Description
The G478 is a DIN rail mount, frequency input signal conditioner
with 1800VDC isolation between input, output and power. The field
configurable input and output offer flexible, wide ranging capability
for variable frequency drives, magnetic pick-ups, turbine flow
meters, and other pulse or frequency output transducers.
The input of the G478 can be configured for any frequency span
from 2Hz to 10,000Hz. The input amplitude threshold sensitivity
can be adjusted from 150mVp to 10Vp to ensure accurate
frequency measurement and minimize transient noise related
errors. The maximum input amplitude is 150 Vrms. The output can
be set for 0-5V, 0-10V, 0-1mA, 0-20mA or 4-20mA.
The G478 to be field configured for virtually any frequency input
to DC signal output within the ranges specified. Calibration utilizes
‘Touch-Cal’ technology in which the user simply applies the
minimum and maximum input frequencies, and touches a re-
cessed button to configure the corresponding minimum and
maximum output range.
The Ultra SlimPak housing allows installation of up to 24 units per
linear foot. The wide ranging power supply is inverter isolated and
accepts any voltage between 9 and 30VDC.
Application
The G478 is useful in eliminating ground loops and interfacing
pulse output transducers, such as turbine flow meters and mag-
netic pick-ups, to data acquisition and control systems.
Advanced digital technology, combined with Action’s ASIC technol-
ogy, provide a stable output at low frequencies for higher accuracy.
‘Touch-CALTM Technology
The G478 utilizes ‘Touch-Cal’ technology to greatly simplify
configuration. To set the input frequency range, simply apply the
high input frequency and push the CAL button while the INPUT
LED is lit. The low input frequency is then applied and pushing the
CAL button once again stores the low frequency input. The high
and low ranges are stored in non-volatile memory and correspond
to the high and low output range which is selected via DIP switches.
Frequency Input,
Field Configurable Isolator
Provides an Isolated DC Output
in Proportion to a Frequency Input
ULTRA SLIMPAK®
G478-0001
Field Configurable Input Ranges from 2Hz to 10,000Hz
Eliminates Ground Loops
Field Configurable Output Ranges: 0-5V, 0-10V,
0-1mA, 0-20mA, 4-20mA
Ultra Slim Housing for High Density Installations
G478-0001
150mV to 150V Input Amplitude Level
Touch-CalTM for Simplified Ranging
Flexible Power Supply Accepts 9 to 30 VDC
ASIC Technology for Enhanced Reliability
RoHS Compliant
To precisely adjust the output, the user adjusts the input fre-
quency while the OUTPUT LED is lit until the desired output level
is achieved. The output levels are locked-in by pushing the CAL
button. Status LEDs show the operation mode of the device.
Status LEDs
The G478 utilizes three status LEDs.
The green LED varies intensity as the frequency changes from 0 to
100% of full scale range (e.g., for a configuration of 0-1000Hz, the LED
will be off with an input of 0Hz and fully illuminated at 1000Hz. With
an input of 500Hz, the LED will be dim). If the input signal is 10% more
than full scale range (over-ranged), the LED will flash at 8Hz.
The yellow INPUT LED denotes input programming modes.
The red OUTPUT LED denotes output programming modes (see
Configuration, Calibration and Figure 2 for details).
Configuration
Any 2Hz range from 0 to 10,000Hz can be converted to a full scale
output signal (e.g. 0-2Hz/4-20mA or 9998-10,000Hz/4-20mA).
Unless otherwise specified, the factory presets the Model G478 as follows:
Input Range: 0 to 1000Hz
Sensitivity: 1V RMS
Output Range: 4 to 20mA
Note: "Sensitivity" refers to the noise rejection level (the trigger
threshold) of the input.
For other I/O ranges, refer to Table 1 and 2. For calibration mode
reference, see the step-by-step flow chart in Figure 4.
1. With DC power off, choose the desired output voltage/current
range from Table 1 and set position 1 through 8 of SW1.
2. Set the Input sensitivity switch (SW1, 9 & 10) to LO for input
amplitudes between 150mVp and 50Vrms, with noise rejection to
1Vp. Set the switch to HI for input amplitudes between 500mVp
and 150Vrms, with noise rejection up to 10Vp (see Table 2).