2Specifications are subject to change without notice (16.10.00)
Compensation
RTD For 3-wire connections, line
resistance up to 10 Ω
TC
Cold junction, within the tem-
perature range from 0 to 55°C
Input RTD ranges
Probe: Pt100
-200°C/-328°F to+600°C /+1112°F
-99.9°C/°F to +600.0°C/+999.9°F
Probe: Ni100
-50°C/-58°F to +150°C/+302°F
-50.0°C/-58.0°F to+150.0°C/+302.0°F
Input PTC ranges:
-50°C/-58°F to +150°C/+302°F
Probe: KTY81 (990Ω@ 25°C)
-50.0°C/-58.0°F to +150.0°C/+302.0°F
Output Working
Direct (cooling) or reverse (heating)
Type of output Relay: 5A-AC1, 2A-AC3,
250 VAC, 100.000 cycles
SSR: 6 VDC/max. 15 mA
Insulation Relay output: 2000 Vrms from
output to: measuring input,
AC power supply input.
SSR output: no insulation from
output to measuring
input.
2000 Vrms from output to
AC power supply input.
Alarm output 1 (on request)
Output types Alarm, ON/OFF, neutral zone
Alarm functions Up alarm or down alarm
Setpoint adjustment
0 to 100% of the input range
Limits of setpoint adjustment Programmable minimum and
maximum values
ON/OFF control parameters
Programmable hysteresis
within the whole measuring
range
Programmable activation
time delay (0 to 500 s)
Neutral zone control Programmable dead band
within the whole measuring
range
Output working
Direct (cooling) or reverse
(heating)
Type of output
Relay: 5A-AC1, 2A-AC3,
250 VAC, 100.000 cycles
SSR: 6 VDC/max. 15 mA
Insulation Relay output: 2000 Vrms from
output to measuring input,
AC power supply input.
SSR output: no insulation from
output to measuring
input.
2000 Vrms from output to
AC power supply input.
Output combinations
- only one control output (Out 1)
type: ON/OFF, PID;
- one independent control
output (Out 1) with additional
alarm output: up, down alarm;
- two dependent ON/OFF
control outputs;
- one ON/OFF control output (Out 1)
with dependent relative or
absolute alarm output:
up, down alarm;
-
one control output with additional
control output (dead band) to
carry out the neutral zone control
Control output 1 (standard)
Control types PID, ON/OFF
Setpoint adjustment
0 to 100% of the input range.
Limits of setpoint adjustment Programmable minimum
and maximum values
PID control parameters Programmable proportional
band within the whole input
range (1 or 0.1°C resolution);
Programmable manual reset
within the whole input range;
Programmable integral time
(0 to 3600 s);
Programmable derivative
time (0 to 3600 s);
Programmable cycle time
(1 to 500 s)
ON/OFF control parameters Programmable hysteresis
within the whole input range;
Programmable activation time
delay (0 to 500 s)
Neutral zone control
Programmable dead band within
the whole input range (available
only if the 2nd output is present)
PDI 20
Output Specifications
Input TC ranges
Probe: TC-J
0°C/+32°F to +800°C/+1472°F
Probe: TC-K
0°C/+32°F to +1200°C/+2192°F
Probe: TC-S
0°C/+32°F to +1600°C/+2912°F
Input process signal ranges -999 to 7000
-99.9 to 700.0
Key-pad
3 keys: “S” to enter into the
programming procedure;
“UP/DOWN” for parameter
selection; “S” + “UP/DOWN”
for value programming
Input Specifications (cont.)
Dynamic setpoint (see fig. 4) - Action only on 1st output,
automatic increase of the
set-point up to the pro-
grammed one
- Half band programming (drb)
(0 to 100% of the input range)
over which the dynamic
set-point is active
Software functions
- step increase (dSI) parameter,
programmable from 0 to
100% of the input range
- time interval (dSt) between
two step increases pro-
grammable from 1 to 3600 s