Uninterruptible Power Supply (UPS) Integrated battery type S8BA-LF DC-DC type small UPS mounts on a DIN rail to provide an ideal countermeasure for momentary power losses and power failures in industrial computers (IPC) and controllers. * System reliability greatly improved because 24VDC power supply is backed up for a certain period of time in the event of voltage drop or power failure. * Compactness, weight reduction, and long battery life realized thanks to the adoption of a lithium-ion battery. * Push-in terminal block adopted for the power input and output I/F. * Shutdown in conjunction with the industrial purpose computer (IPC) or controller realized by the USB/RS-232C/I/O port installed in the UPS. ! Refer to Safety Precautions on page 13. Model Number Structure Model Number Legend * Use the following format to place an order. S8BA- @@@@@@@@@LF Series name 1 2 3 1. Input voltage specification 24D: 24 VDC 3. Capacity 120: 120 W 240: 240 W 360: 360 W 480: 480 W 2. Output voltage 24D: 24 VDC Ordering Information Main body Uninterruptible Power Supply (UPS) Input voltage 24 VDC Output voltage 24 VDC Output current/capacity Model number 5 A/120 W S8BA-24D24D120LF 10 A/240 W S8BA-24D24D240LF 15 A/360 W S8BA-24D24D360LF 20 A/480 W * S8BA-24D24D480LF * 16.7 A/400 W for use as a UL compliant device. Communication cable Specifications Type For RS-232C port RJ45/Dsub9Pin For CONTACT port RJ45/Discrete wire Length Model number S8BW-C01 2m S8BW-C02 Replacement battery pack Rated voltage 14.4 VDC Rated capacity 1600 mAh Weight 0.3 kg Model S8BA-B120L UPS Model : Required units S8BA-24D24D120LF : 1 pcs S8BA-24D24D240LF : 2 pcs S8BA-24D24D360LF : 3 pcs S8BA-24D24D480LF : 4 pcs 1 S8BA-LF Ratings, Characteristics, and Functions Item Capacity Rated input voltage Input voltage range DC input When standard voltage sensitivity is set 24 VDC10% When low voltage sensitivity is set 24 VDC12.5% When high voltage sensitivity is set 24 VDC5% 240 W 360 W Input for rated input voltage for maximum rated loads connected current 5.9 A Input terminal Push-in terminal block Input protection Fuse (cannot be replaced by the customer) Input protection capacity 10 A 15 A 30 A Rated current 5A 10 A 15 A (for rated output voltage) Switching time Output voltage DC output 120 W 11.7 A 17.5 A 23.3 A *5 20 A *6 Uninterrupted Normal operation Output of input voltage as-is Backup operation 24 V5% Output terminal 480 W *4 24 VDC Push-in terminal block Alarm display at a load level of 110% or over (normal operation) Overload protection Alarm display at a load level of 110% or over and output voltage drop (backup operation) Alarm display cancellation at a load equal to or below the rated capacity (normal operation, backup operation) Battery Type Lithium-ion battery Rated voltage 14.4 VDC Rated capacity 1600 mAh x 1 parallel Expected battery life *1 2.5 years (50C), 5 years (40C), 10 years (25C) Replacement by user Yes (Hot swapping) Auto battery check function Yes Battery life counter function Yes Charging time Backup time (25C, initial characteristics) Environment Structure Insulation and withstand voltage Compliance to standard 1600 mAh x 2 parallel 1600 mAh x 3 parallel 1600 mAh x 4 parallel 6 min. (360 W) 6 min. (480 W) 4 hours *7 6 min. (120 W) 6 min. (240 W) Operating ambient temperature/humidity 0 to +55C/10 to 90% (with no condensation) Storage ambient temperature/humidity -20to +55C/10 to 90% (with no condensation) Vibration resistance JIS C 60068-2-6 compliant. 5 to 8.4 Hz amplitude: 3.5 mm, 8.4 to 150 Hz acceleration rate: 9.8 m/s2 X, Y, and Z directions for 100 minutes (Time coefficient: 10 minutes x coefficient factor 10 = total time 100 min.) Shock resistance JIS C 60068-2-27 compliant. 147 m/s2, 3 times in X, Y, and Z directions. Dimensions (W x D x H mm) 94 x 100 x 100 148 x 100 x 100 270 x 100 x 100 Weight of unit Approx. 0.8 kg Approx. 1.3 kg Approx. 2.0 kg Cooling method Natural cooling Withstand voltage 1,000 V 50/60 Hz AC between the DC external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max. Insulation resistance 20 M min. between the DC external terminals and the GR terminal (at 500 VDC) Safety standard UL508/CE/C22.2 No.107.1-01 / EAC EMI Radiated disturbance electromagnetic field strength Ship standard Approx. 2.3 kg EN61000-6-4/FCC/ICES/RCM/KC LR/ABS/EN60945 *8/DNV GL Internal power consumption (normal *2 / maximum *3) 7 W/22 W RS-232C (Interface terminal) Serial communication USB (interface terminal) Yes (RJ45) 11 W/41 W 14 W/60 W 18 W/80 W I/O signal (Interface terminal) Yes (RJ45) Accessories USB cable (1.5 m) Accessory functions Beeper setting; Auto restart setting; Auto test setting; Auto restart mode setting; Input sensitivity setting; Remote ON/OFF signal logic setting; Cold start setting; Battery life counter setting; Power switch function setting; Maximum backup time setting; Startup battery level setting; Backup stop (BS) signal delay time setting; Backup (BU) signal delay time setting; and Contact signal I/O test Yes (B connector) *1. An estimated value for standard mounting. Not a guaranteed value. *2. Conditions: With rated loads connected, at a rated input voltage, and with the battery fully charged. *3. Conditions: With rated loads connected, at a rated input voltage, and at the maximum battery charging current. *4. 400 W for use as a UL compliant device. *5. 20 A for use as a UL compliant device. *6. 16.7 A for use as a UL compliant device. *7. When using in an environment at a high temperature, charging may be paused by charging temperature protection, then the charging time will be longer than specified time. "CS" will be displayed when charging temperature protection is operated. *8. For the S8BA-24D24D120LF, install all of the RSMN-2030, RSHN-2030, and RSEN-2030 EMC filters manufactured by TDK. For the S8BA24D24D240LF, S8BA-24D24D360LF, or S8BA-24D24D480LF, install both the RSMN-2030 and RSHN-2030 or their equivalents. Install these filters in series to the cable connected to the DC input terminal block. When you do, do not connect anything to the GR terminal. The effectiveness of the noise filters may be affected by the installation environment. Be sure to check effectiveness before starting operation. 2 S8BA-LF Nomenclature Front view Enlarged view of the operation panel S8BA-24D24D120LF (120 W) 5 1 2 6 3 4 7 8 9 10 S8BA-24D24D240LF (240 W) 5 1 2 6 3 4 7 S8BA-24D24D360LF (360 W) S8BA-24D24D480LF (480 W) 2 5 1 6 3 4 7 No. 1 Name Function Operation panel Describe the name of each part. 2 DC output terminal block Connect to load lines. (+V), (-V) 3 DC input terminal block Connect to input lines. (+V), (-V) 4 GR terminal Ground this terminal to less than 100 E to improve noise resistance and prevent electrical shock. 5 USB port Connect to a USB cable. 6 RS-232C port Connect to a RS-232C cable. 7 CONTACT port I/O port. Connect to a signal line. 8 "Status indicator" digital indicator The seven-segment display indicates the status of the UPS. 9 "Beep Stop/Test" switch Stop the beeper and perform self-diagnosis testing. 10 "Power" switch Turn the power of the UPS ON/OFF. 3 S8BA-LF Rear view S8BA-24D24D120LF (120 W) 11 12 S8BA-24D24D240LF (240 W) 11 12 S8BA-24D24D360LF (360 W) S8BA-24D24D480LF (480 W) 11 12 No. Name 11 DIN rail mounting hook 12 DIN rail mounting groove 4 Function Hook the UPS on the DIN rail. Groove for positioning the DIN rail and the UPS. S8BA-LF Connections Block Diagrams S8BA-24D24D@@@LF Diagram of the Input/output circuit block 24 VDC Input 24 VDC Output FET Normal operation: ON Backup operation: OFF DC-DC converter FET Normal operation: OFF Backup operation: ON Normal operation: ON Backup operation: OFF FET Charge/Discharge Normal operation Backup operation Battery * In normal operation, 24 VDC is output as-is for charging the battery and from the input power supply. If 24 VDC from the input power supply drops, the operation automatically switches to backup operation, and 24 VDC is output from the battery. Input and output voltage time chart when shifting to backup operation power failure or input voltage drop <4ms DC voltage 24 VDC 22.2 VDC (-7.5%) 21 VDC (-12.5%) 20.4 VDC (-15%) <4ms <4ms When high voltage sensitivity is set* Switching power supply : S8VK-G48024 When standard voltage sensitivity is set* (Factory default) UPS : S8BA-24D24D240LF When low voltage sensitivity is set* Load : Rated load Input voltage When power failure occurs on the AC input side of the switching power supply Connecting a cable to Battery connection terminal block, the input terminal block and the output terminal block For details about the connectable sizes and recommended cable sizes, see the following table. Connectable size Cable Solid wire 0.2 to 4.0 mm2 Twisted pair 0.2 to 2.5 mm2 AWG AWG24 to 12 Stripped cable length 5A 10 A Recommended cable size 15 A 20 A 8 to 10 mm Solid wire/Twisted pair 0.5 mm2 AWG AWG20 Solid wire/Twisted pair 0.75 mm2 AWG AWG16 Solid wire/Twisted pair 1.25 mm2 AWG AWG14 Solid wire/Twisted pair 2.0 mm2 AWG AWG12 Temperature rating for recommended cable 90C 5 S8BA-LF I/O signal functions Type of output signals Signal Description Backup signal output (BU) Stays ON during backup operation at a power failure. Low battery level signal output (BL) Goes ON when the battery becomes weak during backup operation at a power failure. Trouble signal output (TR) Goes ON when an internal failure of the UPS occurs or when the battery life counter expires. Battery replacement signal output (WB) Goes ON when the test determines that battery replacement is necessary due to deterioration or when the battery life counter reaches the replacement period. (The life counter operates while input power is being supplied.) Type of input signals Signal Description Input of the UPS stop signal (BS) When the BS signal is ON (High), the output of the UPS is stopped after the time period specified in advance has elapsed. * Remote ON/OFF signal Remote ON/OFF signals can be used to start and stop the UPS, by using either an externally connected contact or the ON/OFF status of the open collector circuit. When signal is OFF, the UPS will be turned on. When signal is ON, the UPS will be turned off. In the factory settings, the UPS stops operation when this is short-circuited. In addition, it is necessary to turn on the "Power" switch of UPS to use this function. * BS signal delay time It is possible to set the period of time from when a BS signal is received until the output of the UPS is stopped. The output of the UPS can be stopped by inputting the voltage signal (High). I/O signal port (RJ45 connector) Outlook of the connector Pin number Item 1 Backup signal output (BU) 2 Remote ON/OFF input (-) 3 Trouble signal output (TR) 4 COMMON (COM) 5 Battery LOW signal output (BL) 6 Backup stop signal input (BS) 7 Battery Replacement Signal output (WB) 8 Remote ON/OFF input (+) Contact signal ratings Signal 6 Description Signal output (BL, TR, BU, WB) * Applicable voltage: 50 VDC or less * Maximum current: 360 mA * BU signal min. response time: 10 ms Remote ON/OFF * Voltage between terminals: 5 VDC * Current when closed: 10 mA max. * Min. signal response time: When stopped 100 ms When restarting 300 ms UPS Stop Signal input (BS) * Input voltage: HIGH (ON) 8 to 24 VDC LOW (OFF) 0.5 VDC or less * Input current: 1.7 to 5.1 mA * Min. signal response time: When stopped 100 ms When restarting 300 ms S8BA-LF Contact signal circuit Signal output (BU, TR, BL, WB) Remote ON/OFF UPS Stop Signal input (BS) BL 5V TR 680 BU WB Remote ON/OFF (+) 4.7 BS Remote ON/OFF (-) COM Precautions when selecting switch mode power supplies When selecting switch mode power supplies, install devices with a capacity larger than the total of the UPS internal power consumption and internal power consumption of connected devices to the input side of the UPS. When these conditions are met, usage will be possible with no problems even if the rated capacity of the UPS is larger than the rated capacity of the switching power supply. Switch mode power supply capacity > (UPS internal power consumption + Internal power consumption of connected devices) (Ex.) Switch mode power supply (Capacity: 92 W or more) > ( UPS (Internal power consumption: 22 W) computers (IPC)/controllers, etc. + Industrial-purpose ) (Internal power consumption: 70 W, DC input) S8BA (Capacity: 120 W) 7 S8BA-LF Engineering Data Estimated backup time The backup time varies depending on the capacity of connected devices. After calculating the total capacity of connected devices, refer to the graph of the backup time to obtain an estimation of the initial value of the backup time. (This is also applied to checking the battery.) 1. Convert the total capacity (power consumption) of the connected devices to watts (W). For the indication of connected devices, check your computer and the rear of the display. The indicator can show values in two different ways: amperes (A), and watts (W). Example 1: 24 VDC, 145 W Example 2: 24 VDC, 1.8 A Indication Value A W = A x 24 For devices that use the A indication, convert the capacity into W. Example 2: 1.8 (A) = 1.8 x 24 (W) = 43.2 (W) Backup time (Minutes) 2. Add the values converted into W to obtain the total capacity of the connected devices. 3. Calculate the initial value of the backup time for the total capacity of the connected devices from the graph below. * Graph of backup time (graph of initial values for products that have not been used at 25C). The backup time becomes shorter than the graph (table) below when temperature is lower. 120 480 W 100 80 60 360 W 40 20 0 120 W 0 60 240 W 120 180 240 300 360 420 480 Capacity (W) * The smaller the capacity of connected devices becomes, the longer the backup time becomes. Backup time table (Time unit: minutes) Capacity (W) 30 60 90 120 180 240 300 360 420 480 S8BA-24D24D120LF (120 W) 29 14 9 6 -- -- -- -- -- -- S8BA-24D24D240LF (240 W) 58 29 19 15 9 6 -- -- -- -- S8BA-24D24D360LF (360 W) 87 43 28 22 14 10 8 6 -- -- S8BA-24D24D480LF (480 W) 119 59 39 29 19 15 11 9 8 6 Note: The above backup times are for reference only. They may change depending on the battery life and external environment (such as temperature). 8 S8BA-LF Derating curve 120 A 100 80 480 W 120 A B 100 80 Load rate (%) 360 W Load rate (%) Load rate (%) 120, 240 W 120 60 60 40 40 40 20 20 20 0 0 10 20 30 40 50 60 Ambient temperature (C) A: For standard mounting, face-up mounting, stationary mounting C 80 60 0 A B 100 0 0 10 20 30 40 50 60 Ambient temperature (C) A: For standard mounting, B: For face-up mounting, stationary mounting 0 10 20 30 40 50 60 Ambient temperature (C) A: For standard mounting, B: For face-up mounting, stationary mounting C: For standard mounting (For use as a UL compliant device) Backup operation sequence in the event of power failure/voltage drop (instantaneous voltage drop) When the input power supply recovers while the battery level is sufficiently high Input power supply ON OFF Power switch ON OFF Battery level UPS output During power failure High Low Empty ON OFF Indication in the "status display" 0.2 s Beeper * UPS operating mode ON OFF 4s Normal operation Backup operation BU signal (OUT) ON OFF BL signal (OUT) ON OFF BS signal (IN) ON OFF * "Disable beeper" is set by factory default. Even when "Disable beeper" is set, the buzzer sounds at startup. 9 S8BA-LF When the input power supply recovers while the battery level is Low Input power supply During power failure ON OFF ON Power switch OFF High Low Empty Battery level ON OFF UPS output Indication in the "status display" 0.2 s ON Beeper * OFF 4s 1s Normal operation UPS operating mode Backup operation ON BU signal (OUT) OFF ON BL signal (OUT) OFF ON OFF BS signal (IN) * "Disable beeper" is set by factory default. Even when "Disable beeper" is set, the buzzer sounds at startup. When the input power supply does not recover until the battery becomes empty Input power supply ON OFF Power switch ON OFF Battery level UPS output During power failure High Low Empty ON OFF 3s Indication in the "status display" 0.2 s Beeper * ON OFF 4s UPS operating mode 1s Normal operation Backup operation BU signal (OUT) ON OFF BL signal (OUT) ON OFF BS signal (IN) ON OFF * "Disable beeper" is set by factory default. Even when "Disable beeper" is set, the buzzer sounds at startup. 10 S8BA-LF Overcurrent protection curve Output voltage (%) 120W, 240W, 360W, 480W * In backup operation 100 80 60 40 20 0 0 20 40 60 80 100 120 Output current (%) Note: 1. In backup operation, the output voltage drops at a load rate of 110% or higher. 2. In normal operation, the output stops when the input protection fuse blows out. Dimensions (Unit: mm) Main body S8BA-24D24D120LF (120 W) 2 100 94 100 2.5 S8BA-24D24D240LF (240 W) 2 148 100 100 2.5 S8BA-24D24D360LF (360 W) S8BA-24D24D480LF (480 W) 2 270 100 100 2.5 11 S8BA-LF DIN Rail (Order Separately) Mounting Rail (Material: Aluminum) PFP-100N PFP-50N 7.30.15 4.5 350.3 15 25 10 25 25 10 1,000 (500) * 270.15 15(5) * 25 1 * Values in parentheses are for the PFP-50N. Mounting Rail (Material: Aluminum) PFP-100N2 16 4.5 350.3 27 15 25 10 25 25 10 1,000 25 15 24 29.2 1 1.5 End Plate PFP-M 10 6.2 M4x8 panhead screw 1.8 1 50 1.8 35.5 35.3 11.5 10 M4 spring washer 1.3 4.8 Note: 1. If there is a possibility that the Unit will be subject to vibration or shock, use a steel DIN Rail. Otherwise, metallic filings may result from aluminum abrasion. 2. If the Unit may be subjected to sliding to either side, attach an End Plate (model PFP-M) on each side of the Unit. Power management solutions The following software is available as a free download from our website. Name Description Conditions Power Attendant Lite * You can execute computer shutdown and UPS auto stop when an input power problem occurs (power failure, etc.). You can use a computer that has "Power Attendant Lite" installed to send a script over the network to devices that do not have shutdown software installed to log in to each device and execute a device shutdown command. * You can automatically start and stop computers and the UPS according to a preset schedule. Windows 10 / 8.1 / 8 / 7 Windows Server 2016 Windows Server 2012 R2 / 201208 Windows Storage Server 2008 Windows Storage Server 2016 Windows Storage Server 2012 R2 / 2012 Windows Storage Server 2008 R2 / 2008 Simple Shutdown Software Windows 10 / 8.1 / 8 / 7 Windows Server 2012 R2 / 2012 * You can execute computer shutdown and UPS auto stop Windows Server 2008 R2 / 2008 when an input power problem occurs (power failure, etc.). Windows Server 2003R2 / 2003 * You can modify and recompile the source code to Windows Vista / XP incorporate a UPS management function into your Windows/ Windows 10 IoT Enterprise LTSB (R) Linux system. Windows Embedded Standard 7 * Supports Windows and Linux Red Hat Enterprise Linux Ver.7.x CentOS Ver.7.x Setting Utility 12 This software is used to configure UPS settings. (Setting item examples) Function for sending commands Function for saving settings to a backup file Function for restoring settings from a backup file Function for reading UPS settings Function for returning UPS settings to default settings Windows 10 / 8.1 / 8 / 7 Windows Server 2012 R2 / 2012 Windows Server 2008 R2 / 2008 Windows Server 2003R2 / 2003 Windows Vista / XP Windows 10 IoT Enterprise LTSB Windows Embedded Standard 7 Interface RS232C USB RS232C USB RS232C USB S8BA-LF Safety Precautions Warning Indications Caution Warning Indicates a potentially hazardous situation that, if not avoided, could result in serious injury or death. Additionally there may be significant property damage. Caution Indicates a potentially hazardous situation that, if not avoided, could result in minor or moderate injury or property damage. Precautions for Safe Use Supplementary comments on what to do or avoid doing to use the product safely. Precautions for Correct Use Supplementary comments on what to do or avoid doing to prevent failure to operate, malfunction, or undesirable effects on product performance. Meaning of Product Safety Symbols General inhibition Notice prohibiting an unspecified general action. General instruction Notice instructing an unspecified general action. Do-not-disassemble prohibition Notice prohibiting disassembly because disassembling the device may cause such an accident as an electric shock. Prohibition of use in locations subject to water such as a bathroom and shower room Notice prohibiting installation of the device in locations subject to water, because if a device not made water-proof is used in such locations, injury may occur due to an electric leak. Do-not-touch prohibition Indicates the possibility of injuries by touching the specific portion of the device under specific conditions, prohibiting touching of the device. Explosion alert Notice alerting the user to the possibility of explosion under certain conditions. WARNING (for use of this product) * Provide safety measures in external circuits, not in the UPS, in order to ensure safety in the system if an abnormality occurs due to malfunction of the UPS or another external factor affecting the UPS operation. Not doing so may result in serious accidents. (for installation and connection) Carry the unit considering its weight and balance, and place it on a stable and robust base. * If you drop the unit, the battery or the battery protection mechanism may be broken, and it may result eventually in a fluid leak, abnormal heating, smoke, rupture or fire. * If you drop the unit, stop using it and have it inspected and repaired. For details on repair, contact the OMRON representative. Keep plastic package bags out of reach of children. * Children may suffocate if they place their heads into plastic bags. Make sure to connect the "input power supply" to the direct power supply equipment with a rated voltage (24 VDC). * The input voltage ranges for the UPS are as shown below. Check that the output voltage of the direct power supply equipment connected to the input terminal of the UPS is within any of the voltage ranges below. * 24 VDC10% (Input voltage range: When standard voltage sensitivity is set) * 24 VDC12.5% (Input voltage range: When low voltage sensitivity is set) * 24 VDC5% (Input voltage range: When high voltage sensitivity is set) * Connecting to a DC or AC power supply device with a different voltage may result in malfunction in or damage to the UPS, or cause a fire. When an abnormality (unusual sound or smell) occurs, turn OFF the unit's "Power" switch to stop the output, and stop the supply of commercial power. * When performing maintenance on the connected devices, follow the above instructions to ensure safety. When installing the input cable, make sure to perform the connection as specified. Make sure to stop the primary power supply before connecting the unit to the input power supply terminal. * When connecting a cable to the terminal block, use a cable that complies with the input current specification of the UPS. Failure to do so may result in electric shock or ground fault. Do not disassemble, repair, or modify the unit. * Doing so may cause an electric shock or a fire. Do not install the unit in other than specified orientations. * Dropping or toppling the unit may cause injury. * If the UPS is not installed in the specified direction, the internal temperature may rise, eventually damaging the UPS or deteriorating the battery. (When replacing the battery unit) Dispose of or collect (recycle) the battery unit according to your own rules set for that purpose or as instructed by laws and regulations. * Do not dispose of it in fire. Otherwise, it could explode. Do not use the unit where the maximum temperature exceeds 55C. * The battery deteriorates rapidly. It may result in fire. * If the battery's resin separator is damaged, the battery may be short-circuited inside, and may cause an abnormal heating, smoke, rupture or fire. * Doing so may cause a failure or malfunction of the unit. 13 S8BA-LF Do not exceed the ranges specified for environmental conditions during use/storage. Do not install or store the unit in the places listed below. * Do not store in places where the humidity is lower than 10% or higher than 90%. * Do not use the unit in places where the ambient temperature is lower than 0C or higher than 55C. (With no condensation) * Do not use in places where the humidity is lower than 10% or higher than 90%. * Do not install/store the unit in closed places such as cabinets with no clearance, places where there is flammable or corrosive gas, * Places with large amounts of dust, places exposed to direct sunlight, places exposed to shock or vibration, salty or wet places, or outdoors. * Installation or storing the unit in such a place may cause a fire. When you use plug strip and other plugs to connect additional devices, do not connect devices that exceed the current capacity of the available plugs. * The current protection of the unit may operate, which may stop the output. * The cable heats up, which may cause a fire. Do not pinch or sharply bend the cable. Do not fold or knot the cable. * Doing so may cause the cable to be damaged or heated, which may cause an electric shock or a fire. * If the cable is damaged, stop using the unit and have the cable repaired. * For details on repair, contact our sales personnel. Connect only devices using 24 VDC rated voltage. * The rated output voltage of the UPS is 24 VDC. * Overvoltage or overcurrent may damage the connected devices. All the accessories contained in the product package can be used for the UPS only. Do not use any of them for other devices. * Be sure to observe this to use the UPS safely. Include a breaker between the "input power supply" of the UPS and the direct power supply equipment. And, install the breaker where it is easy to operate. To use this product as a CE marking compliant device, use a 2-meter or shorter connection cable. Do not block the air vents (upper and lower). * Doing so will cause the internal temperature to rise, which may cause the unit to fail and the battery to deteriorate. * For stationary installation, leave a space of 50 mm or more above the top, and for installation using a DIN rail and screw clamps, leave a space of 50 mm or more above the top and below the bottom each. Do not connect the RS-232C port or the CONTACT port to a LAN device using a LAN cable. * Connection to a LAN device may result in malfunction in or damage to the UPS or the LAN device. (for use) Do not allow the unit to come in contact with water. If you drop the unit, stop using it. * Doing so may cause an electric shock or a fire. * Doing so may cause an abnormal heating, smoke, rupture, or fire on the battery. * If the unit becomes wet or is dropped, immediately stop using it, disconnect the input power supply from the wall outlet (commercial power source) and have it inspected and repaired. * For details on repair, contact our sales personnel. When the battery is dead, replace it immediately or stop using the unit. * Continuing the use of it may cause fire or electric shock due to liquid leaks. Ambient temperature 50C 40C 25C Expected life 2.5 years 5 years 10 years * The values in the table are the expected life under standard use conditions and are not guaranteed. Occasionally, wipe off dust on the input terminal block and the output terminal block with a dry cloth. * Accumulated dust may cause a fire. * Before wiping off dust, stop all connected devices and the unit, and stop the supply of commercial power. Do not use the unit in a closed place and do not cover the unit. * Doing so may cause abnormal heating or a fire. If you notice something unusual such as abnormal sound or smell, discoloration, deformation, and heating, turn OFF the unit's "Power" switch to stop the output and stop the supply from the "input power supply". * Using the unit under such conditions may cause an abnormal heating, rupture or fire. * If this situation arises, be sure to stop using the UPS and request our sales personnel for inspection and repair. * A readily accessible disconnect device shall be incorporated external to the equipment. If fluid leaks from the interior, do not touch the fluid. * Doing so may cause blindness or burns. * If the fluid contacts your eyes or skin, wash it out with lots of clean water and consult your doctor. The fluid may damage your eye if your eye is left untreated. Do not place any objects on the unit, and do not drop heavy objects onto the unit. * Doing so may cause distortion/damage to the case or a failure of the internal circuit, which may cause a fire. The unit is equipped with a bypass circuit which is able to supply electric power to connected devices even when the inner control circuit is broken down by defects or malfunctions. If you want to stop the output, stop the source of the "input power supply". * Output is continuing even when all indicators of the front panel are off. * Output ON/OFF cannot be controlled with the "Power" switch on the front panel. When charging the battery, if the battery cannot be charged completely even after the predetermined charging time, turn OFF the "Power" switch of the unit to stop charging the battery. * Otherwise, it may cause an abnormal heating, smoke, rupture or fire on the battery. 14 S8BA-LF (for maintenance) When maintaining the connected equipment, turn OFF the unit's "Power" switch to stop the output, and stop the supply of the "input power supply". * Even if the input power supply to the UPS is stopped while it is in operation, the power output of his unit does not stop and power is supplied from the battery. Do not disassemble, repair, or modify the unit. * Doing so may cause an electric shock or a fire. If fluid leaks from the interior, do not touch the fluid. * Doing so may cause blindness or burns. * If the fluid contacts your eyes or skin, wash it out with lots of clean water and consult your doctor. Do not throw the unit into fire. * Since the battery is incorporated in the unit, the insulator may melt, the gas exhaust valve or protection mechanism may be damaged, or the electrolyte may catch fire, and it may result eventually in an abnormal heating, smoke, rupture or fire. Do not insert metal objects into the input terminal block and the output terminal block of the UPS. * Doing so may result in electric shock. Do not insert metal objects into the battery connectors. Do not short between the connector terminals. * Doing so may result in electric shock. * The battery's protection board may be damaged due to a short-circuit. Do not dispose of battery in a fire or damage battery. * The insulator inside the battery may melt, the gas exhaust valve or protection mechanism may be damaged, or the electrolyte may catch fire, and it may result eventually in abnormal heating, smoke, rupture or fire. Do not use a new battery and an old battery at the same time. * The battery may be excessively discharged while being used or excessively charged while being charged, an abnormal chemical reaction may occur inside the battery, and it may result eventually in an abnormal heating, smoke, rupture or fire. * A battery can present a risk of electrical shock and high short circuit current. * Contact with any part of a grounded battery can result in electrical shock. * The following precautions should be observed when working on batteries: (a) Remove watches, rings, or other metal objects. (b) Use screwdrivers with insulated handles. (c) Wear rubber gloves and boots. (d) Do not lay tools or metal parts on top of batteries. (e) Remove the connection from ground if any part of the battery is determined to be grounded. Dispose of or collect (recycle) the battery according to your own rules set for that purpose or as instructed by laws and regulations. Do not dispose of it in fire. Otherwise, it could explode. (for battery replacement) Risk of explosion if battery is replaced by an incorrect type. * Not doing so may cause a fire. * Battery pack for; product model: S8BA-B120L. Do not replace the battery in a place where there is flammable gas. * Spark may occur when connecting the battery, which may cause an explosion or fire. If fluid leaks from the battery, do not touch the fluid. * Doing so may cause blindness or burns. * If the fluid contacts your eyes or skin, wash it out with lots of clean water and consult your doctor. Do not disassemble or modify the battery. * A safety mechanism and protection mechanism to prevent danger are embedded into the battery. If they are damaged, it may cause an abnormal heating, smoke, rupture or fire on the battery. Do not drop the battery and do not expose it to strong impact. * Doing so may cause a leakage, abnormal heating, smoke, rupture or fire on the battery. And, if the battery's protection mechanism is broken, the battery may be charged at an abnormal current or voltage, an abnormal chemical reaction may occur inside the battery, and it may result eventually in an abnormal heating, smoke, rupture or fire. Do not short the battery with metal objects. * Doing so could cause an electric shock, fire or burn. * Some electrical energy still remains inside the spent battery. Precautions for Safe Use Before using Charge the battery soon after purchasing the unit. * If not used for a long time after being purchased, the UPS may become unusable because the characteristics of its battery become inferior. * Connect the UPS to the input power supply and turn ON the "Power" switch to charge the battery. If the UPS is moved from a warm place to a cold place, start using it after leaving it as-is for a few hours. * If the UPS is suddenly moved to a warm place, water may adhere to it (condensation). In such a case, if power is supplied without checking the condition, the UPS may be damaged. * Take measures against the unexpected events such as protecting data and making the system redundant. * The UPS may stop its power due to failure. For Connection Be careful not to let a short-circuit occur between output lines of the UPS and not to let an output line and the ground be short-circuited (a ground fault). * Otherwise, the UPS may be damaged. To transfer or sell the UPS to a third party, attach all the documents and other accessories contained in the product package to the UPS. It is supposed that the UPS is to be used in accordance with the conditions specified in the attached documents. While Using the UPS Turn OFF the "Power" switch of the UPS before turning OFF the input power supply. * When the input power supply is stopped, backup operation starts. * If the frequency of backup operation becomes high, the battery life may be significantly reduced. Do not use the UPS for purposes requiring frequent backup operation. * The battery will deteriorate and become unable to last for the specified backup time. 15 S8BA-LF For Storage Face-up mounting To store the UPS for a long time, store it in an environment where the ambient temperature is 25C or lower, and charge the battery once every year for 10 to 15 minutes. * The battery discharges itself even if it is not used. If the battery is left unused for a long time, it goes into a state of over-discharge. In such a case, the backup time may become shorter, or the battery cannot be used anymore. * We recommend an environment where the ambient temperature is 25C or lower to store the UPS for a long time. * Keep the "Power" switch of the UPS turned OFF during storage. * Do not install or store the UPS in a location exposed to direct sunlight. * The built-in battery may deteriorate rapidly due to an increase in temperature and become unusable. Correct Installation Method * For installation, to improve the long time reliability of the UPS, pay much attention to heat dissipation. Ensure convection of air around the UPS main body, and use the UPS in an operating condition below the derating curve. * During machining work for mounting, make sure that no metal scrap goes into the product. * The heat dissipation of the UPS may become worse depending on how the UPS is mounted; in rare cases, internal components may deteriorate and get damaged. Use the UPS in an operating condition based on the derating curve for each mounting direction. To mount UPS on floor with its top side away from you, mount it so that its top side is 50 mm or more off wall. Incorrect Installation Method Mounting to the DIN Track Standard mounting (Mounting to the DIN rail) Mount UPS upside down Leave space of 50 mm above and below Leave space of 50 mm above and below DIN Track is placed vertically To install devices other than the UPS to both sides, install them by leaving a space specified by each device off the UPS. Stationary mounting To mount UPS on floor with its back side away from you, mount it so that its back side is in contact with wall.(Because PCB is partially exposed in its back side, and UPS may be affected by static electricity for that reason.) 16 S8BA-LF Stationary installation Battery check schedule and frequency Do not mount on floor with front side down Do not stack Ambient temperature 6-Month Inspection 3-Month Inspection 55C 1 year from the date Up to 1 year from the of purchase and date of purchase afterward 50C 1.5 years from the Up to 1.5 years from date of purchase and the date of purchase afterward 40C 3 years from the date Up to 3 year from the of purchase and date of purchase afterward 25C 6 years from the date Up to 6 year from the of purchase and date of purchase afterward Conformance to EC Directives Applicable directives * EMC Directives * Low Voltage Directives Principles regarding conformance To mount UPS on floor with its top side away from you, ensure that its top side is not in contact with wall. Battery Replacement The UPS supports hot swapping. Battery replacement is possible both when the power is turned OFF (while the power output is OFF) and when the power is turned ON (while the power output is ON). Precautions for Correct Use * For battery replacement, hold down the "Buzzer Pause/Test" switch on the unit for 10 seconds or longer to activate the battery replacement mode. When " " is displayed, the activation is completed. * Activate the battery replacement mode while the "input power supply" is turned ON. If you replace the battery without activating the battery replacement mode, the battery life may not be detected accurately because the battery life counter is not reset. * Do not replace the battery during backup operation. Otherwise, the output stops. The life of the battery used in the UPS is limited. This life changes depending on the use environment and the frequency of backup operation. * As the battery life comes closer to its end, the battery deteriorates more rapidly. Be careful. The storage condition also affects the deterioration of the battery. As the storage temperature becomes higher, the battery life becomes shorter. Be careful. OMRON electronic devices that comply with EC Directives also conform to the related EMC standards so that they can be more easily built into other devices or the overall machine. The actual products have been checked for conformity to EMC standards*. Whether the products conform to the standards in the system used by the customer, however, must be checked by the customer. EMCrelated performance of the OMRON devices that comply with EC Directives will vary depending on the configuration, wiring, and other conditions of the equipment or control panel on which the OMRON devices are installed. The customer must, therefore, perform the final check to confirm that devices and the overall machine conform to EMC standards. * Applicable EMC (Electromagnetic Compatibility) standards are as follows: EMS (Electromagnetic Susceptibility): EN 61000-6-2, EMI (Electromagnetic Interference): EN 61000-6-4, and EN 61000-6-4 Radiated emission: 10-m regulations Low Voltage Directives Always ensure that devices operating at voltages of AC 50 to 1,000 V and DC 75 to 1,500 V meet the required safety standards. The applicable directive is EN60950-1. Conformance to EC Directives This product complies with EC Directives. To ensure that the machine or device in which the this product is used complies with EC Directives, the product must be installed as follows: * This product must be installed within a control panel. * You must use reinforced insulation or double insulation for the direct power supply equipment connected to this product. * Models of this product that comply with EC Directives also conform to the Common Emission Standard. Radiated emission characteristics (10-m regulations), in particular, may vary depending on the configuration of the control panel used, other devices connected to the control panel, wiring, and other conditions. Therefore, even when using a model of this product that complies with EC Directives, you must confirm and ensure the compliance to EC Directives of the entire machine or equipment. * This is a Class A product (for industrial environments). In a residential environment, it may cause radio interference. If radio interference occurs, the user may be required to take appropriate measures. 17 S8BA-LF Conformance to UL Conformance to UL * This product must be installed within a control panel with an internal heater or other unit to protect against the formation of condensation. * Gaps in the door to the control panel must be completely filled or covered with gaskets or other material. * For use as a UL compliant device, the specifications for S8BA24D24D480LF become as follows: * Maximum input current: 20 A * Rated output current/capacity: 16.7 A/400 W * For use in Pollution Degree 2 Environment. * Surrounding Air Temperature, 55C. * Make sure to connect the device with Class 2 output to the USB port. Conformance to FCC FCC CAUTION Changes or modifications not expressly approved by the party responsible for compliance could void the user's authority to operate the equipment. * This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. * This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. * Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense. Conformance to KC 18 Uninterruptible Power Supply (UPS) Separated battery type S8BA-SBF DC-DC type small UPS mounts on a DIN rail to provide an ideal countermeasure for momentary power losses and power failures in industrial computers (IPC) and controllers. * System reliability greatly improved because 24VDC power supply is backed up for a certain period of time in the event of voltage drop or power failure. * Compactness, weight reduction, and long battery life realized thanks to the adoption of a lithium-ion battery. * Push-in terminal block adopted for the power input and output I/F. ! Refer to Safety Precautions on page 33. * Shutdown in conjunction with the industrial purpose computer (IPC) or controller realized by the USB/RS232C/I/O port installed in the UPS. * Two types of batteries are selectable for the 480W, allowing the ideal backup time to be realized * A wide lineup culminating in the 960W makes it possible to provide long-lasting backup for every type of industrial controller Model Number Structure Model Number Legend * Use the following format to place an order. The control unit and battery unit are separate, and the battery unit is sold separately. Control unit part S8BA- @@@@@@@@@SBF Series name 1 2 1.Input voltage specification Code 24D Input voltage specification 24 VDC 3 2.Output voltage Code Output voltage 24D 24 VDC 3.Capacity Code Capacity 480 480 W 960 960 W Battery unit part S8BA- @@@@L Series name 1 2 1.Battery type Code S Type Separated battery type 3.Terminal block shape Code Terminal block shape 480 480 W 960 960 W 19 S8BA-SBF Ordering Information Main body Uninterruptible Power Supply (UPS) / Control Unit Part Input voltage 24 VDC Output voltage 24 VDC Output current/capacity Model number 20 A/480 W S8BA-24D24D480SBF 40 A/960 W S8BA-24D24D960SBF Note: The control unit (960 W) and the battery unit (480 W) cannot be connected. Battery unit part Rated voltage Rated capacity Weight Model UPS Model : Required units 25.2 VDC 3900 mAh 1.5 kg S8BA-S480L S8BA-24D24D480SBF 25.2 VDC 7800 mAh 2.5 kg S8BA-S960L S8BA-24D24D960SBF Note: The control unit (960 W) and the battery unit (480 W) cannot be connected. Communication cable Specifications 20 Type For RS-232C port RJ45/Dsub9Pin For CONTACT port RJ45/Discrete wire Length 2m Model number S8BW-C01 S8BW-C02 S8BA-SBF Ratings, Characteristics, and Functions Description DC input Capacity 24 VDC Input voltage range 23 to 28 VDC Input maximum current for rated input voltage 21.5 A for rated loads connected Push-in terminal block Fuse (cannot be replaced by the customer) Input protection capacity 30 A 60 A 20 A 40 A Output voltage for rated output voltage Normal operation Backup operation Output terminal DC output Overload protection Uninterrupted Input voltage through output 21 to 28 V (the voltage cannot be adjusted) Push-in terminal block Warning display * UPS output will continue through bypass [during normal operation] * UPS output will continue through battery [during backup operation] 101% or more Output stopped by overload protection * Stop output [during normal operation] * The internal power supply to the UPS will stop after 10 sec. [during backup operation] 111% or more Warning display cancellation (During normal operation, during backup operation) 93% or more Type Lithium-ion battery Rated voltage 25.2 VDC Rated capacity 3900 mAh Battery life expectancy *1 10 years (25C), 6.7 years (35C), 3.7 years (45C), 1.9 years (55C) Battery unit Replacement by user Battery Life Counter Function Dielectric breakdown voltage 43.5 A Input protection Switching time Structure 960 W Input terminal Rated current Environme nt 480 W Rated input voltage 7800 mAh Yes (Hot swapping) Yes Charging time 8 hours (90%) *3 Backup time (25C, initial characteristics) 6 min. (constant power rated load) The backup time can be set from the mode selection / backup operation time selection switch, or the shutdown software. Operating environment temperature / humidity 0 to +55C / 10 to 90%RH with no condensation Storage environment temperature / humidity -20 to +55C / 10 to 90%RH with no condensation Vibration resistance JIS C 60068-2-6 compliant 5 to 8.4 Hz amplitude: 3.5 mm, 8.4 to 150 Hz acceleration rate: 9.8 m/s2 X, Y, and Z directions: 100 min. (Sweep time: 10 min.xSweep count 10 times=Total: 100 min.) Shock resistance JIS C 60068-2-27 compliant: 147 m/s2 X, Y, and Z directions three times Dimensions (WxHxD mm) *2 44 x 124 x 111.4 (UPS control unit 20 A) 80 x 124 x 111.4 (battery unit 20 A) 52 x 124 x 111.4 (UPS control unit 40 A) 150 x 124 x 111.4 (battery unit 40 A) Weight of control unit Approx. 0.6 kg Approx. 0.7 kg Weight of battery unit Approx. 1.5 kg Approx. 2.5 kg Weight Cooling method Natural cooling Withstand voltage DC external terminals to casing: 510 V AC, 1 minute, leakage current 5 mA max. Insulation resistance DC external terminals to casing: 20 M or more. (500 V DC) Safety standard UL508 / CE / C22.2 No. 107.1-01 Standard compliance EMI Radiation disturbance field strength EN61000-6-4 / FCC / ICES / RCM / KC / EAC Internal power consumption (normal *4 / maximum *5) 7 W / 29 W Serial RS-232C (Interface terminal) communica USB (Interface terminal) tion Yes (RJ45) I/O signal (Interface terminal) Yes (RJ45) Accessories USB cable (2.2 m) (included with control unit) Battery connection cable (included with battery unit) 15 W / 58 W 21 S8BA-SBF Description Accessory functions Capacity 480 W 960 W Remote ON/OFF signal logic setting; Battery life counter setting; Maximum backup time setting; Startup battery level setting; Backup stop (BS) signal delay time setting; and Backup (BU) signal delay time setting *1. Guideline for a standard installation. Not a guaranteed value. *2. Unit dimensions excluding the DIN rail stopper. *3. When using in an environment at a high temperature, charging may be paused by charging temperature protection, then the charging time will be longer than specified time. *4. Conditions: With rated loads connected, at a rated input voltage, and at a full battery charge. *5. Conditions: With rated loads connected, at a rated input voltage and at maximum battery charging current. 22 S8BA-SBF Nomenclature Front view S8BA-24D24D480SBF (1) S8BA-S480L (6) Positive terminal Negative terminal (3) (2) (3) [DC ON] LED (4) [BATT] LED [ALERT] LED (5) No. (1) (2) (3) (4) (6) (7) (8) Name DC input terminal block DC output terminal block Battery connection terminal block LED indicators No. (5) (6) (7) (8) S8BA-24D24D960SBF (1) Name CONTACT port Battery communication port Mode selection / Backup time setting switch RS232C / USB port S8BA-S960L (6) Positive terminal Negative terminal (3) (2) (3) [DC ON] LED (4) [BATT] LED [ALERT] LED (5) No. (1) (2) (3) (4) Name DC input terminal block DC output terminal block Battery connection terminal block LED indicators (6) (7) (8) No. (5) (6) (7) (8) Name CONTACT port Battery communication port Mode selection / Backup time setting switch RS232C / USB port 23 S8BA-SBF Rear view S8BA-24D24D480SBF S8BA-S480L (9) (9) No. (9) Name DIN rail hook S8BA-24D24D960SBF S8BA-S960L (9) No. (9) 24 Name DIN rail hook (9) S8BA-SBF Connections Block Diagrams S8BA-24D24D@@@SBF Control unit FET 24 VDC Input 24 VDC Normal operation: ON Output Backup operation: OFF Charge FET Normal operation: ON Backup operation: OFF Battery unit Normal operation: OFF Backup operation: ON FET Battery Normal operation Backup operation Note: 1. In normal operation, 24 VDC is output as-is for charging the battery and from the input power supply. If the 24 VDC from the input power supply becomes lower, the operation automatically switches to backup operation, and 24 VDC is output from the battery. Input and output voltage time chart when shifting to backup operation 28 V power failure or input voltage drop 24 VDC DC voltage 22 VDC 21 V 18 VDC Output voltage Input voltage Connecting a cable to the input terminal block and the output terminal block For details about the connectable sizes and recommended cable sizes, see the following table. 20 A Connectable sizes Cable Solid wire 0.2 to 10 mm2 Stranded wire 0.2 to 6 mm2 AWG AWG 8 to 24 Stripped cable length Recommended sizes 40 A 0.75 to 16.0 mm2 AWG 6 to 18 8 to 10 mm 18 mm Solid wire / Stranded wire 2.0 mm2 8.0 to 14.0 mm2 AWG AWG 12 Temperature rating for recommended cable AWG 6 to 8 90C 25 S8BA-SBF I/O signal functions Type of output signals Signal Description Backup signal output (BU) Stays ON during backup operation at a power failure. Low battery level signal output (BL) Goes ON when the battery becomes weak during backup operation at a power failure. Trouble signal output (TR) Goes ON when an internal failure of the UPS occurs or when the battery life counter expires. Battery replacement signal output (WB) Goes ON when the test determines that battery replacement is necessary due to deterioration or when the battery life counter goes off-scale. (The battery life counter goes on counting during the input power is being supplied.) Type of input signals Signal Description Input of the UPS stop signal (BS) When the BS signal is ON (High), the output of the UPS is stopped after the time period specified in advance has elapsed.* Remote ON/OFF signal Remote ON/OFF signals can be used to start and stop the UPS, by using either an externally connected contact or the ON/OFF status of the open collector circuit. When signal is OFF, the UPS will be turned on. When signal is ON, the UPS will be turned off. In the factory settings, the UPS stops operation when this is short-circuited. You must connect the unit to the input power supply to be able to use this function. * BS signal delay time It is possible to set the period of time from when a BS signal is received until the output of the UPS is stopped. The output of the UPS can be stopped by inputting the voltage signal (High). I/O signal port (RJ45 connector) Outlook of the connector Pin number 1 Cable color Item White/orange Backup signal output (BU) 2 Orange Remote ON/OFF input (-) 3 White/green Trouble signal output (TR) 4 Blue 5 White/blue 6 Green 7 White/brown 8 Brown COMMON (COM) Battery LOW signal output (BL) Backup stop signal input (BS) Battery Replacement Signal output (WB) Remote ON/OFF input (+) Contact signal ratings Signal 26 Description Signal output (BL, TR, BU, WB) * Applicable voltage: 50 VDC or less * Maximum current: 500 mA * BU signal min. response time: 10 ms Remote ON/OFF * Voltage between terminals: 3.3 VDC * Current when closed: 10 mA max. * Min. signal response time: When stopped 100 ms When restarting 300 ms UPS Stop Signal input (BS) * Input voltage: HIGH (ON) 8 to 24 VDC LOW (OFF) 0.5 VDC or less * Input current: 250 mA * Min. signal response time: When stopped 100 ms When restarting 300 ms Pin number8 Pin number1 S8BA-SBF Contact signal circuit Signal output (BU, TR, BL, WB) Remote ON/OFF UPS Stop Signal input (BS) BL 3.3 V TR 220 BU WB Remote ON/OFF (+) 100 BS Remote ON/OFF (-) COM Precautions when selecting switch mode power supplies When selecting switch mode power supplies, install devices with a capacity larger than the total of the UPS internal power consumption and internal power consumption of connected devices to the input side of the UPS. When these conditions are met, usage will be possible with no problems even if the rated capacity of the UPS is larger than the rated capacity of the switching power supply. Switch mode power supply capacity > (UPS internal power consumption + Internal power consumption of connected devices) (Ex.) Switch mode power supply (Capacity: 92 W or more) > ( UPS (Internal power consumption: 29 W) computers (IPC)/controllers, etc. + Industrial-purpose ) (Internal power consumption: 70 W, DC input) S8BA (Capacity: 480 W) 27 S8BA-SBF Engineering Data Estimated backup time The backup time varies depending on the capacity of connected devices. After calculating the total capacity of connected devices, refer to the graph of the backup time to obtain an estimation of the initial value of the backup time. (This is also applied to checking the battery.) 1. Convert the total capacity (power consumption) of the connected devices to watts (W). For the indication of connected devices, check your computer and the rear of the display. The indicator can show values in two different ways: amperes (A), and watts (W). Example 1: 24 VDC, 145 W Example 2: 24 VDC, 1.8 A Indication Value A W = A x 24 For devices that use the A indication, convert the capacity into W. Example 2: 1.8 (A) = 1.8 x 24 (W) = 43.2 (W) 2. Add the values converted into W to obtain the total capacity of the connected devices. 3. Calculate the initial value of the backup time for the total capacity of the connected devices from the graph below. * Graph of backup time (graph of initial values for products that have not been used at 25C). The backup time becomes shorter than the graph (table) below when temperature is lower. 320 280 Backup time (Minutes) 240 S8BA-24D24D960SBF + S8BA-S960L 200 160 S8BA-24D24D480SBF + S8BA-S960L 120 S8BA-24D24D480SBF + S8BA-S480L 80 40 0 0 60 120 180 240 300 360 420 480 540 600 660 720 780 840 900 960 1020 Capacity (W) * The smaller the capacity of connected devices becomes, the longer the backup time becomes. Model Capacity (Watt) 120 180 240 300 360 420 480 540 600 660 720 780 840 900 960 30 60 90 480W (S8BA-24D24D480SBF + S8BA-S480L) 134 63 41 29 19 15 11 9 8 6 --- --- --- --- --- --- --- --- 480W (S8BA-24D24D480SBF + S8BA-S960L) 290 138 94 66 43 30 24 20 16 14 --- --- --- --- --- --- --- --- 960W (S8BA-24D24D960SBF + S8BA-S960L) 290 138 94 66 43 30 24 20 16 14 13 12 11 10 9 8 7 6 Note: These backup times are for reference only. Times may vary according to battery life and external environmental conditions (temperature, etc). 28 S8BA-SBF Derating curve Load rate (%) Load rate (%) Standard mounting (15 mm or more space Contact mounting (Less than 15 mm between the left and right) space between the left and right) 100 80 100 80 60 60 40 40 20 20 0 0 0 10 20 30 40 50 60 0 Ambient temperature (C) 10 20 30 40 50 60 Ambient temperature (C) Backup operation sequence in the event of power failure/voltage drop (instantaneous voltage drop) When the input power supply recovers while the battery level is sufficiently high Input power supply Durling power failure High Battery restorage Low Empty ON OFF Output from UPS UPS operating mode ON OFF Normal operation Backup operation BU signal (OUT) ON OFF BL signal (OUT) ON OFF BS signal (IN) ON OFF * For details, refer to I/O signal functions on page 26. When the input power supply recovers while the battery level is Low Input power supply ON Durling power failure OFF Battery restorage Output from UPS UPS operating mode High Low Empty ON OFF Normal operation Backup operation BU signal (OUT) ON OFF BL signal (OUT) ON OFF BS signal (IN) ON OFF * For details, refer to I/O signal functions on page 26. 29 S8BA-SBF When the input power supply does not recover until the battery becomes empty Input power supply ON OFF Battery restorage High Durling power failure Low Empty ON OFF Output from UPS UPS operating mode Normal operation Backup operation BU signal (OUT) ON OFF BL signal (OUT) ON OFF BS signal (IN) ON OFF * For details, refer to I/O signal functions on page 26. Overcurrent protection curve Output voltage (%) 480 W/960 W 111% 100 80 60 40 20 0 0 30 20 40 60 80 100 120 Load ratio (%) S8BA-SBF Dimensions (Unit: mm) Control unit S8BA-24D24D480SBF 44 9.5 111.4 31 124 99.4 S8BA-24D24D960SBF 52 9.5 111.4 31 124 99.4 Battery unit S8BA-S480L 111.4 80 9.5 30.7 124 99.4 S8BA-S960L 111.4 9.5 150 30.7 124 99.4 31 S8BA-SBF DIN Rail (Order Separately) Mounting Rail (Material: Aluminum) PFP-100N PFP-50N 7.30.15 4.5 350.3 15 25 10 25 25 10 1,000 (500) * 270.15 15(5) * 25 1 * Values in parentheses are for the PFP-50N. Mounting Rail (Material: Aluminum) PFP-100N2 16 4.5 350.3 27 15 25 10 25 25 10 1,000 25 15 24 29.2 1 1.5 End Plate PFP-M 10 6.2 M4x8 panhead screw 1.8 1 50 1.8 35.5 35.3 11.5 10 M4 spring washer 1.3 4.8 Note: 1. If there is a possibility that the Unit will be subject to vibration or shock, use a steel DIN Rail. Otherwise, metallic filings may result from aluminum abrasion. 2. If the Unit may be subjected to sliding to either side, attach an End Plate (model PFP-M) on each side of the Unit. Power management solutions The following software is available as a free download from our website. Name Description Conditions Power Attendant Lite * You can execute computer shutdown and UPS auto stop when an input power problem occurs (power failure, etc.). You can use a computer that has "Power Attendant Lite" installed to send a script over the network to devices that do not have shutdown software installed to log in to each device and execute a device shutdown command. * You can automatically start and stop computers and the UPS according to a preset schedule. Windows 10 / 8.1 / 8 / 7 Windows Server 2016 Windows Server 2012 R2 / 201208 Windows Storage Server 2008 Windows Storage Server 2016 Windows Storage Server 2012 R2 / 2012 Windows Storage Server 2008 R2 / 2008 Simple Shutdown Software Windows 10 / 8.1 / 8 / 7 Windows Server 2012 R2 / 2012 * You can execute computer shutdown and UPS auto stop Windows Server 2008 R2 / 2008 when an input power problem occurs (power failure, etc.). Windows Server 2003R2 / 2003 * You can modify and recompile the source code to Windows Vista / XP incorporate a UPS management function into your Windows/ Windows 10 IoT Enterprise LTSB Linux system. Windows Embedded Standard 7 * Supports Windows and Linux Red Hat Enterprise Linux Ver.7.x CentOS Ver.7.x Setting Utility 32 This software is used to configure UPS settings. (Setting item examples) Function for sending commands Function for saving settings to a backup file Function for restoring settings from a backup file Function for reading UPS settings Function for returning UPS settings to default settings Windows 10 / 8.1 / 8 / 7 Windows Server 2012 R2 / 2012 Windows Server 2008 R2 / 2008 Windows Server 2003R2 / 2003 Windows Vista / XP Windows 10 IoT Enterprise LTSB Windows Embedded Standard 7 Interface RS232C USB RS232C USB RS232C USB S8BA-SBF Safety Precautions Warning Indications (When replacing the battery unit) Warning Indicates a potentially hazardous situation that, if not avoided, could result in serious injury or death. Additionally there may be significant property damage. Caution Indicates a potentially hazardous situation that, if not avoided, could result in minor or moderate injury or property damage. Precautions for Safe Use Supplementary comments on what to do or avoid doing, to use the product safely. Precautions for Correct Use Supplementary comments on what to do or avoid doing, to prevent failure to operate, malfunction or undesirable effect on product performance. Meaning of Product Safety Symbols General inhibition Notice prohibiting an unspecified general action. Dispose of or collect (recycle) the battery unit according to your own rules set for that purpose or as instructed by laws and regulations. * Do not dispose of it in fire. Otherwise, it could explode. Caution (for installation and connection) Pay attention to the weight and balance when carrying the unit, and install it in a solid and stable location. * Do not drop the battery unit and do not expose it to strong impact. Dropping the unit may result in injury or fire. * If you drop the unit, have it inspected and repaired. For repairs, contact our sales personnel. Keep plastic package bags out of reach of children. * Children may suffocate if they place their heads into plastic bags. General instruction Notice instructing an unspecified general action. Do-not-disassemble prohibition Notice prohibiting disassembly because disassembling the device may cause such an accident as an electric shock. Prohibition of use in locations subject to water such as a bathroom and shower room Notice prohibiting installation of the device in locations subject to water, because if a device not made water-proof is used in such locations, injury may occur due to an electric leak. Do-not-touch prohibition Indicates the possibility of injuries by touching the specific portion of the device under specific conditions, prohibiting touching of the device. Explosion alert Notice alerting the user to the possibility of explosion under certain conditions. Warning (for use of this product) * Provide safety measures outside the UPS to ensure safety in the entire system even if the UPS is damaged or an abnormality occurs due to an external factor. Not doing so may result in serious accidents due to incorrect operation. (Wiring) Do not short between the connector terminals. * Doing so may result in electric shock. * The battery unit's protection board may be damaged due to a short-circuit. * Connect each connection cable to the correct connected device. * Connect the terminal of each connection cable to the connector port with correct polarity. * Be sure to follow the connection procedure described in User's Manual (NUD-D18006A) Be sure to connect the input power supply of the unit to a DC power supply device having a rated voltage (24 VDC), or a battery power feed system. * The input voltage ranges for the UPS are as shown below. Check that the output voltage of the DC power supply device connected to the input terminal of the UPS is within any of the voltage ranges below. * Voltage range: 23 to 28 V DC * Connecting to a DC or AC power supply device with a different voltage may result in malfunction in or damage to the UPS, or cause a fire. When an abnormality (unusual sound or smell) occurs, turn OFF the unit's "Power" switch to stop the output, and stop the supply of commercial power. To make an emergency stop, move the rotary switch to "BATT REP", and when the LED changes from a fast blink to a slow blink, shut off the input power. * When performing maintenance on the connected devices, follow the above instructions to ensure safety. When installing the input cable, make sure to perform the connection as specified. Make sure to stop the primary power supply before connecting the unit to the input power supply terminal. * When connecting a cable to the terminal block, use a cable that complies with the input current specification of the UPS. Failure to do so may result in electric shock or ground fault. Do not disassemble, repair, or modify the unit. * Doing so may cause an electric shock or a fire. Do not install the unit in other than specified orientations. * Dropping or toppling the unit may cause injury. * If you install the unit in an orientation other than specified, the internal temperature may rise, eventually damaging the UPS or deteriorating the battery. 33 S8BA-SBF Do not use the unit at a location where the operating environment temperature is more than 55C * The battery deteriorates rapidly. It may result in fire. * If the battery's resin separator is damaged, the battery may be short-circuited inside, and may cause an abnormal heating, smoke, rupture or fire. * Doing so may cause a failure or malfunction of the unit. Do not run this unit in parallel. * Operating this unit in parallel may cause a failure or malfunction. Do not exceed the ranges specified for environmental conditions during use/storage. Do not install or store the unit in the places listed below. * Do not store in places where the humidity is lower than 10% or higher than 90%. * Do not use the unit in places where the ambient temperature is lower than 0C or higher than 55C. (With no condensation) * Do not use in places where the humidity is lower than 10% or higher than 90%. * Do not install/store the unit in closed places such as cabinets with no clearance, places where there is flammable or corrosive gas, places with large amounts of dust, places exposed to direct sunlight, places exposed to shock or vibration, salty or wet places, or outdoors. * Installation or storing the unit in such a place may cause a fire. Do not allow the unit to come in contact with water. * Doing so may cause an electric shock or a fire. * Doing so may cause an abnormal heating, smoke, rupture, or fire on the battery. * If the unit comes in contact with water, immediately stop using it and have it inspected and repaired. To make an emergency stop, turn the rotary switch to "BATT REP" and turn off the input power after the LED changes from fast blinking to slow blinking. * For repair, contact our sales personnel. When you use plug strip and other plugs to connect additional devices, do not connect devices that exceed the current capacity of the available plugs. * The current protection of the unit may operate, which may stop the output. * The cable heats up, which may cause a fire. Do not use a cable with damaged insulation. Do not pinch or sharply bend the cable. Do not fold or knot the cable. * Doing so may cause the cable to be damaged or heated, which may cause an electric shock or a fire. * If the cable is damaged, stop using the unit and have the cable repaired. * For repair, contact our sales personnel. Do not connect any devices other than rated voltage is 24 VDC. * The rated output voltage of this unit is 24 VDC. * Overvoltage or overcurrent may damage the connected devices. * The output voltage range is 22 to 30 VDC. All of the included accessories are designed to be used with the unit. Do not use the accessories with other devices. * Doing so may compromise the safety of devices. When this product is used in compliance with CE marking, please use under 2 m communication cable. Do not block the air vents (upper and lower). * Doing so will cause the internal temperature to rise, which may cause the unit to fail and the battery to deteriorate. * During installation, leave a space of 50 mm or more above the top and below the bottom. Do not connect the RS232C/USB port or the CONTACT port to a LAN device using a LAN cable. * Connection to a LAN device may result in malfunction in or damage to the UPS or the LAN device. 34 (for use) When the battery unit is dead, replace it immediately or stop using the unit. * Continuing the use of it may cause fire or electric shock due to liquid leaks. Ambient temperature Expected life 25C 10 years 35C 6.7 years 45C 3.7 years 55C 1.9 years * The values in the table are the expected life under standard use conditions and are not guaranteed. Occasionally, wipe off dust on the input terminal block and the output terminal block with a dry cloth. * Accumulated dust may cause a fire. Before wiping off dust, stop all connected devices and the unit, and stop the supply of commercial power. The unit will stop after 30 seconds of setting the mode selection/ backup operation time selection switch to "0.5". Do not use the unit in a closed place and do not cover the unit. * Doing so may cause abnormal heating or a fire. If you notice something unusual such as abnormal sound or smell, discoloration, deformation, and heating, turn OFF the unit's power and stop the supply from the input power supply. To make an emergency stop, move the rotary switch to "BATT REP", and when the LED changes from a fast blink to a slow blink, shut off the input power. * Using the unit under such conditions may cause an abnormal heating, rupture or fire. * If you notice such a condition, stop using the unit and contact our sales personnel for inspection and repairs. If fluid leaks from the interior, do not touch the fluid. * Doing so may cause blindness or burns. * If the fluid contacts your eyes or skin, wash it out with lots of clean water and consult your doctor. The fluid may damage your eye if your eye is left untreated. Do not place any objects on the unit, and do not drop heavy objects onto the unit. * Doing so may cause distortion/damage to the case or a failure of the internal circuit, which may cause a fire. S8BA-SBF The unit is equipped with an output circuit that can supply power to the connected devices even if the unit stops due to a failure or mis-operation of the internal circuit function. If you want to stop the output, stop the source of the "input power supply". * Output is continuing even when all indicators of the front panel are off. When charging the battery, if the battery cannot be charged completely even after the predetermined charging time, turn OFF the "Power" switch of the unit to stop charging the battery. The unit will stop after 30 seconds of setting the mode selection/backup operation time selection switch to "0.5". * Otherwise, it may cause an abnormal heating, smoke, rupture or fire on the battery. (for maintenance) When performing maintenance of the connected equipment, turn OFF the unit's power and stop the supply from the input power supply. The unit will stop after 30 seconds of setting the mode selection/backup operation time selection switch to "0.5". * Even if the input power supply is stopped in the operating state, the power supply output of the unit will not stop, and power will be supplied from the battery. Do not disassemble, repair, or modify the unit. * Doing so may cause an electric shock or a fire. (for battery replacement) Do not use other than the designated battery unit. * Not doing so may cause a fire. * Product model: S8BA-S480L, S8BA-S960L Do not replace the battery unit in a place where there is flammable gas. * Spark may occur when connecting the battery unit, which may cause an explosion or fire. If fluid leaks from the battery unit, do not touch the fluid. * Doing so may cause blindness or burns. * If the fluid contacts your eyes or skin, wash it out with lots of clean water and consult your doctor. Do not disassemble or modify the battery unit. * A safety mechanism and protection mechanism to prevent danger are embedded into the battery unit. If these are damaged, it may cause the battery to emit heat, smoke, explode, or catch fire. Do not drop the battery unit and do not expose it to strong impact. Dropping the unit may result in injury or fire. * Doing so may cause a leakage, abnormal heating, smoke, rupture or fire on the battery unit. And, if the battery unit's protection mechanism is broken, the battery may be charged at an abnormal current or voltage, an abnormal chemical reaction may occur inside the battery, and it may result eventually in an abnormal heating, smoke, rupture or fire. If fluid leaks from the interior, do not touch the fluid. * Doing so may cause blindness or burns. * If the fluid contacts your eyes or skin, wash it out with lots of clean water and consult your doctor. Do not short the battery unit with metal objects. * Doing so could cause an electric shock, fire or burn. * Some electrical energy still remains inside the spent battery unit. Do not throw the unit into fire. * Since the battery is incorporated in the unit, the insulator may melt, the gas exhaust valve or protection mechanism may be damaged, or the electrolyte may catch fire, and it may result eventually in an abnormal heating, smoke, rupture or fire. Do not dispose of battery units in a fire. * The insulator inside the battery unit may melt, the gas exhaust valve or protection mechanism may be damaged, or the electrolyte may catch fire, and it may result eventually in abnormal heating, smoke, rupture or fire. Do not insert metal objects into the input terminal block and the output terminal block of the UPS. * Doing so may result in electric shock. Do not insert metal objects into the battery connectors. Do not short between the connector terminals. * Doing so may result in electric shock. * The battery unit's protection board may be damaged due to a short-circuit. 35 S8BA-SBF Precautions for Safe Use Before using * The battery has not been charged at the time of purchase. Be sure to charge it before use. * Connect this unit to the input power supply to charge the battery unit. When moving the unit from a cold place to a warm place, leave it for several hours before using it. * If the unit is promptly turned ON after being moved to a warmer place, condensation may form inside the unit and cause it to fail. Take measures for handling unforeseen accidents, such as data backup and system redundancy. * The output may stop when there is failure in this unit. Correct Installation Method * For installation, to improve the long time reliability of the UPS, pay much attention to heat dissipation. Ensure convection of air around the UPS main body, and use the UPS in an operating condition below the derating curve. * During machining work for mounting, make sure that no metal scrap goes into the product. * The heat dissipation of the UPS may become worse depending on how the UPS is mounted; in rare cases, internal components may deteriorate and get damaged. Use the UPS in an operating condition based on the derating curve for each mounting direction. Standard mounting Connecting Leave 50 mm of space between the upper and lower. Do not short the unit output lines together, and do not short the battery connection cable (to ground). * The unit may fail. In the event you transfer or sell this unit to a third party, please include all of the documentation that came with the unit. This is to ensure that the unit is used in line with the conditions described in the included documentation. Leave 50 mm of space between the upper and lower. Using Before stopping the commercial power to the unit, turn OFF the "Power" switch of the unit. The unit will stop after 30 seconds of setting the mode selection/ backup operation time selection switch to "0.5". * The unit enters Battery Mode when input power supply is stopped. * If the frequency of backup operation becomes high, the battery life may be significantly reduced. Do not use for an application that frequently requires Battery Mode. * The battery unit will deteriorate and fail to maintain the specified backup time. If you want the UPS to stand by in a UPS startup state, set 3 months or less for the input power supply stop period. * The UPS startup state means the state of waiting for startup triggered by a remote ON/OFF or BS signal. * If the UPS is left unused in the above state for 3 months or longer, the battery goes into overdischarge state, and the backup time may become shorter or the battery may become unusable. Storing Storing the battery in UPS for a long term, store at an environment less than 25C and recharge 15 to 30 minutes the battery within 1 year. * The battery self-discharges even when it not being used, and it goes into overdischarge state if it is left for a long period of time. The backup time may become shorter or the battery may become unusable. * We recommend keeping the temperature 25C or less when storing the unit for long periods of time. * Turn OFF the unit's power when storing it. Do not install or store the unit in a place exposed to direct sunlight. * The rise of temperature may cause the battery unit to deteriorate rapidly and become unusable. 36 Note: 1. This UPS can be mounted with the sides in close contact. Up to 3 units can be mounted in close contact. Follow the derating curve during mounting with the sides in close contact. 2. When you install devices other than the UPS on the left or the right of the UPS, leave a space of at least 15 mm. Face-up mounting S8BA-SBF Incorrect Installation Method Mounting to the DIN Track * Do not short between the terminals. Doing so may result in electric shock. The protection board inside the battery unit may be damaged due to a short-circuit. Connect each connection cable to the correct connected device. Connect the terminal of each connection cable to the connector port with correct polarity. Be sure to follow the above connection procedure. Battery check schedule and frequency Average ambient temperature 55C Mount UPS upside down 50C 45C 40C Bottom mounting DIN rail is placed vertically 25C 6-month check 3-month check For the first year after starting use When 1 year or more have passed after starting use When 1.5 years or For the first 1.5 years after starting more have passed after starting use use For the first 3 years When 3 years or after starting use more have passed after starting use For the first 5 years When 5 years or after starting use more have passed after starting use For the first 6 years When 6 years or after starting use more have passed after starting use Conformance to EC Directives Applicable directives Stack the units Reverse the left/right positions of the battery unit and control unit Battery unit Replacement The UPS supports hot swapping. Battery unit replacement is possible both when the power is turned OFF (while the power output is OFF) and when the power is turned ON (while the power output is ON). Precautions for Correct Use * When replacing the battery unit, set the unit to "BATT REP" (Battery unit replacement mode) using the mode selection / backup operation time selection switch. (Perform a reset with the "input power supply" ON.) * When you replace the battery, the battery life counter automatically resets. If you replace the battery unit without activating the battery unit replacement mode, the battery life may not be detected accurately because the battery life counter is not reset. * Do not replace the battery unit while the UPS is operating in backup mode. Output will stop. * For details on the precautions for maintenance, refer to (for maintenance) on page 35 and (for battery replacement) on page 35. * If an input power supply error such as a power failure occurs when replacing the battery unit while in operation, backup cannot be performed and output stops. * The battery unit used in the unit has a limited lifespan. The life varies depending on your use environment and backup frequency. * The nearer the end of the life is, the more rapidly deterioration proceeds. The battery unit deteriorates even if it is stored. The higher the temperature is, the shorter the life becomes. * EMC Directives * Low Voltage Directives Principles regarding conformance OMRON electronic devices that comply with EC Directives also conform to the related EMC standards so that they can be more easily built into other devices or the overall machine. The actual products have been checked for conformity to EMC standards*. Whether the products conform to the standards in the system used by the customer, however, must be checked by the customer. EMCrelated performance of the OMRON devices that comply with EC Directives will vary depending on the configuration, wiring, and other conditions of the equipment or control panel on which the OMRON devices are installed. The customer must, therefore, perform the final check to confirm that devices and the overall machine conform to EMC standards. * Applicable EMC (Electromagnetic Compatibility) standards are as follows: EMS (Electromagnetic Susceptibility): EN 61000-6-2, EMI (Electromagnetic Interference): EN 61000-6-4, and EN 61000-6-4 Radiated emission: 10-m regulations Low Voltage Directives Always ensure that devices operating at voltages of AC 50 to 1,000 V and DC 75 to 1,500 V meet the required safety standards. The applicable directive is EN60950-1. 37 S8BA-SBF Conformance to EC Directives This product complies with EC Directives. To ensure that the machine or device in which the this product is used complies with EC Directives, the product must be installed as follows: * This product must be installed within a control panel. * You must use reinforced insulation or double insulation for the direct power supply equipment connected to this product. * Models of this product that comply with EC Directives also conform to the Common Emission Standard. Radiated emission characteristics (10-m regulations), in particular, may vary depending on the configuration of the control panel used, other devices connected to the control panel, wiring, and other conditions. Therefore, even when using a model of this product that complies with EC Directives, you must confirm and ensure the compliance to EC Directives of the entire machine or equipment. * This is a Class A product (for industrial environments). In a residential environment, it may cause radio interference. If radio interference occurs, the user may be required to take appropriate measures. Conformance to UL Conformance to UL * This product must be installed within a control panel with an internal heater or other unit to protect against the formation of condensation. * Gaps in the door to the control panel must be completely filled or covered with gaskets or other material. Conformance to FCC FCC CAUTION Changes or modifications not expressly approved by the party responsible for compliance could void the user's authority to operate the equipment. * This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. * This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. * Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense. 38 Terms and Conditions Agreement Read and understand this catalog. Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or comments. Warranties. (a) Exclusive Warranty. Omron's exclusive warranty is that the Products will be free from defects in materials and workmanship for a period of twelve months from the date of sale by Omron (or such other period expressed in writing by Omron). Omron disclaims all other warranties, express or implied. (b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, ABOUT NON-INFRINGEMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE PRODUCTS. BUYER ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. Omron further disclaims all warranties and responsibility of any type for claims or expenses based on infringement by the Products or otherwise of any intellectual property right. (c) Buyer Remedy. Omron's sole obligation hereunder shall be, at Omron's election, to (i) replace (in the form originally shipped with Buyer responsible for labor charges for removal or replacement thereof) the non-complying Product, (ii) repair the non-complying Product, or (iii) repay or credit Buyer an amount equal to the purchase price of the non-complying Product; provided that in no event shall Omron be responsible for warranty, repair, indemnity or any other claims or expenses regarding the Products unless Omron's analysis confirms that the Products were properly handled, stored, installed and maintained and not subject to contamination, abuse, misuse or inappropriate modification. Return of any Products by Buyer must be approved in writing by Omron before shipment. Omron Companies shall not be liable for the suitability or unsuitability or the results from the use of Products in combination with any electrical or electronic components, circuits, system assemblies or any other materials or substances or environments. Any advice, recommendations or information given orally or in writing, are not to be construed as an amendment or addition to the above warranty. See http://www.omron.com/global/ or contact your Omron representative for published information. Limitation on Liability; Etc. OMRON COMPANIES SHALL NOT BE LIABLE FOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY. Further, in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted. Suitability of Use. Omron Companies shall not be responsible for conformity with any standards, codes or regulations which apply to the combination of the Product in the Buyer's application or use of the Product. At Buyer's request, Omron will provide applicable third party certification documents identifying ratings and limitations of use which apply to the Product. This information by itself is not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine, system, or other application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product with respect to Buyer's application, product or system. Buyer shall take application responsibility in all cases. NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY OR IN LARGE QUANTITIES WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM. Programmable Products. Omron Companies shall not be responsible for the user's programming of a programmable Product, or any consequence thereof. Performance Data. Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the result of Omron's test conditions, and the user must correlate it to actual application requirements. Actual performance is subject to the Omron's Warranty and Limitations of Liability. Change in Specifications. Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our practice to change part numbers when published ratings or features are changed, or when significant construction changes are made. However, some specifications of the Product may be changed without any notice. When in doubt, special part numbers may be assigned to fix or establish key specifications for your application. Please consult with your Omron's representative at any time to confirm actual specifications of purchased Product. Errors and Omissions. Information presented by Omron Companies has been checked and is believed to be accurate; however, no responsibility is assumed for clerical, typographical or proofreading errors or omissions. * Windows is a registered trademark of Microsoft Corporation in the USA and other countries. * Linux is a trademark or registered trademark of Linus Torvalds in the USA and other countries. * Other company names and product names mentioned in this document are the trademarks or registered trademarks of their respective companies. OMRON Corporation Industrial Automation Company Authorized Distributor: Kyoto, JAPAN Contact: www.ia.omron.com Regional Headquarters OMRON EUROPE B.V. Wegalaan 67-69, 2132 JD Hoofddorp The Netherlands Tel: (31)2356-81-300/Fax: (31)2356-81-388 OMRON ELECTRONICS LLC 2895 Greenspoint Parkway, Suite 200 Hoffman Estates, IL 60169 U.S.A. Tel: (1) 847-843-7900/Fax: (1) 847-843-7787 OMRON ASIA PACIFIC PTE. LTD. No. 438A Alexandra Road # 05-05/08 (Lobby 2), Alexandra Technopark, Singapore 119967 Tel: (65) 6835-3011/Fax: (65) 6835-2711 OMRON (CHINA) CO., LTD. Room 2211, Bank of China Tower, 200 Yin Cheng Zhong Road, PuDong New Area, Shanghai, 200120, China Tel: (86) 21-5037-2222/Fax: (86) 21-5037-2200 (c) OMRON Corporation 2015-2018 All Rights Reserved. In the interest of product improvement, specifications are subject to change without notice. CSM_4_5_1018 Cat. No. U701-E1-03 0418 (0515)