2ECO# 060615-3, 061207-3, 070612-5, 121120-2
2401 Stanwell Drive, Concord Ca. 94520 Ph: 925-687-4411 Fax: 925-687-3333 www.calex.com Email: sales@calex.com
75 WATT LT TRIPLE SERIES
DC/DC CONVERTERS
Input Parameters
Model 24T5.3.2LT 24T3.2.1R8LT
24T3.2.1R5LT
Units
Voltage Range
MIN
TYP
MAX
18
24
36
VDC
Input Overvoltage (100 ms) MAX 50 VDC
Input Ripple Rejection (120Hz) TYP 50 dB
Undervoltage Lockout Yes
Input Reverse Voltage Protection Yes
Input Current No Load
100% Load
TYP
TYP
12
3.6
mA
A
Inrush Current MAX 0.5 A2s
Reected Ripple, 12µH
Source Impedance (4) TYP 20 mA p-p
Efciency TYP 81 77 %
Switching Frequency TYP 360 kHz
Recommended Fuse (3) AMPS
Unless otherwise stated, these specications apply for baseplate temperature Tb=23±2ºC, nominal input voltage, and rated full load. (1) (2)
Notes:
(1) Refer to the CALEX Application Notes for the denition of terms,
measurement circuits, and other information.
(2) Full Load is dened as the main output operating at 10 Amps.
The Auxiliary outputs are equally loaded to bring output power to
75 Watts, or loaded to 10 Amps maximum on each.
(3) This unit is not fused and needs to be fused by the user. Refer
to the CALEX Application Notes for information on fusing. For
inrush current, refer to the specications above.
(4) Place a 33 µF capacitor between the two “Input” pins. Then
place the current sensor in series with 12 µH inductor between
the capacitor and the source. The reected ripple current is
measured over a 5 Hz to 20 MHz bandwidth. Noise should be
minimized in the measurement.
(5) Noise is measured per the CALEX Application Notes. Output
noise is measured with a 10 µF tantalum capacitor in parallel
with a 0.1 µF ceramic capacitor connected across the output to
CMN. Measurement bandwidth is 0-20 MHz.
(6) Optimum performance is obtained when this power supply is
operated within the minimum to maximum load specications.
No damage to the module will occur when the output is operated
at less than minimum load, but the output voltage may contain
a low frequency component that may exceed output noise
specications. At no load the converter’s Vo1 output voltage
may fall out of regulation, typically rising to the OVP limit. A load
current of between 0.5% to 1% of maximum rated load on any of
the outputs will usually sufce to bring Vo1 within regulation.
(7) Load Transient Recovery Time is dened as the time for the
output to settle from a 50 to 75% or 25% step load change to a
1% error band of output voltage (rise time of step = 2µs).
(8) Load Transient Overshoot is dened as the peak overshoot
during a transient as dened in the Note 7 above.
(9) Load Regulation is dened as the output voltage change when
changing load current from maximum to minimum. The voltage
is measured at the output pin.
(10) Most switches would be suitable for logic ON/OFF control. In case
there is a problem, you can make the following estimations and
then leave some margin.
When open collector is used for logic high, “Open Circuit Voltage
at ON/OFF Pin”, “Output Resistance” and “External Leakage
Current Allowed for Logic High” are used to estimate the high
impedance requirement of open collector.
When switch is used for logic low, “Open Circuit Voltage at
ON/OFF Pin”, “Output Resistance” and “LOW Logic Level” are
used to estimate the low impedance requirement of the switch.
(11) Thermal impedance is tested with the converter mounted vertically
and facing another printed circuit board 1/2 inch away. If converter
is mounted horizontally with no obstruction, thermal impedance is
approximately 7°C/W.
(12) Minimum load is dened as 10% of maximum load. Calex Mfg.
Co. Inc. does not guarantee performance for loads less than the
minimum. Loads less than the minimum shall not damage the
unit.
(13) When an external ON/OFF switch is used, such as open collector
switch, logic high requires the switch to be high-impedance.
Switch leakage currents greater than 10µA may be sufcient to
trigger the ON/OFF to the logic-low state.
(14) Water Washability - Calex DC/DC converters are designed
to withstand most solder/wash processes. Careful attention
should be used when assessing the applicability in your specic
manufacturing process. Converters are not hermetically sealed.
(15) Torque fasteners into threaded mounting inserts at 12 in.oz. or
less. Greater torque may result in damage to unit and void the
warranty.