165
Noise Filter
MZS-SERIES
Features
(1)
Attenuation effect against high voltage pulse
noise
(2)
For equipment designed to conform EMI
regulations such as VCCI, CISPR, FCC, VDE,
etc.
(3) Attenuates conductive emission from power
supply
(4) Leakage current: 1mA max. (250V, 60Hz)
(5) High shielded effect
Safety standard
UL1283, CSA Std. C22. 2 No. 8
VDE0565 Teil. 3
VDE0565 will transfer to EN133200
on and after July 23, 2003.
Request customer specification for further details of specifications, outline, characteristics, etc.
Read the instruction manual before usage.
Contact us about delivery before ordering.
Specifications
(Note) : Value at Ta 55°C. Refer to the derating curve shown below at Ta > 55°C.
Circuit Derating
Outline drawings
Case: Metal
(Unit: mm)
MZS-1215
MZS-1206
MZS-1210
MZS-1220
1
2
3
4
5
6
7
8
9
Rated voltage (AC, DC)
Rated current (AC, DC) (Note)
Test voltage (terminal to case, AC 1 minute)
Isolation resistance (terminal to case, 500VDC)
Leakage current
DC resistance
Temperature rise
Operating temperature range
Weight (typ)
250V
2500V
100Mmin.
0.5mA max.
1mA max.
30°C max.
–25 ~ +85°C
310g
Item Model
125V, 60Hz
250V, 60Hz
R: Breeder resistance
6A 10A 15A 20A
0.10max. 0.05max. 0.03max. 0.02max.
MZS-1206-33 MZS-1210-33 MZS-1215-33 MZS-1220-33
<
=
()
166
Noise Filter
MZS-SERIES
.............. Symmetrical
———— Asymmetrical
Frequency (MHz)
Frequency (MHz)
Frequency (MHz)
Frequency (MHz)
Attenuation (dB)
Attenuation (dB)
Attenuation (dB)
Attenuation (dB)
CHARACTERISTICS
Typical Insertion Loss