Spec-00207 I
SEQUESTR™ PREFERREDCUTOUT DISCONNECTS SEQUESTR™ ExTERnal DiSconnEcTS
EQUIPMENT PROTECTIONSUBJECT TO CHANGE WITHOUT NOTICEDISCONNECT1
Spec-00207
I
763.422.2211
763.422.2600
DISCONNECT
SEQUESTR™ PREfERREd-CUToUT diSConnECTS
SEQUESTR™ ExTERnal diSConnECTS
SEQUESTR™ EXTERNAL DISCONNECT, TYPE 12
INDUSTRY STANDARDS
UL 508A Listed; Type 12; File No. E61997
cUL Listed per CSA C22.2 No. 94; Type 12; File No. E61997
NEMA/EEMAC Type 12
CSA File No. 42186: Type 12
IEC 60529, IP55
APPLICATION
Retrofit disconnect enclosures to isolate incoming power and help
mitigate arc flash occurrences by moving the disconnect switch to
the SEQUESTR™ Enclosure. Power is passed-through to the main
enclosure.
FEATURES
Interlocks with doors of main control cabinet when the disconnect
switch is powered ON
Maintains UL Type 12 rating
Provision for pass-through power into the main cabinet—blank
plate for customer modification
Preferred disconnect cutout
Quarter-turn screwdriver slot latch
Hidden hinges
Bonding provision on door
Conductive back panel included
Installation hardware and templates included
SPECIFICATIONS
16 gauge steel
Continuously welded and ground seams all around
Hinged on right side
FINISH
ANSI 61 gray exterior and interior
Included back panel has conductive finish
ACCESSORIES
See also Accessories.
Industrial Corrosion Inhibitors
Touch-Up Paint
BulletIn: A70D
Standard Product External Diconnect Enclosure including back panel
Catalog Number A (in.) A (mm) B (in.) B (mm) C (in.) C (mm)
AXD18 34.45 875 14.00 356 18.12 460
AXD20 34.45 875 14.00 356 20.12 511
AXD24 34.45 875 14.00 356 24.12 613
Optional Terminal Plates
Catalog Number For
ATBP3060 30 and 60 amp switches
ATPB100 100 amp switches
ATPB200 200 amp switches
Optional Replacement Conductive Panel
Catalog Number Panel Size (in.) Panel Size (mm) Description
A31P12G 31.00 x 12.16 787 x 309 16 gauge
Spec-00207 I
SEQUESTR™ PREFERREDCUTOUT DISCONNECTS SEQUESTR™ ExTERnal DiSconnEcTS
PH 763.422.2211 • FAX 763.422.2600 • HOFFMANONLINE.COMEQUIPMENT PROTECTION DISCONNECT 2
DISCONNECT MOUNTING SPACE
Disconnects are located by dimension E1. Wiring space W1 is
available when disconnect is installed in the enclosure.
See the Hoffman Specifier’s Guide Technical Information chapter
for E1 Spacing by Enclosure Height for various disconnect switch
manufacturers.
Refer to National Electrical Code® 2005 article 430.10(B) for
wiring space required for line side conductors to be connected to
disconnect. Verify your application to determine if wiring space is
adequate.
Consult Space Occupied by Disconnect drawing to determine whether
the disconnect device you are using will fit the enclosure size you have
selected.
SEQUESTR™ PREFERREDCUTOUT OVERVIEW
APPLICATION
The SEQUESTR™ enclosures have the standard preferred cutout
on the left-hand flange. They accept left-hand 1494V Allen-Bradley
variable-depth devices, up to 200A, and left-hand Class 9422 Square
D variable-depth devices, up to 200A.
SEQUESTR cutouts are designed to house the following:
Allen-Bradley Bulletin 1494V DSX left-hand disconnect switches
with flange-mount variable depth operating mechanisms and
Bulletin 1494V flange-mount variable-depth operating mechanisms
for circuit breakers.
These enclosures will NOT accept Allen-Bradley Bulletin 1494F
disconnect devices or Bulletin 1494D circuit breaker operators.
Schneider Square D® Class 9422 disconnect switches with flange-
mount left-hand variable-depth operating mechanisms and Class
9422 flange-mount left-hand variable-depth operating mechanisms
for circuit breakers.
These enclosures will NOT accept Square D Class 9422 bracket-
mounted disconnect devices, Class 9422TGI or TG2 devices.
ORDERING
Disconnect switch (or circuit breakers), operating handle and
operating mechanism are not furnished with enclosure. Consult
the Hoffman Specifier’s Guide Technical Information chapter for
wire bend information and hoffmanonline.com for disconnect
manufacturer information. Consult drawings to match the
disconnect device you are using with the correct enclosure size.
A complete assembly consists of:
1. An enclosure
2. Door interlock brackets
3. Door latching system (2-point on SEQUESTR Enclosure,
3-point on main control cabinet doors)
4. Instructions to locate and install disconnect
5. Grounding hardware kit
6. Conductive panel in SEQUESTR External Disconnect
Enclosure