Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
11/46
H.V. Distribution Equipment
Instrument transformers
ZCT, EVT and special purpose CT
Description
FUJI can supply special purpose CTs,
ZCTs (Zero-phase current
transformers) and EVTs (Earthing
voltage transformers) as well as
standard FUJI instrument transformers.
Some of the versions are described
below.
CED and ZCED
The CED and ZCED are split-
construction types.They can be
mounted in position without
disconnecting the cables.
CED: Epoxy-molded split-toroidal type CT
ZCED: Epoxy-molded split-toroidal type
ZCT
ZCE
ZCE type is toroidal-type ZCTs and
molded in epoxy resin.
GVE and GPE
GVE and GPE series are 3-phase
earthing voltage transformers.
GVE: Epoxy-molded type (3.3kV,
6.6kV)
GPE: Epoxy-molded type (11 to 33kV)
Note: All types are for indoor use only.
Type number nomenclature
• Toroidal type ZCT
ZCE A/
Basic type
ZCE: Epoxy molded toroidal type
ZCED: Epoxy molded
split-toroidal type
Hole diameter, mm
1: 65 4: 125 (ZCE type)
2: 80 (ZCE type) 130 (ZCED type)
90 (ZCED type) 5: 190 (ZCE type)
3: 100 150 (ZCED type)
Rated primary current (Amps.): 200 to 1500
• Split-toroidal type CT
CED /
Basic type
Hole diameter, mm
1: 65
2: 90
3, 3A, 3B: 100
4: 130
Rated primary current (Amps)
200 to 3000
• Earthing voltage transformer EVT
GPE - F -
Basic type
GVE, GPE: Epoxy-molded type
Secondary rated burden
GVE GPE:
1: 3 x 100VA 21: 3 x 200VA
2: 3 x 200VA 13: 3 x 200VA
12: 3 x 200VA
9: 3 x 200VA
8: 3 x 200VA
7: 3 x 200VA(400A)
Rated primary voltage
3: 3.3kV 10: 11kV 20: 22kV
6: 6.6kV 15: 13.2kV 30: 33kV
Rated secondary voltage
Toroidal type ZCT
ZCE2A
Split-toroidal
type CT
CED2
CP-622
CP-620
Earthing voltage
transformer
GVE1
CP-619
Toroidal type ZCT
Description Hole Primary Rated zero-phase Rated Overcurrent Type
diameter current current (mA) burden constant
(mm) (A) Primary Secondary ()(n
0)
Indoor use 65 0200 200 1.5 10 n0 > 2000 ZCE1A/200
80 0400 ZCE2A/400
Epoxy molded 100 0750 ZCE3A/750
toroidal type 125 01200 ZCE4A/1200
190 03000 ZCE5A/3000
Indoor use 65 0200 200 1.5 10 n0 > 2000 ZCED1/200
90 0400 ZCED2/400
Epoxy molded 100 0600 ZCED3/600
split-toroidal 130 0750 ZCED4/750
type 150 01500 ZCED5/1500
( ) Available on request
Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
11
11/47
H.V. Distribution Equipment
Instrument transformers
Split-toroidal type CT
Hole diameter Primary current (A) Secondary Rated Overcurrent Type
(mm) Single ratio Double ratio current (A) burden (VA) constant (n)
65 200 5 15 n > 10 CED1/200
300 15 CED1/300
400 25 CED1/400
500 25 CED1/500
600 40 CED1/600
750 40 CED1/750
90 200 5 15 n > 10 CED2/200
300 25 CED2/300
400 40 CED2/400
500 40 CED2/500
600 40 CED2/600
750 40 CED2/750
1000 5 40 n > 20 CED2/1000
1200 40 CED2/1200
1500 40 CED2/1500
100 300 5 25 n > 10 CED3/300
400 40 CED3/400
500 40 CED3/500
600 40 CED3/600
750 5 40 n > 20 CED3/750
1000 40 CED3/1000
1200 40 CED3/1200
1500 40 CED3/1500
2000 40 CED3/2000
3000 40 CED3/3000
300 300150 5 25 n > 20 CED3A/300
400 400200 40 CED3A/400
500 40 CED3A/500
600 600300 40 CED3A/600
300 300150 5 40 n > 20 CED3B/300
130 400 400200 5 40 n >10 CED4/400
500 40 CED4/500
600 600300 40 CED4/600
750 5 40 n > 20 CED4/750
800400 40 CED4/800
1000 1000500 40 CED4/1000
1200 1200600 40 CED4/1200
1500 1500750 40 CED4/1500
2000 20001000 40 CED4/2000
3000 30001500 40 CED4/3000
Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
11/48
H.V. Distribution Equipment
Instrument transformers
Earthing voltage transformer EVT
Rated voltage (V) Rated burden (VA) Dielectric strength Impulse*1Type Fuse
(kV, 1minute) (kV)
Primary Secondary Tertiary Secondary Tertiary Primary Secondary
3300 110 110 3 × 100 3 × 500 2 2 45 GVE1-3FA-110/5G PTFA-6*2
33 × 200 3 × 500 2 2 45 GVE2-3FA-110/5G
6600 110 110 3 × 100 3 × 500 2 2 60 GVE1-6FA-110/5G
33 × 200 3 × 500 2 2 60 GVE2-6FA-110/5G
11000 110 110 3 × 200 3 × 200 2 2 90 GPE9-10 JR-10/5*3
33 × 200 3 × 200 2 2 75 GPE8-10 JR-10/5*3
3 × 200 3 × 200 2 2 90 GPE7-10 JR-10/5*3
13200 110 110 3 × 200 3 × 200 2 2 95 GPE7-15 JR-10N/5*3
3
22000 110 110 3 × 200 3 × 200 2 2 125 GPE12-20 JR-20/5*3
3
22000 110 110 3 × 200 3 × 200 2 2 150 GPE13-20 JR-20/5*3
3
33000 110 110 3 × 200 3 × 200 2 2 170 GPE21-30
3
ZCE5A/3000
Dimensions, mm
Toroidal-type ZCT
ZCE1A, 2A, 3A,4A
Type d X Y Z H W A B Mass
(kg)
ZCE1A/200 65 140 75 180 110 90 40 25 4.0
ZCE2A/400 80 160 90 210 130 90 40 25 5.6
ZCE3A/750 100 185 105 248 155 120 60 35 8.4
ZCE4A/1200 125 214 120 287 180 120 60 35 12.0
Dimensions for reference only. Please confirm before construction begins.
Note: *1: 1.2 × 50
µ
s *2: Provided *3: Optional
K
X
Z
H
W
A
20
10
3.2
20B
Test terminal 2-M5
Secondary
terminal 2-M5
NP Y
135
175
2-ø15
L
ød
k
kt lt
ø310
K
355
180
200
ø190
Test terminal M5
Secondary
terminal M5
160
200
25
40
25
100
L
2-ø15
3.2
k
kt Lt
Mass: 14kg
Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
11/49
11
Dimensions, mm
Split-toroidal type CT/ZCED
Earth voltage transformer VT/GVE1, GVE2
Type X Y Z a b c d e f g h i j k m n Mass
(kg)
ZCED1 260 95 225 100 125 130 65 27 30 135 175 2 14 M10 3.2 27 15
ZCED2 310 110 270 120 150 150 90 27 40 135 175 2 14 M10 4.5 27 20
ZCED3 340 110 295 130 165 150 100 30 40 135 175 2 14 M10 4.5 27 25
ZCED4 380 140 350 155 195 200 130 30 55 200 250 4 18 M10 6 30 30
ZCED5 460 150 405 185 220 200 150 30 55 200 250 4 18 M12 6 30 52
Dimensions for reference only. Please confirm before construction begins.
Type X Y Z d a1a2b1b2cEFn
CED1 95 260 225 65 260 80 220 125 27 57 2
CED2 110 310 285 90 300 90 260 165 27 82 2
CED3 110 340 295 100 300 95 260 165 27 67 2
CED3A 200 340 295 100 300 190 260 120 165 50 65 4
CED3B 250 340 295 100 300 240 260 120 165 50 65 4
CED4 125 350 305 130 300 110 260 70 165 50 50 4
Dimensions for reference only. Please confirm before construction begins.
Split-toroidal type CT/CED
Secondary
terminal M5 Tertiary
terminal
M5
Primary
neutral
terminal M6
bb
u
v
a
b
v
u
va
b
v
u
va
b
v
Fuse
Primary
terminal M6
4-ø12
f
f+40
Y
UUU
(U) (V) (W)
NP (3-phase)
NP (single-phase)
a
U(U)
UV
U(V)
UV
U(W)
UV
uvwabcf
0
0
uv ab uv ab uv ab
cd
z
e
c
X
X
K
4-k
L
C
ef
a
Z
b
ZCED4,5 Mounting hole
Secondary terminal 2-M5
Test terminal 2-M5
100
ød
g
h
m
i-øj
NP Y
k
kt Lt
n
110
NP
ø
4-M10
Y
d
K
C
Z
3.2
b1
a1
Secondary
terminal M5
NP
Mounting
hole n-ø14
kl
L
X
b2
a2
E
F
Type X Y Z a b c d e f Mass
(kg)
GVE1 428 265 284 136 146 104 220 90 220 59
GVE2 476 305 300 152 162 128 220 100 220 82
Dimensions for reference only. Please confirm before construction begins.
Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
11/50
Dimensions, mm
H.V. Distribution Equipment
Instrument transformers
GPE12-20
Earthing voltage transformer VT (with fuse links)
GPE9-10
GPE7-10, GPE7-15
GPE8-10 GPE13-20
GPE21-30
Mass: 160kg
Earth terminal M8
Primary neutral
terminal M6
85 ø10
4-ø12
220
35
20
301 95
416
20
3
Name plate
3 phase name plate
452
226 226
566
160
295
135 160
160
134
260
6
40
143
153
126
VV
V
v
u
v
u
uuu
a
bv
ua
bv
ua
b
ua
vb
V
ua
vb
V
u
UUU
a
vb
V
320
46750
6
320
260
350
20
900
350
310560
Secondary and tertiary
terminal M6
Neutral terminal M8
2-M8, Depth 15 Lifting lug
ø14
160
U
u
v
a
b
u
v
a
b
u
v
a
b
UUU
VV
V
VW
170
160135
290
Primary neutral
terminal M6
Fuse
170
35
ø10
500
260
252
160
460
4-ø12
M6
220
262 9520
320
40
6
377
35
410
a
b
u
v
a
b
u
v
a
b
u
v
770
Lifting lug
300
350
4-ø14
455
475
315
275275
773
UUU
223 140
20
98
66
25
183
38550 95
530
M6
M8
ø10
226 226
35
452
680
310
350
360
377
135 225
4-ø14
280 95
20
a
b
u
v
a
b
u
v
a
b
u
UUU
v
VVV
50
425
6
ø10
Fuse
Secondary and
tertiary terminal
M6
Primary
neutral
terminal
M8
6
30163
Mass: 125kg
Mass: 140kg
Mass: 76kg
Mass: 75kg
U
U
U
U
U
U
a
b
u
vu
vu
v
V
a
b
V
a
b
V
ø10
901 535
320
560 310
350
510
95
6
6
415
195
148
25
50
4-ø14
320 225
160
310
261
75 35
20
M8
Earth terminal M8
Lifting lug