Solid State Relay G3TB 387
Solid State Relay
G3TB
I/O SSR Used as Interface between Logic
Circuitry and Load
A variety of AC/DC input and output modules classified by
color.
Operation can be
monitored easily
through an
LED indicator.
Dielectric strength of 4,000 V between input and output
terminals.
Certified by UL and CSA.
Ordering Information
Input Modules
Output Modules
Note: When ordering, specify the rated input voltage.
Isolation Indicator Logic level Rated input
voltage
Model
Supply voltage Supply current
Photocoupler Yes 4 to 32 VDC 25 mA 100 to 240 VAC G3TB-IAZR02P-US
4 to 24 VDC G3TB-IDZR02P-US
Isolation Zero cross
function
Indicator Rated output voltage
(Applicable output
load)
Rated input voltage Model
Photocoupler Yes Yes 3 A at 100 to 240 VAC
(3 A at 75 to 264 VAC)
5 to 24 VDC G3TB-OA203PZ-US
No 4 to 24 VDC G3TB-OA203PZM-US
No Yes 5 to 24 VDC G3TB-OA203PL-US
No 4 to 24 VDC G3TB-OA203PLM-US
--- Yes 3 A at 5 to 48 VDC
(3 A at 4 to 60 VAC)
5 to 24 VDC G3TB-ODX03P-US
No 4 to 24 VDC G3TB-ODX03PM-US
Yes 1.5 A at 48 to 200 VDC
(1.5 A at 40 to 200 VDC)
5 to 24 VDC G3TB-OD201P-US
No 4 to 24 VDC G3TB-OD201PM-US
388 Solid State Relay G3TB
Specifications
Ratings (at an Ambient Temperature of 25°C)
Input Module
Input
Output
Output Module
Input
Output
Note: The minimum current value is measured at 10°C min.
Model Rated voltage Operating voltage Input current Voltage level
Must operate voltage Must release voltage
G3TB-IAZR02P-US 100 to 240 VAC 80 to 264 VDC 5 mA max. 80 VAC max. 10 VAC min.
G3TB-IDZR02P-US 4 to 24 VDC 3 to 32 VDC 3 VDC max. 1 VDC min.
Model Logic level supply voltage Output breakdown voltage Output current
G3TB-IAZR02P-US 4 to 32 VDC 32 VDC max. 25 mA max.
G3TB-IDZR02P-US
Model Rated voltage Operating voltage Input current Voltage level
Must operate voltage Must release voltage
G3TB-OA203PZ-US 5 to 24 VDC 4 to 32 VDC 5 mA max. 4 VDC max. 1 VDC min.
G3TB-OA203PZM-US 4 to 24 VDC 3 to 32 VDC 3 VDC max.
G3TB-OA203PL-US 5 to 24 VDC 4 to 32 VDC 4 VDC max.
G3TB-OA203PLM-US 4 to 24 VDC 3 to 32 VDC 3 VDC max.
G3TB-ODX03P-US 5 to 24 VDC 4 to 32 VDC 4 VDC max.
G3TB-ODX03PM-US 4 to 24 VDC 3 to 32 VDC 3 VDC max.
G3TB-OD201P-US 5 to 24 VDC 4 to 32 VDC 4 VDC max.
G3TB-OD201PM-US 4 to 24 VDC 3 to 32 VDC 3 VDC max.
Model Applicable load
Rated load voltage Load voltage range Load current (See note.) Inrush current
G3TB-OA203PZ-US 100 to 240 VAC 75 to 264 VAC 0.05 to 3 A 45 A (60 Hz, 1 cycle)
G3TB-OA203PZM-US
G3TB-OA203PL-US
G3TB-OA203PLM-US
G3TB-ODX03P-US 5 to 48 VDC 4 to 60 VDC 0.01 to 3 A 18 A (10 ms)
G3TB-ODX03PM-US
G3TB-OD201P-US 48 to 200 VDC 40 to 200 VDC 0.01 to 1.5 A 12 A (10 ms)
G3TB-OD201PM-US
Solid State Relay G3TB 389
Characteristics
Input Module
Output Module
Item G3TB-IAZR02P-US G3TB-IDZR02P-US
Operate time 20 ms max. 1 ms max.
Release time 20 ms max. 1 ms max.
Output ON voltage drop 0.4 V max.
Leakage current 100 μA max.
Insulation resistance 100 MΩ min. (at 500 VDC)
Dielectric strength 4,000 VAC, 50/60 Hz for 1 min between input and output
Vibration resistance Malfunction: 10 to 55 Hz, 1.5-mm single amplitude
Shock resistance Malfunction: 1,000 m/s2
Ambient temperature Operating:
Storage:
–30°C to 80°C (with no icing or condensation)
–30°C to 100°C (with no icing or condensation)
Ambient humidity Operating: 45% to 85%
Certified standards UL File No. E41515/CSA File No. LR35535/TÜV R90381 (VDE0806)
Weight Approx. 22 g
Item G3TB-
OA203PZ-US
G3TB-
OA203PZM-US
G3TB-OA
203PL-US
G3TB-OA
203PLM-US
G3TB-
ODX03P-US
G3TB-
ODX03PM-US
G3TB-OD
201P-US
G3TB-OD
201PM-US
Operate time 1/2 of load power source cycle +
1 ms max.
1 ms max. 0.5 ms max.
Release time 1/2 of load power source cycle + 1 ms max. 2 ms max.
Output ON voltage
drop
1.6 V max. 2.5 V max.
Leakage current 5 mA max. (at 200 VAC) 1 mA max.
Insulation resistance 100 MΩ min. (at 500 VDC)
Dielectric strength 4,000 VAC, 50/60 Hz for 1 min between input and output
Vibration resistance Malfunction: 10 to 55 Hz, 1.5-mm single amplitude
Shock resistance Malfunction: 1,000 m/s2
Ambient temperature Operating:
Storage:
–30°C to 80°C (with no icing or condensation)
–30°C to 100°C (with no icing or condensation)
Ambient humidity Operating: 45% to 85%
Certified standards UL File No. E64562/CSA File No. LR35535/TÜV R90381 (VDE0806)
Weight Approx. 32 g
390 Solid State Relay G3TB
Engineering Data
Load Current vs. Ambient Temperature Characteristics
One Cycle Surge Current: Non-repetitive
G3TB-OD201P-US/-OD201PM-USG3TB-OA203PZ-US/-OA203PZM-US
/-OA203PL-US/-OA203PLM-US/
G3TB-ODX03P-US/-ODX03PM-US
Ambient temperature (°C) Ambient temperature (°C)
Load current (A)
Load current (A)
G3TB-ODX03P-US/-ODX03PM-US G3TB-OD201P-US/-OD201PM-USG3TB-OA203PZ-US/-OA203PZM-US/
-OA203PL-US/-OA203PLM-US
Non-repetitive (Keep the inrush current to half the rated value if it occurs repetitively.)
Inrush current (A. Peak)
Energized time (ms)
Inrush current (A)
Energized time (ms)
Inrush current (A)
Energized time (ms)
Solid State Relay G3TB 391
Operation
Circuit Configuration
Example of Logic Output Circuit
Note: AC- and DC-input versions are available.
Dimensions
Note: All units are in millimeters unless otherwise indicated.
Type Model Case
color
Indicator Circuit
AC input G3TB-IAZR02P-US Yellow Yes
DC input G3TB-IDZR02P-US White Yes
AC output G3TB-OA203PZ-US
G3TB-OA203PL-US
Black Yes
G3TB-OA203PZM-US
G3TB-OA203PLM-US
No
DC output G3TB-ODX03P-US
G3TB-OD201P-US
Red Yes
G3TB-ODX03PM-US
G3TB-OD201PM-US
No
Rectification
circuit
Constant-
current circuit Amplification
circuit
Constant-
current circuit
Amplification
circuit
Drive circuit
Constant-
current circuit
Zero cross
circuit
Constant-
current circuit Amplification
circuit
(+)
()
+3
4
5
( )
SW 3.3 K
(+)
()
+3
4
5
( )
SW 3.3 K
Example 1. G3TB-I Example 2. G3TB-I
4 to 32 VDC
Logic circuitry
Load
4 to 32 VDC
Sequential
circuit or
CPU Example: Relay
with built-in
inrush absorption
diode
1
+2
3
+4 5
-1
~2
~3
+4 5
Vcc Vcc
G3TB-I
6.6
6.05±0.1 10.16
22.86
27.94
33.02
23.2
0.6
2.54
2.54
6.05 10.16 12.7 5.08 5.08
Load
External input Output External input Output
Logic circuitry
Load
Logic circuitry
Input SSR PCB Dimensions
(Bottom View)
Terminal Arrangement
(Bottom View)
20.5
max.
43.5 max.
10 max. Five, 1.3-dia. holes
392 Solid State Relay G3TB
G3TB-O
1
~2
~3
+4
-1
~2
~3
+4
Z2
Z1
Z
6.6
6.05±0.1 10.16
22.86
27.94
33.2
29.5
2.54
2.54
6.05 10.16 12.7 5.08
0.6
Output SSR
PCB Dimensions
(Bottom View)
Terminal Arrangement
(Bottom View)
Load
External AC output Logic input
Load
External DC output Logic input
43.5 max.
10 max.
30.5
max.
33.2
Four, 1.2-dia. holes
Note: Z1, Z2, and Z refer to overvoltage absorption elements that
you should connect.
Solid State Relay G3TB 393
Safety Precautions
Precautions for Correct Use
Please observe the following precautions to prevent failure to operate, malfunction, or undesirable effect on product performance.
G3TB
I/O classification by the color is as follows:
When mounting more than one output module, make a distance of 5
mm minimum between adjacent SSRs. Up to 16-point, 3-A load
switching is possible
Connection
With the SSR for DC switching, the load can be connected to either
positive or negative output terminal of the SSR.
Protective Component
Since the SSR does not incorporate an overvoltage absorption com-
ponent, be sure to connect an overvoltage absorption component
when using the SSR under an inductive load.
G3TB-OA203PZ
G3TB-OA203PZM
G3TB-OA203PL
G3TB-OA203PLM
G3TB-ODX03P
G3TB-ODX03PM
G3TB-OD201P*
G3TB-OD201PM*
G3TB-IAZR02P
G3TB-IDZR02P
100 to 240 VAC 5 to 24 VDC
5 to 24 VAC 5 to 24 VDC
100 to 240 VAC 3 A 5 to 24 VDC
(4 to 24 VDC)
AC equipment
Black
AC output module
4 to 60 VDC/
40 to 200 VAC 3 A
5 to 24 VDC
(4 to 24 VDC)
DC equipment
Red
DC output module
AC equipment AC input module
Ye l l o w
DC equipment DC input module
White
PLC or logic circuitry
*With 1.5-A output.
5 mm min. Output module
Complete “Terms and Conditions of Sale” for product purchase and use are on Omron’s website
at http://www.components.omron.com – under the “About Us” tab, in the Legal Matters section.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
394 Solid State Relay G3TB
MEMO
14
Read and Understand This Catalog
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or
comments.
Warranty and Limitations of Liability
WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified)
from date of sale by OMRON.
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR
FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS
DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER
WARRANTIES, EXPRESS OR IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS
IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT
LIABILITY.
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS
OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT
SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's
application or use of the products.
At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the
products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product,
machine, system, or other application or use.
The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible
uses of the products, nor is it intended to imply that the uses listed may be suitable for the products:
Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this catalog.
Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles,
safety equipment, and installations subject to separate industry or government regulations.
Systems, machines, and equipment that could present a risk to life or property.
Please know and observe all prohibitions of use applicable to the products.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE
SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND
INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof.
Disclaimers
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons.
It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made.
However, some specifications of the products may be changed without any notice. When in doubt, special model numbers may be assigned to fix or
establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual
specifications of purchased products.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.
PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the
result of OMRON’s test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON
Warranty and Limitations of Liability.
ERRORS AND OMISSIONS
The information in this document has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical,
typographical, or proofreading errors, or omissions.
2010.1
In the interest of product improvement, specifications are subject to change without notice.
OMRON Corporation
Industrial Automation Company
http://www.ia.omron.com/
(c)Copyright OMRON Corporation 2010 All Right Reserved.
Cat. No. J30I-E-01 06/09 Note: Specications are subject to change. © 2010 Omron Electronics LLC
OMRON CANADA, INC. • HEAD OFFICE


OMRON ELETRÔNICA DO BRASIL LTDA • HEAD OFFICE

OMRON ELECTRONICS MEXICO SA DE CV • HEAD OFFICE

OMRON ARGENTINA • SALES OFFICE

OMRON CHILE • SALES OFFICE

OTHER OMRON LATIN AMERICA SALES

OMRON ELECTRONICS LLC • THE AMERICAS HEADQUARTERS
OMRON EUROpE B.V.
