Solid State Relays G3PA/G3PB
C--4
Solid State Relays (SSRs)
G3PA/G3PB
Long Service Life for Circuits that
Cycle Frequently
DBuilt-in heat sink increases life and reliability
DVoltage turn-on at zero crossing reduces initial inrush
load currents
DLED indicator turns on when control power is applied
DDIN rail mountable
DConforms to UL, CSA, VDE and CE requirements
Ordering Information
JG3PA Relays with Replaceable Triac Output Cartridge
DCurrent indicator turns red when excessive current is applied
DSide-by-side dense mounting is possible using built-in linking brackets
Single-Phase Models
Stock Note: Shaded models are normally stocked.
Max. load current Max. inrush current Operating voltage Load voltage Model
10 amps 150 amps, 60 Hz 5-24 VDC 24-240 VAC G3PA-210B-VD DC5-24
20 amps 220 amps, 60 Hz G3PA-220B-VD DC5-24
40 amps 440 amps, 60 Hz G3PA-240B-VD DC5-24
60 amps 440 amps, 60 Hz G3PA-260B-VD DC5-24
20 amps 220 amps, 60 Hz 12-24 VDC 200-480 VAC G3PA-420B-VD-2 DC12-24
30 amps 440 amps, 60 Hz G3PA-430B-VD-2 DC12-24
50 amps 440 amps, 60 Hz G3PA-450B-VD-2 DC12-24
JG3PB Relays
Single Phase Models
Stock Note: Shaded models are normally stocked.
Max. load current Max. inrush current Operating voltage Load voltage Model
15 amps 150 amps, 60 Hz 12-24 VDC 100-240 VAC G3PB-215B-VD DC12-24
25 amps 220 amps, 60 Hz G3PB-225B-VD DC12-24
35 amps 440 amps, 60 Hz G3PB-235B-VD DC12-24
45 amps 440 amps, 60 Hz G3PB-245B-VD DC12-24
Solid State Relays G3PA/G3PB C--5
JDIN Rail Mounting Track
Stock Note: Shaded models are normally stocked.
Description Model
DIN rail track, 7.3 mm (0.29 in) depth; 50 cm (1.64 ft) length PFP-50N
DIN rail track, 7.3 mm (0.29 in) depth; 1 m (3.28 ft) length PFP-100N
End plate PFP-M
Spacer PFP-S
JReplacement Parts
Stock Note: Shaded models are normally stocked.
Name Carry current Applicable SSR Model
Power device cartridge 10 A G3PA--210B--VD DC5--24 G32A--A10--VD DC5--24
G3PA--210BL--VD DC5--24 G32A--A10L--VD DC5--24
G3PA--210--VD AC24 G32A--A10--VD AC24
20 A G3PA--220--VD DC5--24 G32A--A20--VD DC5--24
G3PA--220L--VD DC5--24 G32A--A20L--VD DC5--24
G3PA--220--VD AC24 G32A--A20--VD AC24
40 A G3PA--240--VD DC5--24 G32A--A40--VD DC5--24
G3PA--240L--VD DC5--24 G32A--A40L--VD DC5--24
G3PA--240--VD AC24 G32A--A40--VD AC24
60 A G3PA--260--VD DC5--24 G32A--A60--VD DC5--24
G3PA--260L--VD DC5--24 G32A--A60L--VD DC5--24
G3PA--260--VD AC24 G32A--A60--VD AC24
20 A G3PA--420--VD DC12--24 G32A--A420--VD DC12--24
30 A G3PA--430--VD DC12--24 G32A--A430--VD DC12--24
20 A G 3 PA -- 4 2 0 -- V D -- 2 D C 5 -- 2 4 G 3 2 A -- A 4 2 0 -- V D -- 2 D C 5 -- 2 4
30 A G 3 PA -- 4 3 0 -- V D -- 2 D C 5 -- 2 4 G 3 2 A -- A 4 3 0 -- V D -- 2 D C 5 -- 2 4
50 A G 3 PA -- 4 5 0 -- V D -- 2 D C 5 -- 2 4 G 3 2 A -- A 4 5 0 -- V D -- 2 D C 5 -- 2 4
A
p
p
l
i
c
a
t
i
o
n
E
x
a
m
p
l
e
s
Load
Heater
Power supply
for load
Direct connection possible
Temperature Controller
Voltage output
terminal
(for driving SSR)
SSR
Input Output
Omron’s SSRs offer these advantages over electro-mechanical relays (EMRs):
DLonger service life with no contacts to wear out
DReduced electromagnetic interference
DFaster response time
DVibration and shock resistance
DNo audible noise when switching
DEnhanced reliability
Solid State Relays G3PA/G3PB
C--6
S
p
e
c
i
f
i
c
a
t
i
o
n
s
JRatings
Input (at 25°C)
Model Rated voltage Voltage range Input current
i
d
Voltage level
g
g
g
p
impedance Must operate voltage Must release voltage
G3PA-210B-VD 5to24VDC 4to30VDC 7mAmax. 4VDCmax. 1 VDC min.
G3PA-220B-VD
G3PA-240B-VD
G3PA-260B-VD
G3PA-420B-VD-2 12 to 24 VDC 9.6 to 30 VDC 7mAmax. 9.6 VDC max. 1 VDC min.
G3PA-430B-VD-2
G3PA-450B-VD-2
G3PB-215B-VD 12 to 24 VDC 9.6 to 30 VDC 7mAmax. 9.6 VDC max. 1 VDC min.
G3PB-225B-VD
G3PB-235B-VD
G3PB-245B-VD
Output
Model Applicable load
Load voltage Load current Inrush current With Class-1 AC resistive load
G3PA-210B-VD 19 to 264 VAC
(
5
0.1 to 10 A 150 A (60 Hz, 1 cycle) 2.4 kW at 240 VAC
G3PA-220B-VD (50/60 Hz) 0.1 to 20 A 220 A (60 Hz, 1 cycle) 4.8 kW at 240 VAC
G3PA-240B-VD 0.5 to 40 A 440 A (60 Hz, 1 cycle) 9.6 kW at 240 VAC
G3PA-260B-VD 0.5 to 60 A 440 A (60 Hz, 1 cycle) 14.4 kW at 240 VAC
G3PA-420B-VD-2 180 to 528 VAC
(
5
0.5 to 20 A 220 A (60 Hz, 1 cycle) 9.6 kW at 480 VAC
G3PA-430B-VD-2 (50/60 Hz) 0.5 to 30 A 440 A (60 Hz, 1 cycle) 14.4 kW at 480 VAC
G3PA-450B-VD-2 0.5 to 50 A 440 A (60 Hz, 1 cycle) 24 kW at 480 VAC
G3PB-215B-VD 75 to 264 VAC
(
5
0.1 to 15 A 150 A (60 Hz, 1 cycle) 3 kW at 200 VAC
G3PB-225B-VD (50/60 Hz) 0.1 to 25 A 220 A (60 Hz, 1 cycle) 5 kW at 200 VAC
G3PB-235B-VD 0.5 to 35 A 440 A (60 Hz, 1 cycle) 7 kW at 200 VAC
G3PB-245B-VD 0.5 to 45 A 440 A (60 Hz, 1 cycle) 9 kW at 200 VAC
Solid State Relays G3PA/G3PB C--7
JCharacteristics
G3PA
Item G3PA-
210B-VD
G3PA-
220B-VD
G3PA-
240B-VD
G3PA-
260B-VD
G3PA-
420B-VD-2
G3PA-
430B-VD-2
G3PA-
450B-VD-2
Operate time 1/2 of load power source cycle + 1 ms max. (DC Input, -B models)
1 1/2 of load power source cycle + 1 ms max. (AC Input)
Release time 1/2 of load power source cycle + 1 ms max. (DC Input)
1 1/2 of load power source cycle + 1 ms max. (AC Input)
Output ON voltage
drop
1.6 V (RMS) max. 1.8 V (RMS) max.
Leakage current 5 mA max. at 120 VAC
10 mA max. at 230 VAC
10 mA max. at 120 VAC
20 mA max. at 230 VAC
20 mA max. at 400 VAC
I2t260 A2S810 A2S260 A2S810 A2S
Insulation resistance 100 Mmin. at 500 VDC
Dielectric strength 4,000 VAC, 50/60 Hz for 1 min
Vibration resistance Malfunction: 10 to 55 Hz, 0.75-mm double amplitude (mounted to DIN rail)
Shock resistance Malfunction: 300 m/s2(mounted to DIN rail)
Ambient temperature Operating: --30°Cto80°C (with no icing or condensation)
Storage: --30°Cto100°C (with no icing or condensation)
Approved standards UL508 File No.E64562, CSA C22.2 (No.14, No.950) File No.LR35535, EN60950 File No. 5915UG
Ambient humidity Operating: 45% to 85%
Weight Approx.
260 g
Approx.
340 g
Approx.
460 g
Approx.
900 g
Approx.
290 g
Approx.
410 g
Approx.
900 g
G3PB
Part number G3PB-215B-VD G3PB-225B-VD G3PB-235B-VD G3PB-245B-VD
Operate time 1/2 of load power source cycle + 1 ms max. (DC input)
Release time 1/2 of load power source cycle + 1 ms max. (DC input)
Output ON voltage drop 1.6 V (RMS) max.
Leakage current 10 mA max. (at 200 VAC)
Permissible I2t (half 60-Hz wave) 121 A2s260 A2s1,260 A2s
Insulation resistance 100 Mmin. at 500 VDC
Dielectric strength 2,500 VAC, 50/60 Hz for 1 min
Vibration resistance Destruction and malfunction: 10 to 55 Hz, 0.75-mm double amplitude
Shock resistance Destruction: 294 m/s2
Malfunction: 294 m/s2(DIN track mounting)
Ambient temperature Operating: --30°Cto80°C (with no icing or condensation)
Storage: --30°Cto100°C (with no icing or condensation)
Approved standards UL508 File No. E64562 (From April 1999)
CSA22.2 No. 14 File No. LR35535 (From April 1999)
IEC947-4-3 File No. 6825 UG
Ambient humidity Operating: 45% to 85%
Weight Approx. 240 g Approx. 240 g Approx. 400 g Approx. 400 g