Batteriemodul 12 Ah Battery module 12 Ah 6EP1935-6MF01 Betriebsanleitung Operating Instructions A5E39404516 https://support.industry.siemens.com 20A Akku-Sicherung F1 nur in Kombination mit DC-USV-Modul 6 oder 15 zulassig 20A Batterymodul-fuse F1 only combination with DC-USV-Modul 6 or 15 permissable 30 Akku-Sicherung F1 nur in Kombination mit DC-USV-Modul 40 zulassig 30A Batterymodul-fuse F1 only combination with DC-USV-Modul 40 permissable Achtung ! Geladene Batterie. Sicherung F1 erst bei Inbetriebnahme einsetzen. Attention ! Full charged battery. Fuse F1 must not fit into before commissioning. Nicht mastablich ! Not to scale ! (c) Siemens AG 2016 A5E39404516, 11.2016 1/2 Batterymodule 12 Ah Deutsch Hardware Kurzbeschreibung: Das Batteriemodul 12Ah besteht aus einer Batterieaufnahme mit 2 Stuck wartungsfreien, verschlossenen Blei-AGM-Akkumulatoren sowie Klemmen fur die Verbindungsleitungen zur unterbrechungsfreien Stromversorgung SITOP Power. Hinweise: Die zutreffenden Betriebsanleitungen der SITOP DC-USV-Module sind zu beachten. ACHTUNG! Die Sicherung ist erst zur Inbetriebnahme in den Sicherungshalter einzusetzen (geladene Akkumulatoren). 20A Akku-Sicherung F1 nur in Kombination mit DC-USV-Modul 6 oder 15 zulassig. 30A/40A Akku-Sicherung F1 nur in Kombination mit DC-USV-Modul 40 zulassig. Bei Akkumulatorenwechsel sind stets Akkumulatoren gleicher Chargennummer zu verwenden, (annahernd gleicher Ladungszustand). Die Entsorgung der Akkumulatoren hat im entladenen Zustand nach den zutreffenden Vorschriften zu erfolgen. Bei Lagerung, Montage und Betrieb der Pufferbatterien sind die Bestimmungen der VDE 0510 Teil 2 / EN 50272-2 bzw. entsprechende nationale Vorschriften zu beachten. Fur ausreichende Be- und Entluftung des Batteriestandortes ist zu sorgen. Einbauort des Batteriemodul : im unteren Teil des Schaltschrankes bzw. an der kuhlsten Stelle im Schaltschrank. Technische Daten: Masse: Hauptabmessungen: Batterie: Sicherung (im Beipackbeutel): Anschlusstechnik: Einsatzbedingungen: zul. Temperatur: Selbstentladung: Schutzklasse: Schutzart: ca. 9 kg Breite 253 mm; Hohe 168 mm; Tiefe ca.122 mm 2 Stuck wartungsfreie Blei-AGM-Akkumulatoren 12V/12Ah Typ: Yuasa NP12-12 oder B.B.Battery BP12-12 Flachsicherung 20A, 30A und 40A (40A nur fur ATEX, nicht fur UL) Federzuganschluss; 0,08 - 4 mm2 Betrieb -15...+50 C Lagerung/Transport -20...+50 C Einsatzbedingungen nach EN 60721-3-3, Klimaklasse 3K3, 5 - 95 % ohne Betauung. Die Selbstentladungsrate der Akkumulatoren betragt ca. 3%/ Monat bei einer Temperatur von 20C. Dieser Wert ist temperaturabhangig und wird bei steigender Temperatur ungunstiger bzw. bei sinkender Temperatur gunstiger. III nach IEC 536; VDE 0106T1 Die naturliche Schutzleiterverbindung uber die Montagebefestigungen ist vorzugsweise auszufuhren. IP00 nach IEC 529 English Hardware Short Description: The battery module 12Ah consists of a battery receptacle with 2 pcs. maintenance-free, sealed lead AGM batteries and terminals for the connection lines with the uninterruptible SITOP power supply (UPS). NOTES: Follow the relevant operating instructions applicable to SITOP DC UPS modules. CAUTION! Insert the fuse into the fuse holder only on commissioning (charged batteries). 20A Batterymodul-fuse F1 only in combination with DC-USV-Modul 6 or 15 permissible. 30A/40A Batterymodul-fuse F1 only in combination with DC-USV-Modul 40 permissible. When replacing the batteries, always use batteries of the same series number (about equal in their charging condition). Disposal of uncharged batteries must be carried out acc. to the relevant standards and instructions. For storage, installation and operation of the batteries the specifications of VDE 0510 part 2 /EN 50272-2 or the relevant national regulations must be observed. Care must be taken to ensure sufficient ventilation for the battery. Place of installation of the battery module: lower part of the cubicle or coolest part in the cubicle Technical Data: Weight: Overall dimensions: Battery: Fuse (enclosed): Connectio technology: Operating Conditions: Admissible temperature: Self-discharge: Class of protection: Degree of protection: approx. 9 kg / 20 lbs width 253 mm; height 168 mm; depth approx. 122 mm 2 pcs. maintenance-free lead AGM battery 12V/7Ah type: Yuasa NP12-12 or B.B.Battery BP12-12 Blade fuse 20A, 30A and 40A (40A only for ATEX, not for UL) Spring-loaded terminals; 0.08 - 4 mm2 operation -15...+50C storage/ transport -20...+50C Operating conditions acc. to EN 60721-3-3, climate model 3K3, 5 - 95 % no condensation The self-discharge rate of the batteries is approx. 3% per month on temperature 20C. This value depends on temperature and gets worse with increasing temperature and resp., better with falling temperature. III acc. to IEC 536; VDE 0106 Part 1 Preferably, the natural protective conductor connection through the fittings should be used. IP00 acc. to IEC 529 Das Gerat erfullt die ATEX Richtlinie 2014/34/EU; EN 60079-0; EN 60079-15 The device complies with ATEX directive 2014/34/EU; EN 60079-0; EN 60079-15 ATEX: WARNUNG: ANSCHLUSSE NUR IN NICHT-EXPLOSIVER UMGEBUNG TRENNEN! WARNUNG: ENTFERNEN / EINSETZEN DER SICHERUNG NUR IN NICHT-EXPLOSIVER UMGEBUNG! WARNING: SEPARATE IN NON-HAZARDOUS AREAS ONLY! WARNING: REMOVE / INSERT FUSE IN NON-HAZARDOUS AREAS ONLY! ATTENTION : RETRAIT UNIQUEMENT EN ZONES NON EXPLOSIBLES ! II 3G Ex nA IIC T3 Gc ATTENTION : RETRAIT OU INSERTION DU FUSIBLE UNIQUEMENT EN ZONES NON EXPLOSIBLES ! Harzardous Areas: For an enclosure / cabinet rated min. IP23 is required - sufficient ventilation must be ensured in the final system GL, ABS (c) Siemens AG Osterreich, AT-1210 Vienna, Austria. All rights reserved. Liefermoglichkeiten und technische Anderungen vorbehalten Availability and technical specifications subject to change without prior notice (c) Siemens AG 2016 A5E39404516, 11.2016 2/2 Batterymodule 12 Ah