 16252727 DS 674 C 10 300mA 3/30
EY 273 5 16252735 DS 674 C 16 300mA 3/30
EY 274 3 16252743 DS 674 C 20 300mA 3/30
EY 275 0 16252750 DS 674 C 25 300mA 3/30
EY 278 4 16252784 DS 674 C 50 300mA 3/30
EY 279 2 16252792 DS 674 C 63 300mA 3/30
EY 515 9 16255159 DS 674 C 32 30mA 3/30
EY 516 7 16255167 DS 674 C 40 30mA 3/30
EY 517 5 16255175 DS 674 C 32 300mA 3/30
EY 518 3 16255183 DS 674 C 40 300mA 3/30
EY 560 5 16255605 DS 651 C 6 30mA 3/27
EY 561 3 16255613 DS 651 C 10 30mA 3/27
EY 562 1 16255621 DS 651 C 16 30mA 3/27
EY 563 9 16255639 DS 651 C 20 30mA 3/27
EY 564 7 16255647 DS 651 C 25 30mA 3/27
EY 565 4 16255654 DS 651 C 32 30mA 3/27
EY 566 2 16255662 DS 651 C 8 30mA 3/27
EY 567 0 16255670 DS 651 C 13 30mA 3/27
EY 570 4 16255704 DS 651 C 6 300mA 3/27
EY 571 2 16255712 DS 651 C 10 300mA 3/27
EY 572 0 16255720 DS 651 C 16 300mA 3/27
EY 573 8 16255738 DS 651 C 20 300mA 3/27
EY 574 6 16255746 DS 651 C 25 300mA 3/27
EY 575 3 16255753 DS 651 C 32 300mA 3/27
EY 576 1 16255761 DS 651 C 8 300mA 3/27
EY 577 9 16255779 DS 651 C 13 300mA 3/27
EY 580 3 16255803 DS 651 B 6 30mA 3/28
EY 581 1 16255811 DS 651 B 8 30mA 3/28
EY 582 9 16255829 DS 651 B 10 30mA 3/28
EY 583 7 16255837 DS 651 B 13 30mA 3/28
EY 584 5 16255845 DS 651 B 16 30mA 3/28
EY 585 2 16255852 DS 651 B 20 30mA 3/28
EY 586 0 16255860 DS 651 B 25 30mA 3/28
EY 587 8 16255878 DS 651 B 32 30mA 3/28
EY 589 4 16255894 DS 652 C 13 30mA 3/28
EY 590 2 16255902 DS 652 C 13 300mA 3/28
EY 595 1 16255951 DS 654 C 13 30mA 3/28
EY 596 9 16255969 DS 654 C 13 300mA 3/28
EY 600 9 16256009 F 362 16/10MA 3/38
EY 601 7 16256017 F 362 25/30MA 3/38
EY 602 5 16256025 F 362 40/30MA 3/38
EY 603 3 16256033 F 362 63/30MA 3/38
EY 604 1 16256041 F 362 80/30MA 3/38
EY 605 8 16256058 F 362 25/300MA 3/38
EY 606 6 16256066 F 362 40/300MA 3/38
EY 607 4 16256074 F 362 63/300MA 3/38
EY 608 2 16256082 F 362 80/300MA 3/38
EY 609 0 16256090 F 372 16/10MA 3/40
EY 610 8 16256108 F 372 25/30MA 3/40
EY 611 6 16256116 F 372 40/30MA 3/40
EY 612 4 16256124 F 372 63/30MA 3/40
EY 613 2 16256132 F 372 80/30MA 3/40
EY 614 0 16256140 F 372 25/300MA 3/40
EY 615 7 16256157 F 372 40/300MA 3/40
EY 616 5 16256165 F 372 63/300MA 3/40
EY 617 3 16256173 F 372 80/300MA 3/40
EY 618 1 16256181 F392 40 300 mA 3/42
EY 619 9 16256199 F392 63 300 mA 3/42
EY 620 7 16256207 F392 40 500 mA 3/42
EY 621 5 16256215 F392 63 500 mA 3/42
EY 622 3 16256223 F 364 25/30MA 3/38
EY 623 1 16256231 F 364 40/30MA 3/38
EY 624 9 16256249 F 364 63/30MA 3/38
EY 625 6 16256256 F 364 25/300MA 3/38
EY 626 4 16256264 F 364 40/300MA 3/38
EY 627 2 16256272 F 364 63/300MA 3/38
EY 628 0 16256280 F 364 25/500MA 3/38
EY 629 8 16256298 F 364 40/500MA 3/38
EY 630 6 16256306 F 364 63/500MA 3/38
EY 631 4 16256314 F 374 25/30MA 3/40
EY 632 2 16256322 F 374 40/30MA 3/40
EY 633 0 16256330 F 374 63/30MA 3/40
EY 634 8 16256348 F 374 25/300MA 3/40
EY 635 5 16256355 F 374 40/300MA 3/40
EY 636 3 16256363 F 374 63/300MA 3/40
EY 637 1 16256371 F 374 25/500MA 3/40
EY 638 9 16256389 F 374 40/500MA 3/40
EY 639 7 16256397 F 374 63/500MA 3/40
EY 640 5 16256405 F394 40 300 mA 3/42
EY 641 3 16256413 F394 63 300 mA 3/42
EY 642 1 16256421 F394 40 500 mA 3/42
EY 643 9 16256439 F394 63 500 mA 3/42
EY 646 2 16256462 F362 AR 25 30 mA 3/43
EY 647 0 16256470 F362 AR 40 30 mA 3/43
EY 648 8 16256488 F372 AR 25 30 mA 3/43
EY 649 6 16256496 F372 AR 40 30 mA 3/43
EY 651 2 16256512 F364 AR 63 30 mA 3/43
EY 652 0 16256520 F364 AR 63 300 mA 3/43
EY 653 8 16256538 F374 AR 63 30 mA 3/43
EY 654 6 16256546 F394 AR 63 500 mA 3/43
EY 700 7 16257007 DS 652 C 0,5 30mA 3/28
EY 701 5 16257015 DS 652 C 1 30mA 3/28
EY 702 3 16257023 DS 652 C 1,6 30mA 3/28
EY 703 1 16257031 DS 652 C 2 30mA 3/28
EY 704 9 16257049 DS 652 C 3 30mA 3/28
EY 705 6 16257056 DS 652 C 4 30mA 3/28
EY 712 2 16257122 DS 654 C 0,5 30mA 3/28
EY 713 0 16257130 DS 654 C 1 30mA 3/28
EY 714 8 16257148 DS 654 C 1,6 30mA 3/28
EY 715 5 16257155 DS 654 C 2 30mA 3/28
EY 716 3 16257163 DS 654 C 3 30mA 3/28
EY 717 1 16257171 DS 654 C 4 30mA 3/28
EY 730 4 16257304 DS 672 C 0,5 30mA 3/29
EY 731 2 16257312 DS 672 C 1 30mA 3/29
EY 732 0 16257320 DS 672 C 1,6 30mA 3/29
EY 733 8 16257338 DS 672 C 2 30mA 3/29
EY 734 6 16257346 DS 672 C 3 30mA 3/29
EY 735 3 16257353 DS 672 C 4 30mA 3/29
EY 742 9 16257429 DS 674 C 0,5 30mA 3/30
EY 743 7 16257437 DS 674 C 1 30mA 3/30
EY 744 5 16257445 DS 674 C 1,6 30mA 3/30
EY 745 2 16257452 DS 674 C 2 30mA 3/30
EY 746 0 16257460 DS 674 C 3 30mA 3/30
EY 747 8 16257478 DS 674 C 4 30mA 3/30
EY 774 2 16257742 DS 672 C 13 30mA 3/29
EY 776 7 16257767 DS 674 C 13 30mA 3/30
EY 778 3 16257783 DS 674 C 13 300mA 3/30
EY 786 6 16257866 F 374/400Hz 25 30 mA 3/44
EY 787 4 16257874 F 374/400Hz 40 30 mA 3/44
EY 788 2 36257882 F 804 63 30 mA 3/45
EY 789 0 36257890 F 804 63 300 mA 3/45
EY 800 5 16258005 DS 651 B 6 300mA 3/28
EY 801 3 16258013 DS 651 B 8 300mA 3/28
EY 802 1 16258021 DS 651 B 10 300mA 3/28
EY 803 9 16258039 DS 651 B 13 300mA 3/28
EY 804 7 16258047 DS 651 B 16 300mA 3/28
EY 805 4 16258054 DS 651 B 20 300mA 3/28
EY 806 2 16258062 DS 651 B 25 300mA 3/28
EY 807 0 16258070 DS 651 B 32 300mA 3/28
EY 850 0 16258500 DDA 62 25A 30mA 3/51
EY 851 8 16258518 DDA 62 40A 30mA 3/51
EY 852 6 16258526 DDA 62 63A 30mA 3/51
EY 853 4 16258534 DDA 62 63A 100mA 3/51
EY 854 2 16258542 DDA 62 25A 300mA 3/51
EY 855 9 16258559 DDA 62 40A 300mA 3/51
EY 856 7 16258567 DDA 62 63A 300mA 3/51
EY 858 3 16258583 DDA 62 40A 500mA 3/51
EY 859 1 16258591 DDA 62 63A 500mA 3/51
EY 860 9 16258609 DDA 62 63A 1A 3/51
EY 861 7 16258617 DDA 62 63A 2A 3/51
EY 862 5 16258625 DDA 63 25A 30mA 3/51
EY 863 3 16258633 DDA 63 40A 30mA 3/51
EY 864 1 16258641 DDA 63 63A 30mA 3/51
EY 865 8 16258658 DDA 63 63A 100mA 3/51
EY 866 6 16258666 DDA 63 25A 300mA 3/51
EY 868 2 16258682 DDA 63 63A 300mA 3/51
EY 869 0 16258690 DDA 63 25A 500mA 3/51
EY 870 8 16258708 DDA 63 40A 500mA 3/51
EY 871 6 16258716 DDA 63 63A 500mA 3/51
EY 872 4 16258724 DDA 63 63A 1A 3/51
EY 874 0 16258740 DDA 64 25A 30mA 3/51
EY 875 7 16258757 DDA 64 40A 30mA 3/51
EY 876 5 16258765 DDA 64 63A 30mA 3/51
EY 877 3 16258773 DDA 64 63A 100mA 3/51
EY 878 1 16258781 DDA 64 25A 300mA 3/51
EY 879 9 16258799 DDA 64 40A 300mA 3/51
EY 880 7 16258807 DDA 64 63A 300mA 3/51
EY 881 5 16258815 DDA 64 25A 500mA 3/51
EY 882 3 16258823 DDA 64 40A 500mA 3/51
EY 883 1 16258831 DDA 64 63A 500mA 3/51
EY 884 9 16258849 DDA 64 63A 1A 3/51
EY 885 6 16258856 DDA 64 63A 2A 3/51
EY 890 6 16258906 DDA 72 25A 30mA 3/52
EY 892 2 16258922 DDA 72 63A 30mA 3/52
EY 893 0 16258930 DDA 72 63A 100mA 3/52
EY 896 3 16258963 DDA 72 63A 300mA 3/52
EY 899 7 16258997 DDA 72 63A 500mA 3/52
EY 900 3 16259003 DDA 72 63A 1 A 3/52
EY 904 5 16259045 DDA 73 63A 30mA 3/52
EY 905 2 16259052 DDA 73 63A 100mA 3/52
EY 908 6 16259086 DDA 73 63A 300mA 3/52
EY 911 0 16259110 DDA 73 63A 500mA 3/52
EY 912 8 16259128 DDA 73 63A 1 A 3/52
EY 913 6 16259136 DDA 74 25A 30mA 3/52
EY 915 1 16259151 DDA 74 63A 30mA 3/52
EY 916 9 16259169 DDA 74 63A 100mA 3/52
EY 919 3 16259193 DDA 74 63A 300mA 3/52
EY 922 7 16259227 DDA 74 63A 500mA 3/52
EY 923 5 16259235 DDA 74 63A 1 A 3/52
EY 927 6 16259276 DDA93 63A 300MA BLOC. 3/53
EY 928 4 16259284 DDA93 63A 500MA BLOC. 3/53
EY 929 2 16259292 DDA93 63A 1A BLOCCO 3/53
EY 930 0 16259300 DDA 92 63A 100mA 3/53
EY 931 8 16259318 DDA 92 63A 300mA 3/53
EY 932 6 16259326 DDA 92 63A 500mA 3/53
EY 933 4 16259334 DDA 92 63A 1 A 3/53
EY 935 9 16259359 DDA 94 63A 300mA 3/53
EY 936 7 16259367 DDA 94 63A 500mA 3/53
EY 937 5 16259375 DDA 94 63A 1 A 3/53
EY 938 3 16259383 DDA 94 63A 2 A 3/53
EY 952 4 16259524 DDA62 AE 63A 30MA BL 3/54
EY 953 2 16259532 DDA62 AE 63A 300MA BL 3/54
EY 954 0 16259540 DDA62 AE 63A 500MA BL 3/54
EY 955 7 16259557 DDA62 AE 63A 1 A BL 3/54
EY 956 5 16259565 DDA63 AE 63A 30MA BL 3/54
EY 957 3 16259573 DDA63 AE 63A 300MA BL 3/54
EY 958 1 16259581 DDA63 AE 63A 500MA BL 3/54
EY 959 9 16259599 DDA63 AE 63A 1A BL 3/54
EY 960 7 16259607 DDA64 AE 63A 30MA BL 3/54
EY 961 5 16259615 DDA64 AE 63A 300MA BL 3/54
EY 962 3 16259623 DDA64 AE 63A 500MA BL 3/54
EY 963 1 16259631 DDA64 AE 63A 1 A BL 3/54
EY 964 9 16259649 DDA62 AP 40A 30MA BL 3/55
EY 965 6 16259656 DDA62 AP 63A 300MA BL 3/55
EY 966 4 16259664 DDA64 AP 63A 30MA 3/55
EY 967 2 16259672 DDA64 AP 63A 300MA 3/55
KU 470 7 16214707 M 281 In=0,5A 2/36
KU 471 5 16214715 M 281 In=1A 2/36
KU 472 3 16214723 M 281 In=1,6A 2/36
KU 473 1 16214731 M 281 In=2,5A 2/36
KU 474 9 16214749 M 281 In=4A 2/36
KU 475 6 16214756 M 281 In=6,3A 2/36
KU 476 4 16214764 M 281 In=10A 2/36
KU 477 2 16214772 M 281 In=12,5A 2/36
KU 478 0 16214780 M 281 In=16A 2/36
KU 479 8 16214798 M 281 In=20A 2/36
KU 480 6 16214806 M 281 In=25A 2/36
KU 481 4 16214814 M 281 In=32A 2/36
KU 482 2 16214822 M 281 In=40A 2/36
KU 483 0 16214830 M 281 In=50A 2/36
KU 484 8 16214848 M 281 In=63A 2/36
KU 602 5 16216025 M 282 In=0,5A 2/36
KU 603 3 16216033 M 282 In=1A 2/36
KU 604 1 16216041 M 282 In=1,6A 2/36
KU 605 8 16216058 M 282 In=2,5A 2/36
14/11
ABB SACE
Code list
Elc code
Elc code Order code Type Pg. Elc code Order code Type Pg. Elc code Order code Type Pg.
14
KU 606 6 16216066 M 282 In=4A 2/36
KU 607 4 16216074 M 282 In=6,3A 2/36
KU 608 2 16216082 M 282 In=10A 2/36
KU 609 0 16216090 M 282 In=12,5A 2/36
KU 610 8 16216108 M 282 In=16A 2/36
KU 611 6 16216116 M 282 In=20A 2/36
KU 612 4 16216124 M 282 In=25A 2/36
KU 613 2 16216132 M 282 In=32A 2/36
KU 614 0 16216140 M 282 In=40A 2/36
KU 615 7 16216157 M 282 In=50A 2/36
KU 616 5 16216165 M 282 In=63A 2/36
KU 617 3 16216173 M 283 In=0,5A 2/37
KU 618 1 16216181 M 283 In=1A 2/37
KU 619 9 16216199 M 283 In=1,6A 2/37
KU 620 7 16216207 M 283 In=2,5A 2/37
KU 621 5 16216215 M 283 In=4A 2/37
KU 622 3 16216223 M 283 In=6,3A 2/37
KU 623 1 16216231 M 283 In=10A 2/37
KU 624 9 16216249 M 283 In=12,5A 2/37
KU 625 6 16216256 M 283 In=16A 2/37
KU 626 4 16216264 M 283 In=20A 2/37
KU 627 2 16216272 M 283 In=25A 2/37
KU 628 0 16216280 M 283 In=32A 2/37
KU 629 8 16216298 M 283 In=40A 2/37
KU 630 6 16216306 M 283 In=50A 2/37
KU 631 4 16216314 M 283 In=63A 2/37
KU 632 2 16216322 M 284 In=0,5A 2/37
KU 633 0 16216330 M 284 In=1A 2/37
KU 634 8 16216348 M 284 In=1,6A 2/37
KU 635 5 16216355 M 284 In=2,5A 2/37
KU 636 3 16216363 M 284 In=4A 2/37
KU 637 1 16216371 M 284 In=6,3A 2/37
KU 638 9 16216389 M 284 In=10A 2/37
KU 639 7 16216397 M 284 In=12,5A 2/37
KU 640 5 16216405 M 284 In=16A 2/37
KU 641 3 16216413 M 284 In=20A 2/37
KU 642 1 16216421 M 284 In=25A 2/37
KU 643 9 16216439 M 284 In=32A 2/37
KU 644 7 16216447 M 284 In=40A 2/37
KU 645 4 16216454 M 284 In=50A 2/37
KU 646 2 16216462 M 284 In=63A 2/37
KU 647 0 16216470 S 281 B 6 2/30
KU 648 8 16216488 S 281 B 10 2/30
KU 649 6 16216496 S 281 B 16 2/30
KU 650 4 16216504 S 281 B 20 2/30
KU 651 2 16216512 S 281 B 25 2/30
KU 652 0 16216520 S 281 B 32 2/30
KU 653 8 16216538 S 281 B 40 2/30
KU 654 6 16216546 S 281 B 13 2/30
KU 655 3 16216553 S 281 B 50 2/30
KU 656 1 16216561 S 281 B 63 2/30
KU 657 9 16216579 S 281 C 6 2/30
KU 658 7 16216587 S 281 C 10 2/30
KU 659 5 16216595 S 281 C 16 2/30
KU 660 3 16216603 S 281 C 20 2/30
KU 661 1 16216611 S 281 C 25 2/30
KU 662 9 16216629 S 281 C 32 2/30
KU 663 7 16216637 S 281 C 40 2/30
KU 664 5 16216645 S 281 C 13 2/30
KU 665 2 16216652 S 281 C 50 2/30
KU 666 0 16216660 S 281 C 63 2/30
KU 674 4 16216744 S 281 D 6 2/30
KU 675 1 16216751 S 283 K 6 2/33
KU 676 9 16216769 S 284 C 63 2/31
KU 677 7 16216777 S 284 D 50 2/31
KU 678 5 16216785 S 284 D 63 2/31
KU 687 6 16216876 S 282 B 6 2/30
KU 688 4 16216884 S 282 B 10 2/30
KU 689 2 16216892 S 282 B 16 2/30
KU 690 0 16216900 S 282 B 20 2/30
KU 691 8 16216918 S 282 B 25 2/30
KU 692 6 16216926 S 282 B 32 2/30
KU 693 4 16216934 S 282 B 40 2/30
KU 694 2 16216942 S 282 B 13 2/30
KU 695 9 16216959 S 282 B 50 2/30
KU 696 7 16216967 S 282 B 63 2/30
KU 697 5 16216975 S 282 C 6 2/30
KU 698 3 16216983 S 282 C 10 2/30
KU 699 1 16216991 S 282 C 16 2/30
KU 700 7 16217007 S 282 C 20 2/30
KU 701 5 16217015 S 282 C 25 2/30
KU 702 3 16217023 S 282 C 32 2/30
KU 703 1 16217031 S 282 C 40 2/30
KU 704 9 16217049 S 282 C 13 2/30
KU 705 6 16217056 S 282 C 50 2/30
KU 706 4 16217064 S 282 C 63 2/30
KU 707 2 16217072 S 283 B 6 2/31
KU 708 0 16217080 S 283 B 10 2/31
KU 709 8 16217098 S 283 B 16 2/31
KU 710 6 16217106 S 283 B 20 2/31
KU 711 4 16217114 S 283 B 25 2/31
KU 712 2 16217122 S 283 B 32 2/31
KU 713 0 16217130 S 283 B 40 2/31
KU 714 8 16217148 S 283 B 13 2/31
KU 715 5 16217155 S 283 B 50 2/31
KU 716 3 16217163 S 283 B 63 2/31
KU 717 1 16217171 S 283 C 6 2/31
KU 718 9 16217189 S 283 C 10 2/31
KU 719 7 16217197 S 283 C 16 2/31
KU 720 5 16217205 S 283 C 20 2/31
KU 721 3 16217213 S 283 C 25 2/31
KU 722 1 16217221 S 283 C 32 2/31
KU 723 9 16217239 S 283 C 40 2/31
KU 724 7 16217247 S 283 C 13 2/31
KU 725 4 16217254 S 283 C 50 2/31
KU 726 2 16217262 S 283 C 63 2/31
KU 727 0 16217270 S 284 B 6 2/31
KU 728 8 16217288 S 284 B 10 2/31
KU 729 6 16217296 S 284 B 16 2/31
KU 730 4 16217304 S 284 B 20 2/31
KU 731 2 16217312 S 284 B 25 2/31
KU 732 0 16217320 S 284 B 32 2/31
KU 733 8 16217338 S 284 B 40 2/31
KU 734 6 16217346 S 284 B 13 2/31
KU 735 3 16217353 S 284 B 50 2/31
KU 736 1 16217361 S 284 B 63 2/31
KU 737 9 16217379 S 284 C 6 2/31
KU 738 7 16217387 S 284 C 10 2/31
KU 739 5 16217395 S 284 C 16 2/31
KU 740 3 16217403 S 284 C 20 2/31
KU 741 1 16217411 S 284 C 25 2/31
KU 742 9 16217429 S 284 C 32 2/31
KU 743 7 16217437 S 284 C 40 2/31
KU 744 5 16217445 S 284 C 13 2/31
KU 745 2 16217452 S 284 C 50 2/31
KU 746 0 16217460 S 281 Z 8 2/32
KU 747 8 16217478 S 282 Z 8 2/32
KU 748 6 16217486 S 283 Z 8 2/33
KU 749 4 16217494 S 284 Z 8 2/33
KU 750 2 16217502 S 281 Z 0,5 2/32
KU 751 0 16217510 S 281 Z 1 2/32
KU 752 8 16217528 S 281 Z 1,6 2/32
KU 753 6 16217536 S 281 Z 2 2/32
KU 754 4 16217544 S 281 Z 3 2/32
KU 755 1 16217551 S 281 Z 4 2/32
KU 756 9 16217569 S 281 Z 6 2/32
KU 757 7 16217577 S 281 Z 10 2/32
KU 758 5 16217585 S 281 Z 16 2/32
KU 759 3 16217593 S 281 Z 20 2/32
KU 760 1 16217601 S 281 Z 25 2/32
KU 761 9 16217619 S 281 Z 32 2/32
KU 762 7 16217627 S 281 Z 40 2/32
KU 763 5 16217635 S 281 Z 50 2/32
KU 764 3 16217643 S 281 Z 63 2/32
KU 765 0 16217650 S 282 Z 0,5 2/32
KU 766 8 16217668 S 282 Z 1 2/32
KU 767 6 16217676 S 282 Z 1,6 2/32
KU 768 4 16217684 S 282 Z 2 2/32
KU 769 2 16217692 S 282 Z 3 2/32
KU 770 0 16217700 S 282 Z 4 2/32
KU 771 8 16217718 S 282 Z 6 2/32
KU 772 6 16217726 S 282 Z 10 2/32
KU 773 4 16217734 S 282 Z 16 2/32
KU 774 2 16217742 S 282 Z 20 2/32
KU 775 9 16217759 S 282 Z 25 2/32
KU 776 7 16217767 S 282 Z 32 2/32
KU 777 5 16217775 S 282 Z 40 2/32
KU 778 3 16217783 S 282 Z 50 2/32
KU 779 1 16217791 S 282 Z 63 2/32
KU 780 9 16217809 S 283 Z 0,5 2/33
KU 781 7 16217817 S 283 Z 1 2/33
KU 782 5 16217825 S 283 Z 1,6 2/33
KU 783 3 16217833 S 283 Z 2 2/33
KU 784 1 16217841 S 283 Z 3 2/33
KU 785 8 16217858 S 283 Z 4 2/33
KU 786 6 16217866 S 283 Z 6 2/33
KU 787 4 16217874 S 283 Z 10 2/33
KU 788 2 16217882 S 283 Z 16 2/33
KU 789 0 16217890 S 283 Z 20 2/33
KU 790 8 16217908 S 283 Z 25 2/33
KU 791 6 16217916 S 283 Z 32 2/33
KU 792 4 16217924 S 283 Z 40 2/33
KU 793 2 16217932 S 283 Z 50 2/33
KU 794 0 16217940 S 283 Z 63 2/33
KU 795 7 16217957 S 284 Z 0,5 2/33
KU 796 5 16217965 S 284 Z 1 2/33
KU 797 3 16217973 S 284 Z 1,6 2/33
KU 798 1 16217981 S 284 Z 2 2/33
KU 799 9 16217999 S 284 Z 3 2/33
KU 800 5 16218005 S 284 Z 4 2/33
KU 801 3 16218013 S 284 Z 6 2/33
KU 802 1 16218021 S 284 Z 10 2/33
KU 803 9 16218039 S 284 Z 16 2/33
KU 804 7 16218047 S 284 Z 20 2/33
KU 805 4 16218054 S 284 Z 25 2/33
KU 806 2 16218062 S 284 Z 32 2/33
KU 807 0 16218070 S 284 Z 40 2/33
KU 808 8 16218088 S 284 Z 50 2/33
KU 809 6 16218096 S 284 Z 63 2/33
KU 810 4 16218104 S 281 D 10 2/30
KU 811 2 16218112 S 281 D 16 2/30
KU 812 0 16218120 S 281 D 20 2/30
KU 813 8 16218138 S 281 D 25 2/30
KU 814 6 16218146 S 281 D 32 2/30
KU 815 3 16218153 S 281 D 40 2/30
KU 817 9 16218179 S 281 D 50 2/30
KU 818 7 16218187 S 281 D 63 2/30
KU 819 5 16218195 S 282 D 6 2/30
KU 820 3 16218203 S 282 D 10 2/30
KU 821 1 16218211 S 282 D 16 2/30
KU 822 9 16218229 S 282 D 20 2/30
KU 823 7 16218237 S 282 D 25 2/30
KU 824 5 16218245 S 282 D 32 2/30
KU 825 2 16218252 S 282 D 40 2/30
KU 827 8 16218278 S 282 D 50 2/30
KU 828 6 16218286 S 282 D 63 2/30
KU 829 4 16218294 S 283 D 6 2/31
KU 830 2 16218302 S 283 D 10 2/31
KU 831 0 16218310 S 283 D 16 2/31
KU 832 8 16218328 S 283 D 20 2/31
KU 833 6 16218336 S 283 D 25 2/31
KU 834 4 16218344 S 283 D 32 2/31
KU 835 1 16218351 S 283 D 40 2/31
KU 837 7 16218377 S 283 D 50 2/31
KU 838 5 16218385 S 283 D 63 2/31
KU 839 3 16218393 S 284 D 6 2/31
KU 840 1 16218401 S 284 D 10 2/31
KU 841 9 16218419 S 284 D 16 2/31
KU 842 7 16218427 S 284 D 20 2/31
KU 843 5 16218435 S 284 D 25 2/31
KU 844 3 16218443 S 284 D 32 2/31
KU 845 0 16218450 S 284 D 40 2/31
KU 847 6 16218476 S 283 K 10 2/33
KU 848 4 16218484 S 283 K 16 2/33
KU 849 2 16218492 S 283 K 20 2/33
KU 850 0 16218500 S 283 K 25 2/33
KU 851 8 16218518 S 283 K 32 2/33
KU 852 6 16218526 S 283 K 40 2/33
KU 853 4 16218534 S 283 K 13 2/33
KU 854 2 16218542 S 283 K 50 2/33
KU 855 9 16218559 S 283 K 63 2/33
KU 856 7 16218567 S 282 K 6 2/32
KU 857 5 16218575 S 282 K 10 2/32
KU 858 3 16218583 S 282 K 16 2/32
KU 859 1 16218591 S 282 K 20 2/32
KU 860 9 16218609 S 282 K 25 2/32
KU 861 7 16218617 S 282 K 32 2/32
KU 862 5 16218625 S 282 K 40 2/32
KU 863 3 16218633 S 282 K 13 2/32
KU 864 1 16218641 S 282 K 50 2/32
KU 865 8 16218658 S 282 K 63 2/32
KU 866 6 16218666 S 281 K 6 2/32
KU 867 4 16218674 S 281 K 10 2/32
KU 868 2 16218682 S 281 K 16 2/32
KU 869 0 16218690 S 281 K 20 2/32
KU 870 8 16218708 S 281 K 25 2/32
KU 871 6 16218716 S 281 K 32 2/32
KU 872 4 16218724 S 281 K 40 2/32
KU 873 2 16218732 S 281 K 13 2/32
KU 874 0 16218740 S 281 K 50 2/32
KU 875 7 16218757 S 281 K 63 2/32
KU 876 5 16218765 S 284 K 6 2/33
14/12 ABB SACE
Code list
Elc code
Elc code Order code Type Pg. Elc code Order code Type Pg. Elc code Order code Type Pg.
14
KU 877 3 16218773 S 284 K 10 2/33
KU 878 1 16218781 S 284 K 16 2/33
KU 879 9 16218799 S 284 K 20 2/33
KU 880 7 16218807 S 284 K 25 2/33
KU 881 5 16218815 S 284 K 32 2/33
KU 882 3 16218823 S 284 K 40 2/33
KU 883 1 16218831 S 284 K 13 2/33
KU 884 9 16218849 S 284 K 50 2/33
KU 885 6 16218856 S 284 K 63 2/33
KU 890 6 36218906 S2-H12 2/40
KU 891 4 36218914 S2-H21 2/40
KU 892 2 36218922 S2-H03 2/40
KU 893 0 36218930 S2-H30 2/40
KU 894 8 36218948 S2-DH 2/44
KU 897 1 36218971 S2-H11X 2/40
KU 898 9 36218989 S2-H02X 2Ö 2/40
KU 899 7 36218997 S2-H20X 2S 2/40
KU 902 9 36219029 S2-S/H 2/40
KU 903 7 36219037 S2-S 2/40
KU 904 5 36219045 F6-H11 CONTATTO AUX 3/46
KU 909 4 16219094 F3-H.. CONTATTO AUX 3/46
KU 912 8 16219128 S2-BM1 2/41
KU 913 6 16219136 S2-BM2 2/41
KU 914 4 16219144 S2-BM3 2/41
KU 915 1 16219151 S2-BM4 2/41
KU 916 9 16219169 S2-BM5 2/41
KU 917 7 16219177 S2-BM6 2/41
KU 918 5 16219185 S2-A1I 2/39
KU 919 3 16219193 S2-A2I 2/39
KU 922 7 16219227 S2-EST 2/46
KU 925 0 16219250 S2-H11-I 2/40
KU 926 8 16219268 S2-H02-I 2/40
KU 927 6 16219276 S2-H20-I 2/40
KU 930 0 16219300 ME 1 2/45
KU 931 8 16219318 ME 2 2/45
KU 932 6 16219326 ME 3 2/45
KU 933 4 16219334 ME 4 2/45
KU 934 2 16219342 ME 6 2/45
KU 935 9 16219359 ME 8 2/45
KU 936 7 16219367 S2-CM2 2/47
KU 937 5 16219375 S2-CM3 2/47
KU 938 3 16219383 S2-CM4 2/47
KU 939 1 16219391 S2-MP2 2/45
KU 943 3 16219433 CPV 2 2/46
KU 950 8 36219508 S 291 C 80 2/51
KU 951 6 36219516 S 291 C 100 2/51
KU 952 4 36219524 S 291 C 125 2/51
KU 953 2 36219532 S 292 C 80 2/51
KU 954 0 36219540 S 292 C 100 2/51
KU 955 7 36219557 S 292 C 125 2/51
KU 956 5 36219565 S 293 C 80 2/51
KU 957 3 36219573 S 293 C 100 2/51
KU 958 1 36219581 S 293 C 125 2/51
KU 959 9 36219599 S 294 C 80 2/51
KU 960 7 36219607 S 294 C 100 2/51
KU 961 5 36219615 S 294 C 125 2/51
KU 974 8 36219748 S 291 D 80 2/51
KU 975 5 36219755 S 291 D 100 2/51
KU 977 1 36219771 S 292 D 80 2/51
KU 978 9 36219789 S 292 D 100 2/51
KU 980 5 36219805 S 293 D 80 2/51
KU 981 3 36219813 S 293 D 100 2/51
KU 983 9 36219839 S 294 D 80 2/51
KU 984 7 36219847 S 294 D 100 2/51
KU 987 0 36219870 S 290 H11 2/54
KU 988 8 36219888 S 290 S 2/54
KU 989 6 36219896 S 290 A1 2/53
KU 990 4 36219904 S 290 UA 230 2/55
KU 991 2 36219912 S 290 A2 2/53
KV 049 8 16220498 DS 751 B 13 300mA 3/31
KV 050 6 16220506 DS 751 B 6 30mA 3/31
KV 051 4 16220514 DS 751 B 10 30mA 3/31
KV 052 2 16220522 DS 751 B 16 30mA 3/31
KV 053 0 16220530 DS 751 B 20 30mA 3/31
KV 054 8 16220548 DS 751 B 25 30mA 3/31
KV 055 5 16220555 DS 751 B 32 30mA 3/31
KV 056 3 16220563 DS 751 B 6 300mA 3/31
KV 057 1 16220571 DS 751 B 10 300mA 3/31
KV 058 9 16220589 DS 751 B 16 300mA 3/31
KV 059 7 16220597 DS 751 B 20 300mA 3/31
KV 060 5 16220605 DS 751 B 25 300mA 3/31
KV 061 3 16220613 DS 751 B 32 300mA 3/31
KV 063 9 16220639 DS 751 C 6 30mA 3/31
KV 064 7 16220647 DS 751 C 10 30mA 3/31
KV 065 4 16220654 DS 751 C 16 30mA 3/31
KV 066 2 16220662 DS 751 C 20 30mA 3/31
KV 067 0 16220670 DS 751 C 25 30mA 3/31
KV 068 8 16220688 DS 751 C 32 30mA 3/31
KV 069 6 16220696 DS 751 C 6 300mA 3/31
KV 070 4 16220704 DS 751 C 10 300mA 3/31
KV 071 2 16220712 DS 751 C 16 300mA 3/31
KV 072 0 16220720 DS 751 C 20 300mA 3/31
KV 073 8 16220738 DS 751 C 25 300mA 3/31
KV 074 6 16220746 DS 751 C 32 300mA 3/31
KV 075 3 16220753 DS751 K6 30mA 3/31
KV 076 1 16220761 DS751 K10 30mA 3/31
KV 077 9 16220779 DS751 K16 30mA 3/31
KV 078 7 16220787 DS751 K20 30mA 3/31
KV 079 5 16220795 DS751 K25 30mA 3/31
KV 080 3 16220803 DS751 K32 30mA 3/31
KV 081 1 16220811 DS751 K6 300mA 3/31
KV 082 9 16220829 DS751 K10 300mA 3/31
KV 083 7 16220837 DS751 K16 300mA 3/31
KV 084 5 16220845 DS751 K20 300mA 3/31
KV 085 2 16220852 DS751 K25 300mA 3/31
KV 086 0 16220860 DS751 K32 300mA 3/31
KV 087 8 16220878 DS 751 C 13 30mA 3/31
KV 088 6 16220886 DS 751 C 13 300mA 3/31
KV 089 4 16220894 DS 751 B 13 30mA 3/31
KV 900 2 36229002 DDA 62 100A 30mA 3/51
KV 901 0 36229010 DDA 62 100A 300mA 3/51
KV 904 4 36229044 DDA 64 100A 30mA 3/51
KV 905 1 36229051 DDA 64 100A 300mA 3/51
KV 906 9 36229069 DDA 72 100A 30mA 3/52
KV 907 7 36229077 DDA 72 100A 300mA 3/52
KV 910 1 36229101 DDA 74 100A 30mA 3/52
KV 911 9 36229119 DDA 74 100A 300mA 3/52
KV 912 7 36229127 DDA 92 100A 300mA 3/53
KV 913 5 36229135 DDA 92 100A 1 A 3/53
KV 916 8 36229168 DDA 94 100A 300mA 3/53
KV 917 6 36229176 DDA 94 100A 1 A 3/53
KX 863 0 36248630 EE 20 7/17
KX 864 8 36248648 EE 20R 7/17
KX 865 5 36248655 EE 20PR 7/17
KX 866 3 36248663 EE 22Rr 7/17
KX 867 1 36248671 EE 22RR 7/17
KX 880 4 36248804 DAB 21 15 00 7/15
KX 881 2 36248812 DAB 29 15 00 7/15
KX 882 0 36248820 DCB 21 15 00 7/15
KX 883 8 36248838 DBB 21 17 00 7/15
KX 884 6 36248846 DBB 29 17 00 7/15
KX 885 3 36248853 DDB 21 17 00 7/15
KX 889 5 36248895 DAB 21 15 10 7/15
KX 890 3 36248903 DBB 21 17 10 7/15
KX 891 1 36248911 DBB 22 17 00 7/15
KX 892 9 36248929 DAB 22 15 00 7/15
KX 893 7 36248937 DAB 27 15 00 7/15
14/13
ABB SACE
Code list
Type
Type Pg. Elc code Order code Type Pg. Elc code Order code Type Pg. Elc code Order code
14
1 SA 12-2 4/9 EP 866 6 36168666
1SAM101909R0001 4/9 EP 915 1 36169151
1SAM101909R0002 4/9 EP 916 9 36169169
4E 1905 2/47 EA 109 7 16011097
ADAT 4/9 EP 894 8 36168948
AMT 1/10 7/2 EG 053 1 16070531
AMT 1/15 7/2 EG 054 9 16070549
AMT 1/20 7/2 EG 055 6 16070556
AMT 1/25 7/2 EG 056 4 16070564
AMT 1/30 7/2 EG 057 2 16070572
AMT 1/5 7/2 EG 059 8 16070598
AMT 1/A1 7/2 EG 058 0 16070580
AMT 1/A5 7/2 EG 108 3 16071083
AMT 2 7/3 EG 081 2 16070812
AMT 2/0,01 7/3 EG 138 0 16071380
AMT 2/0,1 7/3 EG 139 8 16071398
AMT 2/1 7/3 EG 140 6 16071406
AMT 2/10 7/3 EG 074 7 16070747
AMT 2/15 7/3 EG 075 4 16070754
AMT 2/20 7/3 EG 076 2 16070762
AMT 2/25 7/3 EG 077 0 16070770
AMT 2/30 7/3 EG 078 8 16070788
AMT 2/5 7/3 EG 073 9 16070739
AMT-D1 7/4 EG 406 1 16074061
AMT-D2 7/4 EG 407 9 16074079
AS 4/9 EP 847 6 36168476
BA 50 2/71 EL 175 6 16121756
BCF 1/100 2/47 EA 643 5 16016435
BCF 1H/100 2/47 EA 644 3 16016443
BCF 2/100 2/47 EA 645 0 16016450
BCF 3/100 2/47 EA 646 8 16016468
BCF 4/100 2/47 EA 647 6 16016476
BCP 1/100 2/47 EA 650 0 16016500
BCP 2/N 2/47 EA 524 7 16015247
BCP 3/N 2/47 EA 525 4 16015254
BCP 4/N 2/47 EA 526 2 16015262
BSA 1 2/45 EA 214 5 36012145
BSA 2 2/45 EA 213 7 16012137
BSA325 4/9 EP 892 2 36168922
BT 1 2/71 EG 035 8 36070358
CDI 7/5 EA 143 6 16011436
CONB6-7 4/9 EP 890 6 36168906
CONVB6-7 4/9 EP 891 4 36168914
COP-1 4/9 EP 849 2 36168492
CPV 2 2/46 KU 943 3 16219433
CSF 1 7/3 EG 313 9 16073139
CTR 0/1 7/9 EG 750 2 16077502
CTR 0/10 7/9 EG 752 8 16077528
CTR 0/100 7/9 EG 760 1 16077601
CTR 0/15 7/9 EG 753 6 16077536
CTR 0/20 7/9 EG 754 4 16077544
CTR 0/25 7/9 EG 755 1 16077551
CTR 0/40 7/9 EG 756 9 16077569
CTR 0/5 7/9 EG 751 0 16077510
CTR 0/50 7/9 EG 757 7 16077577
CTR 0/60 7/9 EG 758 5 16077585
CTR 0/80 7/9 EG 759 3 16077593
CTR 1/100 7/10 EG 765 0 16077650
CTR 1/150 7/10 EG 766 8 16077668
CTR 1/200 7/10 EG 767 6 16077676
CTR 1/250 7/10 EG 768 4 16077684
CTR 1/40 7/10 EG 761 9 16077619
CTR 1/50 7/10 EG 762 7 16077627
CTR 1/60 7/10 EG 763 5 16077635
CTR 1/80 7/10 EG 764 3 16077643
CTR 3/100 7/10 EG 769 2 16077692
CTR 3/150 7/10 EG 770 0 16077700
CTR 3/200 7/10 EG 771 8 16077718
CTR 3/250 7/10 EG 772 6 16077726
CTR 3/300 7/10 EG 773 4 16077734
CTR 3/400 7/10 EG 774 2 16077742
CTR 3/500 7/10 EG 775 9 16077759
CTR 3/600 7/10 EG 776 7 16077767
CTR 4/1000 7/10 EG 783 3 16077833
CTR 4/250 7/10 EG 777 5 16077775
CTR 4/300 7/10 EG 778 3 16077783
CTR 4/400 7/10 EG 779 1 16077791
CTR 4/500 7/10 EG 780 9 16077809
CTR 4/600 7/10 EG 781 7 16077817
CTR 4/800 7/10 EG 782 5 16077825
CTR 6/1000 7/11 EG 788 2 16077882
CTR 6/1200 7/11 EG 789 0 16077890
CTR 6/1500 7/11 EG 790 8 16077908
CTR 6/400 7/11 EG 784 1 16077841
CTR 6/500 7/11 EG 785 8 16077858
CTR 6/600 7/11 EG 786 6 16077866
CTR 6/800 7/11 EG 787 4 16077874
CTR 8/1000 7/11 EG 793 2 16077932
CTR 8/1200 7/11 EG 794 0 16077940
CTR 8/1500 7/11 EG 795 7 16077957
CTR 8/2000 7/11 EG 796 5 16077965
CTR 8/2500 7/11 EG 797 3 16077973
CTR 8/800 7/11 EG 792 4 16077924
CUS 7/5 EA 144 4 16011444
D62 16A 10mA (0015) 3/58 11176027 11176027
D62 32A 30mA (0015) 3/58 11176028 11176028
D62 32A 300mA (0015) 3/58 11176032 11176032
D62 32A 500mA (0015) 3/58 11176034 11176034
D62 63A 30mA (0015) 3/58 11176029 11176029
D62 63A 300mA (0015) 3/58 11176033 11176033
D62 63A 500mA (0015) 3/58 11176035 11176035
D63 32A 30mA (0015) 3/58 11176036 11176036
D63 32A 300mA (0015) 3/58 11176040 11176040
D63 63A 30mA (0015) 3/58 11176037 11176037
D63 63A 300mA (0015) 3/58 11176041 11176041
D64 32A 30mA (0015) 3/58 11176044 11176044
D64 32A 300mA (0015) 3/58 11176048 11176048
D64 32A 500mA (0015) 3/58 11176050 11176050
D64 63A 30mA (0015) 3/58 11176045 11176045
D64 63A 300mA (0015) 3/58 11176049 11176049
D64 63A 500mA (0015) 3/58 11176051 11176051
D72 16A 10mA (0015) 3/59 11176127 11176127
D72 32A 300mA (0015) 3/59 11176132 11176132
D72 32A 30mA (0015) 3/59 11176128 11176128
D72 63A 300mA (0015) 3/59 11176133 11176133
D72 63A 30mA (0015) 3/59 11176129 11176129
D73 32A 300mA (0015) 3/59 11176140 11176140
D73 32A 30mA (0015) 3/59 11176136 11176136
D73 63A 300mA (0015) 3/59 11176141 11176141
D73 63A 30mA (0015) 3/59 11176137 11176137
D74 32A 300mA (0015) 3/59 11176148 11176148
D74 32A 30mA (0015) 3/59 11176144 11176144
D74 63A 300mA (0015) 3/59 11176149 11176149
D74 63A 30mA (0015) 3/59 11176145 11176145
D92 63A 300mA (0015) 3/60 11176233 11176233
D94 63A 1A (0015) 3/60 11176252 11176252
D94 63A 300mA (0015) 3/60 11176249 11176249
DAB 21 15 00 7/15 KX 880 4 36248804
DAB 21 15 10 7/15 KX 889 5 36248895
DAB 22 15 00 7/15 KX 892 9 36248929
DAB 27 15 00 7/15 KX 893 7 36248937
DAB 29 15 00 7/15 KX 881 2 36248812
DBB 21 17 00 7/15 KX 883 8 36248838
DBB 21 17 10 7/15 KX 890 3 36248903
DBB 22 17 00 7/15 KX 891 1 36248911
DBB 29 17 00 7/15 KX 884 6 36248846
DCB 21 15 00 7/15 KX 882 0 36248820
DDA 62 100A 300mA 3/51 KV 901 0 36229010
DDA 62 100A 30mA 3/51 KV 900 2 36229002
DDA 62 25A 300mA 3/51 EY 854 2 16258542
DDA 62 25A 30mA 3/51 EY 850 0 16258500
DDA 62 40A 300mA 3/51 EY 855 9 16258559
DDA 62 40A 30mA 3/51 EY 851 8 16258518
DDA 62 40A 500mA 3/51 EY 858 3 16258583
DDA 62 63A 100mA 3/51 EY 853 4 16258534
DDA 62 63A 1A 3/51 EY 860 9 16258609
DDA 62 63A 2A 3/51 EY 861 7 16258617
DDA 62 63A 300mA 3/51 EY 856 7 16258567
DDA 62 63A 30mA 3/51 EY 852 6 16258526
DDA 62 63A 500mA 3/51 EY 859 1 16258591
DDA 63 25A 300mA 3/51 EY 866 6 16258666
DDA 63 25A 30mA 3/51 EY 862 5 16258625
DDA 63 25A 500mA 3/51 EY 869 0 16258690
DDA 63 40A 30mA 3/51 EY 863 3 16258633
DDA 63 40A 500mA 3/51 EY 870 8 16258708
DDA 63 63A 100mA 3/51 EY 865 8 16258658
DDA 63 63A 1A 3/51 EY 872 4 16258724
DDA 63 63A 300mA 3/51 EY 868 2 16258682
DDA 63 63A 30mA 3/51 EY 864 1 16258641
DDA 63 63A 500mA 3/51 EY 871 6 16258716
DDA 64 100A 300mA 3/51 KV 905 1 36229051
DDA 64 100A 30mA 3/51 KV 904 4 36229044
DDA 64 25A 300mA 3/51 EY 878 1 16258781
DDA 64 25A 30mA 3/51 EY 874 0 16258740
DDA 64 25A 500mA 3/51 EY 881 5 16258815
DDA 64 40A 300mA 3/51 EY 879 9 16258799
DDA 64 40A 30mA 3/51 EY 875 7 16258757
DDA 64 40A 500mA 3/51 EY 882 3 16258823
DDA 64 63A 100mA 3/51 EY 877 3 16258773
DDA 64 63A 1A 3/51 EY 884 9 16258849
DDA 64 63A 2A 3/51 EY 885 6 16258856
DDA 64 63A 300mA 3/51 EY 880 7 16258807
DDA 64 63A 30mA 3/51 EY 876 5 16258765
DDA 64 63A 500mA 3/51 EY 883 1 16258831
DDA 72 100A 300mA 3/52 KV 907 7 36229077
DDA 72 100A 30mA 3/52 KV 906 9 36229069
DDA 72 25A 30mA 3/52 EY 890 6 16258906
DDA 72 63A 1 A 3/52 EY 900 3 16259003
DDA 72 63A 100mA 3/52 EY 893 0 16258930
DDA 72 63A 300mA 3/52 EY 896 3 16258963
DDA 72 63A 30mA 3/52 EY 892 2 16258922
DDA 72 63A 500mA 3/52 EY 899 7 16258997
DDA 73 63A 1 A 3/52 EY 912 8 16259128
DDA 73 63A 100mA 3/52 EY 905 2 16259052
DDA 73 63A 300mA 3/52 EY 908 6 16259086
DDA 73 63A 30mA 3/52 EY 904 5 16259045
DDA 73 63A 500mA 3/52 EY 911 0 16259110
DDA 74 100A 300mA 3/52 KV 911 9 36229119
DDA 74 100A 30mA 3/52 KV 910 1 36229101
DDA 74 25A 30mA 3/52 EY 913 6 16259136
DDA 74 63A 1 A 3/52 EY 923 5 16259235
DDA 74 63A 100mA 3/52 EY 916 9 16259169
DDA 74 63A 300mA 3/52 EY 919 3 16259193
DDA 74 63A 30mA 3/52 EY 915 1 16259151
DDA 74 63A 500mA 3/52 EY 922 7 16259227
DDA 92 100A 1 A 3/53 KV 913 5 36229135
DDA 92 100A 300mA 3/53 KV 912 7 36229127
DDA 92 63A 1 A 3/53 EY 933 4 16259334
DDA 92 63A 100mA 3/53 EY 930 0 16259300
DDA 92 63A 300mA 3/53 EY 931 8 16259318
DDA 92 63A 500mA 3/53 EY 932 6 16259326
DDA 94 100A 1 A 3/53 KV 917 6 36229176
DDA 94 100A 300mA 3/53 KV 916 8 36229168
DDA 94 63A 1 A 3/53 EY 937 5 16259375
DDA 94 63A 2 A 3/53 EY 938 3 16259383
DDA 94 63A 300mA 3/53 EY 935 9 16259359
DDA 94 63A 500mA 3/53 EY 936 7 16259367
DDA62 AE 63A 1 A BL 3/54 EY 955 7 16259557
DDA62 AE 63A 300MA BL 3/54 EY 953 2 16259532
DDA62 AE 63A 30MA BL 3/54 EY 952 4 16259524
DDA62 AE 63A 500MA BL 3/54 EY 954 0 16259540
DDA62 AP 40A 30MA BL 3/55 EY 964 9 16259649
DDA62 AP 63A 300MA BL 3/55 EY 965 6 16259656
DDA63 AE 63A 1A BL 3/54 EY 959 9 16259599
DDA63 AE 63A 300MA BL 3/54 EY 957 3 16259573
DDA63 AE 63A 30MA BL 3/54 EY 956 5 16259565
DDA63 AE 63A 500MA BL 3/54 EY 958 1 16259581
DDA64 AE 63A 1 A BL 3/54 EY 963 1 16259631
DDA64 AE 63A 300MA BL 3/54 EY 961 5 16259615
DDA64 AE 63A 30MA BL 3/54 EY 960 7 16259607
DDA64 AE 63A 500MA BL 3/54 EY 962 3 16259623
DDA64 AP 63A 300MA 3/55 EY 967 2 16259672
DDA64 AP 63A 30MA 3/55 EY 966 4 16259664
DDA93 63A 1A BLOCCO 3/53 EY 929 2 16259292
DDA93 63A 300MA BLOC. 3/53 EY 927 6 16259276
DDA93 63A 500MA BLOC. 3/53 EY 928 4 16259284
DDB 21 17 00 7/15 KX 885 3 36248853
DS 642 C 10 300mA 3/26 EY 032 5 16250325
DS 642 C 10 30mA 3/26 EY 012 7 16250127
DS 642 C 13 300mA 3/26 EY 038 2 16250382
DS 642 C 13 30mA 3/26 EY 018 4 16250184
DS 642 C 16 300mA 3/26 EY 033 3 16250333
DS 642 C 16 30mA 3/26 EY 013 5 16250135
DS 642 C 20 300mA 3/26 EY 034 1 16250341
DS 642 C 20 30mA 3/26 EY 014 3 16250143
DS 642 C 25 300mA 3/26 EY 035 8 16250358
DS 642 C 25 30mA 3/26 EY 015 0 16250150
DS 642 C 32 300mA 3/26 EY 036 6 16250366
DS 642 C 32 30mA 3/26 EY 016 8 16250168
DS 642 C 6 300mA 3/26 EY 031 7 16250317
DS 642 C 6 30mA 3/26 EY 011 9 16250119
DS 642 C 8 300mA 3/26 EY 037 4 16250374
DS 642 C 8 30mA 3/26 EY 017 6 16250176
DS 642 P C 10 30mA 3/26 EY 022 6 16250226
14/14 ABB SACE
Code list
Type
Type Pg. Elc code Order code Type Pg. Elc code Order code Type Pg. Elc code Order code
14
DS 642 P C 13 30mA 3/26 EY 028 3 16250283
DS 642 P C 16 30mA 3/26 EY 023 4 16250234
DS 642 P C 20 30mA 3/26 EY 024 2 16250242
DS 642 P C 25 30mA 3/26 EY 025 9 16250259
DS 642 P C 32 30mA 3/26 EY 026 7 16250267
DS 642 P C 6 30mA 3/26 EY 021 8 16250218
DS 642 P C 8 30mA 3/26 EY 027 5 16250275
DS 651 B 10 300mA 3/28 EY 802 1 16258021
DS 651 B 10 30mA 3/28 EY 582 9 16255829
DS 651 B 13 300mA 3/28 EY 803 9 16258039
DS 651 B 13 30mA 3/28 EY 583 7 16255837
DS 651 B 16 300mA 3/28 EY 804 7 16258047
DS 651 B 16 30mA 3/28 EY 584 5 16255845
DS 651 B 20 300mA 3/28 EY 805 4 16258054
DS 651 B 20 30mA 3/28 EY 585 2 16255852
DS 651 B 25 300mA 3/28 EY 806 2 16258062
DS 651 B 25 30mA 3/28 EY 586 0 16255860
DS 651 B 32 300mA 3/28 EY 807 0 16258070
DS 651 B 32 30mA 3/28 EY 587 8 16255878
DS 651 B 6 300mA 3/28 EY 800 5 16258005
DS 651 B 6 30mA 3/28 EY 580 3 16255803
DS 651 B 8 300mA 3/28 EY 801 3 16258013
DS 651 B 8 30mA 3/28 EY 581 1 16255811
DS 651 C 10 300mA 3/27 EY 571 2 16255712
DS 651 C 10 30mA 3/27 EY 561 3 16255613
DS 651 C 13 300mA 3/27 EY 577 9 16255779
DS 651 C 13 30mA 3/27 EY 567 0 16255670
DS 651 C 16 300mA 3/27 EY 572 0 16255720
DS 651 C 16 30mA 3/27 EY 562 1 16255621
DS 651 C 20 300mA 3/27 EY 573 8 16255738
DS 651 C 20 30mA 3/27 EY 563 9 16255639
DS 651 C 25 300mA 3/27 EY 574 6 16255746
DS 651 C 25 30mA 3/27 EY 564 7 16255647
DS 651 C 32 300mA 3/27 EY 575 3 16255753
DS 651 C 32 30mA 3/27 EY 565 4 16255654
DS 651 C 6 300mA 3/27 EY 570 4 16255704
DS 651 C 6 30mA 3/27 EY 560 5 16255605
DS 651 C 8 300mA 3/27 EY 576 1 16255761
DS 651 C 8 30mA 3/27 EY 566 2 16255662
DS 652 C 0,5 30mA 3/28 EY 700 7 16257007
DS 652 C 1 30mA 3/28 EY 701 5 16257015
DS 652 C 1,6 30mA 3/28 EY 702 3 16257023
DS 652 C 10 10mA 3/28 EY 042 4 16250424
DS 652 C 10 300mA 3/28 EY 062 2 16250622
DS 652 C 10 30mA 3/28 EY 052 3 16250523
DS 652 C 13 300mA 3/28 EY 590 2 16255902
DS 652 C 13 30mA 3/28 EY 589 4 16255894
DS 652 C 16 10mA 3/28 EY 043 2 16250432
DS 652 C 16 300mA 3/28 EY 063 0 16250630
DS 652 C 16 30mA 3/28 EY 053 1 16250531
DS 652 C 2 30mA 3/28 EY 703 1 16257031
DS 652 C 20 10mA 3/28 EY 044 0 16250440
DS 652 C 20 300mA 3/28 EY 064 8 16250648
DS 652 C 20 30mA 3/28 EY 054 9 16250549
DS 652 C 25 300mA 3/28 EY 065 5 16250655
DS 652 C 25 30mA 3/28 EY 055 6 16250556
DS 652 C 3 30mA 3/28 EY 704 9 16257049
DS 652 C 32 300mA 3/28 EY 066 3 16250663
DS 652 C 32 30mA 3/28 EY 056 4 16250564
DS 652 C 4 30mA 3/28 EY 705 6 16257056
DS 652 C 40 300mA 3/28 EY 067 1 16250671
DS 652 C 40 30mA 3/28 EY 057 2 16250572
DS 652 C 50 300mA 3/28 EY 068 9 16250689
DS 652 C 50 30mA 3/28 EY 058 0 16250580
DS 652 C 6 10mA 3/28 EY 040 8 16250408
DS 652 C 6 300mA 3/28 EY 060 6 16250606
DS 652 C 6 30mA 3/28 EY 050 7 16250507
DS 652 C 63 300mA 3/28 EY 069 7 16250697
DS 652 C 63 30mA 3/28 EY 059 8 16250598
DS 652 C 8 10mA 3/28 EY 041 6 16250416
DS 652 C 8 300mA 3/28 EY 061 4 16250614
DS 652 C 8 30mA 3/28 EY 051 5 16250515
DS 654 C 0,5 30mA 3/28 EY 712 2 16257122
DS 654 C 1 30mA 3/28 EY 713 0 16257130
DS 654 C 1,6 30mA 3/28 EY 714 8 16257148
DS 654 C 10 300mA 3/28 EY 122 4 16251224
DS 654 C 10 30mA 3/28 EY 112 5 16251125
DS 654 C 13 300mA 3/28 EY 596 9 16255969
DS 654 C 13 30mA 3/28 EY 595 1 16255951
DS 654 C 16 300mA 3/28 EY 123 2 16251232
DS 654 C 16 30mA 3/28 EY 113 3 16251133
DS 654 C 2 30mA 3/28 EY 715 5 16257155
DS 654 C 20 300mA 3/28 EY 124 0 16251240
DS 654 C 20 30mA 3/28 EY 114 1 16251141
DS 654 C 25 300mA 3/28 EY 125 7 16251257
DS 654 C 25 30mA 3/28 EY 115 8 16251158
DS 654 C 3 30mA 3/28 EY 716 3 16257163
DS 654 C 32 300mA 3/28 EY 193 5 16251935
DS 654 C 32 30mA 3/28 EY 191 9 16251919
DS 654 C 4 30mA 3/28 EY 717 1 16257171
DS 654 C 40 300mA 3/28 EY 194 3 16251943
DS 654 C 40 30mA 3/28 EY 192 7 16251927
DS 654 C 50 300mA 3/28 EY 128 1 16251281
DS 654 C 50 30mA 3/28 EY 118 2 16251182
DS 654 C 6 300mA 3/28 EY 120 8 16251208
DS 654 C 6 30mA 3/28 EY 110 9 16251109
DS 654 C 63 300mA 3/28 EY 129 9 16251299
DS 654 C 63 30mA 3/28 EY 119 0 16251190
DS 654 C 8 300mA 3/28 EY 121 6 16251216
DS 654 C 8 30mA 3/28 EY 111 7 16251117
DS 672 C 0,5 30mA 3/29 EY 730 4 16257304
DS 672 C 1 30mA 3/29 EY 731 2 16257312
DS 672 C 1,6 30mA 3/29 EY 732 0 16257320
DS 672 C 10 30mA 3/29 EY 202 4 16252024
DS 672 C 13 30mA 3/29 EY 774 2 16257742
DS 672 C 16 30mA 3/29 EY 203 2 16252032
DS 672 C 2 30mA 3/29 EY 733 8 16257338
DS 672 C 20 30mA 3/29 EY 204 0 16252040
DS 672 C 25 30mA 3/29 EY 205 7 16252057
DS 672 C 3 30mA 3/29 EY 734 6 16257346
DS 672 C 32 30mA 3/29 EY 206 5 16252065
DS 672 C 4 30mA 3/29 EY 735 3 16257353
DS 672 C 40 30mA 3/29 EY 207 3 16252073
DS 672 C 50 30mA 3/29 EY 208 1 16252081
DS 672 C 6 30mA 3/29 EY 200 8 16252008
DS 672 C 63 30mA 3/29 EY 209 9 16252099
DS 672 C 8 30mA 3/29 EY 201 6 16252016
DS 674 C 0,5 30mA 3/30 EY 742 9 16257429
DS 674 C 1 30mA 3/30 EY 743 7 16257437
DS 674 C 1,6 30mA 3/30 EY 744 5 16257445
DS 674 C 10 300mA 3/30 EY 272 7 16252727
DS 674 C 10 30mA 3/30 EY 262 8 16252628
DS 674 C 13 300mA 3/30 EY 778 3 16257783
DS 674 C 13 30mA 3/30 EY 776 7 16257767
DS 674 C 16 300mA 3/30 EY 273 5 16252735
DS 674 C 16 30mA 3/30 EY 263 6 16252636
DS 674 C 2 30mA 3/30 EY 745 2 16257452
DS 674 C 20 300mA 3/30 EY 274 3 16252743
DS 674 C 20 30mA 3/30 EY 264 4 16252644
DS 674 C 25 300mA 3/30 EY 275 0 16252750
DS 674 C 25 30mA 3/30 EY 265 1 16252651
DS 674 C 3 30mA 3/30 EY 746 0 16257460
DS 674 C 32 300mA 3/30 EY 517 5 16255175
DS 674 C 32 30mA 3/30 EY 515 9 16255159
DS 674 C 4 30mA 3/30 EY 747 8 16257478
DS 674 C 40 300mA 3/30 EY 518 3 16255183
DS 674 C 40 30mA 3/30 EY 516 7 16255167
DS 674 C 50 300mA 3/30 EY 278 4 16252784
DS 674 C 50 30mA 3/30 EY 268 5 16252685
DS 674 C 6 300mA 3/30 EY 270 1 16252701
DS 674 C 6 30mA 3/30 EY 260 2 16252602
DS 674 C 63 300mA 3/30 EY 279 2 16252792
DS 674 C 63 30mA 3/30 EY 269 3 16252693
DS 674 C 8 300mA 3/30 EY 271 9 16252719
DS 674 C 8 30mA 3/30 EY 261 0 16252610
DS 751 B 10 300mA 3/31 KV 057 1 16220571
DS 751 B 10 30mA 3/31 KV 051 4 16220514
DS 751 B 13 300mA 3/31 KV 049 8 16220498
DS 751 B 13 30mA 3/31 KV 089 4 16220894
DS 751 B 16 300mA 3/31 KV 058 9 16220589
DS 751 B 16 30mA 3/31 KV 052 2 16220522
DS 751 B 20 300mA 3/31 KV 059 7 16220597
DS 751 B 20 30mA 3/31 KV 053 0 16220530
DS 751 B 25 300mA 3/31 KV 060 5 16220605
DS 751 B 25 30mA 3/31 KV 054 8 16220548
DS 751 B 32 300mA 3/31 KV 061 3 16220613
DS 751 B 32 30mA 3/31 KV 055 5 16220555
DS 751 B 6 300mA 3/31 KV 056 3 16220563
DS 751 B 6 30mA 3/31 KV 050 6 16220506
DS 751 C 10 300mA 3/31 KV 070 4 16220704
DS 751 C 10 30mA 3/31 KV 064 7 16220647
DS 751 C 13 300mA 3/31 KV 088 6 16220886
DS 751 C 13 30mA 3/31 KV 087 8 16220878
DS 751 C 16 300mA 3/31 KV 071 2 16220712
DS 751 C 16 30mA 3/31 KV 065 4 16220654
DS 751 C 20 300mA 3/31 KV 072 0 16220720
DS 751 C 20 30mA 3/31 KV 066 2 16220662
DS 751 C 25 300mA 3/31 KV 073 8 16220738
DS 751 C 25 30mA 3/31 KV 067 0 16220670
DS 751 C 32 300mA 3/31 KV 074 6 16220746
DS 751 C 32 30mA 3/31 KV 068 8 16220688
DS 751 C 6 300mA 3/31 KV 069 6 16220696
DS 751 C 6 30mA 3/31 KV 063 9 16220639
DS 852 C 10 3/32 EY 188 5 16251885
DS 852 C 16 3/32 EY 189 3 16251893
DS 852 C 20 3/32 EY 190 1 16251901
DS651 C10 100 mA 3/27 11170563 11170563
DS651 C10 10mA (F) 3/27 EY 0069 16250069
DS651 C16 100 mA 3/27 11170564 11170564
DS651 C16 10mA (F) 3/27 EY 0085 16250085
DS651 C20 100 mA 3/27 11170565 11170565
DS651 K 6 30mA (0020) 3/27 11170771 11170771
DS651 K 6 300mA (0020) 3/27 11170787 11170787
DS651 K10 300mA (0020) 3/27 11170789 11170789
DS651 K10 30mA (0020) 3/27 11170773 11170773
DS651 K16 300mA (0020) 3/27 11170790 11170790
DS651 K16 30mA (0020) 3/27 11170774 11170774
DS651 K20 300mA (0020) 3/27 11170791 11170791
DS651 K20 30mA (0020) 3/27 11170775 11170775
DS651 K25 30mA (0020) 3/27 11170776 11170776
DS651 K32 30mA (0020) 3/27 11170777 11170777
DS671 C 6 30mA 3/29 11812281 11812281
DS671 C10 30mA 3/29 11812282 11812282
DS671 C16 30mA 3/29 11812283 11812283
DS671 C20 30mA 3/29 11812284 11812284
DS671 C25 30mA 3/29 11812285 11812285
DS671 C32 30mA 3/29 11812286 11812286
DS751 C10 10mA (0008) 3/31 11170387 11170387
DS751 C13 10mA (0008) (CH) 3/31 11170388
11170388
DS751 C16 10mA (0008) 3/31 11170389 11170389
DS751 K10 300mA 3/31 KV 0829 16220829
DS751 K10 30mA 3/31 KV 0761 16220761
DS751 K16 300mA 3/31 KV 0837 16220837
DS751 K16 30mA 3/31 KV 0779 16220779
DS751 K20 300mA 3/31 KV 0845 16220845
DS751 K20 30mA 3/31 KV 0787 16220787
DS751 K25 300mA 3/31 KV 0852 16220852
DS751 K25 30mA 3/31 KV 0795 16220795
DS751 K32 300mA 3/31 KV 0860 16220860
DS751 K32 30mA 3/31 KV 0803 16220803
DS751 K6 300mA 3/31 KV 0811 16220811
DS751 K6 30mA 3/31 KV 0753 16220753
DS941 B10-1000MA/A 3/9 EB 404 1 16024041
DS941 B10-1000MA/AC 3/7 EB 029 6 16020296
DS941 B10-100MA/A 3/8 EB 383 7 16023837
DS941 B10-100MA/AC 3/6 EB 008 0 16020080
DS941 B10-10MA/A 3/8 EB 356 3 16023563
DS941 B10-300MA/A 3/9 EB 390 2 16023902
DS941 B10-300MA/AC 3/7 EB 015 5 16020155
DS941 B10-30MA/A 3/8 EB 376 1 16023761
DS941 B10-30MA/AC 3/6 EB 001 5 16020015
DS941 B10-500MA/A 3/9 EB 397 7 16023977
DS941 B10-500MA/AC 3/7 EB 022 1 16020221
DS941 B16-10000MA/AC 3/7 EB 030 4 16020304
DS941 B16-1000MA/A 3/8 EB 384 5 16023845
DS941 B16-1000MA/A 3/9 EB 405 8 16024058
DS941 B16-1000MA/AC 3/6 EB 009 8 16020098
DS941 B16-10MA/A 3/8 EB 357 1 16023571
DS941 B16-3000MA/A 3/9 EB 391 0 16023910
DS941 B16-3000MA/AC 3/7 EB 016 3 16020163
DS941 B16-30MA/A 3/8 EB 377 9 16023779
DS941 B16-30MA/AC 3/6 EB 002 3 16020023
DS941 B16-5000MA/A 3/9 EB 398 5 16023985
DS941 B16-5000MA/AC 3/7 EB 023 9 16020239
DS941 B20-1000MA/A 3/9 EB 406 6 16024066
DS941 B20-1000MA/AC 3/7 EB 031 2 16020312
DS941 B20-100MA/A 3/8 EB 385 2 16023852
DS941 B20-100MA/AC 3/6 EB 010 6 16020106
DS941 B20-300MA/A 3/9 EB 392 8 16023928
DS941 B20-300MA/AC 3/7 EB 017 1 16020171
DS941 B20-30MA/A 3/8 EB 378 7 16023787
DS941 B20-30MA/AC 3/6 EB 003 1 16020031
DS941 B20-500MA/A 3/9 EB 399 3 16023993
DS941 B20-500MA/AC 3/7 EB 024 7 16020247
DS941 B25-1000MA/A 3/9 EB 407 4 16024074
DS941 B25-1000MA/AC 3/7 EB 032 0 16020320
DS941 B25-100MA/A 3/8 EB 386 0 16023860
DS941 B25-100MA/AC 3/6 EB 011 4 16020114
DS941 B25-300MA/A 3/9 EB 393 6 16023936
DS941 B25-300MA/AC 3/7 EB 018 9 16020189
DS941 B25-30MA/A 3/8 EB 379 5 16023795
14/15
ABB SACE
Code list
Type
Type Pg. Elc code Order code Type Pg. Elc code Order code Type Pg. Elc code Order code
14
DS941 B25-30MA/AC 3/6 EB 004 9 16020049
DS941 B25-500MA/A 3/9 EB 400 9 16024009
DS941 B25-500MA/AC 3/7 EB 025 4 16020254
DS941 B32-1000MA/A 3/9 EB 408 2 16024082
DS941 B32-1000MA/AC 3/7 EB 033 8 16020338
DS941 B32-100MA/A 3/8 EB 387 8 16023878
DS941 B32-100MA/AC 3/6 EB 012 2 16020122
DS941 B32-300MA/A 3/9 EB 394 4 16023944
DS941 B32-300MA/AC 3/7 EB 019 7 16020197
DS941 B32-30MA/A 3/8 EB 380 3 16023803
DS941 B32-30MA/AC 3/6 EB 005 6 16020056
DS941 B32-500MA/A 3/9 EB 401 7 16024017
DS941 B32-500MA/AC 3/7 EB 026 2 16020262
DS941 B40-1000MA/A 3/9 EB 409 0 16024090
DS941 B40-1000MA/AC 3/7 EB 034 6 16020346
DS941 B40-100MA/A 3/8 EB 388 6 16023886
DS941 B40-100MA/AC 3/6 EB 013 0 16020130
DS941 B40-300MA/A 3/9 EB 395 1 16023951
DS941 B40-300MA/AC 3/7 EB 020 5 16020205
DS941 B40-30MA/A 3/8 EB 381 1 16023811
DS941 B40-30MA/AC 3/6 EB 006 4 16020064
DS941 B40-500MA/A 3/9 EB 402 5 16024025
DS941 B40-500MA/AC 3/7 EB 027 0 16020270
DS941 B6-1000MA/A 3/9 EB 403 3 16024033
DS941 B6-1000MA/AC 3/7 EB 028 8 16020288
DS941 B6-100MA/A 3/8 EB 382 9 16023829
DS941 B6-100MA/AC 3/6 EB 007 2 16020072
DS941 B6-10MA/A 3/8 EB 355 5 16023555
DS941 B6-300MA/A 3/9 EB 389 4 16023894
DS941 B6-300MA/AC 3/7 EB 014 8 16020148
DS941 B6-30MA/A 3/8 EB 375 3 16023753
DS941 B6-30MA/AC 3/6 EB 000 7 16020007
DS941 B6-500MA/A 3/9 EB 396 9 16023969
DS941 B6-500MA/AC 3/7 EB 021 3 16020213
DS941 C10-1000MA/A 3/9 EB 439 7 16024397
DS941 C10-1000MA/AC 3/7 EB 083 3 16020833
DS941 C10-100MA/A 3/8 EB 418 1 16024181
DS941 C10-100MA/AC 3/6 EB 047 8 16020478
DS941 C10-300MA/A 3/9 EB 425 6 16024256
DS941 C10-300MA/AC 3/7 EB 054 4 16020544
DS941 C10-30MA/A 3/8 EB 411 6 16024116
DS941 C10-30MA/AC 3/6 EB 040 3 16020403
DS941 C10-500MA/A 3/9 EB 432 2 16024322
DS941 C10-500MA/AC 3/7 EB 061 9 16020619
DS941 C16-1000MA/A 3/9 EB 440 5 16024405
DS941 C16-1000MA/AC 3/7 EB 084 1 16020841
DS941 C16-100MA/A 3/8 EB 419 9 16024199
DS941 C16-100MA/AC 3/6 EB 048 6 16020486
DS941 C16-300MA/A 3/9 EB 426 4 16024264
DS941 C16-300MA/AC 3/7 EB 055 1 16020551
DS941 C16-30MA/A 3/8 EB 412 4 16024124
DS941 C16-30MA/AC 3/6 EB 041 1 16020411
DS941 C16-500MA/A 3/9 EB 433 0 16024330
DS941 C16-500MA/AC 3/7 EB 062 7 16020627
DS941 C20-1000MA/A 3/9 EB 441 3 16024413
DS941 C20-1000MA/AC 3/7 EB 085 8 16020858
DS941 C20-100MA/A 3/8 EB 420 7 16024207
DS941 C20-100MA/AC 3/6 EB 049 4 16020494
DS941 C20-300MA/A 3/9 EB 427 2 16024272
DS941 C20-300MA/AC 3/7 EB 056 9 16020569
DS941 C20-30MA/A 3/8 EB 413 2 16024132
DS941 C20-30MA/AC 3/6 EB 042 9 16020429
DS941 C20-500MA/A 3/9 EB 434 8 16024348
DS941 C20-500MA/AC 3/7 EB 063 5 16020635
DS941 C25-1000MA/A 3/9 EB 442 1 16024421
DS941 C25-1000MA/AC 3/7 EB 086 6 16020866
DS941 C25-100MA/A 3/8 EB 421 5 16024215
DS941 C25-100MA/AC 3/6 EB 050 2 16020502
DS941 C25-300MA/A 3/9 EB 428 0 16024280
DS941 C25-300MA/AC 3/7 EB 057 7 16020577
DS941 C25-30MA/A 3/8 EB 414 0 16024140
DS941 C25-30MA/AC 3/6 EB 043 7 16020437
DS941 C25-500MA/A 3/9 EB 435 5 16024355
DS941 C25-500MA/AC 3/7 EB 064 3 16020643
DS941 C32-1000MA/A 3/9 EB 443 9 16024439
DS941 C32-1000MA/AC 3/7 EB 087 4 16020874
DS941 C32-100MA/A 3/8 EB 422 3 16024223
DS941 C32-100MA/AC 3/6 EB 051 0 16020510
DS941 C32-300MA/A 3/9 EB 429 8 16024298
DS941 C32-300MA/AC 3/7 EB 058 5 16020585
DS941 C32-30MA/A 3/8 EB 415 7 16024157
DS941 C32-30MA/AC 3/6 EB 044 5 16020445
DS941 C32-500MA/A 3/9 EB 436 3 16024363
DS941 C32-500MA/AC 3/7 EB 065 0 16020650
DS941 C40-1000MA/A 3/9 EB 444 7 16024447
DS941 C40-1000MA/AC 3/7 EB 088 2 16020882
DS941 C40-100MA/A 3/8 EB 423 1 16024231
DS941 C40-100MA/AC 3/6 EB 052 8 16020528
DS941 C40-300MA/A 3/9 EB 430 6 16024306
DS941 C40-300MA/AC 3/7 EB 059 3 16020593
DS941 C40-30MA/A 3/8 EB 416 5 16024165
DS941 C40-30MA/AC 3/6 EB 045 2 16020452
DS941 C40-500MA/A 3/9 EB 437 1 16024371
DS941 C40-500MA/AC 3/7 EB 066 8 16020668
DS941 C6-1000MA/A 3/9 EB 438 9 16024389
DS941 C6-1000MA/AC 3/7 EB 082 5 16020825
DS941 C6-100MA/A 3/8 EB 417 3 16024173
DS941 C6-100MA/AC 3/6 EB 046 0 16020460
DS941 C6-300MA/A 3/9 EB 424 9 16024249
DS941 C6-300MA/AC 3/7 EB 053 6 16020536
DS941 C6-30MA/A 3/8 EB 410 8 16024108
DS941 C6-30MA/AC 3/6 EB 039 5 16020395
DS941 C6-500MA/A 3/9 EB 431 4 16024314
DS941 C6-500MA/AC 3/7 EB 060 1 16020601
DS951 B10-1000MA/A 3/13 EB 504 8 16025048
DS951 B10-1000MA/AC 3/11 EB 129 4 16021294
DS951 B10-100MA/A 3/12 EB 483 5 16024835
DS951 B10-100MA/AC 3/10 EB 108 8 16021088
DS951 B10-300MA/A 3/13 EB 490 0 16024900
DS951 B10-300MA/AC 3/11 EB 115 3 16021153
DS951 B10-30MA/A 3/12 EB 476 9 16024769
DS951 B10-30MA/AC 3/10 EB 101 3 16021013
DS951 B10-500MA/A 3/13 EB 497 5 16024975
DS951 B10-500MA/AC 3/11 EB 122 9 16021229
DS951 B16-10000MA/A 3/13 EB 505 5 16025055
DS951 B16-10000MA/AC 3/11 EB 130 2 16021302
DS951 B16-1000MA/A 3/12 EB 484 3 16024843
DS951 B16-1000MA/AC 3/10 EB 109 6 16021096
DS951 B16-3000MA/A 3/13 EB 491 8 16024918
DS951 B16-3000MA/AC 3/11 EB 116 1 16021161
DS951 B16-30MA/A 3/12 EB 477 7 16024777
DS951 B16-30MA/AC 3/10 EB 102 1 16021021
DS951 B16-5000MA/A 3/13 EB 498 3 16024983
DS951 B16-5000MA/AC 3/11 EB 123 7 16021237
DS951 B20-1000MA/A 3/13 EB 506 3 16025063
DS951 B20-1000MA/AC 3/11 EB 131 0 16021310
DS951 B20-100MA/A 3/12 EB 485 0 16024850
DS951 B20-100MA/AC 3/10 EB 110 4 16021104
DS951 B20-300MA/A 3/13 EB 492 6 16024926
DS951 B20-300MA/AC 3/11 EB 117 9 16021179
DS951 B20-30MA/A 3/12 EB 478 5 16024785
DS951 B20-30MA/AC 3/10 EB 103 9 16021039
DS951 B20-500MA/A 3/13 EB 499 1 16024991
DS951 B20-500MA/AC 3/11 EB 124 5 16021245
DS951 B25-1000MA/A 3/13 EB 507 1 16025071
DS951 B25-1000MA/AC 3/11 EB 132 8 16021328
DS951 B25-100MA/A 3/12 EB 486 8 16024868
DS951 B25-100MA/AC 3/10 EB 111 2 16021112
DS951 B25-300MA/A 3/13 EB 493 4 16024934
DS951 B25-300MA/AC 3/11 EB 118 7 16021187
DS951 B25-30MA/A 3/12 EB 479 3 16024793
DS951 B25-30MA/AC 3/10 EB 104 7 16021047
DS951 B25-500MA/A 3/13 EB 500 6 16025006
DS951 B25-500MA/AC 3/11 EB 125 2 16021252
DS951 B32-1000MA/A 3/13 EB 508 9 16025089
DS951 B32-1000MA/AC 3/11 EB 133 6 16021336
DS951 B32-100MA/A 3/12 EB 487 6 16024876
DS951 B32-100MA/AC 3/10 EB 112 0 16021120
DS951 B32-300MA/A 3/13 EB 494 2 16024942
DS951 B32-300MA/AC 3/11 EB 119 5 16021195
DS951 B32-30MA/A 3/12 EB 480 1 16024801
DS951 B32-30MA/AC 3/10 EB 105 4 16021054
DS951 B32-500MA/A 3/13 EB 501 4 16025014
DS951 B32-500MA/AC 3/11 EB 126 0 16021260
DS951 B40-1000MA/A 3/13 EB 509 7 16025097
DS951 B40-1000MA/AC 3/11 EB 134 4 16021344
DS951 B40-100MA/A 3/12 EB 488 4 16024884
DS951 B40-100MA/AC 3/10 EB 113 8 16021138
DS951 B40-300MA/A 3/13 EB 495 9 16024959
DS951 B40-300MA/AC 3/11 EB 120 3 16021203
DS951 B40-30MA/A 3/12 EB 481 9 16024819
DS951 B40-30MA/AC 3/10 EB 106 2 16021062
DS951 B40-500MA/A 3/13 EB 502 2 16025022
DS951 B40-500MA/AC 3/11 EB 127 8 16021278
DS951 B6-1000MA/A 3/13 EB 503 0 16025030
DS951 B6-1000MA/AC 3/11 EB 128 6 16021286
DS951 B6-100MA/A 3/12 EB 482 7 16024827
DS951 B6-100MA/AC 3/10 EB 107 0 16021070
DS951 B6-300MA/A 3/13 EB 489 2 16024892
DS951 B6-300MA/AC 3/11 EB 114 6 16021146
DS951 B6-30MA/A 3/12 EB 475 1 16024751
DS951 B6-30MA/AC 3/10 EB 100 5 16021005
DS951 B6-500MA/A 3/13 EB 496 7 16024967
DS951 B6-500MA/AC 3/11 EB 121 1 16021211
DS951 C10-1000MA/A 3/13 EB 544 4 16025444
DS951 C10-1000MA/AC 3/11 EB 164 1 16021641
DS951 C10-100MA/A 3/12 EB 523 8 16025238
DS951 C10-100MA/AC 3/10 EB 143 5 16021435
DS951 C10-300MA/A 3/13 EB 530 3 16025303
DS951 C10-300MA/AC 3/11 EB 150 0 16021500
DS951 C10-30MA/A 3/12 EB 516 2 16025162
DS951 C10-30MA/AC 3/10 EB 136 9 16021369
DS951 C10-500MA/A 3/13 EB 537 8 16025378
DS951 C10-500MA/AC 3/11 EB 157 5 16021575
DS951 C16-1000MA/A 3/13 EB 545 1 16025451
DS951 C16-1000MA/AC 3/11 EB 165 8 16021658
DS951 C16-100MA/A 3/12 EB 524 6 16025246
DS951 C16-100MA/AC 3/10 EB 144 3 16021443
DS951 C16-300MA/A 3/13 EB 531 1 16025311
DS951 C16-300MA/AC 3/11 EB 151 8 16021518
DS951 C16-30MA/A 3/12 EB 517 0 16025170
DS951 C16-30MA/AC 3/10 EB 137 7 16021377
DS951 C16-500MA/A 3/13 EB 538 6 16025386
DS951 C16-500MA/AC 3/11 EB 158 3 16021583
DS951 C20-1000MA/A 3/13 EB 546 9 16025469
DS951 C20-1000MA/AC 3/11 EB 166 6 16021666
DS951 C20-100MA/A 3/12 EB 525 3 16025253
DS951 C20-100MA/AC 3/10 EB 145 0 16021450
DS951 C20-300MA/A 3/13 EB 532 9 16025329
DS951 C20-300MA/AC 3/11 EB 152 6 16021526
DS951 C20-30MA/A 3/12 EB 518 8 16025188
DS951 C20-30MA/AC 3/10 EB 138 5 16021385
DS951 C20-500MA/A 3/13 EB 539 4 16025394
DS951 C20-500MA/AC 3/11 EB 159 1 16021591
DS951 C25-1000MA/A 3/13 EB 547 7 16025477
DS951 C25-1000MA/AC 3/11 EB 167 4 16021674
DS951 C25-100MA/A 3/12 EB 526 1 16025261
DS951 C25-100MA/AC 3/10 EB 146 8 16021468
DS951 C25-300MA/A 3/13 EB 533 7 16025337
DS951 C25-300MA/AC 3/11 EB 153 4 16021534
DS951 C25-30MA/A 3/12 EB 519 6 16025196
DS951 C25-30MA/AC 3/10 EB 139 3 16021393
DS951 C25-500MA/A 3/13 EB 540 2 16025402
DS951 C25-500MA/AC 3/11 EB 160 9 16021609
DS951 C32-1000MA/A 3/13 EB 548 5 16025485
DS951 C32-1000MA/AC 3/11 EB 168 2 16021682
DS951 C32-100MA/A 3/12 EB 527 9 16025279
DS951 C32-100MA/AC 3/10 EB 147 6 16021476
DS951 C32-300MA/A 3/13 EB 534 5 16025345
DS951 C32-300MA/AC 3/11 EB 154 2 16021542
DS951 C32-30MA/A 3/12 EB 520 4 16025204
DS951 C32-30MA/AC 3/10 EB 140 1 16021401
DS951 C32-500MA/A 3/13 EB 541 0 16025410
DS951 C32-500MA/AC 3/11 EB 161 7 16021617
DS951 C40-1000MA/A 3/13 EB 549 3 16025493
DS951 C40-1000MA/AC 3/11 EB 169 0 16021690
DS951 C40-100MA/A 3/12 EB 528 7 16025287
DS951 C40-100MA/AC 3/10 EB 148 4 16021484
DS951 C40-300MA/A 3/13 EB 535 2 16025352
DS951 C40-300MA/AC 3/11 EB 155 9 16021559
DS951 C40-30MA/A 3/12 EB 521 2 16025212
DS951 C40-30MA/AC 3/10 EB 141 9 16021419
DS951 C40-500MA/A 3/13 EB 542 8 16025428
DS951 C40-500MA/AC 3/11 EB 162 5 16021625
DS951 C6-1000MA/A 3/13 EB 543 6 16025436
DS951 C6-1000MA/AC 3/11 EB 163 3 16021633
DS951 C6-100MA/A 3/12 EB 522 0 16025220
DS951 C6-100MA/AC 3/10 EB 142 7 16021427
DS951 C6-300MA/A 3/13 EB 529 5 16025295
DS951 C6-300MA/AC 3/11 EB 149 2 16021492
DS951 C6-30MA/A 3/12 EB 515 4 16025154
DS951 C6-30MA/AC 3/10 EB 135 1 16021351
DS951 C6-500MA/A 3/13 EB 536 0 16025360
DS951 C6-500MA/AC 3/11 EB 156 7 16021567
DS971 B10-1000MA/A 3/17 EB 604 6 16026046
DS971 B10-1000MA/AC 3/15 EB 224 3 16022243
DS971 B10-100MA/A 3/16 EB 583 2 16025832
DS971 B10-100MA/AC 3/14 EB 203 7 16022037
DS971 B10-300MA/A 3/17 EB 590 7 16025907
DS971 B10-300MA/AC 3/15 EB 210 2 16022102
DS971 B10-30MA/A 3/16 EB 576 6 16025766
DS971 B10-30MA/AC 3/14 EB 196 3 16021963
14/16 ABB SACE
Code list
Type
Type Pg. Elc code Order code Type Pg. Elc code Order code Type Pg. Elc code Order code
14
DS971 B10-500MA/A 3/17 EB 597 2 16025972
DS971 B10-500MA/AC 3/15 EB 217 7 16022177
DS971 B16-10000MA/A 3/17 EB 605 3 16026053
DS971 B16-10000MA/AC 3/15 EB 225 0 16022250
DS971 B16-1000MA/A 3/16 EB 584 0 16025840
DS971 B16-1000MA/AC 3/14 EB 204 5 16022045
DS971 B16-3000MA/A 3/17 EB 591 5 16025915
DS971 B16-3000MA/AC 3/15 EB 211 0 16022110
DS971 B16-30MA/A 3/16 EB 577 4 16025774
DS971 B16-30MA/AC 3/14 EB 197 1 16021971
DS971 B16-5000MA/A 3/17 EB 598 0 16025980
DS971 B16-5000MA/AC 3/15 EB 218 5 16022185
DS971 B20-1000MA/A 3/17 EB 606 1 16026061
DS971 B20-1000MA/AC 3/15 EB 226 8 16022268
DS971 B20-100MA/A 3/16 EB 585 7 16025857
DS971 B20-100MA/AC 3/14 EB 205 2 16022052
DS971 B20-300MA/A 3/17 EB 592 3 16025923
DS971 B20-300MA/AC 3/15 EB 212 8 16022128
DS971 B20-30MA/A 3/16 EB 578 2 16025782
DS971 B20-30MA/AC 3/14 EB 198 9 16021989
DS971 B20-500MA/A 3/17 EB 599 8 16025998
DS971 B20-500MA/AC 3/15 EB 219 3 16022193
DS971 B25-1000MA/A 3/17 EB 607 9 16026079
DS971 B25-1000MA/AC 3/15 EB 227 6 16022276
DS971 B25-100MA/A 3/16 EB 586 5 16025865
DS971 B25-100MA/AC 3/14 EB 206 0 16022060
DS971 B25-300MA/A 3/17 EB 593 1 16025931
DS971 B25-300MA/AC 3/15 EB 213 6 16022136
DS971 B25-30MA/A 3/16 EB 579 0 16025790
DS971 B25-30MA/AC 3/14 EB 199 7 16021997
DS971 B25-500MA/A 3/17 EB 600 4 16026004
DS971 B25-500MA/AC 3/15 EB 220 1 16022201
DS971 B32-1000MA/A 3/17 EB 608 7 16026087
DS971 B32-1000MA/AC 3/15 EB 228 4 16022284
DS971 B32-100MA/A 3/16 EB 587 3 16025873
DS971 B32-100MA/AC 3/14 EB 207 8 16022078
DS971 B32-300MA/A 3/17 EB 594 9 16025949
DS971 B32-300MA/AC 3/15 EB 214 4 16022144
DS971 B32-30MA/A 3/16 EB 580 8 16025808
DS971 B32-30MA/AC 3/14 EB 200 3 16022003
DS971 B32-500MA/A 3/17 EB 601 2 16026012
DS971 B32-500MA/AC 3/15 EB 221 9 16022219
DS971 B40-1000MA/A 3/17 EB 609 5 16026095
DS971 B40-1000MA/AC 3/15 EB 229 2 16022292
DS971 B40-100MA/A 3/16 EB 588 1 16025881
DS971 B40-100MA/AC 3/14 EB 208 6 16022086
DS971 B40-300MA/A 3/17 EB 595 6 16025956
DS971 B40-300MA/AC 3/15 EB 215 1 16022151
DS971 B40-30MA/A 3/16 EB 581 6 16025816
DS971 B40-30MA/AC 3/14 EB 201 1 16022011
DS971 B40-500MA/A 3/17 EB 602 0 16026020
DS971 B40-500MA/AC 3/15 EB 222 7 16022227
DS971 B6-1000MA/A 3/17 EB 603 8 16026038
DS971 B6-1000MA/AC 3/15 EB 223 5 16022235
DS971 B6-100MA/A 3/16 EB 582 4 16025824
DS971 B6-100MA/AC 3/14 EB 202 9 16022029
DS971 B6-300MA/A 3/17 EB 589 9 16025899
DS971 B6-300MA/AC 3/15 EB 209 4 16022094
DS971 B6-30MA/A 3/16 EB 575 8 16025758
DS971 B6-30MA/AC 3/14 EB 195 5 16021955
DS971 B6-500MA/A 3/17 EB 596 4 16025964
DS971 B6-500MA/AC 3/15 EB 216 9 16022169
DS971 C10-1000MA/A 3/17 EB 694 7 16026947
DS971 C10-1000MA/AC 3/15 EB 344 9 16023449
DS971 C10-100MA/A 3/16 EB 673 1 16026731
DS971 C10-100MA/AC 3/14 EB 323 3 16023233
DS971 C10-300MA/A 3/17 EB 680 6 16026806
DS971 C10-300MA/AC 3/15 EB 330 8 16023308
DS971 C10-30MA/A 3/16 EB 666 5 16026665
DS971 C10-30MA/AC 3/14 EB 316 7 16023167
DS971 C10-500MA/A 3/17 EB 687 1 16026871
DS971 C10-500MA/AC 3/15 EB 337 3 16023373
DS971 C16-1000MA/A 3/17 EB 695 4 16026954
DS971 C16-1000MA/AC 3/15 EB 345 6 16023456
DS971 C16-100MA/A 3/16 EB 674 9 16026749
DS971 C16-100MA/AC 3/14 EB 324 1 16023241
DS971 C16-300MA/A 3/17 EB 681 4 16026814
DS971 C16-300MA/AC 3/15 EB 331 6 16023316
DS971 C16-30MA/A 3/16 EB 667 3 16026673
DS971 C16-30MA/AC 3/14 EB 317 5 16023175
DS971 C16-500MA/A 3/17 EB 688 9 16026889
DS971 C16-500MA/AC 3/15 EB 338 1 16023381
DS971 C20-1000MA/A 3/17 EB 696 2 16026962
DS971 C20-1000MA/AC 3/15 EB 346 4 16023464
DS971 C20-100MA/A 3/16 EB 675 6 16026756
DS971 C20-100MA/AC 3/14 EB 325 8 16023258
DS971 C20-300MA/A 3/17 EB 682 2 16026822
DS971 C20-300MA/AC 3/15 EB 332 4 16023324
DS971 C20-30MA/A 3/16 EB 668 1 16026681
DS971 C20-30MA/AC 3/14 EB 318 3 16023183
DS971 C20-500MA/A 3/17 EB 689 7 16026897
DS971 C20-500MA/AC 3/15 EB 339 9 16023399
DS971 C25-1000MA/A 3/17 EB 697 0 16026970
DS971 C25-1000MA/AC 3/15 EB 347 2 16023472
DS971 C25-100MA/A 3/16 EB 676 4 16026764
DS971 C25-100MA/AC 3/14 EB 326 6 16023266
DS971 C25-300MA/A 3/17 EB 683 0 16026830
DS971 C25-300MA/AC 3/15 EB 333 2 16023332
DS971 C25-30MA/A 3/16 EB 669 9 16026699
DS971 C25-30MA/AC 3/14 EB 319 1 16023191
DS971 C25-500MA/A 3/17 EB 690 5 16026905
DS971 C25-500MA/AC 3/15 EB 340 7 16023407
DS971 C32-1000MA/A 3/17 EB 698 8 16026988
DS971 C32-1000MA/AC 3/15 EB 348 0 16023480
DS971 C32-100MA/A 3/16 EB 677 2 16026772
DS971 C32-100MA/AC 3/14 EB 327 4 16023274
DS971 C32-300MA/A 3/17 EB 684 8 16026848
DS971 C32-300MA/AC 3/15 EB 334 0 16023340
DS971 C32-30MA/A 3/16 EB 670 7 16026707
DS971 C32-30MA/AC 3/14 EB 320 9 16023209
DS971 C32-500MA/A 3/17 EB 691 3 16026913
DS971 C32-500MA/AC 3/15 EB 341 5 16023415
DS971 C40-1000MA/A 3/17 EB 699 6 16026996
DS971 C40-1000MA/AC 3/15 EB 349 8 16023498
DS971 C40-100MA/A 3/16 EB 678 0 16026780
DS971 C40-100MA/AC 3/14 EB 328 2 16023282
DS971 C40-300MA/A 3/17 EB 685 5 16026855
DS971 C40-300MA/AC 3/15 EB 335 7 16023357
DS971 C40-30MA/A 3/16 EB 671 5 16026715
DS971 C40-30MA/AC 3/14 EB 321 7 16023217
DS971 C40-500MA/A 3/17 EB 692 1 16026921
DS971 C40-500MA/AC 3/15 EB 342 3 16023423
DS971 C6-1000MA/A 3/17 EB 693 9 16026939
DS971 C6-1000MA/AC 3/15 EB 343 1 16023431
DS971 C6-100MA/A 3/16 EB 672 3 16026723
DS971 C6-100MA/AC 3/14 EB 322 5 16023225
DS971 C6-300MA/A 3/17 EB 679 8 16026798
DS971 C6-300MA/AC 3/15 EB 329 0 16023290
DS971 C6-30MA/A 3/16 EB 665 7 16026657
DS971 C6-30MA/AC 3/14 EB 315 9 16023159
DS971 C6-500MA/A 3/17 EB 686 3 16026863
DS971 C6-500MA/AC 3/15 EB 336 5 16023365
DTS 1/1 6/4 EA 554 4 16015544
DTS 7/1 6/4 EA 555 1 16015551
DTS 7/2 6/4 EA 556 9 16015569
DTS 7/2 I 6/4 EA 557 7 16015577
DTS 7/3 6/4 EA 558 5 16015585
E 10/230 5/9 EF 915 2 16069152
E 1175 8/5 EA 943 9 16019439
E 1175-C 8/5 EA 942 1 16019421
E 220-B 5/9 EF 926 9 16069269
E 220-B3 5/9 EF 929 3 16069293
E 220-C 5/9 EF 924 4 16069244
E 220-C3 5/9 EF 927 7 16069277
E 220-D 5/9 EF 925 1 16069251
E 220-D3 5/9 EF 928 5 16069285
E 220-E 5/9 EA 723 5 16017235
E 220-E3 5/9 EA 724 3 16017243
E 220-G 5/9 EA 172 5 16011725
E 221-10 5/6 EF 901 2 16069012
E 221-10X 5/6 EF 909 5 16069095
E 221-11 5/6 EA 151 9 16011519
E 221-20 5/6 EF 903 8 16069038
E 221-20X 5/6 EF 910 3 16069103
E 221-22 5/6 EA 152 7 16011527
E 221-30 5/6 EF 905 3 16069053
E 221-30X 5/6 EA 150 1 16011501
E 221-31 5/6 EA 153 5 16011535
E 221-4 5/6 EF 913 7 16069137
E 221-4/2 5/6 EF 914 5 16069145
E 221-40 5/6 EF 907 9 16069079
E 221-6 5/6 EF 911 1 16069111
E 221-6/2 5/6 EF 912 9 16069129
E 222-10 5/7 EA 154 3 16011543
E 222-10X 5/7 EF 916 0 16069160
E 222-11 5/7 EA 159 2 16011592
E 222-20 5/7 EA 155 0 16011550
E 222-20X 5/7 EF 917 8 16069178
E 222-30 5/7 EA 156 8 16011568
E 222-30X 5/7 EA 158 4 16011584
E 222-4 5/7 EF 919 4 16069194
E 222-40 5/7 EA 157 6 16011576
E 222-6 5/7 EF 918 6 16069186
E 223-10 5/7 EF 902 0 16069020
E 223-20 5/7 EF 904 6 16069046
E 223-30 5/7 EF 906 1 16069061
E 223-40 5/7 EF 908 7 16069087
E 225-11B 5/8 EF 920 2 16069202
E 225-11C 5/8 EA 715 1 16017151
E 225-11D 5/8 EA 716 9 16017169
E 225-11E 5/8 EA 717 7 16017177
E 227-11B 5/8 EA 718 5 16017185
E 227-11C 5/8 EF 921 0 16069210
E 227-11D 5/8 EF 922 8 16069228
E 227-11E 5/8 EA 719 3 16017193
E 228-WM 6/12 EF 930 1 16069301
E 229-B 5/8 EA 720 1 16017201
E 229-C 5/8 EF 923 6 16069236
E 229-D 5/8 EA 721 9 16017219
E 229-E 5/8 EA 722 7 16017227
E 232-230 6/5 EA 519 7 36015197
E 232E-230 6/5 EA 520 5 36015205
E 232E-8/230 6/5 EA 523 9 36015239
E 233 12/48 7/14 EG 593 6 36075936
E 233-230 7/14 EG 595 1 36075951
E 233-24 7/14 EG 594 4 36075944
E 234-AV 6/2 EA 635 1 36016351
E 234-AW 6/2 EA 638 5 36016385
E 234-EW 6/2 EA 639 3 36016393
E 234-MFR 6/2 EA 634 4 36016344
E 234-RV 6/2 EA 636 9 36016369
E 234-TI2 6/2 EA 642 7 36016427
E 241/16 5/2 EF 931 9 36069319
E 241/32 5/2 EF 935 0 36069350
E 241/45 5/2 EF 939 2 36069392
E 242/16 5/2 EF 932 7 36069327
E 242/32 5/2 EF 936 8 36069368
E 242/45 5/2 EF 940 0 36069400
E 243/16 5/3 EF 933 5 36069335
E 243/32 5/3 EF 937 6 36069376
E 243/45 5/3 EF 941 8 36069418
E 244/16 5/3 EF 934 3 36069343
E 244/32 5/3 EF 938 4 36069384
E 244/45 5/3 EF 942 6 36069426
E 251-12 V 5/14 EA 584 1 36015841
E 251-230 V 5/14 EA 382 0 36013820
E 251-24 V 5/14 EA 381 2 36013812
E 251-8V 5/14 EA 380 4 36013804
E 252-12 V 5/14 EA 585 8 36015858
E 252-230 V 5/14 EA 385 3 36013853
E 252-24 V 5/14 EA 384 6 36013846
E 252-8 V 5/14 EA 383 8 36013838
E 254-12 V 5/14 EA 586 6 36015866
E 254-230 V 5/14 EA 388 7 36013887
E 254-24 V 5/14 EA 387 9 36013879
E 254-8 V 5/14 EA 386 1 36013861
E 255-12 V 5/14 EA 581 7 36015817
E 255-230 V 5/14 EA 583 3 36015833
E 255-24 V 5/14 EA 582 5 36015825
E 255-8 V 5/14 EA 580 9 36015809
E 256-12V 5/14 EA 587 4 36015874
E 256-230 V 5/14 EA 391 1 36013911
E 256-24 V 5/14 EA 390 3 36013903
E 256-8 V 5/14 EA 389 5 36013895
E 259 R10-12V 5/13 EA 589 0 36015890
E 259 R10-230V 5/13 EA 591 6 36015916
E 259 R10-24V 5/13 EA 590 8 36015908
E 259 R10-8V 5/13 EA 588 2 36015882
E 259 R11-12V 5/13 EA 593 2 36015932
E 259 R11-230V 5/13 EA 595 7 36015957
E 259 R11-24V 5/13 EA 594 0 36015940
E 259 R11-8V 5/13 EA 592 4 36015924
E 259 R20-12V 5/13 EA 597 3 36015973
E 259 R20-230V 5/13 EA 599 9 36015999
E 259 R20-24V 5/13 EA 598 1 36015981
E 259 R20-8V 5/13 EA 596 5 36015965
E 261 C-12 V 5/17 EA 618 7 36016187
E 261 C-230 V 5/17 EA 620 3 36016203
E 261 C-24 V 5/17 EA 619 5 36016195
E 261-230 V 5/16 EA 611 2 36016112
14/17
ABB SACE
Code list
Type
Type Pg. Elc code Order code Type Pg. Elc code Order code Type Pg. Elc code Order code
14
E 261-24 V 5/16 EA 610 4 36016104
E 262 C-12 V 5/17 EA 621 1 36016211
E 262 C-230 V 5/17 EA 623 7 36016237
E 262 C-24 V 5/17 EA 622 9 36016229
E 262-230 V 5/16 EA 614 6 36016146
E 262-24 V 5/16 EA 613 8 36016138
E 266 C-12 V 5/17 EA 624 5 36016245
E 266 C-230 V 5/17 EA 626 0 36016260
E 266 C-24 V 5/17 EA 625 2 36016252
E 266-230 V 5/16 EA 617 9 36016179
E 266-24 V 5/16 EA 616 1 36016161
E 271/100 5/2 EF 944 2 36069442
E 271/125 5/2 EF 973 1 36069731
E 271/63 5/2 EF 950 9 36069509
E 271/80 5/2 EF 943 4 36069434
E 272/100 5/2 EF 957 4 36069574
E 272/125 5/2 EF 960 8 36069608
E 272/63 5/2 EF 951 7 36069517
E 272/80 5/2 EF 954 1 36069541
E 273/100 5/3 EF 958 2 36069582
E 273/125 5/3 EF 961 6 36069616
E 273/63 5/2 EF 952 5 36069525
E 273/80 5/3 EF 955 8 36069558
E 274/100 5/3 EF 959 0 36069590
E 274/125 5/3 EF 962 4 36069624
E 274/63 5/2 EF 953 3 36069533
E 274/80 5/3 EF 956 6 36069566
E 930/ACP125 4/11 EA 070 1 16010701
E 930/ACP50 4/11 EA 069 3 16010693
E 930/KIT 4/11 EA 211 1 16012111
E 930/MCR1P125 4/11 EA 067 7 16010677
E 930/MCR1P50 4/11 EA 065 1 16010651
E 930/MCR3P125 4/11 EA 068 5 16010685
E 930/MCR3P50 4/11 EA 066 9 16010669
E 931/125 4/11 EA 058 6 16010586
E 931/20 4/10 EA 191 5 16011915
E 931/32 4/10 EA 201 2 16012012
E 931/50 4/11 EA 051 1 16010511
E 931N/125 4/11 EA 059 4 16010594
E 931N/20 4/10 EA 291 3 16012913
E 931N/32 4/10 EA 293 9 16012939
E 931N/50 4/11 EA 052 9 16010529
E 932/125 4/11 EA 060 2 16010602
E 932/20 4/10 EA 193 1 16011931
E 932/32 4/10 EA 203 8 16012038
E 932/50 4/11 EA 053 7 16010537
E 933/125 4/11 EA 061 0 16010610
E 933/20 4/10 EA 194 9 16011949
E 933/32 4/10 EA 204 6 16012046
E 933/50 4/11 EA 054 5 16010545
E 933N/125 4/11 EA 062 8 16010628
E 933N/20 4/10 EA 292 1 16012921
E 933N/32 4/10 EA 294 7 16012947
E 933N/50 4/11 EA 055 2 16010552
E10/110 5/9 EA 177 4 16011774
E10/12 5/9 EA 173 3 16011733
E10/24 5/9 EA 174 1 16011741
E10/48 5/9 EA 175 8 16011758
E10/60 5/9 EA 176 6 16011766
E220-B1 5/9 EA 167 5 16011675
E220-C1 5/9 EA 168 3 16011683
E220-D1 5/9 EA 169 1 16011691
E220-E1 5/9 EA 170 9 16011709
E220-G1 5/9 EA 171 7 16011717
E225-11F 5/8 EA 160 0 16011600
E225-11G 5/8 EA 161 8 16011618
E225-11Z 5/8 EA 162 6 16011626
E227-11G 5/8 EA 163 4 16011634
E227-11Z 5/8 EA 164 2 16011642
E229-G 5/8 EA 165 9 16011659
E229-Z 5/8 EA 166 7 16011667
EE 20 7/17 KX 863 0 36248630
EE 20PR 7/17 KX 865 5 36248655
EE 20R 7/17 KX 864 8 36248648
EE 22Rr 7/17 KX 866 3 36248663
EE 22RR 7/17 KX 867 1 36248671
EH 04-11 5/11 EL 901 5 36129015
EH 04-20 5/11 EL 900 7 36129007
EK - B 2/47 EA 549 4 16015494
EK - C 2/47 EA 648 4 16016484
EK - C4 2/47 EA 649 2 16016492
EK - M 2/47 EA 550 2 16015502
EMT 3 7/17 EG 578 7 16075787
EN 20-20/230 5/12 EL 820 7 36128207
EN 24-30/230 5/12 EL 821 5 36128215
EN 24-40/230 5/12 EL 822 3 36128223
EN 40-20/230 5/12 EL 823 1 36128231
EN 40-30/230 5/12 EL 824 9 36128249
EN 40-40/230 5/12 EL 825 6 36128256
ESB 20-02/110 5/10 EL 877 7 36128777
ESB 20-02/12 5/10 EL 874 4 36128744
ESB 20-02/230 5/10 EL 878 5 36128785
ESB 20-02/24 5/10 EL 875 1 36128751
ESB 20-02/48 5/10 EL 876 9 36128769
ESB 20-11/110 5/10 EL 872 8 36128728
ESB 20-11/12 5/10 EL 869 4 36128694
ESB 20-11/230 5/10 EL 873 6 36128736
ESB 20-11/24 5/10 EL 870 2 36128702
ESB 20-11/48 5/10 EL 871 0 36128710
ESB 20-20/110 5/10 EL 882 7 36128827
ESB 20-20/12 5/10 EL 879 3 36128793
ESB 20-20/230 5/10 EL 883 5 36128835
ESB 20-20/24 5/10 EL 880 1 36128801
ESB 20-20/48 5/10 EL 881 9 36128819
ESB 24-40/12 5/10 EL 884 3 36128843
ESB 24-40/230 5/10 EL 888 4 36128884
ESB 24-40/24 5/10 EL 885 0 36128850
ESB 40-40/230 5/11 EL 893 4 36128934
ESB 40-40/24 5/11 EL 890 0 36128900
ESB 63-40/230 5/11 EL 898 3 36128983
ESB 63-40/24 5/11 EL 895 9 36128959
ESB-DIS 5/11 EL 902 3 36129023
ESB-PLK 24 5/11 EL 903 1 36129031
ESB-PLK 40/63 5/11 EL 904 9 36129049
EST 1 2/71 EG 046 5 36070465
EST 2 2/71 EG 047 3 36070473
ETS 1 6/3 EA 511 4 16015114
ETS 1/R 6/3 EA 512 2 16015122
ETS 7/R 6/3 EA 513 0 16015130
ETS-1M 6/3 EA 502 3 16015023
ETS-1RM 6/3 EA 503 1 16015031
ETS-KIT 6/3 EA 510 6 16015106
F 362 16/10MA 3/38 EY 600 9 16256009
F 362 25/300MA 3/38 EY 605 8 16256058
F 362 25/30MA 3/38 EY 601 7 16256017
F 362 40/300MA 3/38 EY 606 6 16256066
F 362 40/30MA 3/38 EY 602 5 16256025
F 362 63/300MA 3/38 EY 607 4 16256074
F 362 63/30MA 3/38 EY 603 3 16256033
F 362 80/300MA 3/38 EY 608 2 16256082
F 362 80/30MA 3/38 EY 604 1 16256041
F 364 25/300MA 3/38 EY 625 6 16256256
F 364 25/30MA 3/38 EY 622 3 16256223
F 364 25/500MA 3/38 EY 628 0 16256280
F 364 40/300MA 3/38 EY 626 4 16256264
F 364 40/30MA 3/38 EY 623 1 16256231
F 364 40/500MA 3/38 EY 629 8 16256298
F 364 63/300MA 3/38 EY 627 2 16256272
F 364 63/30MA 3/38 EY 624 9 16256249
F 364 63/500MA 3/38 EY 630 6 16256306
F 372 16/10MA 3/40 EY 609 0 16256090
F 372 25/300MA 3/40 EY 614 0 16256140
F 372 25/30MA 3/40 EY 610 8 16256108
F 372 40/300MA 3/40 EY 615 7 16256157
F 372 40/30MA 3/40 EY 611 6 16256116
F 372 63/300MA 3/40 EY 616 5 16256165
F 372 63/30MA 3/40 EY 612 4 16256124
F 372 80/300MA 3/40 EY 617 3 16256173
F 372 80/30MA 3/40 EY 613 2 16256132
F 374 25/300MA 3/40 EY 634 8 16256348
F 374 25/30MA 3/40 EY 631 4 16256314
F 374 25/500MA 3/40 EY 637 1 16256371
F 374 40/300MA 3/40 EY 635 5 16256355
F 374 40/30MA 3/40 EY 632 2 16256322
F 374 40/500MA 3/40 EY 638 9 16256389
F 374 63/300MA 3/40 EY 636 3 16256363
F 374 63/30MA 3/40 EY 633 0 16256330
F 374 63/500MA 3/40 EY 639 7 16256397
F 374/400Hz 25 30 mA 3/44 EY 786 6 16257866
F 374/400Hz 40 30 mA 3/44 EY 787 4 16257874
F 804 63 30 mA 3/45 EY 788 2 36257882
F 804 63 300 mA 3/45 EY 789 0 36257890
F3-H.. CONTATTO AUX 3/46 KU 909 4 16219094
F362 AR 25 30 mA 3/43 EY 646 2 16256462
F362 AR 40 30 mA 3/43 EY 647 0 16256470
F364 AR 63 30 mA 3/43 EY 651 2 16256512
F364 AR 63 300 mA 3/43 EY 652 0 16256520
F372 AR 25 30 mA 3/43 EY 648 8 16256488
F372 AR 40 30 mA 3/43 EY 649 6 16256496
F374 AR 63 30 mA 3/43 EY 653 8 16256538
F392 40 300 mA 3/42 EY 618 1 16256181
F392 40 500 mA 3/42 EY 620 7 16256207
F392 63 300 mA 3/42 EY 619 9 16256199
F392 63 500 mA 3/42 EY 621 5 16256215
F394 40 300 mA 3/42 EY 640 5 16256405
F394 40 500 mA 3/42 EY 642 1 16256421
F394 63 300 mA 3/42 EY 641 3 16256413
F394 63 500 mA 3/42 EY 643 9 16256439
F394 AR 63 500 mA 3/43 EY 654 6 16256546
F6-H11 CONTATTO AUX 3/46 KU 904 5 36219045
F662 100 300mA 3/39 EB 879 4 36028794
F662 100 30mA 3/39 EB 877 8 36028778
F662 80 300mA 3/39 EB 878 6 36028786
F662 80 30mA 3/39 EB 876 0 36028760
F664 100 300mA 3/39 EB 884 4 36028844
F664 100 30mA 3/39 EB 881 0 36028810
F664 125 300mA 3/39 EB 966 9 36029669
F664 125 30mA 3/39 EB 947 9 36029479
F664 80 300mA 3/39 EB 883 6 36028836
F664 80 30mA 3/39 EB 880 2 36028802
F672 100 30mA 3/41 EB 893 5 36028935
F672 80 30mA 3/41 EB 892 7 36028927
F674 100 300mA 3/41 EB 890 1 36028901
F674 100 30mA 3/41 EB 887 7 36028877
F674 125 300mA 3/41 EB 998 2 36029982
F674 125 30mA 3/41 EB 950 3 36029503
F674 80 300mA 3/41 EB 889 3 36028893
F674 80 30mA 3/41 EB 886 9 36028869
FERMO END 2/45 EA 215 2 36012152
FP 1 2/45 EB 176 5 16021765
FP 2 2/45 EB 177 3 16021773
FP 4 2/45 EB 178 1 16021781
FP 6 2/45 EB 179 9 16021799
FRZ 1 7/2 EG 060 6 16070606
FRZ-D1 7/4 EG 410 3 16074103
GA 02 4/9 EP 893 0 36168930
HK 02 4/8 EP 844 3 36168443
HK 11 4/8 EP 842 7 36168427
HK 20 4/8 EP 843 5 36168435
HKF11 4/8 EP 977 1 36169771
HKF20 4/8 EP 978 9 36169789
HMT 1/110 7/14 EG 402 0 16074020
HMT 1/220 7/14 EG 403 8 16074038
HMT 1/24 7/14 EG 401 2 16074012
HMT 11 7/14 EG 107 5 16071075
ISOLTESTER-C [NEW] 7/18 EB 246 6 16022466
KA 1 2/71 EG 037 4 36070374
LE-230 6/11 EG 296 6 16072966
LS-1 6/7 EG 574 6 16075746
LSS1/2 6/9 EG 417 8 16074178
M 1173 8/5 EA 944 7 16019447
M 1174 8/5 EA 945 4 16019454
M 2061 4/12 EA 948 8 16019488
M 2061 Na 4/12 EA 949 6 16019496
M 2062 4/12 EA 950 4 16019504
M 2063 4/12 EA 951 2 16019512
M 2063 Na 4/12 EA 952 0 16019520
M 2161 4/12 EA 953 8 16019538
M 2161 Na 4/12 EA 954 6 16019546
M 2162 4/12 EA 955 3 16019553
M 2163 4/12 EA 956 1 16019561
M 2163 Na 4/12 EA 957 9 16019579
M 281 In=0,5A 2/36 KU 470 7 16214707
M 281 In=1,6A 2/36 KU 472 3 16214723
M 281 In=10A 2/36 KU 476 4 16214764
M 281 In=12,5A 2/36 KU 477 2 16214772
M 281 In=16A 2/36 KU 478 0 16214780
M 281 In=1A 2/36 KU 471 5 16214715
14/18 ABB SACE
Code list
Type
Type Pg. Elc code Order code Type Pg. Elc code Order code Type Pg. Elc code Order code
14
M 281 In=2,5A 2/36 KU 473 1 16214731
M 281 In=20A 2/36 KU 479 8 16214798
M 281 In=25A 2/36 KU 480 6 16214806
M 281 In=32A 2/36 KU 481 4 16214814
M 281 In=40A 2/36 KU 482 2 16214822
M 281 In=4A 2/36 KU 474 9 16214749
M 281 In=50A 2/36 KU 483 0 16214830
M 281 In=6,3A 2/36 KU 475 6 16214756
M 281 In=63A 2/36 KU 484 8 16214848
M 282 In=0,5A 2/36 KU 602 5 16216025
M 282 In=1,6A 2/36 KU 604 1 16216041
M 282 In=10A 2/36 KU 608 2 16216082
M 282 In=12,5A 2/36 KU 609 0 16216090
M 282 In=16A 2/36 KU 610 8 16216108
M 282 In=1A 2/36 KU 603 3 16216033
M 282 In=2,5A 2/36 KU 605 8 16216058
M 282 In=20A 2/36 KU 611 6 16216116
M 282 In=25A 2/36 KU 612 4 16216124
M 282 In=32A 2/36 KU 613 2 16216132
M 282 In=40A 2/36 KU 614 0 16216140
M 282 In=4A 2/36 KU 606 6 16216066
M 282 In=50A 2/36 KU 615 7 16216157
M 282 In=6,3A 2/36 KU 607 4 16216074
M 282 In=63A 2/36 KU 616 5 16216165
M 283 In=0,5A 2/37 KU 617 3 16216173
M 283 In=1,6A 2/37 KU 619 9 16216199
M 283 In=10A 2/37 KU 623 1 16216231
M 283 In=12,5A 2/37 KU 624 9 16216249
M 283 In=16A 2/37 KU 625 6 16216256
M 283 In=1A 2/37 KU 618 1 16216181
M 283 In=2,5A 2/37 KU 620 7 16216207
M 283 In=20A 2/37 KU 626 4 16216264
M 283 In=25A 2/37 KU 627 2 16216272
M 283 In=32A 2/37 KU 628 0 16216280
M 283 In=40A 2/37 KU 629 8 16216298
M 283 In=4A 2/37 KU 621 5 16216215
M 283 In=50A 2/37 KU 630 6 16216306
M 283 In=6,3A 2/37 KU 622 3 16216223
M 283 In=63A 2/37 KU 631 4 16216314
M 284 In=0,5A 2/37 KU 632 2 16216322
M 284 In=1,6A 2/37 KU 634 8 16216348
M 284 In=10A 2/37 KU 638 9 16216389
M 284 In=12,5A 2/37 KU 639 7 16216397
M 284 In=16A 2/37 KU 640 5 16216405
M 284 In=1A 2/37 KU 633 0 16216330
M 284 In=2,5A 2/37 KU 635 5 16216355
M 284 In=20A 2/37 KU 641 3 16216413
M 284 In=25A 2/37 KU 642 1 16216421
M 284 In=32A 2/37 KU 643 9 16216439
M 284 In=40A 2/37 KU 644 7 16216447
M 284 In=4A 2/37 KU 636 3 16216363
M 284 In=50A 2/37 KU 645 4 16216454
M 284 In=6,3A 2/37 KU 637 1 16216371
M 284 In=63A 2/37 KU 646 2 16216462
M 9100 8/6 EA 947 0 16019470
MCA 4 7/6 EG 592 8 16075928
MCV 4 7/6 EG 590 2 16075902
MCV 7 7/6 EG 591 0 16075910
ME 1 2/45 KU 930 0 16219300
ME 2 2/45 KU 931 8 16219318
ME 3 2/45 KU 932 6 16219326
ME 4 2/45 KU 933 4 16219334
ME 6 2/45 KU 934 2 16219342
ME 8 2/45 KU 935 9 16219359
MR/35 S 2/47 EA 546 0 16015460
MS 225/0,16 4/7 EP 680 1 36166801
MS 225/0,25 4/7 EP 681 9 36166819
MS 225/0,4 4/7 EP 682 7 36166827
MS 225/0,63 4/7 EP 683 5 36166835
MS 225/1,0 4/7 EP 684 3 36166843
MS 225/1,6 4/7 EP 685 0 36166850
MS 225/12,5 4/7 EP 690 0 36166900
MS 225/16 4/7 EP 691 8 36166918
MS 225/2,5 4/7 EP 686 8 36166868
MS 225/20 4/7 EP 692 6 36166926
MS 225/25 4/7 EP 693 4 36166934
MS 225/4,0 4/7 EP 687 6 36166876
MS 225/6,3 4/7 EP 688 4 36166884
MS 225/9 4/7 EP 689 2 36166892
MTM 7/5 EG 616 5 16076165
MTME 7/5 EA 140 2 16011402
MTME-485 7/5 EA 142 8 16011428
MTME-I 7/5 EA 141 0 16011410
OHB 2AJ 2/46 EO 010 2 36150102
OTPA325A1P1 [NEW] 4/9 EP 981 3 36169813
OTPA325A2P1 [NEW] 4/9 EP 983 9 36169839
OTPA325B1P1 [NEW] 4/9 EP 982 1 36169821
OTPA325B2P1 [NEW] 4/9 EP 984 7 36169847
OVR /115P 4/6 EA 836 5 16018365
OVR /140P 4/5 EA 838 1 16018381
OVR /15P 4/6 EA 860 5 16018605
OVR /165P 4/5 EA 840 7 16018407
OVR /315P 4/6 EA 837 3 16018373
OVR /340P 4/5 EA 839 9 16018399
OVR /365P 4/5 EA 841 5 16018415
OVR /40P 4/6 EA 861 3 16018613
OVR /65P 4/6 EA 862 1 16018621
OVR /BASE1N 4/6 EA 858 9 16018589
OVR /BASE3N 4/6 EA 859 7 16018597
OVR /N 4/6 EA 863 9 16018639
OVR/115 4/4 EA 876 1 16018761
OVR/140 4/3 EA 877 9 16018779
OVR/165 4/3 EA 878 7 16018787
OVR/315 4/4 EA 879 5 16018795
OVR/340 4/3 EA 880 3 16018803
OVR/365 4/3 EA 881 1 16018811
OVR/SIGN 4/4 EA 883 7 16018837
OVR/TEL 4/4 EA 882 9 16018829
OXS 5X 330 2/46 EO 070 6 36150706
PB 2/45 EC 068 3 36030683
PCD/N2 2/45 EB 185 6 36021856
PCD/N4 2/45 EB 186 4 36021864
PCD/N6 2/45 EB 187 2 36021872
PCD/N8 2/45 EB 188 0 36021880
PS3-2-0 4/9 EP 867 4 36168674
PS3-2-1 4/9 EP 868 2 36168682
PS3-2-2 4/9 EP 869 0 36168690
PS3-4-0 4/9 EP 870 8 36168708
PS3-4-1 4/9 EP 871 6 36168716
PS3-4-2 4/9 EP 872 4 36168724
QSD230/24-C [NEW] 7/19 EB 248 2 16022482
RAL3 6/8 EG 411 1 16074111
RAL6 6/8 EG 412 9 16074129
RD2 4/2 EG 316 2 16073089
RHI 6/13 EG 599 3 16075993
RHV 6/13 EG 597 7 16075977
RLI 6/13 EG 598 5 16075985
RLV 6/13 EG 596 9 16075969
RM1/12 8/4 EA 427 3 16014273
RM1/230 8/4 EA 428 1 16014281
RS 370/11 5/5 EA 129 5 36011295
RS 370/1S 5/5 EA 133 7 36011337
RS 370/3S 5/5 EA 134 5 36011345
RS 370/4P 5/5 EA 128 7 36011287
RS 370/SH 5/5 EA 132 9 36011329
RS 373/100 5/4 EA 123 8 36011238
RS 373/45 5/4 EA 120 4 36011204
RS 373/63 5/4 EA 121 2 36011212
RS 373/80 5/4 EA 122 0 36011220
RS 374/100 5/4 EA 127 9 36011279
RS 374/45 5/4 EA 124 6 36011246
RS 374/63 5/4 EA 125 3 36011253
RS 374/80 5/4 EA 126 1 36011261
S 241 C 10 2/22 EF 011 0 16060110
S 241 C 13 2/22 EF 017 7 16060177
S 241 C 16 2/22 EF 012 8 16060128
S 241 C 20 2/22 EF 013 6 16060136
S 241 C 25 2/22 EF 014 4 16060144
S 241 C 32 2/22 EF 015 1 16060151
S 241 C 40 2/22 EF 018 5 16060185
S 241 C 6 2/22 EF 010 2 16060102
S 241 C 8 2/22 EF 016 9 16060169
S 241 Na C 10 2/22 EF 021 9 16060219
S 241 Na C 13 2/22 EF 027 6 16060276
S 241 Na C 16 2/22 EF 022 7 16060227
S 241 Na C 20 2/22 EF 023 5 16060235
S 241 Na C 25 2/22 EF 024 3 16060243
S 241 Na C 32 2/22 EF 025 0 16060250
S 241 Na C 40 2/22 EF 028 4 16060284
S 241 Na C 6 2/22 EF 020 1 16060201
S 241 Na C 8 2/22 EF 026 8 16060268
S 242 C 10 2/22 EF 031 8 16060318
S 242 C 13 2/22 EF 037 5 16060375
S 242 C 16 2/22 EF 032 6 16060326
S 242 C 20 2/22 EF 033 4 16060334
S 242 C 25 2/22 EF 034 2 16060342
S 242 C 32 2/22 EF 035 9 16060359
S 242 C 40 2/22 EF 038 3 16060383
S 242 C 6 2/22 EF 030 0 16060300
S 242 C 8 2/22 EF 036 7 16060367
S 243 C 10 2/23 EF 041 7 16060417
S 243 C 13 2/23 EF 047 4 16060474
S 243 C 16 2/23 EF 042 5 16060425
S 243 C 20 2/23 EF 043 3 16060433
S 243 C 25 2/23 EF 044 1 16060441
S 243 C 32 2/23 EF 045 8 16060458
S 243 C 40 2/23 EF 048 2 16060482
S 243 C 6 2/23 EF 040 9 16060409
S 243 C 8 2/23 EF 046 6 16060466
S 244 C 10 2/23 EE 382 6 16053826
S 244 C 13 2/23 EE 383 4 16053834
S 244 C 16 2/23 EE 384 2 16053842
S 244 C 20 2/23 EE 385 9 16053859
S 244 C 25 2/23 EE 386 7 16053867
S 244 C 32 2/23 EE 387 5 16053875
S 244 C 40 2/23 EE 388 3 16053883
S 244 C 6 2/23 EE 380 0 16053800
S 244 C 8 2/23 EE 381 8 16053818
S 251 B 10 2/24 EF 112 6 16061126
S 251 B 13 2/24 EF 176 1 16061761
S 251 B 16 2/24 EF 113 4 16061134
S 251 B 20 2/24 EF 114 2 16061142
S 251 B 25 2/24 EF 115 9 16061159
S 251 B 32 2/24 EF 116 7 16061167
S 251 B 40 2/24 EF 117 5 16061175
S 251 B 50 2/24 EF 118 3 16061183
S 251 B 6 2/24 EF 110 0 16061100
S 251 B 63 2/24 EF 119 1 16061191
S 251 B 8 2/24 EF 111 8 16061118
S 251 C 0,5 2/24 EF 536 6 16065366
S 251 C 1 2/24 EF 537 4 16065374
S 251 C 1,6 2/24 EF 538 2 16065382
S 251 C 10 2/24 EF 062 3 16060623
S 251 C 13 2/24 EF 177 9 16061779
S 251 C 16 2/24 EF 063 1 16060631
S 251 C 2 2/24 EF 539 0 16065390
S 251 C 20 2/24 EF 064 9 16060649
S 251 C 25 2/24 EF 065 6 16060656
S 251 C 3 2/24 EF 540 8 16065408
S 251 C 32 2/24 EF 066 4 16060664
S 251 C 4 2/24 EF 541 6 16065416
S 251 C 40 2/24 EF 067 2 16060672
S 251 C 50 2/24 EF 068 0 16060680
S 251 C 6 2/24 EF 060 7 16060607
S 251 C 63 2/24 EF 069 8 16060698
S 251 C 8 2/24 EF 061 5 16060615
S 251 D 0,5 2/24 11178108 11178108
S 251 D 1 2/24 11178109 11178109
S 251 D 1,6 2/24 11178110 11178110
S 251 D 10 2/24 11178115 11178115
S 251 D 16 2/24 11178116 11178116
S 251 D 2 2/24 11178111 11178111
S 251 D 20 2/24 11178117 11178117
S 251 D 25 2/24 11178118 11178118
S 251 D 3 2/24 11178112 11178112
S 251 D 32 2/24 11178119 11178119
S 251 D 4 2/24 11178113 11178113
S 251 D 40 2/24 11178120 11178120
S 251 D 50 2/24 11178121 11178121
S 251 D 6 2/24 11178114 11178114
S 251 D 63 2/24 11178122 11178122
S 251 K 0,5 2/24 EF 160 5 16061605
S 251 K 1 2/24 EF 161 3 16061613
S 251 K 1,6 2/24 EF 162 1 16061621
S 251 K 10 2/24 EF 168 8 16061688
S 251 K 16 2/24 EF 169 6 16061696
S 251 K 2 2/24 EF 163 9 16061639
S 251 K 20 2/24 EF 170 4 16061704
S 251 K 25 2/24 EF 171 2 16061712
S 251 K 3 2/24 EF 164 7 16061647
S 251 K 32 2/24 EF 172 0 16061720
S 251 K 4 2/24 EF 165 4 16061654
14/19
ABB SACE
Code list
Type
Type Pg. Elc code Order code Type Pg. Elc code Order code Type Pg. Elc code Order code
14
S 251 K 40 2/24 EF 173 8 16061738
S 251 K 50 2/24 EF 174 6 16061746
S 251 K 6 2/24 EF 166 2 16061662
S 251 K 63 2/24 EF 175 3 16061753
S 251 K 8 2/24 EF 167 0 16061670
S 251 Na B 10 2/25 EF 122 5 16061225
S 251 Na B 13 2/25 EF 196 9 16061969
S 251 Na B 16 2/25 EF 123 3 16061233
S 251 Na B 20 2/25 EF 124 1 16061241
S 251 Na B 25 2/25 EF 125 8 16061258
S 251 Na B 32 2/25 EF 126 6 16061266
S 251 Na B 40 2/25 EF 127 4 16061274
S 251 Na B 50 2/25 EF 128 2 16061282
S 251 Na B 6 2/25 EF 120 9 16061209
S 251 Na B 63 2/25 EF 129 0 16061290
S 251 Na B 8 2/25 EF 121 7 16061217
S 251 Na C 0,5 2/25 EF 542 4 16065424
S 251 Na C 1 2/25 EF 543 2 16065432
S 251 Na C 1,6 2/25 EF 544 0 16065440
S 251 Na C 10 2/25 EF 072 2 16060722
S 251 Na C 13 2/25 EF 197 7 16061977
S 251 Na C 16 2/25 EF 073 0 16060730
S 251 Na C 2 2/25 EF 545 7 16065457
S 251 Na C 20 2/25 EF 074 8 16060748
S 251 Na C 25 2/25 EF 075 5 16060755
S 251 Na C 3 2/25 EF 546 5 16065465
S 251 Na C 32 2/25 EF 076 3 16060763
S 251 Na C 4 2/25 EF 547 3 16065473
S 251 Na C 40 2/25 EF 077 1 16060771
S 251 Na C 50 2/25 EF 078 9 16060789
S 251 Na C 6 2/25 EF 070 6 16060706
S 251 Na C 63 2/25 EF 079 7 16060797
S 251 Na C 8 2/25 EF 071 4 16060714
S 251 Na K 0,5 2/25 EF 180 3 16061803
S 251 Na K 1 2/25 EF 181 1 16061811
S 251 Na K 1,6 2/25 EF 182 9 16061829
S 251 Na K 10 2/25 EF 188 6 16061886
S 251 Na K 16 2/25 EF 189 4 16061894
S 251 Na K 2 2/25 EF 183 7 16061837
S 251 Na K 20 2/25 EF 190 2 16061902
S 251 Na K 25 2/25 EF 191 0 16061910
S 251 Na K 3 2/25 EF 184 5 16061845
S 251 Na K 32 2/25 EF 192 8 16061928
S 251 Na K 4 2/25 EF 185 2 16061852
S 251 Na K 40 2/25 EF 193 6 16061936
S 251 Na K 50 2/25 EF 194 4 16061944
S 251 Na K 6 2/25 EF 186 0 16061860
S 251 Na K 63 2/25 EF 195 1 16061951
S 251 Na K 8 2/25 EF 187 8 16061878
S 252 B 10 2/26 EF 132 4 16061324
S 252 B 13 2/26 EF 216 5 16062165
S 252 B 16 2/26 EF 133 2 16061332
S 252 B 20 2/26 EF 134 0 16061340
S 252 B 25 2/26 EF 135 7 16061357
S 252 B 32 2/26 EF 136 5 16061365
S 252 B 40 2/26 EF 137 3 16061373
S 252 B 50 2/26 EF 138 1 16061381
S 252 B 6 2/26 EF 130 8 16061308
S 252 B 63 2/26 EF 139 9 16061399
S 252 B 8 2/26 EF 131 6 16061316
S 252 C 0,5 2/26 EF 548 1 16065481
S 252 C 1 2/26 EF 549 9 16065499
S 252 C 1,6 2/26 EF 550 7 16065507
S 252 C 10 2/26 EF 082 1 16060821
S 252 C 13 2/26 EF 217 3 16062173
S 252 C 16 2/26 EF 083 9 16060839
S 252 C 2 2/26 EF 551 5 16065515
S 252 C 20 2/26 EF 084 7 16060847
S 252 C 25 2/26 EF 085 4 16060854
S 252 C 3 2/26 EF 552 3 16065523
S 252 C 32 2/26 EF 086 2 16060862
S 252 C 4 2/26 EF 553 1 16065531
S 252 C 40 2/26 EF 087 0 16060870
S 252 C 50 2/26 EF 088 8 16060888
S 252 C 6 2/26 EF 080 5 16060805
S 252 C 63 2/26 EF 089 6 16060896
S 252 C 8 2/26 EF 081 3 16060813
S 252 D 0,5 2/26 11178123 11178123
S 252 D 1 2/26 11178124 11178124
S 252 D 1,6 2/26 11178125 11178125
S 252 D 10 2/26 11178130 11178130
S 252 D 16 2/26 11178131 11178131
S 252 D 2 2/26 11178126 11178126
S 252 D 20 2/26 11178132 11178132
S 252 D 25 2/26 11178133 11178133
S 252 D 3 2/26 11178127 11178127
S 252 D 32 2/26 11178134 11178134
S 252 D 4 2/26 11178128 11178128
S 252 D 40 2/26 11178135 11178135
S 252 D 50 2/26 11178136 11178136
S 252 D 6 2/26 11178129 11178129
S 252 D 63 2/26 11178137 11178137
S 252 K 0,5 2/26 EF 200 9 16062009
S 252 K 1 2/26 EF 201 7 16062017
S 252 K 1,6 2/26 EF 202 5 16062025
S 252 K 10 2/26 EF 208 2 16062082
S 252 K 16 2/26 EF 209 0 16062090
S 252 K 2 2/26 EF 203 3 16062033
S 252 K 20 2/26 EF 210 8 16062108
S 252 K 25 2/26 EF 211 6 16062116
S 252 K 3 2/26 EF 204 1 16062041
S 252 K 32 2/26 EF 212 4 16062124
S 252 K 4 2/26 EF 205 8 16062058
S 252 K 40 2/26 EF 213 2 16062132
S 252 K 50 2/26 EF 214 0 16062140
S 252 K 6 2/26 EF 206 6 16062066
S 252 K 63 2/26 EF 215 7 16062157
S 252 K 8 2/26 EF 207 4 16062074
S 253 B 10 2/26 EF 142 3 16061423
S 253 B 13 2/26 EF 236 3 16062363
S 253 B 16 2/26 EF 143 1 16061431
S 253 B 20 2/26 EF 144 9 16061449
S 253 B 25 2/26 EF 145 6 16061456
S 253 B 32 2/26 EF 146 4 16061464
S 253 B 40 2/26 EF 147 2 16061472
S 253 B 50 2/26 EF 148 0 16061480
S 253 B 6 2/26 EF 140 7 16061407
S 253 B 63 2/26 EF 149 8 16061498
S 253 B 8 2/26 EF 141 5 16061415
S 253 C 0,5 2/26 EF 554 9 16065549
S 253 C 1 2/26 EF 555 6 16065556
S 253 C 1,6 2/26 EF 556 4 16065564
S 253 C 10 2/26 EF 092 0 16060920
S 253 C 13 2/26 EF 237 1 16062371
S 253 C 16 2/26 EF 093 8 16060938
S 253 C 2 2/26 EF 557 2 16065572
S 253 C 20 2/26 EF 094 6 16060946
S 253 C 25 2/26 EF 095 3 16060953
S 253 C 3 2/26 EF 558 0 16065580
S 253 C 32 2/26 EF 096 1 16060961
S 253 C 4 2/26 EF 559 8 16065598
S 253 C 40 2/26 EF 097 9 16060979
S 253 C 50 2/26 EF 098 7 16060987
S 253 C 6 2/26 EF 090 4 16060904
S 253 C 63 2/26 EF 099 5 16060995
S 253 C 8 2/26 EF 091 2 16060912
S 253 D 0,5 2/26 11178138 11178138
S 253 D 1 2/26 11178139 11178139
S 253 D 1,6 2/26 11178140 11178140
S 253 D 10 2/26 11178145 11178145
S 253 D 16 2/26 11178146 11178146
S 253 D 2 2/26 11178141 11178141
S 253 D 20 2/26 11178147 11178147
S 253 D 25 2/26 11178148 11178148
S 253 D 3 2/26 11178142 11178142
S 253 D 32 2/26 11178149 11178149
S 253 D 4 2/26 11178143 11178143
S 253 D 40 2/26 11178150 11178150
S 253 D 50 2/26 11178151 11178151
S 253 D 6 2/26 11178144 11178144
S 253 D 63 2/26 11178152 11178152
S 253 K 0,5 2/26 EF 220 7 16062207
S 253 K 1 2/26 EF 221 5 16062215
S 253 K 1,6 2/26 EF 222 3 16062223
S 253 K 10 2/26 EF 228 0 16062280
S 253 K 16 2/26 EF 229 8 16062298
S 253 K 2 2/26 EF 223 1 16062231
S 253 K 20 2/26 EF 230 6 16062306
S 253 K 25 2/26 EF 231 4 16062314
S 253 K 3 2/26 EF 224 9 16062249
S 253 K 32 2/26 EF 232 2 16062322
S 253 K 4 2/26 EF 225 6 16062256
S 253 K 40 2/26 EF 233 0 16062330
S 253 K 50 2/26 EF 234 8 16062348
S 253 K 6 2/26 EF 226 4 16062264
S 253 K 63 2/26 EF 235 5 16062355
S 253 K 8 2/26 EF 227 2 16062272
S 254 B 10 2/26 EF 885 7 16068857
S 254 B 13 2/26 EF 886 5 16068865
S 254 B 16 2/26 EF 887 3 16068873
S 254 B 20 2/26 EF 888 1 16068881
S 254 B 25 2/26 EF 889 9 16068899
S 254 B 32 2/26 EF 890 7 16068907
S 254 B 40 2/26 EF 891 5 16068915
S 254 B 50 2/26 EF 892 3 16068923
S 254 B 6 2/26 EF 883 2 16068832
S 254 B 63 2/26 EF 893 1 16068931
S 254 B 8 2/26 EF 884 0 16068840
S 254 C 1 2/26 EF 841 0 16068410
S 254 C 10 2/26 EF 848 5 16068485
S 254 C 13 2/26 EF 849 3 16068493
S 254 C 16 2/26 EF 850 1 16068501
S 254 C 2 2/26 EF 843 6 16068436
S 254 C 20 2/26 EF 851 9 16068519
S 254 C 25 2/26 EF 852 7 16068527
S 254 C 3 2/26 EF 844 4 16068444
S 254 C 32 2/26 EF 853 5 16068535
S 254 C 4 2/26 EF 845 1 16068451
S 254 C 40 2/26 EF 854 3 16068543
S 254 C 50 2/26 EF 855 0 16068550
S 254 C 6 2/26 EF 846 9 16068469
S 254 C 63 2/26 EF 856 8 16068568
S 254 C 8 2/26 EF 847 7 16068477
S 254 C0,5 2/26 EF 840 2 16068402
S 254 C1,6 2/26 EF 842 8 16068428
S 254 D 0,5 2/26 11178153 11178153
S 254 D 1 2/26 11178154 11178154
S 254 D 1,6 2/26 11178155 11178155
S 254 D 10 2/26 11178160 11178160
S 254 D 16 2/26 11178161 11178161
S 254 D 2 2/26 11178156 11178156
S 254 D 20 2/26 11178162 11178162
S 254 D 25 2/26 11178163 11178163
S 254 D 3 2/26 11178157 11178157
S 254 D 32 2/26 11178164 11178164
S 254 D 4 2/26 11178158 11178158
S 254 D 40 2/26 11178165 11178165
S 254 D 50 2/26 11178166 11178166
S 254 D 6 2/26 11178159 11178159
S 254 D 63 2/26 11178167 11178167
S 254 K 0,5 2/26 EE 390 9 16053909
S 254 K 1 2/26 EE 391 7 16053917
S 254 K 10 2/26 EE 398 2 16053982
S 254 K 16 2/26 EE 399 0 16053990
S 254 K 2 2/26 EE 393 3 16053933
S 254 K 20 2/26 EE 400 6 16054006
S 254 K 25 2/26 EE 401 4 16054014
S 254 K 3 2/26 EE 394 1 16053941
S 254 K 32 2/26 EE 402 2 16054022
S 254 K 4 2/26 EE 395 8 16053958
S 254 K 40 2/26 EE 403 0 16054030
S 254 K 50 2/26 EE 404 8 16054048
S 254 K 6 2/26 EE 396 6 16053966
S 254 K 63 2/26 EE 405 5 16054055
S 254 K 8 2/26 EE 397 4 16053974
S 254 K1,6 2/26 EE 392 5 16053925
S 271 B 10 2/27 EF 312 2 16063122
S 271 B 13 2/27 EF 830 3 16068303
S 271 B 16 2/27 EF 313 0 16063130
S 271 B 20 2/27 EF 314 8 16063148
S 271 B 25 2/27 EF 315 5 16063155
S 271 B 32 2/27 EF 316 3 16063163
S 271 B 40 2/27 EF 317 1 16063171
S 271 B 50 2/27 EF 318 9 16063189
S 271 B 6 2/27 EF 310 6 16063106
S 271 B 63 2/27 EF 319 7 16063197
S 271 B 8 2/27 EF 311 4 16063114
S 271 C 0,5 2/27 EF 566 3 16065663
S 271 C 1 2/27 EF 567 1 16065671
S 271 C 1,6 2/27 EF 568 9 16065689
S 271 C 10 2/27 EF 262 9 16062629
S 271 C 13 2/27 EF 835 2 16068352
S 271 C 16 2/27 EF 263 7 16062637
S 271 C 2 2/27 EF 569 7 16065697
S 271 C 20 2/27 EF 264 5 16062645
S 271 C 25 2/27 EF 265 2 16062652
S 271 C 3 2/27 EF 570 5 16065705
S 271 C 32 2/27 EF 266 0 16062660
S 271 C 4 2/27 EF 571 3 16065713
S 271 C 40 2/27 EF 267 8 16062678
S 271 C 50 2/27 EF 268 6 16062686
S 271 C 6 2/27 EF 260 3 16062603
14/20 ABB SACE
Code list
Type
Type Pg. Elc code Order code Type Pg. Elc code Order code Type Pg. Elc code Order code
14
S 271 C 63 2/27 EF 269 4 16062694
S 271 C 8 2/27 EF 261 1 16062611
S 271 D 0,5 2/27 EF 600 0 16066000
S 271 D 1 2/27 EF 601 8 16066018
S 271 D 1,6 2/27 EF 602 6 16066026
S 271 D 10 2/27 EF 608 3 16066083
S 271 D 16 2/27 EF 609 1 16066091
S 271 D 2 2/27 EF 603 4 16066034
S 271 D 20 2/27 EF 610 9 16066109
S 271 D 25 2/27 EF 611 7 16066117
S 271 D 3 2/27 EF 604 2 16066042
S 271 D 32 2/27 EF 612 5 16066125
S 271 D 4 2/27 EF 605 9 16066059
S 271 D 40 2/27 EF 613 3 16066133
S 271 D 50 2/27 EF 614 1 16066141
S 271 D 6 2/27 EF 606 7 16066067
S 271 D 63 2/27 EF 615 8 16066158
S 271 D 8 2/27 EF 607 5 16066075
S 271 K 0,5 2/27 EF 360 1 16063601
S 271 K 1 2/27 EF 361 9 16063619
S 271 K 1,6 2/27 EF 362 7 16063627
S 271 K 10 2/27 EF 368 4 16063684
S 271 K 16 2/27 EF 369 2 16063692
S 271 K 2 2/27 EF 363 5 16063635
S 271 K 20 2/27 EF 370 0 16063700
S 271 K 25 2/27 EF 371 8 16063718
S 271 K 3 2/27 EF 364 3 16063643
S 271 K 32 2/27 EF 372 6 16063726
S 271 K 4 2/27 EF 365 0 16063650
S 271 K 40 2/27 EF 373 4 16063734
S 271 K 50 2/27 EF 374 2 16063742
S 271 K 6 2/27 EF 366 8 16063668
S 271 K 63 2/27 EF 375 9 16063759
S 271 K 8 2/27 EF 367 6 16063676
S 271 Na B 10 2/28 EF 322 1 16063221
S 271 Na B 13 2/28 EF 831 1 16068311
S 271 Na B 16 2/28 EF 323 9 16063239
S 271 Na B 20 2/28 EF 324 7 16063247
S 271 Na B 25 2/28 EF 325 4 16063254
S 271 Na B 32 2/28 EF 326 2 16063262
S 271 Na B 40 2/28 EF 327 0 16063270
S 271 Na B 50 2/28 EF 328 8 16063288
S 271 Na B 6 2/28 EF 320 5 16063205
S 271 Na B 63 2/28 EF 329 6 16063296
S 271 Na B 8 2/28 EF 321 3 16063213
S 271 Na C 0,5 2/28 EF 572 1 16065721
S 271 Na C 1 2/28 EF 573 9 16065739
S 271 Na C 1,6 2/28 EF 574 7 16065747
S 271 Na C 10 2/28 EF 272 8 16062728
S 271 Na C 13 2/28 EF 836 0 16068360
S 271 Na C 16 2/28 EF 273 6 16062736
S 271 Na C 2 2/28 EF 575 4 16065754
S 271 Na C 20 2/28 EF 274 4 16062744
S 271 Na C 25 2/28 EF 275 1 16062751
S 271 Na C 3 2/28 EF 576 2 16065762
S 271 Na C 32 2/28 EF 276 9 16062769
S 271 Na C 4 2/28 EF 577 0 16065770
S 271 Na C 40 2/28 EF 277 7 16062777
S 271 Na C 50 2/28 EF 278 5 16062785
S 271 Na C 6 2/28 EF 270 2 16062702
S 271 Na C 63 2/28 EF 279 3 16062793
S 271 Na C 8 2/28 EF 271 0 16062710
S 271 Na D 0,5 2/28 EF 616 6 16066166
S 271 Na D 1 2/28 EF 617 4 16066174
S 271 Na D 1,6 2/28 EF 618 2 16066182
S 271 Na D 10 2/28 EF 624 0 16066240
S 271 Na D 16 2/28 EF 625 7 16066257
S 271 Na D 2 2/28 EF 619 0 16066190
S 271 Na D 20 2/28 EF 626 5 16066265
S 271 Na D 25 2/28 EF 627 3 16066273
S 271 Na D 3 2/28 EF 620 8 16066208
S 271 Na D 32 2/28 EF 628 1 16066281
S 271 Na D 4 2/28 EF 621 6 16066216
S 271 Na D 40 2/28 EF 629 9 16066299
S 271 Na D 50 2/28 EF 630 7 16066307
S 271 Na D 6 2/28 EF 622 4 16066224
S 271 Na D 63 2/28 EF 631 5 16066315
S 271 Na D 8 2/28 EF 623 2 16066232
S 271 Na K 0,5 2/28 EF 380 9 16063809
S 271 Na K 1 2/28 EF 381 7 16063817
S 271 Na K 1,6 2/28 EF 382 5 16063825
S 271 Na K 10 2/28 EF 388 2 16063882
S 271 Na K 16 2/28 EF 389 0 16063890
S 271 Na K 2 2/28 EF 383 3 16063833
S 271 Na K 20 2/28 EF 390 8 16063908
S 271 Na K 25 2/28 EF 391 6 16063916
S 271 Na K 3 2/28 EF 384 1 16063841
S 271 Na K 32 2/28 EF 392 4 16063924
S 271 Na K 4 2/28 EF 385 8 16063858
S 271 Na K 40 2/28 EF 393 2 16063932
S 271 Na K 50 2/28 EF 394 0 16063940
S 271 Na K 6 2/28 EF 386 6 16063866
S 271 Na K 63 2/28 EF 395 7 16063957
S 271 Na K 8 2/28 EF 387 4 16063874
S 272 B 10 2/28 EF 332 0 16063320
S 272 B 13 2/28 EF 832 9 16068329
S 272 B 16 2/28 EF 333 8 16063338
S 272 B 20 2/28 EF 334 6 16063346
S 272 B 25 2/28 EF 335 3 16063353
S 272 B 32 2/28 EF 336 1 16063361
S 272 B 40 2/28 EF 337 9 16063379
S 272 B 50 2/28 EF 338 7 16063387
S 272 B 6 2/28 EF 330 4 16063304
S 272 B 63 2/28 EF 339 5 16063395
S 272 B 8 2/28 EF 331 2 16063312
S 272 C 0,5 2/28 EF 578 8 16065788
S 272 C 1 2/28 EF 579 6 16065796
S 272 C 1,6 2/28 EF 580 4 16065804
S 272 C 10 2/28 EF 282 7 16062827
S 272 C 13 2/28 EF 837 8 16068378
S 272 C 16 2/28 EF 283 5 16062835
S 272 C 2 2/28 EF 581 2 16065812
S 272 C 20 2/28 EF 284 3 16062843
S 272 C 25 2/28 EF 285 0 16062850
S 272 C 3 2/28 EF 582 0 16065820
S 272 C 32 2/28 EF 286 8 16062868
S 272 C 4 2/28 EF 583 8 16065838
S 272 C 40 2/28 EF 287 6 16062876
S 272 C 50 2/28 EF 288 4 16062884
S 272 C 6 2/28 EF 280 1 16062801
S 272 C 63 2/28 EF 289 2 16062892
S 272 C 8 2/28 EF 281 9 16062819
S 272 D 0,5 2/28 EF 632 3 16066323
S 272 D 1 2/28 EF 633 1 16066331
S 272 D 1,6 2/28 EF 634 9 16066349
S 272 D 10 2/28 EF 640 6 16066406
S 272 D 16 2/28 EF 641 4 16066414
S 272 D 2 2/28 EF 635 6 16066356
S 272 D 20 2/28 EF 642 2 16066422
S 272 D 25 2/28 EF 643 0 16066430
S 272 D 3 2/28 EF 636 4 16066364
S 272 D 32 2/28 EF 644 8 16066448
S 272 D 4 2/28 EF 637 2 16066372
S 272 D 40 2/28 EF 645 5 16066455
S 272 D 50 2/28 EF 646 3 16066463
S 272 D 6 2/28 EF 638 0 16066380
S 272 D 63 2/28 EF 647 1 16066471
S 272 D 8 2/28 EF 639 8 16066398
S 272 K 0,5 2/28 EF 400 5 16064005
S 272 K 1 2/28 EF 401 3 16064013
S 272 K 1,6 2/28 EF 402 1 16064021
S 272 K 10 2/28 EF 408 8 16064088
S 272 K 16 2/28 EF 409 6 16064096
S 272 K 2 2/28 EF 403 9 16064039
S 272 K 20 2/28 EF 410 4 16064104
S 272 K 25 2/28 EF 411 2 16064112
S 272 K 3 2/28 EF 404 7 16064047
S 272 K 32 2/28 EF 412 0 16064120
S 272 K 4 2/28 EF 405 4 16064054
S 272 K 40 2/28 EF 413 8 16064138
S 272 K 50 2/28 EF 414 6 16064146
S 272 K 6 2/28 EF 406 2 16064062
S 272 K 63 2/28 EF 415 3 16064153
S 272 K 8 2/28 EF 407 0 16064070
S 273 B 10 2/29 EF 342 9 16063429
S 273 B 13 2/29 EF 833 7 16068337
S 273 B 16 2/29 EF 343 7 16063437
S 273 B 20 2/29 EF 344 5 16063445
S 273 B 25 2/29 EF 345 2 16063452
S 273 B 32 2/29 EF 346 0 16063460
S 273 B 40 2/29 EF 347 8 16063478
S 273 B 50 2/29 EF 348 6 16063486
S 273 B 6 2/29 EF 340 3 16063403
S 273 B 63 2/29 EF 349 4 16063494
S 273 B 8 2/29 EF 341 1 16063411
S 273 C 0,5 2/29 EF 584 6 16065846
S 273 C 1 2/29 EF 585 3 16065853
S 273 C 1,6 2/29 EF 586 1 16065861
S 273 C 10 2/29 EF 292 6 16062926
S 273 C 13 2/29 EF 838 6 16068386
S 273 C 16 2/29 EF 293 4 16062934
S 273 C 2 2/29 EF 587 9 16065879
S 273 C 20 2/29 EF 294 2 16062942
S 273 C 25 2/29 EF 295 9 16062959
S 273 C 3 2/29 EF 588 7 16065887
S 273 C 32 2/29 EF 296 7 16062967
S 273 C 4 2/29 EF 589 5 16065895
S 273 C 40 2/29 EF 297 5 16062975
S 273 C 50 2/29 EF 298 3 16062983
S 273 C 6 2/29 EF 290 0 16062900
S 273 C 63 2/29 EF 299 1 16062991
S 273 C 8 2/29 EF 291 8 16062918
S 273 D 0,5 2/29 EF 648 9 16066489
S 273 D 1 2/29 EF 649 7 16066497
S 273 D 1,6 2/29 EF 650 5 16066505
S 273 D 10 2/29 EF 656 2 16066562
S 273 D 16 2/29 EF 657 0 16066570
S 273 D 2 2/29 EF 651 3 16066513
S 273 D 20 2/29 EF 658 8 16066588
S 273 D 25 2/29 EF 659 6 16066596
S 273 D 3 2/29 EF 652 1 16066521
S 273 D 32 2/29 EF 660 4 16066604
S 273 D 4 2/29 EF 653 9 16066539
S 273 D 40 2/29 EF 661 2 16066612
S 273 D 50 2/29 EF 662 0 16066620
S 273 D 6 2/29 EF 654 7 16066547
S 273 D 63 2/29 EF 663 8 16066638
S 273 D 8 2/29 EF 655 4 16066554
S 273 K 0,5 2/29 EF 420 3 16064203
S 273 K 1 2/29 EF 421 1 16064211
S 273 K 1,6 2/29 EF 422 9 16064229
S 273 K 10 2/29 EF 428 6 16064286
S 273 K 16 2/29 EF 429 4 16064294
S 273 K 2 2/29 EF 423 7 16064237
S 273 K 20 2/29 EF 430 2 16064302
S 273 K 25 2/29 EF 431 0 16064310
S 273 K 3 2/29 EF 424 5 16064245
S 273 K 32 2/29 EF 432 8 16064328
S 273 K 4 2/29 EF 425 2 16064252
S 273 K 40 2/29 EF 433 6 16064336
S 273 K 50 2/29 EF 434 4 16064344
S 273 K 6 2/29 EF 426 0 16064260
S 273 K 63 2/29 EF 435 1 16064351
S 273 K 8 2/29 EF 427 8 16064278
S 274 B 10 2/29 EF 947 5 16069475
S 274 B 13 2/29 EF 948 3 16069483
S 274 B 16 2/29 EF 949 1 16069491
S 274 B 20 2/29 EF 963 2 16069632
S 274 B 25 2/29 EF 964 0 16069640
S 274 B 32 2/29 EF 965 7 16069657
S 274 B 40 2/29 EF 966 5 16069665
S 274 B 50 2/29 EF 967 3 16069673
S 274 B 6 2/29 EF 945 9 16069459
S 274 B 63 2/29 EF 968 1 16069681
S 274 B 8 2/29 EF 946 7 16069467
S 274 C 1 2/29 EF 701 6 16067016
S 274 C 10 2/29 EF 709 9 16067099
S 274 C 13 2/29 EF 800 6 16068006
S 274 C 16 2/29 EF 801 4 16068014
S 274 C 2 2/29 EF 703 2 16067032
S 274 C 20 2/29 EF 804 8 16068048
S 274 C 25 2/29 EF 805 5 16068055
S 274 C 3 2/29 EF 704 0 16067040
S 274 C 32 2/29 EF 806 3 16068063
S 274 C 4 2/29 EF 706 5 16067065
S 274 C 40 2/29 EF 807 1 16068071
S 274 C 50 2/29 EF 808 9 16068089
S 274 C 6 2/29 EF 707 3 16067073
S 274 C 63 2/29 EF 809 7 16068097
S 274 C 8 2/29 EF 708 1 16067081
S 274 C0,5 2/29 EF 700 8 16067008
S 274 C1,6 2/29 EF 702 4 16067024
S 274 D 0,5 2/29 EE 430 3 16054303
S 274 D 1 2/29 EE 431 1 16054311
S 274 D 1,6 2/29 EE 432 9 16054329
S 274 D 10 2/29 EE 438 6 16054386
S 274 D 16 2/29 EE 439 4 16054394
S 274 D 2 2/29 EE 433 7 16054337
S 274 D 20 2/29 EE 440 2 16054402
S 274 D 25 2/29 EE 441 0 16054410
S 274 D 3 2/29 EE 434 5 16054345
S 274 D 32 2/29 EE 442 8 16054428
14/21
ABB SACE
Code list
Type
Type Pg. Elc code Order code Type Pg. Elc code Order code Type Pg. Elc code Order code
14
S 274 D 4 2/29 EE 435 2 16054352
S 274 D 40 2/29 EE 443 6 16054436
S 274 D 50 2/29 EE 444 4 16054444
S 274 D 6 2/29 EE 436 0 16054360
S 274 D 63 2/29 EE 445 1 16054451
S 274 D 8 2/29 EE 437 8 16054378
S 274 K 0,5 2/29 EE 410 5 16054105
S 274 K 1 2/29 EE 411 3 16054113
S 274 K 1,6 2/29 EE 412 1 16054121
S 274 K 10 2/29 EE 418 8 16054188
S 274 K 16 2/29 EE 419 6 16054196
S 274 K 2 2/29 EE 413 9 16054139
S 274 K 20 2/29 EE 420 4 16054204
S 274 K 25 2/29 EE 421 2 16054212
S 274 K 3 2/29 EE 414 7 16054147
S 274 K 32 2/29 EE 422 0 16054220
S 274 K 4 2/29 EE 415 4 16054154
S 274 K 40 2/29 EE 423 8 16054238
S 274 K 50 2/29 EE 424 6 16054246
S 274 K 6 2/29 EE 416 2 16054162
S 274 K 63 2/29 EE 425 3 16054253
S 274 K 8 2/29 EE 417 0 16054170
S 281 B 10 2/30 KU 648 8 16216488
S 281 B 13 2/30 KU 654 6 16216546
S 281 B 16 2/30 KU 649 6 16216496
S 281 B 20 2/30 KU 650 4 16216504
S 281 B 25 2/30 KU 651 2 16216512
S 281 B 32 2/30 KU 652 0 16216520
S 281 B 40 2/30 KU 653 8 16216538
S 281 B 50 2/30 KU 655 3 16216553
S 281 B 6 2/30 KU 647 0 16216470
S 281 B 63 2/30 KU 656 1 16216561
S 281 C 10 2/30 KU 658 7 16216587
S 281 C 13 2/30 KU 664 5 16216645
S 281 C 16 2/30 KU 659 5 16216595
S 281 C 20 2/30 KU 660 3 16216603
S 281 C 25 2/30 KU 661 1 16216611
S 281 C 32 2/30 KU 662 9 16216629
S 281 C 40 2/30 KU 663 7 16216637
S 281 C 50 2/30 KU 665 2 16216652
S 281 C 6 2/30 KU 657 9 16216579
S 281 C 63 2/30 KU 666 0 16216660
S 281 D 10 2/30 KU 810 4 16218104
S 281 D 16 2/30 KU 811 2 16218112
S 281 D 20 2/30 KU 812 0 16218120
S 281 D 25 2/30 KU 813 8 16218138
S 281 D 32 2/30 KU 814 6 16218146
S 281 D 40 2/30 KU 815 3 16218153
S 281 D 50 2/30 KU 817 9 16218179
S 281 D 6 2/30 KU 674 4 16216744
S 281 D 63 2/30 KU 818 7 16218187
S 281 K 10 2/32 KU 867 4 16218674
S 281 K 13 2/32 KU 873 2 16218732
S 281 K 16 2/32 KU 868 2 16218682
S 281 K 20 2/32 KU 869 0 16218690
S 281 K 25 2/32 KU 870 8 16218708
S 281 K 32 2/32 KU 871 6 16218716
S 281 K 40 2/32 KU 872 4 16218724
S 281 K 50 2/32 KU 874 0 16218740
S 281 K 6 2/32 KU 866 6 16218666
S 281 K 63 2/32 KU 875 7 16218757
S 281 UC B 10 2/34 EF 692 7 16066927
S 281 UC B 16 2/34 EF 693 5 16066935
S 281 UC B 20 2/34 EF 694 3 16066943
S 281 UC B 25 2/34 EF 695 0 16066950
S 281 UC B 32 2/34 EF 696 8 16066968
S 281 UC B 40 2/34 EF 697 6 16066976
S 281 UC B 50 2/34 EF 698 4 16066984
S 281 UC B 6 2/34 EF 690 1 16066901
S 281 UC B 63 2/34 EF 699 2 16066992
S 281 UC B 8 2/34 EF 691 9 16066919
S 281 UC C 0,5 2/34 EF 720 6 16067206
S 281 UC C 1 2/34 EF 721 4 16067214
S 281 UC C 1,6 2/34 EF 722 2 16067222
S 281 UC C 10 2/34 EF 728 9 16067289
S 281 UC C 16 2/34 EF 729 7 16067297
S 281 UC C 2 2/34 EF 723 0 16067230
S 281 UC C 20 2/34 EF 730 5 16067305
S 281 UC C 25 2/34 EF 731 3 16067313
S 281 UC C 3 2/34 EF 724 8 16067248
S 281 UC C 32 2/34 EF 732 1 16067321
S 281 UC C 4 2/34 EF 725 5 16067255
S 281 UC C 40 2/34 EF 733 9 16067339
S 281 UC C 50 2/34 EF 734 7 16067347
S 281 UC C 6 2/34 EF 726 3 16067263
S 281 UC C 63 2/34 EF 735 4 16067354
S 281 UC C 8 2/34 EF 727 1 16067271
S 281 UC K 0,5 2/34 EF 752 9 16067529
S 281 UC K 1 2/34 EF 753 7 16067537
S 281 UC K 1,6 2/34 EF 754 5 16067545
S 281 UC K 10 2/34 EF 760 2 16067602
S 281 UC K 16 2/34 EF 761 0 16067610
S 281 UC K 2 2/34 EF 755 2 16067552
S 281 UC K 20 2/34 EF 762 8 16067628
S 281 UC K 25 2/34 EF 763 6 16067636
S 281 UC K 3 2/34 EF 756 0 16067560
S 281 UC K 32 2/34 EF 764 4 16067644
S 281 UC K 4 2/34 EF 757 8 16067578
S 281 UC K 40 2/34 EF 765 1 16067651
S 281 UC K 50 2/34 EF 766 9 16067669
S 281 UC K 6 2/34 EF 758 6 16067586
S 281 UC K 63 2/34 EF 767 7 16067677
S 281 UC K 8 2/34 EF 759 4 16067594
S 281 UC Z 0,5 2/34 EF 784 2 16067842
S 281 UC Z 1 2/34 EF 785 9 16067859
S 281 UC Z 1,6 2/34 EF 786 7 16067867
S 281 UC Z 10 2/34 EF 792 5 16067925
S 281 UC Z 16 2/34 EF 793 3 16067933
S 281 UC Z 2 2/34 EF 787 5 16067875
S 281 UC Z 20 2/34 EF 794 1 16067941
S 281 UC Z 25 2/34 EF 795 8 16067958
S 281 UC Z 3 2/34 EF 788 3 16067883
S 281 UC Z 32 2/34 EF 796 6 16067966
S 281 UC Z 4 2/34 EF 789 1 16067891
S 281 UC Z 40 2/34 EF 797 4 16067974
S 281 UC Z 50 2/34 EF 798 2 16067982
S 281 UC Z 6 2/34 EF 790 9 16067909
S 281 UC Z 63 2/34 EF 799 0 16067990
S 281 UC Z 8 2/34 EF 791 7 16067917
S 281 Z 0,5 2/32 KU 750 2 16217502
S 281 Z 1 2/32 KU 751 0 16217510
S 281 Z 1,6 2/32 KU 752 8 16217528
S 281 Z 10 2/32 KU 757 7 16217577
S 281 Z 16 2/32 KU 758 5 16217585
S 281 Z 2 2/32 KU 753 6 16217536
S 281 Z 20 2/32 KU 759 3 16217593
S 281 Z 25 2/32 KU 760 1 16217601
S 281 Z 3 2/32 KU 754 4 16217544
S 281 Z 32 2/32 KU 761 9 16217619
S 281 Z 4 2/32 KU 755 1 16217551
S 281 Z 40 2/32 KU 762 7 16217627
S 281 Z 50 2/32 KU 763 5 16217635
S 281 Z 6 2/32 KU 756 9 16217569
S 281 Z 63 2/32 KU 764 3 16217643
S 281 Z 8 2/32 KU 746 0 16217460
S 282 B 10 2/30 KU 688 4 16216884
S 282 B 13 2/30 KU 694 2 16216942
S 282 B 16 2/30 KU 689 2 16216892
S 282 B 20 2/30 KU 690 0 16216900
S 282 B 25 2/30 KU 691 8 16216918
S 282 B 32 2/30 KU 692 6 16216926
S 282 B 40 2/30 KU 693 4 16216934
S 282 B 50 2/30 KU 695 9 16216959
S 282 B 6 2/30 KU 687 6 16216876
S 282 B 63 2/30 KU 696 7 16216967
S 282 C 0,5 2/30 11865333 11865333
S 282 C 1 2/30 11865334 11865334
S 282 C 1,6 2/30 11865335 11865335
S 282 C 10 2/30 KU 698 3 16216983
S 282 C 13 2/30 KU 704 9 16217049
S 282 C 16 2/30 KU 699 1 16216991
S 282 C 2 2/30 11865336 11865336
S 282 C 20 2/30 KU 700 7 16217007
S 282 C 25 2/30 KU 701 5 16217015
S 282 C 3 2/30 11865337 11865337
S 282 C 32 2/30 KU 702 3 16217023
S 282 C 4 2/30 11865338 11865338
S 282 C 40 2/30 KU 703 1 16217031
S 282 C 50 2/30 KU 705 6 16217056
S 282 C 6 2/30 KU 697 5 16216975
S 282 C 63 2/30 KU 706 4 16217064
S 282 D 10 2/30 KU 820 3 16218203
S 282 D 16 2/30 KU 821 1 16218211
S 282 D 20 2/30 KU 822 9 16218229
S 282 D 25 2/30 KU 823 7 16218237
S 282 D 32 2/30 KU 824 5 16218245
S 282 D 40 2/30 KU 825 2 16218252
S 282 D 50 2/30 KU 827 8 16218278
S 282 D 6 2/30 KU 819 5 16218195
S 282 D 63 2/30 KU 828 6 16218286
S 282 K 0,5 2/32 11865375 11865375
S 282 K 1 2/32 11865376 11865376
S 282 K 1,6 2/32 11865377 11865377
S 282 K 10 2/32 KU 857 5 16218575
S 282 K 13 2/32 KU 863 3 16218633
S 282 K 16 2/32 KU 858 3 16218583
S 282 K 2 2/32 11865378 11865378
S 282 K 20 2/32 KU 859 1 16218591
S 282 K 25 2/32 KU 860 9 16218609
S 282 K 3 2/32 11865379 11865379
S 282 K 32 2/32 KU 861 7 16218617
S 282 K 4 2/32 11865380 11865380
S 282 K 40 2/32 KU 862 5 16218625
S 282 K 50 2/32 KU 864 1 16218641
S 282 K 6 2/32 KU 856 7 16218567
S 282 K 63 2/32 KU 865 8 16218658
S 282 UC B 10 2/35 EF 712 3 16067123
S 282 UC B 16 2/35 EF 713 1 16067131
S 282 UC B 20 2/35 EF 714 9 16067149
S 282 UC B 25 2/35 EF 715 6 16067156
S 282 UC B 32 2/35 EF 716 4 16067164
S 282 UC B 40 2/35 EF 717 2 16067172
S 282 UC B 50 2/35 EF 718 0 16067180
S 282 UC B 6 2/35 EF 710 7 16067107
S 282 UC B 63 2/35 EF 719 8 16067198
S 282 UC B 8 2/35 EF 711 5 16067115
S 282 UC C 0,5 2/35 EF 736 2 16067362
S 282 UC C 1 2/35 EF 737 0 16067370
S 282 UC C 1,6 2/35 EF 738 8 16067388
S 282 UC C 10 2/35 EF 744 6 16067446
S 282 UC C 16 2/35 EF 745 3 16067453
S 282 UC C 2 2/35 EF 739 6 16067396
S 282 UC C 20 2/35 EF 746 1 16067461
S 282 UC C 25 2/35 EF 747 9 16067479
S 282 UC C 3 2/35 EF 740 4 16067404
S 282 UC C 32 2/35 EF 748 7 16067487
S 282 UC C 4 2/35 EF 741 2 16067412
S 282 UC C 40 2/35 EF 749 5 16067495
S 282 UC C 50 2/35 EF 750 3 16067503
S 282 UC C 6 2/35 EF 742 0 16067420
S 282 UC C 63 2/35 EF 751 1 16067511
S 282 UC C 8 2/35 EF 743 8 16067438
S 282 UC K 0,5 2/35 EF 768 5 16067685
S 282 UC K 1 2/35 EF 769 3 16067693
S 282 UC K 1,6 2/35 EF 770 1 16067701
S 282 UC K 10 2/35 EF 776 8 16067768
S 282 UC K 16 2/35 EF 777 6 16067776
S 282 UC K 2 2/35 EF 771 9 16067719
S 282 UC K 20 2/35 EF 778 4 16067784
S 282 UC K 25 2/35 EF 779 2 16067792
S 282 UC K 3 2/35 EF 772 7 16067727
S 282 UC K 32 2/35 EF 780 0 16067800
S 282 UC K 4 2/35 EF 773 5 16067735
S 282 UC K 40 2/35 EF 781 8 16067818
S 282 UC K 50 2/35 EF 782 6 16067826
S 282 UC K 6 2/35 EF 774 3 16067743
S 282 UC K 63 2/35 EF 783 4 16067834
S 282 UC K 8 2/35 EF 775 0 16067750
S 282 UC Z 0,5 2/35 EF 810 5 16068105
S 282 UC Z 1 2/35 EF 811 3 16068113
S 282 UC Z 1,6 2/35 EF 812 1 16068121
S 282 UC Z 10 2/35 EF 818 8 16068188
S 282 UC Z 16 2/35 EF 819 6 16068196
S 282 UC Z 2 2/35 EF 813 9 16068139
S 282 UC Z 20 2/35 EF 820 4 16068204
S 282 UC Z 25 2/35 EF 821 2 16068212
S 282 UC Z 3 2/35 EF 814 7 16068147
S 282 UC Z 32 2/35 EF 822 0 16068220
S 282 UC Z 4 2/35 EF 815 4 16068154
S 282 UC Z 40 2/35 EF 823 8 16068238
S 282 UC Z 50 2/35 EF 824 6 16068246
S 282 UC Z 6 2/35 EF 816 2 16068162
S 282 UC Z 63 2/35 EF 825 3 16068253
S 282 UC Z 8 2/35 EF 817 0 16068170
S 282 Z 0,5 2/32 KU 765 0 16217650
S 282 Z 1 2/32 KU 766 8 16217668
S 282 Z 1,6 2/32 KU 767 6 16217676
S 282 Z 10 2/32 KU 772 6 16217726
S 282 Z 16 2/32 KU 773 4 16217734
S 282 Z 2 2/32 KU 768 4 16217684
S 282 Z 20 2/32 KU 774 2 16217742
S 282 Z 25 2/32 KU 775 9 16217759
14/22 ABB SACE
Code list
Type
Type Pg. Elc code Order code Type Pg. Elc code Order code Type Pg. Elc code Order code
14
S 282 Z 3 2/32 KU 769 2 16217692
S 282 Z 32 2/32 KU 776 7 16217767
S 282 Z 4 2/32 KU 770 0 16217700
S 282 Z 40 2/32 KU 777 5 16217775
S 282 Z 50 2/32 KU 778 3 16217783
S 282 Z 6 2/32 KU 771 8 16217718
S 282 Z 63 2/32 KU 779 1 16217791
S 282 Z 8 2/32 KU 747 8 16217478
S 283 B 10 2/31 KU 708 0 16217080
S 283 B 13 2/31 KU 714 8 16217148
S 283 B 16 2/31 KU 709 8 16217098
S 283 B 20 2/31 KU 710 6 16217106
S 283 B 25 2/31 KU 711 4 16217114
S 283 B 32 2/31 KU 712 2 16217122
S 283 B 40 2/31 KU 713 0 16217130
S 283 B 50 2/31 KU 715 5 16217155
S 283 B 6 2/31 KU 707 2 16217072
S 283 B 63 2/31 KU 716 3 16217163
S 283 C 0,5 2/31 11866313 11866313
S 283 C 1 2/31 11866314 11866314
S 283 C 1,6 2/31 11866315 11866315
S 283 C 10 2/31 KU 718 9 16217189
S 283 C 13 2/31 KU 724 7 16217247
S 283 C 16 2/31 KU 719 7 16217197
S 283 C 2 2/31 11866316 11866316
S 283 C 20 2/31 KU 720 5 16217205
S 283 C 25 2/31 KU 721 3 16217213
S 283 C 3 2/31 11866317 11866317
S 283 C 32 2/31 KU 722 1 16217221
S 283 C 4 2/31 11866318 11866318
S 283 C 40 2/31 KU 723 9 16217239
S 283 C 50 2/31 KU 725 4 16217254
S 283 C 6 2/31 KU 717 1 16217171
S 283 C 63 2/31 KU 726 2 16217262
S 283 D 10 2/31 KU 830 2 16218302
S 283 D 16 2/31 KU 831 0 16218310
S 283 D 20 2/31 KU 832 8 16218328
S 283 D 25 2/31 KU 833 6 16218336
S 283 D 32 2/31 KU 834 4 16218344
S 283 D 40 2/31 KU 835 1 16218351
S 283 D 50 2/31 KU 837 7 16218377
S 283 D 6 2/31 KU 829 4 16218294
S 283 D 63 2/31 KU 838 5 16218385
S 283 K 0,5 2/33 11866329 11866329
S 283 K 1 2/33 11866330 11866330
S 283 K 1,6 2/33 11866331 11866331
S 283 K 10 2/33 KU 847 6 16218476
S 283 K 13 2/33 KU 853 4 16218534
S 283 K 16 2/33 KU 848 4 16218484
S 283 K 2 2/33 11866332 11866332
S 283 K 20 2/33 KU 849 2 16218492
S 283 K 25 2/33 KU 850 0 16218500
S 283 K 3 2/33 11866333 11866333
S 283 K 32 2/33 KU 851 8 16218518
S 283 K 4 2/33 11866334 11866334
S 283 K 40 2/33 KU 852 6 16218526
S 283 K 50 2/33 KU 854 2 16218542
S 283 K 6 2/33 KU 675 1 16216751
S 283 K 63 2/33 KU 855 9 16218559
S 283 Z 0,5 2/33 KU 780 9 16217809
S 283 Z 1 2/33 KU 781 7 16217817
S 283 Z 1,6 2/33 KU 782 5 16217825
S 283 Z 10 2/33 KU 787 4 16217874
S 283 Z 16 2/33 KU 788 2 16217882
S 283 Z 2 2/33 KU 783 3 16217833
S 283 Z 20 2/33 KU 789 0 16217890
S 283 Z 25 2/33 KU 790 8 16217908
S 283 Z 3 2/33 KU 784 1 16217841
S 283 Z 32 2/33 KU 791 6 16217916
S 283 Z 4 2/33 KU 785 8 16217858
S 283 Z 40 2/33 KU 792 4 16217924
S 283 Z 50 2/33 KU 793 2 16217932
S 283 Z 6 2/33 KU 786 6 16217866
S 283 Z 63 2/33 KU 794 0 16217940
S 283 Z 8 2/33 KU 748 6 16217486
S 284 B 10 2/31 KU 728 8 16217288
S 284 B 13 2/31 KU 734 6 16217346
S 284 B 16 2/31 KU 729 6 16217296
S 284 B 20 2/31 KU 730 4 16217304
S 284 B 25 2/31 KU 731 2 16217312
S 284 B 32 2/31 KU 732 0 16217320
S 284 B 40 2/31 KU 733 8 16217338
S 284 B 50 2/31 KU 735 3 16217353
S 284 B 6 2/31 KU 727 0 16217270
S 284 B 63 2/31 KU 736 1 16217361
S 284 C 10 2/31 KU 738 7 16217387
S 284 C 13 2/31 KU 744 5 16217445
S 284 C 16 2/31 KU 739 5 16217395
S 284 C 20 2/31 KU 740 3 16217403
S 284 C 25 2/31 KU 741 1 16217411
S 284 C 32 2/31 KU 742 9 16217429
S 284 C 40 2/31 KU 743 7 16217437
S 284 C 50 2/31 KU 745 2 16217452
S 284 C 6 2/31 KU 737 9 16217379
S 284 C 63 2/31 KU 676 9 16216769
S 284 D 10 2/31 KU 840 1 16218401
S 284 D 16 2/31 KU 841 9 16218419
S 284 D 20 2/31 KU 842 7 16218427
S 284 D 25 2/31 KU 843 5 16218435
S 284 D 32 2/31 KU 844 3 16218443
S 284 D 40 2/31 KU 845 0 16218450
S 284 D 50 2/31 KU 677 7 16216777
S 284 D 6 2/31 KU 839 3 16218393
S 284 D 63 2/31 KU 678 5 16216785
S 284 K 10 2/33 KU 877 3 16218773
S 284 K 13 2/33 KU 883 1 16218831
S 284 K 16 2/33 KU 878 1 16218781
S 284 K 20 2/33 KU 879 9 16218799
S 284 K 25 2/33 KU 880 7 16218807
S 284 K 32 2/33 KU 881 5 16218815
S 284 K 40 2/33 KU 882 3 16218823
S 284 K 50 2/33 KU 884 9 16218849
S 284 K 6 2/33 KU 876 5 16218765
S 284 K 63 2/33 KU 885 6 16218856
S 284 Z 0,5 2/33 KU 795 7 16217957
S 284 Z 1 2/33 KU 796 5 16217965
S 284 Z 1,6 2/33 KU 797 3 16217973
S 284 Z 10 2/33 KU 802 1 16218021
S 284 Z 16 2/33 KU 803 9 16218039
S 284 Z 2 2/33 KU 798 1 16217981
S 284 Z 20 2/33 KU 804 7 16218047
S 284 Z 25 2/33 KU 805 4 16218054
S 284 Z 3 2/33 KU 799 9 16217999
S 284 Z 32 2/33 KU 806 2 16218062
S 284 Z 4 2/33 KU 800 5 16218005
S 284 Z 40 2/33 KU 807 0 16218070
S 284 Z 50 2/33 KU 808 8 16218088
S 284 Z 6 2/33 KU 801 3 16218013
S 284 Z 63 2/33 KU 809 6 16218096
S 284 Z 8 2/33 KU 749 4 16217494
S 290 A1 2/53 KU 989 6 36219896
S 290 A2 2/53 KU 991 2 36219912
S 290 H11 2/54 KU 987 0 36219870
S 290 S 2/54 KU 988 8 36219888
S 290 UA 230 2/55 KU 990 4 36219904
S 291 C 100 2/51 KU 951 6 36219516
S 291 C 125 2/51 KU 952 4 36219524
S 291 C 80 2/51 KU 950 8 36219508
S 291 D 100 2/51 KU 975 5 36219755
S 291 D 80 2/51 KU 974 8 36219748
S 292 C 100 2/51 KU 954 0 36219540
S 292 C 125 2/51 KU 955 7 36219557
S 292 C 80 2/51 KU 953 2 36219532
S 292 D 100 2/51 KU 978 9 36219789
S 292 D 80 2/51 KU 977 1 36219771
S 293 C 100 2/51 KU 957 3 36219573
S 293 C 125 2/51 KU 958 1 36219581
S 293 C 80 2/51 KU 956 5 36219565
S 293 D 100 2/51 KU 981 3 36219813
S 293 D 80 2/51 KU 980 5 36219805
S 294 C 100 2/51 KU 960 7 36219607
S 294 C 125 2/51 KU 961 5 36219615
S 294 C 80 2/51 KU 959 9 36219599
S 294 D 100 2/51 KU 984 7 36219847
S 294 D 80 2/51 KU 983 9 36219839
S 501 B 10 2/60 EI 061 2 36090612
S 501 B 13 2/60 EI 062 0 36090620
S 501 B 16 2/60 EI 063 8 36090638
S 501 B 20 2/60 EI 064 6 36090646
S 501 B 25 2/60 EI 065 3 36090653
S 501 B 32 2/60 EI 066 1 36090661
S 501 B 40 2/60 EI 067 9 36090679
S 501 B 50 2/60 EI 068 7 36090687
S 501 B 6 2/60 EI 060 4 36090604
S 501 B 63 2/60 EI 069 5 36090695
S 501 C 10 2/60 EI 101 6 36091016
S 501 C 13 2/60 EI 102 4 36091024
S 501 C 16 2/60 EI 103 2 36091032
S 501 C 20 2/60 EI 104 0 36091040
S 501 C 25 2/60 EI 105 7 36091057
S 501 C 32 2/60 EI 106 5 36091065
S 501 C 40 2/60 EI 107 3 36091073
S 501 C 50 2/60 EI 108 1 36091081
S 501 C 6 2/60 EI 100 8 36091008
S 501 C 63 2/60 EI 109 9 36091099
S 501 K 0,1 - 0,15 2/64 EI 450 7 36094507
S 501 K 0,14 - 0,21 2/64 EI 451 5 36094515
S 501 K 0,2 - 0,3 2/64 EI 452 3 36094523
S 501 K 0,28 - 0,42 2/64 EI 453 1 36094531
S 501 K 0,38 - 0,58 2/64 EI 454 9 36094549
S 501 K 0,53 - 0,8 2/64 EI 455 6 36094556
S 501 K 0,73 - 1,1 2/64 EI 456 4 36094564
S 501 K 1 - 1,5 2/64 EI 457 2 36094572
S 501 K 1,4 - 2,1 2/64 EI 458 0 36094580
S 501 K 10 - 15 2/64 EI 464 8 36094648
S 501 K 14 - 20 2/64 EI 465 5 36094655
S 501 K 18 - 26 2/64 EI 466 3 36094663
S 501 K 2,8 - 4,2 2/64 EI 460 6 36094606
S 501 K 2-3 2/64 EI 459 8 36094598
S 501 K 23 - 32 2/64 EI 467 1 36094671
S 501 K 29 - 37 2/64 EI 468 9 36094689
S 501 K 3,8 - 5,8 2/64 EI 461 4 36094614
S 501 K 34 - 41 2/64 EI 469 7 36094697
S 501 K 38 - 45 2/64 EI 470 5 36094705
S 501 K 5,3 - 8 2/64 EI 462 2 36094622
S 501 K 7,3 - 11 2/64 EI 463 0 36094630
S 501 UC B 10 2/62 EI 316 0 36093160
S 501 UC B 13 2/62 EI 317 8 36093178
S 501 UC B 16 2/62 EI 318 6 36093186
S 501 UC B 20 2/62 EI 319 4 36093194
S 501 UC B 25 2/62 EI 320 2 36093202
S 501 UC B 32 2/62 EI 321 0 36093210
S 501 UC B 40 2/62 EI 322 8 36093228
S 501 UC B 50 2/62 EI 323 6 36093236
S 501 UC B 6 2/62 EI 315 2 36093152
S 501 UC B 63 2/62 EI 324 4 36093244
S 502 B 10 2/60 EI 071 1 36090711
S 502 B 13 2/60 EI 072 9 36090729
S 502 B 16 2/60 EI 073 7 36090737
S 502 B 20 2/60 EI 074 5 36090745
S 502 B 25 2/60 EI 075 2 36090752
S 502 B 32 2/60 EI 076 0 36090760
S 502 B 40 2/60 EI 077 8 36090778
S 502 B 50 2/60 EI 078 6 36090786
S 502 B 6 2/60 EI 070 3 36090703
S 502 B 63 2/60 EI 079 4 36090794
S 502 C 10 2/60 EI 111 5 36091115
S 502 C 13 2/60 EI 112 3 36091123
S 502 C 16 2/60 EI 113 1 36091131
S 502 C 20 2/60 EI 114 9 36091149
S 502 C 25 2/60 EI 115 6 36091156
S 502 C 32 2/60 EI 116 4 36091164
S 502 C 40 2/60 EI 117 2 36091172
S 502 C 50 2/60 EI 118 0 36091180
S 502 C 6 2/60 EI 110 7 36091107
S 502 C 63 2/60 EI 119 8 36091198
S 502 K 0,1 - 0,15 2/64 EI 475 4 36094754
S 502 K 0,14 - 0,21 2/64 EI 476 2 36094762
S 502 K 0,2 - 0,3 2/64 EI 477 0 36094770
S 502 K 0,28 - 0,42 2/64 EI 478 8 36094788
S 502 K 0,38 - 0,58 2/64 EI 479 6 36094796
S 502 K 0,53 - 0,8 2/64 EI 480 4 36094804
S 502 K 0,73 - 1,1 2/64 EI 481 2 36094812
S 502 K 1 - 1,5 2/64 EI 482 0 36094820
S 502 K 1,4 - 2,1 2/64 EI 483 8 36094838
S 502 K 10 - 15 2/64 EI 489 5 36094895
S 502 K 14 - 20 2/64 EI 490 3 36094903
S 502 K 18 - 26 2/64 EI 491 1 36094911
S 502 K 2,8 - 4,2 2/64 EI 485 3 36094853
S 502 K 2-3 2/64 EI 484 6 36094846
S 502 K 23 - 32 2/64 EI 492 9 36094929
S 502 K 29 - 37 2/64 EI 493 7 36094937
S 502 K 3,8 - 5,8 2/64 EI 486 1 36094861
S 502 K 34 - 41 2/64 EI 494 5 36094945
S 502 K 38 - 45 2/64 EI 495 2 36094952
S 502 K 5,3 - 8 2/64 EI 487 9 36094879
S 502 K 7,3 - 11 2/64 EI 488 7 36094887
S 502 UC B 10 2/62 EI 326 9 36093269
S 502 UC B 13 2/62 EI 327 7 36093277
S 502 UC B 16 2/62 EI 328 5 36093285
S 502 UC B 20 2/62 EI 329 3 36093293
S 502 UC B 25 2/62 EI 330 1 36093301
14/23
ABB SACE
Code list
Type
Type Pg. Elc code Order code Type Pg. Elc code Order code Type Pg. Elc code Order code
14
S 502 UC B 32 2/62 EI 331 9 36093319
S 502 UC B 40 2/62 EI 332 7 36093327
S 502 UC B 50 2/62 EI 333 5 36093335
S 502 UC B 6 2/62 EI 325 1 36093251
S 502 UC B 63 2/62 EI 334 3 36093343
S 503 B 10 2/61 EI 081 0 36090810
S 503 B 13 2/61 EI 082 8 36090828
S 503 B 16 2/61 EI 083 6 36090836
S 503 B 20 2/61 EI 084 4 36090844
S 503 B 25 2/61 EI 085 1 36090851
S 503 B 32 2/61 EI 086 9 36090869
S 503 B 40 2/61 EI 087 7 36090877
S 503 B 50 2/61 EI 088 5 36090885
S 503 B 6 2/61 EI 080 2 36090802
S 503 B 63 2/61 EI 089 3 36090893
S 503 C 10 2/61 EI 121 4 36091214
S 503 C 13 2/61 EI 122 2 36091222
S 503 C 16 2/61 EI 123 0 36091230
S 503 C 20 2/61 EI 124 8 36091248
S 503 C 25 2/61 EI 125 5 36091255
S 503 C 32 2/61 EI 126 3 36091263
S 503 C 40 2/61 EI 127 1 36091271
S 503 C 50 2/61 EI 128 9 36091289
S 503 C 6 2/61 EI 120 6 36091206
S 503 C 63 2/61 EI 129 7 36091297
S 503 K 0,1 - 0,15 2/64 EI 345 9 36093459
S 503 K 0,14 - 0,21 2/64 EI 346 7 36093467
S 503 K 0,2 - 0,3 2/64 EI 347 5 36093475
S 503 K 0,28 - 0,42 2/64 EI 348 3 36093483
S 503 K 0,38 - 0,58 2/64 EI 349 1 36093491
S 503 K 0,53 - 0,8 2/64 EI 350 9 36093509
S 503 K 0,73 - 1,1 2/64 EI 351 7 36093517
S 503 K 1 - 1,5 2/64 EI 352 5 36093525
S 503 K 1,4 - 2,1 2/64 EI 353 3 36093533
S 503 K 10 - 15 2/64 EI 359 0 36093590
S 503 K 14 - 20 2/64 EI 360 8 36093608
S 503 K 18 - 26 2/64 EI 361 6 36093616
S 503 K 2,8 - 4,2 2/64 EI 355 8 36093558
S 503 K 2-3 2/64 EI 354 1 36093541
S 503 K 23 - 32 2/64 EI 362 4 36093624
S 503 K 29 - 37 2/64 EI 363 2 36093632
S 503 K 3,8 - 5,8 2/64 EI 356 6 36093566
S 503 K 34 - 41 2/64 EI 364 0 36093640
S 503 K 38 - 45 2/64 EI 365 7 36093657
S 503 K 5,3 - 8 2/64 EI 357 4 36093574
S 503 K 7,3 - 11 2/64 EI 358 2 36093582
S 503 KM 1,6 2/64 EI 417 6 36094176
S 503 KM 2,5 2/64 EI 418 4 36094184
S 503 KM 20 2/64 EI 422 6 36094226
S 503 KM 32 2/64 EI 423 4 36094234
S 503 KM 4 2/64 EI 419 2 36094192
S 503 KM 52 2/64 EI 424 2 36094242
S 503 KM 6 2/64 EI 420 0 36094200
S 503 KM 63 2/64 EI 425 9 36094259
S 503 KM 75 2/64 EI 428 3 36094283
S 503 KM 9 2/64 EI 421 8 36094218
S 503 UC B 10 2/63 EI 336 8 36093368
S 503 UC B 13 2/63 EI 337 6 36093376
S 503 UC B 16 2/63 EI 338 4 36093384
S 503 UC B 20 2/63 EI 339 2 36093392
S 503 UC B 25 2/63 EI 340 0 36093400
S 503 UC B 32 2/63 EI 341 8 36093418
S 503 UC B 40 2/63 EI 342 6 36093426
S 503 UC B 50 2/63 EI 343 4 36093434
S 503 UC B 6 2/63 EI 335 0 36093350
S 503 UC B 63 2/63 EI 344 2 36093442
S 504 B 10 2/61 EI 091 9 36090919
S 504 B 13 2/61 EI 092 7 36090927
S 504 B 16 2/61 EI 093 5 36090935
S 504 B 20 2/61 EI 094 3 36090943
S 504 B 25 2/61 EI 095 0 36090950
S 504 B 32 2/61 EI 096 8 36090968
S 504 B 40 2/61 EI 097 6 36090976
S 504 B 50 2/61 EI 098 4 36090984
S 504 B 6 2/61 EI 090 1 36090901
S 504 B 63 2/61 EI 099 2 36090992
S 504 C 10 2/61 EI 131 3 36091313
S 504 C 13 2/61 EI 132 1 36091321
S 504 C 16 2/61 EI 133 9 36091339
S 504 C 20 2/61 EI 134 7 36091347
S 504 C 25 2/61 EI 135 4 36091354
S 504 C 32 2/61 EI 136 2 36091362
S 504 C 40 2/61 EI 137 0 36091370
S 504 C 50 2/61 EI 138 8 36091388
S 504 C 6 2/61 EI 130 5 36091305
S 504 C 63 2/61 EI 139 6 36091396
S 701 100 A ACCESS. 2/71 EG 705 6 36077056
S 701 25 A ACCESS. 2/71 EG 700 7 36077007
S 701 35 A ACCESS. 2/71 EG 701 5 36077015
S 701 50 A ACCESS. 2/71 EG 702 3 36077023
S 701 63 A ACCESS. 2/71 EG 703 1 36077031
S 701 80 A ACCESS. 2/71 EG 704 9 36077049
S 702 100 A ACCESS. 2/71 EG 711 4 36077114
S 702 100 A NAVAL 2/71 EG 735 3 36077353
S 702 25 A ACCESS. 2/71 EG 706 4 36077064
S 702 25 A NAVAL 2/71 EG 730 4 36077304
S 702 35 A ACCESS. 2/71 EG 707 2 36077072
S 702 35 A NAVAL 2/71 EG 731 2 36077312
S 702 50 A ACCESS. 2/71 EG 708 0 36077080
S 702 50 A NAVAL 2/71 EG 732 0 36077320
S 702 63 A ACCESS. 2/71 EG 709 8 36077098
S 702 63 A NAVAL 2/71 EG 733 8 36077338
S 702 80 A ACCESS. 2/71 EG 710 6 36077106
S 702 80 A NAVAL 2/71 EG 734 6 36077346
S 703 100 A ACCESS. 2/71 EG 717 1 36077171
S 703 100 A NAVAL 2/71 EG 741 1 36077411
S 703 25 A ACCESS. 2/71 EG 712 2 36077122
S 703 25 A NAVAL 2/71 EG 736 1 36077361
S 703 35 A ACCESS. 2/71 EG 713 0 36077130
S 703 35 A NAVAL 2/71 EG 737 9 36077379
S 703 50 A ACCESS. 2/71 EG 714 8 36077148
S 703 50 A NAVAL 2/71 EG 738 7 36077387
S 703 63 A ACCESS. 2/71 EG 715 5 36077155
S 703 63 A NAVAL 2/71 EG 739 5 36077395
S 703 80 A ACCESS. 2/71 EG 716 3 36077163
S 703 80 A NAVAL 2/71 EG 740 3 36077403
S 704 100 A ACCESS. 2/71 EG 723 9 36077239
S 704 25 A ACCESS. 2/71 EG 718 9 36077189
S 704 35 A ACCESS. 2/71 EG 719 7 36077197
S 704 50 A ACCESS. 2/71 EG 720 5 36077205
S 704 63 A ACCESS. 2/71 EG 721 3 36077213
S 704 80 A ACCESS. 2/71 EG 722 1 36077221
S 941N B 10 2/11 EE 541 7 16055417
S 941N B 16 2/11 EE 542 5 16055425
S 941N B 20 2/11 EE 543 3 16055433
S 941N B 25 2/11 EE 544 1 16055441
S 941N B 32 2/11 EE 545 8 16055458
S 941N B 40 2/11 EE 546 6 16055466
S 941N B 6 2/11 EE 540 9 16055409
S 941N C 10 2/11 EE 553 2 16055532
S 941N C 16 2/11 EE 554 0 16055540
S 941N C 2 2/11 EE 550 8 16055508
S 941N C 20 2/11 EE 555 7 16055557
S 941N C 25 2/11 EE 556 5 16055565
S 941N C 32 2/11 EE 557 3 16055573
S 941N C 4 2/11 EE 551 6 16055516
S 941N C 40 2/11 EE 558 1 16055581
S 941N C 6 2/11 EE 552 4 16055524
S 951N B 10 2/12 EE 561 5 16055615
S 951N B 16 2/12 EE 562 3 16055623
S 951N B 20 2/12 EE 563 1 16055631
S 951N B 25 2/12 EE 564 9 16055649
S 951N B 32 2/12 EE 565 6 16055656
S 951N B 40 2/12 EE 566 4 16055664
S 951N B 6 2/12 EE 560 7 16055607
S 951N C 10 2/12 EE 573 0 16055730
S 951N C 16 2/12 EE 574 8 16055748
S 951N C 2 2/12 EE 570 6 16055706
S 951N C 20 2/12 EE 575 5 16055755
S 951N C 25 2/12 EE 576 3 16055763
S 951N C 32 2/12 EE 577 1 16055771
S 951N C 4 2/12 EE 571 4 16055714
S 951N C 40 2/12 EE 578 9 16055789
S 951N C 6 2/12 EE 572 2 16055722
S 971N B 10 2/13 EE 581 3 16055813
S 971N B 16 2/13 EE 582 1 16055821
S 971N B 20 2/13 EE 583 9 16055839
S 971N B 25 2/13 EE 584 7 16055847
S 971N B 32 2/13 EE 585 4 16055854
S 971N B 40 2/13 EE 586 2 16055862
S 971N B 6 2/13 EE 580 5 16055805
S 971N C 10 2/13 EE 593 8 16055938
S 971N C 16 2/13 EE 594 6 16055946
S 971N C 2 2/13 EE 590 4 16055904
S 971N C 20 2/13 EE 595 3 16055953
S 971N C 25 2/13 EE 596 1 16055961
S 971N C 32 2/13 EE 597 9 16055979
S 971N C 4 2/13 EE 591 2 16055912
S 971N C 40 2/13 EE 598 7 16055987
S 971N C 6 2/13 EE 592 0 16055920
S2-A1I 2/39 KU 918 5 16219185
S2-A2I 2/39 KU 919 3 16219193
S2-BM1 2/41 KU 912 8 16219128
S2-BM2 2/41 KU 913 6 16219136
S2-BM3 2/41 KU 914 4 16219144
S2-BM4 2/41 KU 915 1 16219151
S2-BM5 2/41 KU 916 9 16219169
S2-BM6 2/41 KU 917 7 16219177
S2-BP 2/42 EF 998 8 16069988
S2-BPS 2/43 EF 999 6 16069996
S2-CM2 2/47 KU 936 7 16219367
S2-CM3 2/47 KU 937 5 16219375
S2-CM4 2/47 KU 938 3 16219383
S2-DH 2/44 KU 894 8 36218948
S2-EST 2/46 KU 922 7 16219227
S2-H02-I 2/40 KU 926 8 16219268
S2-H02X 2Ö 2/40 KU 898 9 36218989
S2-H03 2/40 KU 892 2 36218922
S2-H11-I 2/40 KU 925 0 16219250
S2-H11X 2/40 KU 897 1 36218971
S2-H12 2/40 KU 890 6 36218906
S2-H20-I 2/40 KU 927 6 16219276
S2-H20X 2S 2/40 KU 899 7 36218997
S2-H21 2/40 KU 891 4 36218914
S2-H30 2/40 KU 893 0 36218930
S2-MP2 2/45 KU 939 1 16219391
S2-S 2/40 KU 903 7 36219037
S2-S/H 2/40 KU 902 9 36219029
S3-M1 4/9 EP 873 2 36168732
S3-M2 4/9 EP 874 0 36168740
S5-H11 2/66 EI 410 1 36094101
S5-H20 2/66 EI 411 9 36094119
S5-S11 2/66 EI 412 7 36094127
S5-S20 2/66 EI 413 5 36094135
S500 H2B1 2/68 EI 427 5 36094275
S500 H2B2 2/68 EI 438 2 36094382
S500 H2Y1 2/68 EI 437 4 36094374
S500 H2Y2 2/68 EI 439 0 36094390
S500 H8B 2/68 EI 440 8 36094408
S500 H8Y 2/68 EI 441 6 36094416
S500 HP2B 2/68 EI 442 4 36094424
S500 HP2Y 2/68 EI 443 2 36094432
S500 RD3 2/68 EI 409 3 36094093
S500 RD4 2/68 EI 426 7 36094267
S500 S51 2/68 EI 416 8 36094168
S500 S52 2/68 EI 415 0 36094150
S500 S56 2/68 EI 444 0 36094440
S9-S 2/16 EE 611 8 16056118
S9-T130 2/15 EE 620 9 16056209
S9-T24 2/15 EE 619 1 16056191
S9-T415 2/15 EE 621 7 16056217
S9-V230CA 2/17 EE 616 7 16056167
S9-V24CA 2/17 EE 612 6 16056126
S9-V24CC 2/17 EE 613 4 16056134
S9-V48CA 2/17 EE 614 2 16056142
S9-V48CC 2/17 EE 615 9 16056159
S9-X 2/16 EE 610 0 16056100
S931N C 2 R 2/10 11861114 11861114
S931N C 4 R 2/10 11861115 11861115
S931N C 6 R 2/10 11861116 11861116
S931N C10 R 2/10 11861117 11861117
S931N C16 R 2/10 11861118 11861118
S931N C20 R 2/10 11861119 11861119
S931N C25 R 2/10 11861120 11861120
S931N C32 R 2/10 11861121 11861121
S931N C40 R 2/10 11861122 11861122
SA 2/71 EG 040 8 36070408
SA 1 4/9 EP 862 5 36168625
SA 3 4/9 EP 863 3 36168633
SCL 1/10 7/7 EG 062 2 16070622
SCL 1/100 7/7 EG 067 1 16070671
SCL 1/1000 7/7 EG 086 1 16070861
SCL 1/150 7/7 EG 068 9 16070689
SCL 1/1500 7/7 EG 548 0 16075480
SCL 1/20 7/7 EG 063 0 16070630
SCL 1/200 7/7 EG 069 7 16070697
SCL 1/2000 7/7 EG 549 8 16075498
SCL 1/25 7/7 EG 171 1 16071711
SCL 1/250 7/7 EG 048 1 16070481
SCL 1/2500 7/7 EG 550 6 16075506
SCL 1/30 7/7 EG 064 8 16070648
SCL 1/300 7/7 EG 070 5 16070705
14/24 ABB SACE
Code list
Type
Type Pg. Elc code Order code Type Pg. Elc code Order code Type Pg. Elc code Order code
14
SCL 1/40 7/7 EG 172 9 16071729
SCL 1/400 7/7 EG 083 8 16070838
SCL 1/5 7/7 EG 061 4 16070614
SCL 1/50 7/7 EG 065 5 16070655
SCL 1/500 7/7 EG 084 6 16070846
SCL 1/60 7/7 EG 173 7 16071737
SCL 1/600 7/7 EG 174 5 16071745
SCL 1/75 7/7 EG 106 7 16071067
SCL 1/80 7/7 EG 066 3 16070663
SCL 1/800 7/7 EG 085 3 16070853
SCL 1/A5/10 7/7 EG 088 7 16070887
SCL 1/A5/100 7/7 EG 119 0 16071190
SCL 1/A5/150 7/7 EG 120 8 16071208
SCL 1/A5/20 7/7 EG 089 5 16070895
SCL 1/A5/30 7/7 EG 090 3 16070903
SCL 1/A5/5 7/7 EG 087 9 16070879
SCL 1/A5/50 7/7 EG 109 1 16071091
SCL 1/A5/80 7/7 EG 110 9 16071109
SCL 2/10 7/8 EG 080 4 16070804
SCL 2/100 7/8 EG 195 0 16071950
SCL 2/150 7/8 EG 196 8 16071968
SCL 2/20 7/8 EG 149 7 16071497
SCL 2/200 7/8 EG 197 6 16071976
SCL 2/250 7/8 EG 198 4 16071984
SCL 2/30 7/8 EG 150 5 16071505
SCL 2/300 7/8 EG 199 2 16071992
SCL 2/400 7/8 EG 102 6 16071026
SCL 2/5 7/8 EG 082 0 16070820
SCL 2/50 7/8 EG 193 5 16071935
SCL 2/500 7/8 EG 103 4 16071034
SCL 2/6 7/8 EG 079 6 16070796
SCL 2/80 7/8 EG 194 3 16071943
SELVTESTER-C [NEW] 7/19 EB 247 4 16022474
SFP 2/45 EB 183 1 16021831
SK 01 & 4/8 EP 846 8 36168468
SK 10 & 4/8 EP 845 0 36168450
SK 11 [NEW] 4/8 EP 979 7 36169797
SM1/12 8/4 EA 425 7 16014257
SM1/230 8/4 EA 426 5 16014265
SNT 1/10 7/13 EG 181 0 16071810
SNT 1/100 7/13 EG 183 6 16071836
SNT 1/1000 7/13 EG 189 3 16071893
SNT 1/15 7/13 EG 125 7 16071257
SNT 1/150 7/13 EG 136 4 16071364
SNT 1/1500 7/13 EG 190 1 16071901
SNT 1/20 7/13 EG 126 5 16071265
SNT 1/200 7/13 EG 162 0 16071620
SNT 1/2000 7/13 EG 191 9 16071919
SNT 1/25 7/13 EG 127 3 16071273
SNT 1/250 7/13 EG 184 4 16071844
SNT 1/2500 7/13 EG 192 7 16071927
SNT 1/30 7/13 EG 128 1 16071281
SNT 1/40 7/13 EG 129 9 16071299
SNT 1/400 7/13 EG 185 1 16071851
SNT 1/5 7/13 EG 132 3 16071323
SNT 1/50 7/13 EG 182 8 16071828
SNT 1/500 7/13 EG 186 9 16071869
SNT 1/6 7/13 EG 135 6 16071356
SNT 1/60 7/13 EG 130 7 16071307
SNT 1/600 7/13 EG 187 7 16071877
SNT 1/80 7/13 EG 131 5 16071315
SNT 1/800 7/13 EG 188 5 16071885
SPA 2/71 EG 041 6 36070416
SPB 1 2/71 EG 042 4 36070424
SPE 2/71 EG 044 0 36070440
SQZ3 6/10 EG 617 3 16076173
ST 2/46 EP 742 9 36167429
ST-E 2/46 EP 743 7 36167437
STD 50-4 6/15 EG 745 2 36077452
STD-1000 U 6/15 EG 744 5 36077445
STD-420 LS 6/14 EG 743 7 36077437
STD-500 MA 6/14 EG 742 9 36077429
STD-MTS 6/15 EG 746 0 36077460
SW01 7/5 EA 145 1 16011451
SWD 6/6 EG 405 3 16074053
TAR-1 4/9 EP 850 0 36168500
TCS 1 7/12 EG 568 8 16075688
TCS 2 7/12 EG 569 6 16075696
TM10/12 8/2 EA 260 8 16012608
TM10/24 8/2 EA 261 6 16012616
TM15/12 8/2 EA 262 4 16012624
TM15/24 8/2 EA 263 2 16012632
TM30/12 8/2 EA 264 0 16012640
TM30/24 8/2 EA 265 7 16012657
TM40/12 8/2 EA 266 5 16012665
TM40/24 8/2 EA 267 3 16012673
TR 1 4/2 EG 309 7 16073097
TR 2 4/2 EG 310 5 16073105
TR 3 4/2 EG 311 3 16073113
TR 4 4/2 EG 312 1 16073121
TR 5/A 4/2 EG 415 2 16074152
TR 5/C 4/2 EG 416 0 16074160
TRFM/100 7/11 EG 291 7 16072917
TRFM/150 7/11 EG 292 5 16072925
TRFM/250 7/11 EG 293 3 16072933
TRFM/40 7/11 EG 289 1 16072891
TRFM/400 7/11 EG 294 1 16072941
TRFM/60 7/11 EG 290 9 16072909
TRFM/600 7/11 EG 295 8 16072958
TRM 4/2 EG 299 0 16072990
TS16/12 8/2 EA 278 0 16012780
TS16/24 8/2 EA 279 8 16012798
TS16/4-6-8 8/2 EA 280 6 16012806
TS16/4-8-12 8/2 EA 281 4 16012814
TS16/8 8/2 EA 277 2 16012772
TS24/4-8-12 8/2 EA 282 2 16012822
TS24/8-12-24 8/2 EA 283 0 16012830
TS8/12 8/2 EA 270 7 16012707
TS8/12SW 8/2 EA 273 1 16012731
TS8/24 8/2 EA 271 5 16012715
TS8/24SW 8/2 EA 274 9 16012749
TS8/4-6-8SW 8/2 EA 275 6 16012756
TS8/4-8-12SW 8/2 EA 276 4 16012764
TS8/8 8/2 EA 269 9 16012699
TS8/8SW 8/2 EA 272 3 16012723
TSM 8/4 EA 414 1 16014141
TSR [NEW] 8/4 EA 429 9 16014299
TWS-1 6/7 EG 573 8 16075738
UA 110 Vc.a. 4/8 EP 838 5 36168385
UA 230 Vc.a. 4/8 EP 839 3 36168393
UA 24 Vc.a. 4/8 EP 835 1 36168351
UA 415 Vc.a. 4/8 EP 840 1 36168401
UA 415 Vc.a.. - S 4/8 EP 834 4 36168344
UA 48 Vc.a. 4/8 EP 836 9 36168369
UA 500 Vc.a. 4/8 EP 841 9 36168419
UA 60 Vc.a. 4/8 EP 837 7 36168377
VLM 1/300 7/2 EG 051 5 16070515
VLM 1/500 7/2 EG 052 3 16070523
VLM 2/100 7/3 EG 071 3 16070713
VLM 2/300 7/3 EG 072 1 16070721
VLM-D1 7/4 EG 408 7 16074087
VLM-D2 7/4 EG 409 5 16074095
603221/011 gb - July ’01
Printed in Italy
2.000 - Océ Facility Services - CAL
ABB SACE S.p.A.
Line Protection Devices
Viale dellIndustria, 18
20010 Vittuone (MI) - Italy
Tel.: +39.02.9034.1 - Telefax: +39.02.9034.7609
http://www.abb.com/it
In consideration of modifications to Standards and materials,
the characteristics and overall dimensions indicated in this
catalogue may be considered binding only following confirmation
by ABB SACE