REV. JUN 09, 2004
Page 8 of 11
FHS D
DC Series Data Shee
50
Watt, Ful
Brick Converte
Notes:
1. When the output voltage is trimmed up, the output power from
the converter must not exceed its maximum rating. The
power is determined by measuring the output voltage on the
output pins, and multiplying it by the output current.
2. In order to avoid creating apparent load regulation
degradation, it is important that the trim resistors are
connected directly to the remote sense pins, and not to the
load or to traces going to the load.
3. The FHS Series converters will trim down further than the
10% limit. In general, this is permissible. The user must
confirm that the results are acceptable in the application.
Safety Considerations
The FHS Series converters feature 1500 Volt DC
isolation from input to output. The input-to-output
resistance is greater than 10MΩ. These converters
are provided with Basic insulation between input and
output circuits according to all IEC60950 based
standards. Nevertheless, if the system using the
converter needs to receive safety agency approval,
certain rules must be followed in the design of the
system. In particular, all of the creepage and
clearance requirements of the end-use safety
requirements must be observed. These documents
include UL60950 - CSA60950-00 and EN60950,
although other or additional requirements may be
needed for specific applications.
The FHS Series converters have no internal fuse.
The external fuse must be provided to protect the
system from catastrophic failure as shown in Figure
6. The fuse with a rating not greater than 20A is
recommended. The user can select a lower rating
fuse based upon the highest inrush transient at the
maximum input voltage and the maximum input
current of the converter, which occurs at the
minimum input voltage. Both input traces and the
chassis ground trace (if applicable) must be capable
of conducting a current of 1.5 times the value of the
fuse without opening. The fuse must not be placed in
the grounded input line, if any.
In order for the output of the FHS Series converter to
be considered as SELV (Safety Extra Low Voltage)
or TNV-1, according to all IEC60950 based
standards, one of the following requirements must be
met in the system design:
• If the voltage source feeding the module is SELV
or TNV-2, the output of the converter may be
grounded or ungrounded.
• If the voltage source feeding the module is ELV,
the output of the converter may be considered
SELV only if the output is grounded per the
requirements of the standard.
• If the voltage source feeding the module is a
Hazardous Voltage Secondary Circuit, the
voltage source feeding the module must be
provided with at least Basic insulation between
the source to the converter and any hazardous
voltages. The entire system, including the FHS
converter, must pass a dielectric withstand test
for Reinforced insulation. Design of this type of
systems requires expert engineering and
understanding of the overall safety
requirements and should be performed by
qualified personnel.
Thermal Considerations
FHS Series converters are designed for natural or
forced convection cooling. The maximum allowable
output current of the converters is determined by
meeting the derating criteria for all components
used in the converters. For example, the maximum
semiconductor junction temperature is not allowed
to exceed 125°C to ensure reliable long-term
operation of the converters. Contact Power-One for
the complete list of the derating criteria.
Figure 9 shows the maximum output current of the
FHS Series at different ambient temperatures under
both natural and forced (longitudinal airflow
direction, from pin 1 to pin 4) convection.
THERMAL DERATING CURVE
Vin = 54V, Orientation : Vin- to Vin +
0
5
10
15
20
25 40 55 70 85
Ambient Temperature (Deg C)
Load Current (A)
NC (25 - 35 LFM) 100 LFM 200 LFM 300 LFM 400 LFM
FHS18Z28
Data Rev: 01
Figure 9. FHS18Z28 Derating Curves