PSR-SCP- 24DC/FSP/2X1/1X2 Order No.: 2986960
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2986960
PHOENIX CONTACT Inc., USA Page 2 / 6
http://www.phoenixcon.com May 9, 2011
Typical inrush current max. 100 mA
Typical response time 50 ms
Typical release time 50 ms
Recovery time 1 s
Output data
Contact type 2 undelayed enabling current paths, 1 undelayed confirmation
path
Contact material AgCuNi, + 0.2 µm Au
Maximum switching voltage 250 V AC/DC
Minimum switching voltage 15 V AC/DC
Limiting continuous current 5 A (N/O contact)
100 mA (N/C contact)
Maximum inrush current 5 A
Inrush current, minimum 5 mA
Sq. Total current 50 A2 (ITH
2 = I1
2 + I2
2 + ... + IN
2)
Interrupting rating (ohmic load) max. 120 W (24 V DC, τ = 0 ms, N/C contact: 2.4 W)
192 W (48 V DC, τ = 0 ms, N/C contact: 4.8 W)
162 W (60 V DC, τ = 0 ms, N/C contact: 6 W)
66 W (110 V DC, τ = 0 ms, N/C contact: 11 W)
60 W (220 V DC, τ = 0 ms, N/C contact: 22 W)
1250 VA (250 V AC, τ = 0 ms, N/C contact: 25 VA)
Maximum interrupting rating (inductive load) 72 W (24 V DC, τ = 40 ms, N/C contact: 2.4 W)
43 W (48 V DC, τ = 40 ms, N/C contact: 4.8 W)
41 W (60 V DC, τ = 40 ms, N/C contact: 6 W)
35 W (110 V DC, τ = 40 ms, N/C contact: 11 W)
48 W (220 V DC, τ = 40 ms, N/C contact: 22 W)
Switching capacity min. 75 mW
Output fuse 10 A gL/gG (N/O contact)
6 A gL/gG (N/C contact)
General data
Width 17.5 mm
Height 99 mm
Depth 114.5 mm
Ambient temperature (operation) -20 °C ... 55 °C
Ambient temperature (storage/transport) -40 °C ... 70 °C