AC/DC SENSITIVE
EARTH-LEAKAGE RELAY
EL731
+ –
Specifications
IEEE Device Numbers AC ground fault (50G/N, 51G/N),
DC ground fault (79G),
PTC overtemperature (49),
RTD temperature (38, 49)
Supply Voltage 120/240 Vac/Vdc, 24 Vdc,
48 Vdc/24 Vac
Trip Level Settings 30-5,000 mA AC and DC
Alarm Level Settings 30-5,000 mA AC and DC
Trip Delay 0.05-2 s
Output Contacts 3 Form C (programmable)
Contact Operating Mode Fail-safe & non-fail-safe
Reset Front panel and remote
Freq. Response, CT1 0-90 Hz
Freq. Response, CT2 20-6,000, 190-6,000, 20-90, 20-3,000 Hz;
selectable
Current Transformer EFCT-x series
CT Detection Open & short detection
Terminals Plug-in, wire clamping,
24 to 12 AWG (0.2-2.5 mm2)
Communications EtherNet/IP™, DeviceNet™, Profibus®,
Modbus® TCP (optional)
Analog Output 4-20 mA (selectable 0-5 A or
0-100% trip-level setting)
Conformal Coating Standard feature
Dimensions H 48 mm (1.9”); W 96 mm (3.8”);
D 129 mm (5.0”)
Approvals UL Listed (E340889), CSA,
RCM (Australia), CE
Warranty 5 years
Mounting Panel; Surface and DIN (with optional
AC700-SMK)
FEATURES BENEFITS
Adjustable pickup (30-5,000 mA) Adjustable trip setting provides a wide range of low-level protection and system coordination
Frequency range (0-90 Hz, 20-6,000 Hz) Operate in either AC or DC mode or both. Use single or combined ranges. Separate metering
32-char OLED display Earth-leakage metering, setup and programming
Local LED indication Visual Trip, Alarm, CT connection indication
CT-Loop monitoring Alarms when CT is not connected
Analog output (4-20 mA) Connect to DCS. Allows connection to an optional meter (PGA-0520) or control system
Adjustable time delay Adjustable trip delay for quick protection and system coordination
Alarm and trip settings Detect a deteriorating condition before damage occurs
Temperature-sensor input Drive or motor temperature protection
Output contacts 3 programmable: Operate 2 alarm and 1 trip circuit
Network communication Optional connection to plant network
Harmonic filtering Eliminates nuisance tripping due to harmonic noise
Microprocessor based No required calibration saves maintenance cost
Universal power supply Provides flexibility for numerous applications
Features & Benefits
Wiring Diagram
Earth-Leakage Protection–Grounded AC or DC Systems
EL731 SERIES
AC/DC Sensitive Earth-Leakage Relay
Littelfuse reserves the right to make product changes, without notice. Material in this document is as accurate as known at the time of publication. Visit Littelfuse.com for the most up-to-date information.
Littelfuse.com/el731
Rev: 4-F-040716
Based on Manual Rev 6-F-031116