0713 BU-SB13688 Page 1 of 3 Data Sheet # 1006
Low-Peak™ Class J
LPJ — 600Vac/300Vdc, 1-60A, Dual Element, Time-Delay Fuses
Description: Ultra protection Class J dual element, current-
limiting, time-delay fuses available with optional open fuse in-
dication. Time-delay – 10 seconds (minimum) at 500% of
rated current.
Catalog Symbol: LPJ-(amp)SP (non-indicating)
LPJ-(amp)SPI (indicating)
Ratings:
Volts — 600Vac, 300Vdc
Amps — 1-60A
IR — 300kA Vac RMS Sym.
— 100kA Vdc
Agency Information:
CE, UL Listed, Guide JDDZ, File E4273
CSA Certified, Class 1422-02, File 53787,
Class J per CSA 22.2 No. 248.
Catalog Numners (amps) – Non-indicating Fuses
LPJ-1SP LPJ-3SP LPJ-7SP* LPJ-25SP*
LPJ-11⁄4SP LPJ-32⁄10SP LPJ-8SP* LPJ-30SP*
LPJ-16⁄10SP LPJ-31⁄2SP LPJ-9SP* LPJ-35SP*
LPJ-18⁄10SP LPJ-4SP LPJ-10SP* LPJ-40SP*
LPJ-2SP LPJ-41⁄2SP LPJ-12SP* LPJ-45SP*
LPJ-21⁄4SP LPJ-5SP LPJ-15SP* LPJ-50SP*
LPJ-21⁄2SP LPJ-56⁄10SP LPJ-171⁄2SP* LPJ-60SP*
LPJ-28⁄10SP LPJ-6SP* LPJ-20SP*
* Open fuse indication available by inserting the suffix “I,” e.g., LPJ-15SPI.
Requires 75Vac minimum voltage.
Carton Quantity and Weight
Amp Rating Carton Qty.
1–30 10
35–60 10
Dimensions - in
Features:
• Industry’s only UL Listed and CSA Certified fuse with a
300kA Vac interrupting rating that exceeds requirements for
virtually all applications
• Long time-delay minimizes needless fuse openings due to
temporary overloads and transient surges
• Easy selective coordination with all Low-Peak fuses using
simple 2:1 ampacity ratio
• Can often be sized for back-up protection against motor
burnout from overload or single-phasing if other overload
protective devices fail
• High degree of current limitation due to the fast speed-of-
response to short-circuits
• Faster response to damaging short-circuit currents than
mechanical overcurrent protective devices
• Reduces let-through thermal and magnetic forces in order
to protect low withstand rated components
• Proper sizing provides “no damage” Type “2” coordinated
protection for NEMA and IEC motor control in accordance
with IEC Standard 947-4-1
• Dual-element fuses have lower resistance than ordinary
fuses so they run cooler
• Lower watts loss reduces power consumption
• Space-saving package for equipment downsizing
Recommended Fuse Blocks and Holders
Fuse Amps 1-Pole 2-Pole 3-Pole
Open Blocks
0-30 J60030-1 J60030-2 J60030-3
35-60 J60060-1 J60060-2 J60060-3
“Pyramid” Blocks
0-30 JP60030-1 JP60030-2 JP60030-3
35-60 JP60060-1 JP60060-2 JP60060-3
CH Series Holders
0-30 CH30J1 CH30J2 CH30J3
35-60 CH60J1 CH60J2 CH60J3
Safety J™ Holders
0-30 JT60030 ——
35-60 JT60060 ——
For additional information on the Class J fuse blocks and
holders, see data sheets # 1114 (open blocks), #1108
(pyramid blocks), # 2144 (CH Series) and # 1152 (Safety J).
Fuse Reducers For Class R Fuses
Equipment Desired Fuse Catalog Numbers
Fuse Clips (Case) Size (Pairs)
60A 30A J-63
100A 30A J-13
60A J-16
200A 60A J-26†
† Not for bolt-in applications.
2.38"
0.63"
35 to 60A
1.06"
0.5"
1 to 30A
0.81"
2.25"
(±0.03)
(±0.03) (±0.03)
(±0.03)
Available with easyID™