Thermal-magnetic (TM and AS-line) AS168XDC1
www.schurter.com/PG17_20
Circuit Breakers
Circuit Breaker for Equipment thermal-magnetic, 1 pole
Description
- Thermal-magnetic circuit breaker
- High short circuit performance
- Availability of AC and DC in the same frame size
- DIN-Rail Mounting
Standards
- Approval Reference Type: AS168X
- VDE Certificate Number: IEC 60934
- UL File Number: UL 1077
- CSA File Number: CSA C22.2
Applications
- Industrial appliances
Weblinks
pdf-datasheet, html-datasheet, General Product Information, Approvals,
CE declaration of conformity, RoHS, CHINA-RoHS, REACH, e-Shop,
SCHURTER-Stock-Check, Distributor-Stock-Check, Detailed request for
product, Product News
Technical Data
General data
Rated Voltage DC IEC 180 V
UL/CSA 120/180 V
Rated current 0.5 - 50 A , see approbations
Conditional short circuit capa-
city IEC 60934
Icn: DC 180 V: 4.5 kA (no fuse)
Conditional short circuit capa-
city UL 1077
Icn: DC 120 V; DF/DG: 0.5A-40A: 10 kA
(no fuse)
Icn: DC 120 V; DH: 0.5A-40A: 5 kA (no
fuse)
Icn: DC 180 V; 0.5A-50A: 2 kA (no fuse)
Degree of Protection from front side IP 40 acc. to IEC 60529
Lifetime 1 x Ir 6000 switching cycles
Dielectric Strength 50 Hz: > 2 kV
Impulse 1.2/50 μs
Vibration Resistance ± 0.75 mm @ 5 - 60 Hz
acc. to IEC 60068-2-6, test Fc
10 G @ 60 - 500 Hz
acc. to IEC 60068-2-6, test Fc
Insulation Resistance 250/440 VAC > 5 MΩ
Shock Resistance 30 G / 18 ms
acc. to IEC 60068-2-27, test Ea
Ambient temperature -10 °C to 55 °C
Weight 100 - 130 g
Tripping Type
Positively trip free
Actuation type Manual ON/OFF
Permissible wire cross section 1.5 - 25 mm² / 16 - 4 AWG
Switched neutral
Rated Voltage AC 277 V
Rated current AC/DC 65 A
Function The switched neutral closes with ma-
nual closure of the poles and opens
automatically with thermal magnetic
tripping of the poles.
Add-on modules
Add-on modules Technical data for the additional module
see separate data sheet