G2IM5AL20
24-240V
www.tele-online.com
Window function (WIN, WIN+LATCH)
The output relays switch into on-position (yellow LED illuminated) when
the measured current exceeds the value adjusted at the MIN-regulator.
When the measured current exceeds the value adjusted at the MAX-
regulator, the set interval of the tripping delay (DELAY) begins (red LED
MAX flashes). After the interval has expired (red LED MAX illuminated),
the output relays switch into off-position (yellow LED not illuminated).
The output relays again switch into on-position (yellow LED illuminated)
when the measured current falls below the value adjusted at the MAX-
regulator (red LED MAX not illuminated). When the measured current
falls below the value adjusted at the MIN-regulator, the set interval of the
tripping delay (DELAY) begins again (red LED MIN flashes). After the
interval has expired (red LED MIN illuminated), the output relays switch
into off-position (yellow LED not illuminated).
If the fault latch is activated (WIN+LATCH) and the measured current
remains below the MIN-value longer than the set interval of the tripping
delay, the output relays remain in the off-position even if the measured
current exceeds the value adjusted at the MIN-regulator. If the measured
current remains above the MAX-value longer than the set interval of
the tripping delay, the output relays remain in the off-position even if the
measured current falls below the value adjusted at the MAX-regulator.
After resetting the failure (interrupting and re-applying the supply
voltage), the output relays switch into on-position and a new measuring
cycle begins with the set interval of the start-up suppression (START).
Functions
When the supply voltage U is applied, the output relays switch into
on-position (yellow LED illuminated) and the set interval of the start-up
suppression (START) begins (green LED U flashes). Changes of the
measured current during this period do not affect the state of the output
relay. After the interval has expired the green LED is illuminated steadily.
For all the functions the LEDs MIN and MAX are flashing alternating,
when the minimum value for the measured current was chosen to be
greater than the maximum value.
Overcurrent monitoring (OVER, OVER+LATCH)
When the measured current exceeds the value adjusted at the MAX-
regulator, the set interval of the tripping delay (DELAY) begins (red LED
MAX flashes). After the interval has expired (red LED MAX illuminated),
the output relays switch into off-position (yellow LED not illuminated).
The output relays again switch into on-position (yellow LED illuminated),
when the measured current falls below the value adjusted at the MIN-
regulator (red LED MAX not illuminated).
If the fault latch is activated (OVER+LATCH) and the measured current
remains above the MAX-value longer than the set interval of the tripping
delay, the output relays remain in the off-position even if the measured
current falls below the value adjusted at the MIN-regulator. After
resetting the failure (interrupting and re-applying the supply voltage), the
output relays switch into on-position and a new measuring cycle begins
with the set interval of the start-up suppression (START).
Undercurrent monitoring (UNDER, UNDER+LATCH)
When the measured current falls below the value adjusted at the MIN-
regulator, the set interval of the tripping delay (DELAY) begins (red LED
MIN flashes). After the interval has expired (red LED MIN illuminated),
the output relays switch into off-position (yellow LED not illuminated).
The output relays again switch into on-position (yellow LED illuminated),
when the measured current exceeds the value adjusted at the MAX-
regulator.
If the fault latch is activated (UNDER+LATCH) and the measured current
remains below the MIN-value longer than the set interval of the tripping
delay, the output relays remain in the off-position even if the measured
current exceeds the value adjusted at the MAX-regulator. After resetting
the failure (interrupting and re-applying the supply voltage), the output
relays switch into on-position and a new measuring cycle begins with the
set interval of the start-up suppression (START).