https://www.phoenixcontact.com/us/products/2880367
10/22/2014Page1/5
Type 2 surge protection device-SYS-SET/3+1/T2/690-2880367
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Surge protection combination type 2 for 500 V AC and 690 V AC in an IT system (without neutral conductor)
Key commercial data
Packing unit 1 pc
Weight per Piece (excluding packing) 576.4 GRM
Custom tariff number 85363030
Country of origin Germany
Technical data
Dimensions
Height 96.8 mm
Width 70.8 mm
Depth 65.5 mm
Horizontal pitch 4 Div.
Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -40 °C ... 80 °C
General
IEC power supply system IT
Housing material PA
Inflammability class according to UL 94 V0
Standards for air and creepage distances IEC 60664-1
DIN VDE 0110-1
Surge voltage category III
Pollution degree 2
https://www.phoenixcontact.com/us/products/2880367
10/22/2014Page2/5
Type 2 surge protection device-SYS-SET/3+1/T2/690-2880367
Technical data
General
Total surge current (8/20) µs 15 kA
Mounting type DIN rail: 35 mm
Type DIN rail module, two-section, divisible
Surge protection fault message Optical, remote indicator contact
Direction of action 3L-PE
Protective circuit
IEC test classification II
EN type T2
Nominal voltage UN690 V AC
Maximum continuous operating voltage UC (L-PE) 750 V AC
Nominal frequency fN50 Hz (60 Hz)
Residual current IPE ≤ 0.25 mA
Max. discharge current Imax (8/20) µs maximum (L-PE) 30 kA
Nominal discharge current In (8/20) µs (L-PE) 15 kA
Voltage protection level Up (L-PE) ≤ 5.6 kV
Residual voltage (L-PE) ≤ 5.6 kV
≤ 5.6 kV (at 5 kA)
Response time (L-PEN) ≤ 25 ns
Max. backup fuse with branch wiring 125 A (gL)
Short-circuit resistance IP with max. backup fuse (effective) 25 kA (effective)
Connection, protective circuit
Connection method Screw terminal block
Connection type IN Biconnect screw terminal block
Connection type OUT Biconnect screw terminal block
Connection method Biconnect terminal block
Screw thread M5
Tightening torque 4.5 Nm
Stripping length 14.5 mm
Conductor cross section stranded min. 0.5 mm²
Conductor cross section stranded max. 25 mm²
Conductor cross section solid min. 0.5 mm²
Conductor cross section solid max. 35 mm²
Conductor cross section AWG/kcmil min. 20
Conductor cross section AWG/kcmil max 2
Remote indicator contact
https://www.phoenixcontact.com/us/products/2880367
10/22/2014Page3/5
Type 2 surge protection device-SYS-SET/3+1/T2/690-2880367
Technical data
Remote indicator contact
Connection name Remote fault indicator contact
Switching function PDT contact
Connection method Screw connection
Screw thread M2
Tightening torque 0.25 Nm
Stripping length 7 mm
Conductor cross section stranded min. 1.5 mm²
Conductor cross section stranded max. 0.14 mm²
Conductor cross section solid min. 1.5 mm²
Conductor cross section solid max. 0.14 mm²
Conductor cross section AWG/kcmil min. 28
Conductor cross section AWG/kcmil max 16
Maximum operating voltage Umax. AC 250 V AC
Maximum operating voltage Umax DC 125 V DC
Max. operating current Imax 1 A AC (inductive)
1 A AC (ohmic)
30 mA DC (inductive)
200 mA DC (ohmic)
Standards and Regulations
Standards/regulations IEC 61643-1
EN 61643-11
Classifications
eCl@ss
eCl@ss 4.0 27140201
eCl@ss 4.1 27140201
eCl@ss 5.0 27140201
eCl@ss 5.1 27140201
eCl@ss 6.0 27140201
eCl@ss 7.0 27140201
ETIM
ETIM 2.0 EC001457
ETIM 3.0 EC001457
ETIM 4.0 EC001457
ETIM 5.0 EC001457
https://www.phoenixcontact.com/us/products/2880367
10/22/2014Page4/5
Type 2 surge protection device-SYS-SET/3+1/T2/690-2880367
Classifications
UNSPSC
UNSPSC 6.01 30212010
UNSPSC 7.0901 39121610
UNSPSC 11 39121610
UNSPSC 12.01 39121610
UNSPSC 13.2 39121620
Approvals
Approvals
Approvals
UL Recognized / cUL Recognized / GOST / cULus Recognized
Ex Approvals
Approvals submitted
Approval details
UL Recognized
cUL Recognized
GOST
cULus Recognized
Drawings
https://www.phoenixcontact.com/us/products/2880367
10/22/2014Page5/5
Type 2 surge protection device-SYS-SET/3+1/T2/690-2880367
Dimensioned drawing
99
45 22,5
65,5
58
51,5
Phoenix Contact 2014 © - all rights reserved
http://www.phoenixcontact.com