MFM-05 series
SPECIFICATIONSPECIFICATION
MODEL
DC VOLTAGE
RATED CURRENT
CURRENT RANGE Note.2
RATED POWER
OUTPUT
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE Note.6
FREQUENCY RANGE
EFFICIENCY (Typ.)
INPUT
INRUSH CURRENT (Typ.)
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
WORKING HUMIDITY
WORKING TEMP.
OVER TEMPERATURE
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MTBF
DIMENSIONOTHERS
NOTE
PACKING
OVERLOAD
OVER VOLTAGE
AC CURRENT (Typ.)
1000ms, 30ms/230VAC 1000ms, 30ms/115VAC at full load
40ms/230VAC 12ms/115VAC at full load
80 ~ 264VAC
47 ~ 440Hz
0.2A/115VAC 0.1A/230VAC
110% ~ 180% rated output power
Protection type : Hiccup mode, recovers automatically after fault condition is removed
20 ~ 90% RH non-condensing
-40 ~ +85 (Refer to "Derating Curve")℃
-40 ~ +100 , 10 ~ 95% RH non-condensing℃
±℃ ℃0.03%/ (0 ~ 60 )
10 ~ 500Hz, 5G 10min./1cycle, period for 60min. each along X, Y, Z axes
1799.5Khrs min. MIL-HDBK-217F (25 )℃
42*22.3*20.5mm (L*W*H) or 1.65 *0.88 0.8" " 0" inch
SAFETY STANDARDS
RIPPLE & NOISE (max.) Note.4
VOLTAGE TOLERANCE Note.5
ENVIRONMENT
SAFETY &
EMC
(Note 9)
PROTECTION
Protection type : Shut off o/p voltage, clamping by zener diode
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
I/P-O/P:4KVAC
I/P-O/P:100M Ohms / 500VDC / 25 / 70% RH℃
LEAKAGE CURRENT (max.) Note.7
Touch current <80 A/264VAC
μ
ISOLATION LEVEL Primary-Secondary: 2xMOPP
Parameter
Parameter
Conducted
Radiated
Harmonic Current
Voltage Flicker
Standard
Standard
EN55011 (CISPR11)
EN55011 (CISPR11)
EN61000-3-2
EN61000-3-3
Test Level / Note
Test Level / Note
Class B
Class B
Class A
-----
EMC IMMUNITY
EMC EMISSION
MFM-05-3.3 MFM-05-5 MFM-05-12 MFM-05-15 MFM-05-24
±0.3%
±0.5%
±0.3%
±0.5%
±0.3%
±0.5%
±0.3%
±0.5%
±0.3%
±0.5%
±2.5% ±2.5% ±2.5% ±2.5%±2.5%
5V3.3V 12V 15V 24V
1A1.25A 0.42A 0.33A 0.23A
0 ~ 1A0 ~ 1.25A 0 ~ 0.42A 0 ~ 0.33A 0 ~ 0.23A
5W4.1W 5W 5W 5.5W
13.8 ~ 16.2V 17.3 ~ 20.3V 27.6 ~ 32.4V
5.75 ~ 6.8V3.8 ~ 5V
SOLDERING TEMPERATURE 260 5 /10sec.max.℃± ℃
PEAK CURRENT 1.38A 1.1A 0.46A 0.36A 0.25A
OPERATING ALTITUDE Note.8 5000 meters
0.018Kg; 270pcs/5.8Kg/0.97CUFT
100mVp-p
100mVp-p
150mVp-p 150mVp-p 180mVp-p
78%74% 80% 81% 82%
PEAK LOAD(10sec.)
Note.3 4.6W 5.5W 5.5W 5.4W 6W
COLD START 25A/115VAC 45A/230VAC
IEC60601-1, EN60601-1, , UL ANSI/AAMI ES60601-1(3.1 version), CAN/CSA-C22 3 Edition approved ; Design
rd
EAC TP TC 004
refer to EN60335 1-
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.℃
2. No minimum load required.
3. 33% Duty cycle maximum within every 30 seconds. Average output power should not exceed the rated power
4. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1 f & 47 f parallel capacitor.
5. Tolerance : includes set up tolerance, line regulation and load regulation.
6. Derating may be needed under low input voltages. Please check the derating curve for more details.
7. Touch current was measured from primary input to DC output.
8. The ambient temperature derating of 3.5 /1000m with fanless models and of 5 /1000m with fan models for operating altitude higher than 2000m(6500ft).℃℃
9. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still
meets EMC directives. For guidance on how to perform these EMC tests, please refer to EMI testing of component power supplies.
(as available on http://www.meanwell.com)
μμ
5W High Reliable Green Medical On Board Type
ESD EN61000-4-2
EN61000-4-3
EN61000-4-4
EN61000-4-5
EN61000-4-6
EN61000-4-8
EN61000-4-11 100% dip 1 periods, 30% dip 25 periods,
100% interruptions 250 periods
Level 4, 15KV air ; Level 4, 8KV contact
Level 3, 1KV/Line-Line
EN60601-1-2
RF field susceptibility
EFT bursts
Surge susceptibility
Conducted susceptibility
Magnetic field immunity Level 4, 30A/m
Level 3, 10V
Level 3, 2KV
Voltage dip, interruption
Level 3, 10V/m( 80MHz~2.7GHz )
Table 9, 9~28V/m( 385MHz~5.78GHz )
SAFETY STANDARDS
File Name:MFM-05-SPEC 2019-06-28