DATASHEET - M22-WK
Changeover switch, RMQ-Titan, With thumb-grip, momentary, 2 positions,
Bezel: titanium
Part no. M22-WK
Catalog No. 216865
Alternate Catalog
No.
M22-WKQ
EL-Nummer
(Norway)
4355316
Delivery program
Product range RMQ-Titan
Basic function Selector switch actuators
Mounting hole diameter mm 22.5
Single unit/Complete unit Single unit
Design With thumb-grip
momentary
Function:
40°
2 positions
Degree of Protection IP66
Front ring Bezel: titanium
Connection to SmartWire-DT yes
with SWD-RMQ connections
Instructions Stay-put/spring-return function, can be changed with coding parts M22-XC-Y
Technical data
General
Standards IEC/EN 60947
VDE 0660
Lifespan, mechanical Operations x 106> 0.1
Operating frequency Operations/h ≦ 2000
Operating torque (screw terminals) Nm ≦ 0.3
Climatic proofing Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Degree of Protection IP66
Ambient temperature
Open °C -25 - +70
Storage °C - 40 - + 80
Mounting position As required
Mechanical shock resistance g 30
Shock duration 11 ms
Sinusoidal
according to IEC 60068-2-27
shipping classification DNV
GL
LR
Indoor and protected outdoor installation
01/13/2021 Eaton 216865 ED2020 V75.0 EN 1 / 4
Design verification as per IEC/EN 61439
Technical data for design verification
Rated operational current for specified heat dissipation InA 0
Heat dissipation per pole, current-dependent Pvid W 0
Equipment heat dissipation, current-dependent Pvid W 0
Static heat dissipation, non-current-dependent Pvs W 0
Heat dissipation capacity Pdiss W 0
Operating ambient temperature min. °C -25
Operating ambient temperature max. °C 70
IEC/EN 61439 design verification
10.2 Strength of materials and parts
10.2.2 Corrosion resistance Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat
and fire due to internal electric effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation Please enquire
10.2.5 Lifting Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances Meets the product standard's requirements.
10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections Is the panel builder's responsibility.
10.8 Connections for external conductors Is the panel builder's responsibility.
10.9 Insulation properties
10.9.2 Power-frequency electric strength Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material Is the panel builder's responsibility.
10.10 Temperature rise Not applicable.
10.11 Short-circuit rating Is the panel builder's responsibility. The specifications for the switchgear must be
observed.
10.12 Electromagnetic compatibility Is the panel builder's responsibility. The specifications for the switchgear must be
observed.
10.13 Mechanical function The device meets the requirements, provided the information in the instruction
leaflet (IL) is observed.
Technical data ETIM 7.0
Low-voltage industrial components (EG000017) / Front element for selector switch (EC000222)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Command and alarm device / Front element for selector switches (ecl@ss10.0.1-27-37-12-13
[AKF031014])
Number of switch positions 2
Type of control element Toggle
Suitable for illumination No
Colour control element Black
Colour indicator light cap Other
Construction type lens Round
Hole diameter mm 22.5
Width opening mm 0
Height opening mm 0
Switching function latching No
Spring-return Yes
With front ring Yes
Material front ring Plastic
Colour front ring Other
Degree of protection (IP), front side IP66
01/13/2021 Eaton 216865 ED2020 V75.0 EN 2 / 4
Degree of protection (NEMA) 4X
Approvals
Product Standards IEC/EN 60947-5; UL 508; CSA-C22.2 No. 14-05; CSA-C22.2 No. 94-91; CE marking
UL File No. E29184
UL Category Control No. NKCR
CSA File No. 012528
CSA Class No. 3211-03
North America Certification UL listed, CSA certified
Degree of Protection UL/CSA Type 3R, 4X, 12, 13
Dimensions
01/13/2021 Eaton 216865 ED2020 V75.0 EN 3 / 4
Additional product information (links)
IL04716002Z (AWA1160-1745) RMQ-Titan System
IL04716002Z (AWA1160-1745) RMQ-Titan
System
https://es-assets.eaton.com/DOCUMENTATION/AWA_INSTRUCTIONS/IL04716002Z2020_09.pdf
01/13/2021 Eaton Industries GmbH
http://www.eaton.eu
© 12/2020 by Eaton Industries GmbH
Eaton 216865 ED2020 V75.0 EN
4 / 4