Solid State Relays (SSRs) G3PA/G3PB Long Service Life for Circuits that Cycle Frequently Built-in heat sink increases life and reliability Voltage turn-on at zero crossing reduces initial inrush load currents LED indicator turns on when control power is applied DIN rail mountable Conforms to UL, CSA, VDE and CE requirements D D D D D Ordering Information J G3PA Relays with Replaceable Triac Output Cartridge D Current indicator turns red when excessive current is applied D Side-by-side dense mounting is possible using built-in linking brackets Single-Phase Models Stock Note: Shaded models are normally stocked. Max. load current Max. inrush current Operating voltage 5-24 VDC Load voltage 24-240 VAC Model 10 amps 150 amps, 60 Hz 20 amps 220 amps, 60 Hz G3PA-210B-VD DC5-24 G3PA-220B-VD DC5-24 40 amps 440 amps, 60 Hz G3PA-240B-VD DC5-24 60 amps 440 amps, 60 Hz 20 amps 220 amps, 60 Hz 30 amps 440 amps, 60 Hz G3PA-430B-VD-2 DC12-24 50 amps 440 amps, 60 Hz G3PA-450B-VD-2 DC12-24 G3PA-260B-VD DC5-24 12-24 VDC 200-480 VAC G3PA-420B-VD-2 DC12-24 J G3PB Relays Single Phase Models Stock Note: Shaded models are normally stocked. Max. load current Max. inrush current Operating voltage 12-24 VDC Load voltage 100-240 VAC Model 15 amps 150 amps, 60 Hz 25 amps 220 amps, 60 Hz G3PB-225B-VD DC12-24 35 amps 440 amps, 60 Hz G3PB-235B-VD DC12-24 45 amps 440 amps, 60 Hz G3PB-245B-VD DC12-24 C--4 Solid State Relays G3PA/G3PB G3PB-215B-VD DC12-24 J DIN Rail Mounting Track Stock Note: Shaded models are normally stocked. Model Description DIN rail track, 7.3 mm (0.29 in) depth; 50 cm (1.64 ft) length PFP-50N DIN rail track, 7.3 mm (0.29 in) depth; 1 m (3.28 ft) length PFP-100N End plate PFP-M Spacer PFP-S J Replacement Parts Stock Note: Shaded models are normally stocked. Carry current Name Power device cartridge 10 A Applicable SSR Model G3PA--210B--VD DC5--24 G32A--A10--VD DC5--24 G3PA--210BL--VD DC5--24 G32A--A10L--VD DC5--24 G3PA--210--VD AC24 G32A--A10--VD AC24 G3PA--220--VD DC5--24 G32A--A20--VD DC5--24 G3PA--220L--VD DC5--24 G32A--A20L--VD DC5--24 G3PA--220--VD AC24 G32A--A20--VD AC24 G3PA--240--VD DC5--24 G32A--A40--VD DC5--24 G3PA--240L--VD DC5--24 G32A--A40L--VD DC5--24 G3PA--240--VD AC24 G32A--A40--VD AC24 G3PA--260--VD DC5--24 G32A--A60--VD DC5--24 G3PA--260L--VD DC5--24 G32A--A60L--VD DC5--24 G3PA--260--VD AC24 G32A--A60--VD AC24 20 A G3PA--420--VD DC12--24 G32A--A420--VD DC12--24 30 A G3PA--430--VD DC12--24 G32A--A430--VD DC12--24 20 A G3PA--420--VD--2 DC5--24 G32A--A420--VD--2 DC5--24 30 A G3PA--430--VD--2 DC5--24 G32A--A430--VD--2 DC5--24 50 A G3PA--450--VD--2 DC5--24 G32A--A450--VD--2 DC5--24 20 A 40 A 60 A Application Examples Temperature Controller SSR Voltage output terminal (for driving SSR) Load Heater Input Output Power supply for load Direct connection possible Omron's SSRs offer these advantages over electro-mechanical relays (EMRs): D Longer service life with no contacts to wear out D Vibration and shock resistance D Reduced electromagnetic interference D No audible noise when switching D Faster response time D Enhanced reliability Solid State Relays G3PA/G3PB C--5 Specifications J Ratings Input (at 25C) Model Rated voltage g G3PA-210B-VD Voltage g range g Input p current i impedance d Voltage level Must operate voltage Must release voltage 5 to 24 VDC 4 to 30 VDC 7 mA max. 4 VDC max. 1 VDC min. 12 to 24 VDC 9.6 to 30 VDC 7 mA max. 9.6 VDC max. 1 VDC min. 12 to 24 VDC 9.6 to 30 VDC 7 mA max. 9.6 VDC max. 1 VDC min. G3PA-220B-VD G3PA-240B-VD G3PA-260B-VD G3PA-420B-VD-2 G3PA-430B-VD-2 G3PA-450B-VD-2 G3PB-215B-VD G3PB-225B-VD G3PB-235B-VD G3PB-245B-VD Output Applicable load Model Load voltage G3PA-210B-VD 19 to 264 VAC (50/60 Hz) H ) Load current Inrush current With Class-1 AC resistive load 0.1 to 10 A 150 A (60 Hz, 1 cycle) 2.4 kW at 240 VAC 0.1 to 20 A 220 A (60 Hz, 1 cycle) 4.8 kW at 240 VAC G3PA-240B-VD 0.5 to 40 A 440 A (60 Hz, 1 cycle) 9.6 kW at 240 VAC G3PA-260B-VD 0.5 to 60 A 440 A (60 Hz, 1 cycle) 14.4 kW at 240 VAC 0.5 to 20 A 220 A (60 Hz, 1 cycle) 9.6 kW at 480 VAC 0.5 to 30 A 440 A (60 Hz, 1 cycle) 14.4 kW at 480 VAC 0.5 to 50 A 440 A (60 Hz, 1 cycle) 24 kW at 480 VAC 0.1 to 15 A 150 A (60 Hz, 1 cycle) 3 kW at 200 VAC 0.1 to 25 A 220 A (60 Hz, 1 cycle) 5 kW at 200 VAC G3PB-235B-VD 0.5 to 35 A 440 A (60 Hz, 1 cycle) 7 kW at 200 VAC G3PB-245B-VD 0.5 to 45 A 440 A (60 Hz, 1 cycle) 9 kW at 200 VAC G3PA-220B-VD G3PA-420B-VD-2 G3PA-430B-VD-2 180 to 528 VAC H ) (50/60 Hz) G3PA-450B-VD-2 G3PB-215B-VD G3PB-225B-VD C--6 75 to 264 VAC (50/60 Hz) H ) Solid State Relays G3PA/G3PB J Characteristics G3PA Item G3PA210B-VD G3PA220B-VD G3PA240B-VD G3PA260B-VD G3PA420B-VD-2 G3PA430B-VD-2 G3PA450B-VD-2 Operate time 1/2 of load power source cycle + 1 ms max. (DC Input, -B models) 1 1/2 of load power source cycle + 1 ms max. (AC Input) Release time 1/2 of load power source cycle + 1 ms max. (DC Input) 1 1/2 of load power source cycle + 1 ms max. (AC Input) Output ON voltage drop 1.6 V (RMS) max. Leakage current 5 mA max. at 120 VAC 10 mA max. at 230 VAC 10 mA max. at 120 VAC 20 mA max. at 230 VAC 20 mA max. at 400 VAC I 2t 260 A2S 810 A2S 260 A2S Insulation resistance 100 M min. at 500 VDC Dielectric strength 4,000 VAC, 50/60 Hz for 1 min Vibration resistance Malfunction: 10 to 55 Hz, 0.75-mm double amplitude (mounted to DIN rail) Shock resistance Malfunction: 300 m/s2 (mounted to DIN rail) Ambient temperature Operating: --30C to 80C (with no icing or condensation) Storage: --30C to 100C (with no icing or condensation) Approved standards UL508 File No.E64562, CSA C22.2 (No.14, No.950) File No.LR35535, EN60950 File No. 5915UG Ambient humidity Operating: 45% to 85% Weight Approx. 260 g 1.8 V (RMS) max. Approx. 340 g Approx. 460 g Approx. 900 g Approx. 290 g 810 A2S Approx. 410 g Approx. 900 g G3PB Part number G3PB-215B-VD Operate time 1/2 of load power source cycle + 1 ms max. (DC input) G3PB-225B-VD G3PB-235B-VD Release time 1/2 of load power source cycle + 1 ms max. (DC input) Output ON voltage drop 1.6 V (RMS) max. Leakage current 10 mA max. (at 200 VAC) Permissible I2t (half 60-Hz wave) 121 A2s Insulation resistance 100 M min. at 500 VDC Dielectric strength 2,500 VAC, 50/60 Hz for 1 min Vibration resistance Destruction and malfunction: 10 to 55 Hz, 0.75-mm double amplitude Shock resistance Destruction: 294 m/s2 Malfunction: 294 m/s2 (DIN track mounting) Ambient temperature Operating: Storage: Approved standards UL508 File No. E64562 (From April 1999) CSA22.2 No. 14 File No. LR35535 (From April 1999) IEC947-4-3 File No. 6825 UG Ambient humidity Operating: 45% to 85% Weight Approx. 240 g 260 A2s G3PB-245B-VD 1,260 A2s --30C to 80C (with no icing or condensation) --30C to 100C (with no icing or condensation) Approx. 240 g Solid State Relays Approx. 400 g G3PA/G3PB Approx. 400 g C--7