DIN rail power supply unit, primary-switched mode, 3-phase, output:
24 V DC / 5 A
Commercial data
EAN
4 046356 128544
Pack 1
Customs tariff 85044081
Country of Origin CN
Catalog page information Page 592 (IF-2011)
Product notes
WEEE/RoHS-compliant since:
11/01/2008
Please note that the data given
here has been taken from the
online catalog. For comprehensive
information and data, please refer
to the user documentation at http://
www.download.phoenixcontact.com.
The General Terms and Conditions
of Use apply to Internet downloads.
Product description
TRIO POWER is the DIN-rail-mountable power supply unit with basic functions. With an output voltage of 5 V DC, 12
V DC, 24 V DC, and 48 V DC and 1- and 3-phase versions with 60 W or 960 W, it is particularly suited for use in series
production in mechanical engineering. The wide-range input and international certification package allow worldwide
implementation.
The high MTBF of 500,000 h stands for high supply reliability. The devices can be connected in parallel to increase the
capacity and redundancy.
The clear LED signaling and the device connection with double terminal block for plus and minus for fast potential
distribution are further advantages of this device series. A third minus terminal block simplifies the grounding on the
TRIO-PS/ 3AC/24DC/ 5 Order No.: 2866462
http://eshop.phoenixcontact.co.uk/phoenix/treeViewClick.do?UID=2866462
PHOENIX CONTACT Ltd Page 2 / 6
http://www.phoenixcontact.co.uk 18-Jan-2012
secondary side. All power supply units are idle-proof and short-circuit-proof and provide a regulated and adjustable
output voltage.
Technical data
Input data
Nominal input voltage 2x / 3x 400 V AC ... 500 V AC
AC input voltage range 3x 320 V AC ... 575 V AC (for 3-phase operation)
2x 360 V AC ... 575 V AC (for 2-phase operation)
AC frequency range 45 Hz ... 65 Hz
Current consumption Approx. 3x 0.3 A (400 V AC)
Approx. 3x 0.25 A (500 V AC)
2x 0.65 A (400 V AC)
2x 0.5 A (500 V AC)
Nominal power consumption (> 24 V constant capacity)
Inrush surge current < 15 A
Power failure bypass > 20 ms (400 V AC)
> 30 ms (480 V AC)
Permissible backup fuse B6
B10
B16
Type of protection Transient surge protection
Protective circuit/component Varistor
Output data
Nominal output voltage 24 V DC ±1%
Setting range of the output voltage 22.5 V DC ... 29.5 V DC (> 24 V constant capacity)
Output current 5 A (-25°C ... 55°C)
Derating 55 °C ... 70 °C (2.5%/K)
Connection in parallel Yes, for redundancy and increased capacity
Connection in series Yes
Max. capacitive load Unlimited
Current limitation Approx 6 A (in the event of a short-circuit)
Control deviation < 1 % (change in load, static 10% ... 90%)
< 2 % (change in load, dynamic 10% ... 90%)
< 0.1 % (change in input voltage ±10%)
Residual ripple < 30 mVPP
Peak switching voltages nominal load < 30 mVPP
TRIO-PS/ 3AC/24DC/ 5 Order No.: 2866462
http://eshop.phoenixcontact.co.uk/phoenix/treeViewClick.do?UID=2866462
PHOENIX CONTACT Ltd Page 3 / 6
http://www.phoenixcontact.co.uk 18-Jan-2012
Maximum power dissipation idling 4 W
Power loss nominal load max. 15 W
General data
Width 40 mm
Height 130 mm
Depth 115 mm
Net weight 0.6 kg
Operating voltage display Green LED
Efficiency > 89 % (at 400 V AC and nominal values)
Insulation voltage input/output 4 kV AC (type test)
2 kV AC (routine test)
Degree of protection IP20
Protection class I, with PE connection
MTBF (IEC 61709, SN 29500) > 500000 h
Ambient temperature (operation) -25 °C ... 70 °C (> 55° C derating)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Max. permissible relative humidity (operation) 95 % (at 25 °C, no condensation)
Mounting position horizontal DIN rail NS 35, EN 60715
Assembly instructions Can be aligned: Horizontally 0 mm, vertically 50 mm
Electromagnetic compatibility Conformance with EMC Directive 2004/108/EC
Noise immunity EN 61000-6-2:2005
Low Voltage Directive Conformance with LV directive 2006/95/EC
Standard – Electrical equipment of machines EN 60204
Standard - Safety of transformers EN 61558-2-17
Standard - Electrical safety EN 60950-1/VDE 0805 (SELV)
EN 61558-2-17
Standard – Electronic equipment for use in
electrical power installations and their assembly
into electrical power installations
EN 50178/VDE 0160 (PELV)
Standard – Safety extra-low voltage EN 60950-1 (SELV)
EN 60204 (PELV)
Standard - Safe isolation DIN VDE 0100-410
DIN VDE 0106-1010
Standard – Protection against electric shock DIN 57100-410
TRIO-PS/ 3AC/24DC/ 5 Order No.: 2866462
http://eshop.phoenixcontact.co.uk/phoenix/treeViewClick.do?UID=2866462
PHOENIX CONTACT Ltd Page 4 / 6
http://www.phoenixcontact.co.uk 18-Jan-2012
Standard – Protection against shock currents,
basic requirements for protective separation in
electrical equipment
DIN VDE 0106-101
Standard – Limitation of mains harmonic currents EN 61000-3-2
UL approvals UL/C-UL listed UL 508
UL/C-UL Recognized UL 60950
Surge voltage category III
Connection data, input
Connection method Screw connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section stranded min. 0.2 mm²
Conductor cross section stranded max. 2.5 mm²
Conductor cross section AWG/kcmil min. 24
Conductor cross section AWG/kcmil max 14
Stripping length 9 mm
Screw thread M2,5
Connection data, output
Connection method Screw connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section stranded min. 0.2 mm²
Conductor cross section stranded max. 2.5 mm²
Conductor cross section AWG/kcmil min. 16
Conductor cross section AWG/kcmil max 12
Stripping length 9 mm
Signaling
Status display "DC OK" LED green
Note on status display UOUT > 21.5 V: LED lights up
Certificates
Certification CUL, CUL Listed, UL, UL Listed
TRIO-PS/ 3AC/24DC/ 5 Order No.: 2866462
http://eshop.phoenixcontact.co.uk/phoenix/treeViewClick.do?UID=2866462
PHOENIX CONTACT Ltd Page 5 / 6
http://www.phoenixcontact.co.uk 18-Jan-2012
Drawings
Block diagram
TRIO-PS/ 3AC/24DC/ 5 Order No.: 2866462
http://eshop.phoenixcontact.co.uk/phoenix/treeViewClick.do?UID=2866462
PHOENIX CONTACT Ltd Page 6 / 6
http://www.phoenixcontact.co.uk 18-Jan-2012
Address
PHOENIX CONTACT Ltd
Halesfield 13
Telford / Shropshire / TF7 4PG,England
Phone 01952 681 700
Fax 01952 681 799
http://www.phoenixcontact.co.uk
Phoenix Contact Ltd.
Technical modifications reserved;