3
SCHRACK
Socket with screw-type terminals for DIN rail mounting
RT 78 724 Socket with screw-type terminals, pinning 3.5 mm
for DIN rail mounting
RT 78 726 Socket with screw-type terminals, pinning 5 mm for
DIN rail mounting, logical terminal arrangement
n DIN-rail socket with logical setup of connections (input/output)
n High quality rising clamp terminals
n Captive combination terminal screws
n Jumper bars for interconnection
RT 78 725 Socket with screw-type terminals, pinning 5 mm for
DIN rail mounting, conventional terminal arrangement
n Conventional terminal arrangement
Approvals
VDE Cert. No. 40007571, cULus E135149
Technical data RT78724/RT78726 RT78725
Rated voltage/Max. switching voltage AC 240/400 VAC
Rated current 12 A, 2 x 8 A, 16 A*)
Dielectric strength
coil-contact circuit 5000 Vrms 4000 Vrms
open contact circuit 1000 Vrms 1000 Vrms
adjacent contact circuits 2500 Vrms 2500 Vrms
Clearance / creepage
coil-contact circuit ≥ 10/10 mm ≥ 4.7/4.7 mm
Material group of insulation parts IIIa
Flammability class UL 94 V-0
Insulation to IEC 60664-1
Type of insulation coil-contact circuit reinforced basic
open contact circuit functional
adjacent contact circuits functional
Rated insulation voltage 250 V
Pollution degree 2
Rated voltage system 230 / 400 V
Overvoltage category III
Material compliance: EU RoHS/ELV, China RoHS, REACH, Halogen content
refer to the Product Compliance Support Center at
www.te.com/customersupport/rohssupportcenter
*) For 1 pole relays (16 A) the relay terminals 11-21, 12-22 and 14-24 have to be bridged.
For 1 pole relays (12 A) the relay terminals 11-12-14 have to be connected to the socket
terminals 21-12-14.
General Purpose Relays
Accessories
Accessories Industrial Power Relay RT (Continued)
F0261-C
S0416-CB
F0284-B
S0416-CA
S0540-BT
n Not suitable for bistable relays with 2 coils!
RT 78 724 RT 78 726