1
Uninterruptible Power Supply (UPS)
Integrated battery type
S8BA-LF
DC-DC type small UPS mounts on a
DIN rail to provide an ideal
countermeasure for momentary power
losses and power failures in industrial
computers (IPC) and controllers.
System reliability greatly improved because
24VDC power supply is backed up for a certain
period of time in the event of voltage drop or power failure.
Compactness, weight reduction, and long battery life
realized thanks to the adoption of a lithium-ion battery.
Push-in terminal block adopted for the power input and
output I/F.
Shutdown in conjunction with the industrial
purpose computer (IPC) or controller realized
by the USB/RS-232C/I/O port installed in the UPS.
Model Number Structure
Model Number Legend * Use the following format to place an order.
Ordering Information
Main body
Uninterruptible Power Supply (UPS)
*16.7 A/400 W for use as a UL compliant device.
Communication cable
Replacement battery pack
Input voltage Output voltage Output current/capacity Model number
24 VDC 24 VDC
5 A/120 W S8BA-24D24D120LF
10 A/240 W S8BA-24D24D240LF
15 A/360 W S8BA-24D24D360LF
20 A/480 W * S8BA-24D24D480LF
Specifications Type Length Model number
For RS-232C port RJ45/Dsub9Pin 2 m S8BW-C01
For CONTACT port RJ45/Discrete wire S8BW-C02
Rated voltage Rated capacity Weight Model UPS Model : Required units
14.4 VDC 1600 mAh 0.3 kg S8BA-B120L
S8BA-24D24D120LF : 1 pcs
S8BA-24D24D240LF : 2 pcs
S8BA-24D24D360LF : 3 pcs
S8BA-24D24D480LF : 4 pcs
!Refer to Safety Precautions on page 13.
2 31
Series name
S8BA-
@@@@@@@@@LF
1. Input voltage specification
24D: 24 VDC
2. Output voltage
24D: 24 VDC
3. Capacity
120: 120 W
240: 240 W
360: 360 W
480: 480 W
S8BA-LF
2
Ratings, Characteristics, and Functions
*1. An estimated value for standard mounting. Not a guaranteed value.
*2. Conditions: With rated loads connected, at a rated input voltage, and with the battery fully charged.
*3. Conditions: With rated loads connected, at a rated input voltage, and at the maximum battery charging current.
*4. 400 W for use as a UL compliant device.
*5. 20 A for use as a UL compliant device.
*6. 16.7 A for use as a UL compliant device.
*7. When using in an environment at a high temperature, charging may be paused by charging temperature protection, then the charging time will
be longer than specified time.
"CS" will be displayed when charging temperature protection is operated.
*8. For the S8BA-24D24D120LF, install all of the RSMN-2030, RSHN-2030, and RSEN-2030 EMC filters manufactured by TDK. For the S8BA-
24D24D240LF, S8BA-24D24D360LF, or S8BA-24D24D480LF, install both the RSMN-2030 and RSHN-2030 or their equivalents. Install these
filters in series to the cable connected to the DC input terminal block.
When you do, do not connect anything to the GR terminal.
The effectiveness of the noise filters may be affected by the installation environment. Be sure to check effectiveness before starting operation.
Item Capacity 120 W 240 W 360 W 480 W *4
DC input
Rated input voltage 24 VDC
Input
voltage
range
When standard voltage
sensitivity is set 24 VDC±10%
When low voltage sensitivity
is set 24 VDC±12.5%
When high voltage
sensitivity is set 24 VDC±5%
Input
maximum
current
for rated input voltage for
rated loads connected 5.9 A 11.7 A 17.5 A 23.3 A *5
Input terminal Push-in terminal block
Input protection Fuse (cannot be replaced by the customer)
Input protection capacity 10 A 15 A 30 A
DC output
Rated
current (for rated output voltage) 5 A 10 A 15 A 20 A *6
Switching time Uninterrupted
Output
voltage
Normal operation Output of input voltage as-is
Backup operation 24 V±5%
Output terminal Push-in terminal block
Overload protection
Alarm display at a load level of 110% or over (normal operation)
Alarm display at a load level of 110% or over and output voltage drop (backup operation)
Alarm display cancellation at a load equal to or below the rated capacity (normal operation, backup
operation)
Battery
Type Lithium-ion battery
Rated voltage 14.4 VDC
Rated capacity 1600 mAh × 1 parallel 1600 mAh × 2 parallel 1600 mAh × 3 parallel 1600 mAh × 4 parallel
Expected battery life *1 2.5 years (50°C), 5 years (40°C), 10 years (25°C)
Replacement by user Yes (Hot swapping)
Auto battery check function Yes
Battery life counter function Yes
Charging time 4 hours *7
Backup time (25°C, initial characteristics) 6 min. (120 W) 6 min. (240 W) 6 min. (360 W) 6 min. (480 W)
Environment
Operating ambient temperature/humidity
0 to +55°C/10 to 90% (with no condensation)
Storage ambient temperature/humidity –20°to +55°C/10 to 90% (with no condensation)
Vibration resistance JIS C 60068-2-6 compliant. 5 to 8.4 Hz amplitude: 3.5 mm, 8.4 to 150 Hz acceleration rate: 9.8 m/s2
X, Y, and Z directions for 100 minutes (Time coefficient: 10 minutes × coefficient factor 10 = total time 100 min.)
Shock resistance JIS C 60068-2-27 compliant. 147 m/s2, 3 times in X, Y, and Z directions.
Structure
Dimensions (W × D × H mm) 94 × 100 × 100 148 × 100 × 100 270 × 100 × 100
Weight of unit Approx. 0.8 kg Approx. 1.3 kg Approx. 2.0 kg Approx. 2.3 kg
Cooling method Natural cooling
Insulation and
withstand
voltage
Withstand voltage 1,000 V 50/60 Hz AC between the DC external terminals and the GR terminal for 1 minute at a leakage
current of 10 mA max.
Insulation resistance 20 MΩ min. between the DC external terminals and the GR terminal (at 500 VDC)
Compliance
to standard
Safety standard UL508/CE/C22.2 No.107.1-01 / EAC
EMI
Radiated disturbance
electromagnetic field strength
EN61000-6-4/FCC/ICES/RCM/KC
Ship standard LR/ABS/EN60945 *8/DNV GL
Internal power consumption (normal *2 / maximum *3)
7 W/22 W 11 W/41 W 14 W/60 W 18 W/80 W
Serial
communication
RS-232C (Interface terminal) Yes (RJ45)
USB (interface terminal) Yes (B connector)
I/O signal (Interface terminal) Yes (RJ45)
Accessories USB cable (1.5 m)
Accessory functions
Beeper setting; Auto restart setting; Auto test setting; Auto restart mode setting; Input sensitivity setting;
Remote ON/OFF signal logic setting; Cold start setting; Battery life counter setting; Power switch function
setting; Maximum backup time setting; Startup battery level setting; Backup stop (BS) signal delay time
setting; Backup (BU) signal delay time setting; and Contact signal I/O test
S8BA-LF
3
Nomenclature
Front view
S8BA-24D24D120LF (120 W)
S8BA-24D24D240LF (240 W)
Enlarged view of the operation panel
S8BA-24D24D360LF (360 W)
S8BA-24D24D480LF (480 W)
1
2
3
4
5
6
7
1
2
3
4
5
6
7
8
9
10
1
2
3
4
5
6
7
No. Name Function
1 Operation panel Describe the name of each part.
2 DC output terminal block Connect to load lines. (+V), (-V)
3 DC input terminal block Connect to input lines. (+V), (-V)
4GR terminal Ground this terminal to less than 100 ɹ to improve noise resistance and prevent electrical shock.
5 USB port Connect to a USB cable.
6 RS-232C port Connect to a RS-232C cable.
7 CONTACT port I/O port. Connect to a signal line.
8 “Status indicator” digital indicator The seven-segment display indicates the status of the UPS.
9 “Beep Stop/Test” switch Stop the beeper and perform self-diagnosis testing.
10 “Power” switch Turn the power of the UPS ON/OFF.
S8BA-LF
4
Rear view
S8BA-24D24D120LF (120 W)
S8BA-24D24D240LF (240 W)
S8BA-24D24D360LF (360 W)
S8BA-24D24D480LF (480 W)
No. Name Function
11 DIN rail mounting hook Hook the UPS on the DIN rail.
12 DIN rail mounting groove Groove for positioning the DIN rail and the UPS.
11
12
11
12
S8BA-LF
5
Connections
Block Diagrams
S8BA-24D24D@@@LF
*In normal operation, 24 VDC is output as-is for charging the battery and from the input power supply. If 24 VDC from the input power supply
drops, the operation automatically switches to backup operation, and 24 VDC is output from the battery.
Input and output voltage time chart when shifting to backup operation
Connecting a cable to Battery connection terminal block, the input terminal block and
the output terminal block
For details about the connectable sizes and recommended cable sizes, see the following table.
Connectable size Cable
Solid wire 0.2 to 4.0 mm2
Twisted pair 0.2 to 2.5 mm2
AWG AWG24 to 12
Stripped cable length 8 to 10 mm
Recommended
cable size
5 A Solid wire/Twisted pair 0.5 mm2
AWG AWG20
10 A Solid wire/Twisted pair 0.75 mm2
AWG AWG16
15 A Solid wire/Twisted pair 1.25 mm2
AWG AWG14
20 A Solid wire/Twisted pair 2.0 mm2
AWG AWG12
Temperature rating for recommended cable 90°C
Diagram of the Input/output circuit block
FET
FET
Charge/Discharge
Battery
DC-DC converter
Normal operation
Backup operation
FET
24 VDC
Input
24 VDC
Output
Normal operation: OFF
Backup operation: ON
Normal operation: ON
Backup operation: OFF
Normal operation: ON
Backup operation: OFF
<4ms
<4ms
When high voltage sensitivity is set
*
When standard voltage sensitivity is set*
(Factory default)
When low voltage sensitivity is set*
Input voltage
<4ms
power failure or input voltage drop
22.2 VDC (-7.5%)
21 VDC (-12.5%)
20.4 VDC (-15%)
<Measurement condition>
Switching power supply : S8VK-G48024
UPS : S8BA-24D24D240LF
Load : Rated load
When power failure occurs on the AC input side of the switching power supply
DC voltage 24 VDC
S8BA-LF
6
I/O signal functions
Type of output signals
Type of input signals
*BS signal delay time
It is possible to set the period of time from when a BS signal is received until the output of the UPS is stopped. The output of the UPS can be
stopped by inputting the voltage signal (High).
I/O signal port (RJ45 connector)
Contact signal ratings
Signal Description
Backup signal output (BU) Stays ON during backup operation at a power failure.
Low battery level signal output (BL) Goes ON when the battery becomes weak during backup operation at a power failure.
Trouble signal output (TR) Goes ON when an internal failure of the UPS occurs or when the battery life counter expires.
Battery replacement signal output (WB) Goes ON when the test determines that battery replacement is necessary due to deterioration
or when the battery life counter reaches the replacement period. (The life counter operates while
input power is being supplied.)
Signal Description
Input of the UPS stop signal (BS) When the BS signal is ON (High), the output of the UPS is stopped after the time period specified
in advance has elapsed. *
Remote ON/OFF signal
Remote ON/OFF signals can be used to start and stop the UPS, by using either an externally
connected contact or the ON/OFF status of the open collector circuit.
When signal is OFF, the UPS will be turned on. When signal is ON, the UPS will be turned off.
In the factory settings, the UPS stops operation when this is short-circuited.
In addition, it is necessary to turn on the "Power" switch of UPS to use this function.
Outlook of the connector Pin number Item
1 Backup signal output (BU)
2 Remote ON/OFF input (-)
3 Trouble signal output (TR)
4 COMMON (COM)
5 Battery LOW signal output (BL)
6 Backup stop signal input (BS)
7 Battery Replacement Signal output (WB)
8 Remote ON/OFF input (+)
Signal Description
Signal output (BL, TR, BU, WB)
Applicable voltage: 50 VDC or less
Maximum current: 360 mA
BU signal min. response time: 10 ms
Remote ON/OFF
Voltage between terminals: 5 VDC
Current when closed: 10 mA max.
Min. signal response time: When stopped 100 ms
When restarting 300 ms
UPS Stop Signal input (BS)
Input voltage: HIGH (ON) 8 to 24 VDC
LOW (OFF) 0.5 VDC or less
Input current: 1.7 to 5.1 mA
Min. signal response time: When stopped 100 ms
When restarting 300 ms
S8BA-LF
7
Contact signal circuit
Precautions when selecting switch mode power supplies
When selecting switch mode power supplies, install devices with a capacity larger than the total of the UPS internal power consumption and internal
power consumption of connected devices to the input side of the UPS. When these conditions are met, usage will be possible with no problems
even if the rated capacity of the UPS is larger than the rated capacity of the switching power supply.
Switch mode power supply capacity > (UPS internal power consumption + Internal power consumption of connected devices)
(Ex.)
Signal output (BU, TR, BL, WB) Remote ON/OFF
UPS Stop Signal input (BS)
Switch mode power supply
(Capacity: 92 W or more) >
(
UPS
(Internal power consumption: 22 W) +Industrial-purpose computers (IPC)/controllers, etc.
(Internal power consumption: 70 W, DC input)
)
S8BA
(Capacity: 120 W)
BL
TR
BU
WB
BS
COM
4.7 Ω
5 V
680 Ω
Remote ON/OFF (+)
Remote ON/OFF (–)
S8BA-LF
8
Engineering Data
Estimated backup time
The backup time varies depending on the capacity of connected devices.
After calculating the total capacity of connected devices, refer to the graph of the backup time to obtain an estimation of the initial value of the
backup time. (This is also applied to checking the battery.)
1. Convert the total capacity (power consumption) of the connected devices to watts (W).
For the indication of connected devices, check your computer and the rear of the display.
The indicator can show values in two different ways: amperes (A), and watts (W).
Example 1: 24 VDC, 145 W
Example 2: 24 VDC, 1.8 A
For devices that use the A indication, convert the capacity into W.
Example 2: 1.8 (A) = 1.8 × 24 (W) = 43.2 (W)
2. Add the values converted into W to obtain the total capacity of the connected devices.
3. Calculate the initial value of the backup time for the total capacity of the connected devices from the graph below.
Graph of backup time (graph of initial values for products that have not been used at 25°C). The backup time becomes shorter than the graph
(table) below when temperature is lower.
The smaller the capacity of connected devices becomes, the longer the backup time becomes.
Backup time table (Time unit: minutes)
Note: The above backup times are for reference only. They may change depending on the battery life and external environment (such as
temperature).
Indication Value
A W = A × 24
Capacity (W)
30 60 90 120 180 240 300 360 420 480
S8BA-24D24D120LF
(120 W) 2914 9 6 ——————
S8BA-24D24D240LF
(240 W) 58 29 19 15 9 6
S8BA-24D24D360LF
(360 W) 87 43 28 22 14 10 8 6
S8BA-24D24D480LF
(480 W) 119 59 39 29 19 15 11 9 8 6
120 W
480 W
360 W
240 W
Capacity (W)
Backup time (Minutes)
0480
120
100
80
60
40
20
060 120 180240300360420
S8BA-LF
9
Derating curve
Backup operation sequence in the event of power failure/voltage drop (instantaneous voltage drop)
When the input power supply recovers while the battery level is sufficiently high
*"Disable beeper" is set by factory default. Even when "Disable beeper" is set, the buzzer sounds at startup.
Ambient temperature (°C)
Load rate (%)
A
0 102030405060
120
100
80
60
40
20
0
A: For standard mounting, face-up mounting, sta-
tionary mounting
A
B
0 102030405060
120
100
80
60
40
20
0
Ambient temperature (°C)
Load rate (%)
A: For standard mounting,
B: For face-up mounting, stationary mounting
A
C
B
0 102030405060
120
100
80
60
40
20
0
Ambient temperature (°C)
Load rate (%)
A: For standard mounting,
B: For face-up mounting, stationary mounting
C: For standard mounting (For use as a UL compli-
ant device)
120, 240 W
<S8BA-24D24D120LF>
<S8BA-24D24D240LF>
360 W
<S8BA-24D24D360LF>
480 W
<S8BA-24D24D480LF>
0.2 s
4 s
Input power supply
Power switch
Battery level
UPS output
Indication in the "status display"
Beeper *
UPS operating mode
BU signal (OUT)
BL signal (OUT)
BS signal (IN)
Normal operation
Backup operation
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
During power failure
High
Low
Empty
OFF
ON
ON
ON
ON
S8BA-LF
10
When the input power supply recovers while the battery level is Low
*"Disable beeper" is set by factory default. Even when "Disable beeper" is set, the buzzer sounds at startup.
When the input power supply does not recover until the battery becomes empty
*"Disable beeper" is set by factory default. Even when "Disable beeper" is set, the buzzer sounds at startup.
0.2 s
4 s
1 s
During power failure
Power switch
Battery level
UPS output
Indication in the "status display"
Beeper *
UPS operating mode
BU signal (OUT)
BL signal (OUT)
BS signal (IN)
Normal operation
Backup operation
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
High
Low
Empty
OFF
ON
ON
ON
ON
Input power supply
1 s
3 s
During power failure
Input power supply
Power switch
Battery level
UPS output
Indication in the "status display"
Beeper *
UPS operating mode
BU signal (OUT)
BL signal (OUT)
BS signal (IN)
Normal operation
Backup operation
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
High
Low
Empty
OFF
ON
ON
ON
ON
0.2 s
4 s
S8BA-LF
11
Overcurrent protection curve
120W, 240W, 360W, 480W
Note: 1. In backup operation, the output voltage drops at a load rate of 110% or higher.
2. In normal operation, the output stops when the input protection fuse blows out.
Dimensions (Unit: mm)
Main body
0
20
40
60
80
100
0 20 40 60 80 100 120
* In backup operation
Output current (%)
Output voltage (%)
100
94
100
2
2.5
S8BA-24D24D120LF (120 W)
S8BA-24D24D240LF (240 W)
100
148
100
2
2.5
S8BA-24D24D360LF (360 W)
S8BA-24D24D480LF (480 W)
270 100
2.5
100
2
S8BA-LF
12
DIN Rail (Order Separately)
Mounting Rail (Material: Aluminum)
PFP-100N
PFP-50N
Mounting Rail (Material: Aluminum)
PFP-100N2
End Plate
PFP-M
Note: 1. If there is a possibility that the Unit will be subject to vibration or shock, use a steel DIN Rail. Otherwise, metallic filings may result from
aluminum abrasion.
2. If the Unit may be subjected to sliding to either side, attach an End Plate (model PFP-M) on each side of the Unit.
Power management solutions
The following software is available as a free download from our website.
Name Description Conditions Interface
Power Attendant
Lite
You can execute computer shutdown and UPS auto stop
when an input power problem occurs (power failure, etc.).
You can use a computer that has "Power Attendant Lite"
installed to send a script over the network to devices that do
not have shutdown software installed to log in to each device
and execute a device shutdown command.
You can automatically start and stop computers and the
UPS according to a preset schedule.
Windows 10 / 8.1 / 8 / 7
Windows Server 2016
Windows Server 2012 R2 / 201208
Windows Storage Server 2008
Windows Storage Server 2016
Windows Storage Server 2012 R2 / 2012
Windows Storage Server 2008 R2 / 2008
RS232C
USB
Simple Shutdown
Software
You can execute computer shutdown and UPS auto stop
when an input power problem occurs (power failure, etc.).
You can modify and recompile the source code to
incorporate a UPS management function into your Windows/
Linux® system.
Supports Windows and Linux
<For Windows>
Windows 10 / 8.1 / 8 / 7
Windows Server 2012 R2 / 2012
Windows Server 2008 R2 / 2008
Windows Server 2003R2 / 2003
Windows Vista / XP
Windows 10 IoT Enterprise LTSB
Windows Embedded Standard 7
<For Linux>
Red Hat Enterprise Linux Ver.7.x
CentOS Ver.7.x
RS232C
USB
Setting Utility
This software is used to configure UPS settings.
(Setting item examples)
Function for sending commands
Function for saving settings to a backup file
Function for restoring settings from a backup file
Function for reading UPS settings
Function for returning UPS settings to default settings
Windows 10 / 8.1 / 8 / 7
Windows Server 2012 R2 / 2012
Windows Server 2008 R2 / 2008
Windows Server 2003R2 / 2003
Windows Vista / XP
Windows 10 IoT Enterprise LTSB
Windows Embedded Standard 7
RS232C
USB
4.5
15 25 25
10 10
1,000 (500) *
25 25 15(5) *
35±0.3
7.3±0.15
27±0.15
1
* Values in parentheses are for the PFP-50N.
4.5
15 25 25
10 10
1,000
25 25 15 1 1.5
29.2242735±0.3
16
1.3
4.8
35.5 35.3
1.8
1.8
10
6.2
1
50
11.5
10
M4 spring washer
M4×8 pan-
head screw
S8BA-LF
13
Safety Precautions
Warning Indications
Meaning of Product Safety Symbols
(for use of this product)
Provide safety measures in external circuits, not in the
UPS, in order to ensure safety in the system if an
abnormality occurs due to malfunction of the UPS or
another external factor affecting the UPS operation.
Not doing so may result in serious accidents.
(When replacing the battery unit)
Dispose of or collect (recycle) the battery unit according
to your own rules set for that purpose or as instructed by
laws and regulations.
Do not dispose of it in fire. Otherwise, it could explode.
(for installation and connection)
Carry the unit considering its weight and balance, and
place it on a stable and robust base.
If you drop the unit, the battery or the battery protection
mechanism may be broken, and it may result
eventually in a fluid leak, abnormal heating, smoke,
rupture or fire.
If you drop the unit, stop using it and have it inspected
and repaired.
For details on repair, contact the OMRON
representative.
Keep plastic package bags out of reach of children.
Children may suffocate if they place their heads into
plastic bags.
Make sure to connect the “input power supply” to the
direct power supply equipment with a rated voltage (24
VDC).
The input voltage ranges for the UPS are as shown
below. Check that the output voltage of the direct
power supply equipment connected to the input
terminal of the UPS is within any of the voltage ranges
below.
24 VDC±10% (Input voltage range: When standard
voltage sensitivity is set)
24 VDC±12.5% (Input voltage range: When low
voltage sensitivity is set)
24 VDC±5% (Input voltage range: When high
voltage sensitivity is set)
Connecting to a DC or AC power supply device with a
different voltage may result in malfunction in or
damage to the UPS, or cause a fire.
When an abnormality (unusual sound or smell) occurs,
turn OFF the unit’s “Power” switch to stop the output, and
stop the supply of commercial power.
When performing maintenance on the connected
devices, follow the above instructions to ensure safety.
When installing the input cable, make sure to perform the
connection as specified.
Make sure to stop the primary power supply before
connecting the unit to the input power supply terminal.
When connecting a cable to the terminal block, use a
cable that complies with the input current specification
of the UPS. Failure to do so may result in electric
shock or ground fault.
Do not disassemble, repair, or modify the unit.
Doing so may cause an electric shock or a fire.
Do not install the unit in other than specified orientations.
Dropping or toppling the unit may cause injury.
If the UPS is not installed in the specified direction, the
internal temperature may rise, eventually damaging
the UPS or deteriorating the battery.
Do not use the unit where the maximum temperature
exceeds 55°C.
The battery deteriorates rapidly. It may result in fire.
If the battery's resin separator is damaged, the battery
may be short-circuited inside, and may cause an
abnormal heating, smoke, rupture or fire.
Doing so may cause a failure or malfunction of the unit.
Warning
Indicates a potentially hazardous
situation that, if not avoided, could
result in serious injury or death.
Additionally there may be significant
property damage.
Caution
Indicates a potentially hazardous
situation that, if not avoided, could
result in minor or moderate injury or
property damage.
Precautions
for Safe Use
Supplementary comments on what to
do or avoid doing to use the product
safely.
Precautions
for Correct
Use
Supplementary comments on what to
do or avoid doing to prevent failure to
operate, malfunction, or undesirable
effects on product performance.
General inhibition
Notice prohibiting an unspecified general action.
General instruction
Notice instructing an unspecified general action.
Do-not-disassemble prohibition
Notice prohibiting disassembly because
disassembling the device may cause such an
accident as an electric shock.
Prohibition of use in locations subject to water
such as a bathroom and shower room
Notice prohibiting installation of the device in
locations subject to water, because if a device not
made water-proof is used in such locations, injury
may occur due to an electric leak.
Do-not-touch prohibition
Indicates the possibility of injuries by touching
the specific portion of the device under specific
conditions, prohibiting touching of the device.
Explosion alert
Notice alerting the user to the possibility of
explosion under certain conditions.
WARNING
廢電池請回收
Caution
S8BA-LF
14
Do not exceed the ranges specified for environmental
conditions during use/storage.
Do not install or store the unit in the places listed below.
Do not store in places where the humidity is lower than
10% or higher than 90%.
Do not use the unit in places where the ambient
temperature is lower than 0°C or higher than 55°C.
(With no condensation)
Do not use in places where the humidity is lower than
10% or higher than 90%.
Do not install/store the unit in closed places such as
cabinets with no clearance, places where there is
flammable or corrosive gas,
Places with large amounts of dust, places exposed to
direct sunlight, places exposed to shock or vibration,
salty or wet places, or outdoors.
Installation or storing the unit in such a place may
cause a fire.
When you use plug strip and other plugs to connect
additional devices, do not connect devices that exceed
the current capacity of the available plugs.
The current protection of the unit may operate, which
may stop the output.
The cable heats up, which may cause a fire.
Do not pinch or sharply bend the cable.
Do not fold or knot the cable.
Doing so may cause the cable to be damaged or
heated, which may cause an electric shock or a fire.
If the cable is damaged, stop using the unit and have
the cable repaired.
For details on repair, contact our sales personnel.
Connect only devices using 24 VDC rated voltage.
The rated output voltage of the UPS is 24 VDC.
Overvoltage or overcurrent may damage the
connected devices.
All the accessories contained in the product package can
be used for the UPS only. Do not use any of them for
other devices.
Be sure to observe this to use the UPS safely.
Include a breaker between the “input power supply” of the
UPS and the direct power supply equipment. And, install
the breaker where it is easy to operate.
To use this product as a CE marking compliant device,
use a 2-meter or shorter connection cable.
Do not block the air vents (upper and lower).
Doing so will cause the internal temperature to rise,
which may cause the unit to fail and the battery to
deteriorate.
For stationary installation, leave a space of 50 mm or
more above the top, and for installation using a DIN rail
and screw clamps, leave a space of 50 mm or more
above the top and below the bottom each.
Do not connect the RS-232C port or the CONTACT port
to a LAN device using a LAN cable.
Connection to a LAN device may result in malfunction
in or damage to the UPS or the LAN device.
(for use)
Do not allow the unit to come in contact with water. If you
drop the unit, stop using it.
Doing so may cause an electric shock or a fire.
Doing so may cause an abnormal heating, smoke,
rupture, or fire on the battery.
If the unit becomes wet or is dropped, immediately
stop using it, disconnect the input power supply from
the wall outlet (commercial power source) and have it
inspected and repaired.
For details on repair, contact our sales personnel.
When the battery is dead, replace it immediately or stop
using the unit.
Continuing the use of it may cause fire or electric
shock due to liquid leaks.
*The values in the table are the expected life under
standard use conditions and are not guaranteed.
Occasionally, wipe off dust on the input terminal block
and the output terminal block with a dry cloth.
Accumulated dust may cause a fire.
Before wiping off dust, stop all connected devices and
the unit, and stop the supply of commercial power.
Do not use the unit in a closed place and do not cover the
unit.
Doing so may cause abnormal heating or a fire.
If you notice something unusual such as abnormal sound
or smell, discoloration, deformation, and heating, turn
OFF the unit’s “Power” switch to stop the output and stop
the supply from the “input power supply”.
Using the unit under such conditions may cause an
abnormal heating, rupture or fire.
If this situation arises, be sure to stop using the UPS
and request our sales personnel for inspection and
repair.
A readily accessible disconnect device shall be
incorporated external to the equipment.
If fluid leaks from the interior, do not touch the fluid.
Doing so may cause blindness or burns.
If the fluid contacts your eyes or skin, wash it out with
lots of clean water and consult your doctor. The fluid
may damage your eye if your eye is left untreated.
Do not place any objects on the unit, and do not drop
heavy objects onto the unit.
Doing so may cause distortion/damage to the case or
a failure of the internal circuit, which may cause a fire.
The unit is equipped with a bypass circuit which is able to
supply electric power to connected devices even when
the inner control circuit is broken down by defects or
malfunctions.
If you want to stop the output, stop the source of the “input
power supply”.
Output is continuing even when all indicators of the
front panel are off.
Output ON/OFF cannot be controlled with the “Power”
switch on the front panel.
When charging the battery, if the battery cannot be
charged completely even after the predetermined
charging time, turn OFF the “Power” switch of the unit to
stop charging the battery.
Otherwise, it may cause an abnormal heating, smoke,
rupture or fire on the battery.
Ambient temperature Expected life
50°C 2.5 years
40°C 5 years
25°C 10 years
S8BA-LF
15
(for maintenance)
When maintaining the connected equipment, turn OFF
the unit’s “Power” switch to stop the output, and stop the
supply of the “input power supply”.
Even if the input power supply to the UPS is stopped
while it is in operation, the power output of his unit
does not stop and power is supplied from the battery.
Do not disassemble, repair, or modify the unit.
Doing so may cause an electric shock or a fire.
If fluid leaks from the interior, do not touch the fluid.
Doing so may cause blindness or burns.
If the fluid contacts your eyes or skin, wash it out with
lots of clean water and consult your doctor.
Do not throw the unit into fire.
Since the battery is incorporated in the unit, the
insulator may melt, the gas exhaust valve or protection
mechanism may be damaged, or the electrolyte may
catch fire, and it may result eventually in an abnormal
heating, smoke, rupture or fire.
Do not insert metal objects into the input terminal block
and the output terminal block of the UPS.
Doing so may result in electric shock.
Do not insert metal objects into the battery connectors.
Do not short between the connector terminals.
Doing so may result in electric shock.
The battery's protection board may be damaged due
to a short-circuit.
(for battery replacement)
Risk of explosion if battery is replaced by an incorrect
type.
Not doing so may cause a fire.
Battery pack for; product model: S8BA-B120L.
Do not replace the battery in a place where there is
flammable gas.
Spark may occur when connecting the battery, which
may cause an explosion or fire.
If fluid leaks from the battery, do not touch the fluid.
Doing so may cause blindness or burns.
If the fluid contacts your eyes or skin, wash it out with
lots of clean water and consult your doctor.
Do not disassemble or modify the battery.
A safety mechanism and protection mechanism to
prevent danger are embedded into the battery. If they
are damaged, it may cause an abnormal heating,
smoke, rupture or fire on the battery.
Do not drop the battery and do not expose it to strong
impact.
Doing so may cause a leakage, abnormal heating,
smoke, rupture or fire on the battery. And, if the
battery's protection mechanism is broken, the battery
may be charged at an abnormal current or voltage, an
abnormal chemical reaction may occur inside the
battery, and it may result eventually in an abnormal
heating, smoke, rupture or fire.
Do not short the battery with metal objects.
Doing so could cause an electric shock, fire or burn.
Some electrical energy still remains inside the spent
battery.
Do not dispose of battery in a fire or damage battery.
The insulator inside the battery may melt, the gas
exhaust valve or protection mechanism may be
damaged, or the electrolyte may catch fire, and it may
result eventually in abnormal heating, smoke, rupture
or fire.
Do not use a new battery and an old battery at the same
time.
The battery may be excessively discharged while
being used or excessively charged while being
charged, an abnormal chemical reaction may occur
inside the battery, and it may result eventually in an
abnormal heating, smoke, rupture or fire.
A battery can present a risk of electrical shock and
high short circuit current.
Contact with any part of a grounded battery can result
in electrical shock.
The following precautions should be observed when
working on batteries:
(a) Remove watches, rings, or other metal objects.
(b) Use screwdrivers with insulated handles.
(c) Wear rubber gloves and boots.
(d) Do not lay tools or metal parts on top of batteries.
(e) Remove the connection from ground if any part of
the battery is determined to be grounded.
Dispose of or collect (recycle) the battery according to
your own rules set for that purpose or as instructed by
laws and regulations.
Do not dispose of it in fire. Otherwise, it could explode.
Before using
Charge the battery soon after purchasing the unit.
If not used for a long time after being purchased, the UPS may
become unusable because the characteristics of its battery
become inferior.
Connect the UPS to the input power supply and turn ON the
“Power” switch to charge the battery.
If the UPS is moved from a warm place to a cold place, start using it
after leaving it as-is for a few hours.
If the UPS is suddenly moved to a warm place, water may adhere
to it (condensation). In such a case, if power is supplied without
checking the condition, the UPS may be damaged.
Take measures against the unexpected events such as protecting
data and making the system redundant.
The UPS may stop its power due to failure.
For Connection
Be careful not to let a short-circuit occur between output lines of the
UPS and not to let an output line and the ground be short-circuited (a
ground fault).
Otherwise, the UPS may be damaged.
To transfer or sell the UPS to a third party, attach all the documents
and other accessories contained in the product package to the UPS.
It is supposed that the UPS is to be used in accordance with the
conditions specified in the attached documents.
While Using the UPS
Turn OFF the “Power” switch of the UPS before turning OFF the input
power supply.
When the input power supply is stopped, backup operation starts.
If the frequency of backup operation becomes high, the battery life
may be significantly reduced.
Do not use the UPS for purposes requiring frequent backup operation.
The battery will deteriorate and become unable to last for the
specified backup time.
Precautions for Safe Use
廢電池請回收
S8BA-LF
16
For Storage
To store the UPS for a long time, store it in an environment where the
ambient temperature is 25°C or lower, and charge the battery once
every year for 10 to 15 minutes.
The battery discharges itself even if it is not used. If the battery is
left unused for a long time, it goes into a state of over-discharge. In
such a case, the backup time may become shorter, or the battery
cannot be used anymore.
We recommend an environment where the ambient temperature is
25°C or lower to store the UPS for a long time.
Keep the “Power” switch of the UPS turned OFF during storage.
Do not install or store the UPS in a location exposed to direct sunlight.
The built-in battery may deteriorate rapidly due to an increase in
temperature and become unusable.
Correct Installation Method
For installation, to improve the long time reliability of the UPS, pay
much attention to heat dissipation. Ensure convection of air around
the UPS main body, and use the UPS in an operating condition
below the derating curve.
During machining work for mounting, make sure that no metal
scrap goes into the product.
The heat dissipation of the UPS may become worse depending on
how the UPS is mounted; in rare cases, internal components may
deteriorate and get damaged. Use the UPS in an operating
condition based on the derating curve for each mounting direction.
Standard mounting (Mounting to the DIN rail)
Stationary mounting
Face-up mounting
Incorrect Installation Method
Mounting to the DIN Track
To install devices other than the UPS to both sides, install them by leaving
a space specified by each device off the UPS.
Leave space of 50 mm above and below
Leave space of 50 mm above and below
To mount UPS on floor with its back side away
from you, mount it so that its back side is in contact
with wall.(Because PCB is partially exposed in its
back side, and UPS may be affected by static
electricity for that reason.)
To mount UPS on floor with its top side away from
you, mount it so that its top side is 50 mm or more
off wall.
Mount UPS upside down
DIN Track is placed vertically
S8BA-LF
17
Stationary installation
Battery Replacement
The UPS supports hot swapping. Battery replacement is possible
both when the power is turned OFF (while the power output is OFF)
and when the power is turned ON (while the power output is ON).
For battery replacement, hold down the “Buzzer Pause/Test”
switch on the unit for 10 seconds or longer to activate the battery
replacement mode. When “ ” is displayed, the activation is
completed.
*Activate the battery replacement mode while the “input power
supply” is turned ON.
If you replace the battery without activating the battery
replacement mode, the battery life may not be detected
accurately because the battery life counter is not reset.
Do not replace the battery during backup operation. Otherwise, the
output stops.
The life of the battery used in the UPS is limited. This life changes
depending on the use environment and the frequency of backup
operation.
As the battery life comes closer to its end, the battery deteriorates
more rapidly. Be careful.
The storage condition also affects the deterioration of the battery. As
the storage temperature becomes higher, the battery life becomes
shorter. Be careful.
Battery check schedule and frequency
Applicable directives
EMC Directives
Low Voltage Directives
Principles regarding conformance
OMRON electronic devices that comply with EC Directives also
conform to the related EMC standards so that they can be more easily
built into other devices or the overall machine. The actual products
have been checked for conformity to EMC standards*.
Whether the products conform to the standards in the system used by
the customer, however, must be checked by the customer. EMC-
related performance of the OMRON devices that comply with EC
Directives will vary depending on the configuration, wiring, and other
conditions of the equipment or control panel on which the OMRON
devices are installed. The customer must, therefore, perform the final
check to confirm that devices and the overall machine conform to
EMC standards.
*Applicable EMC (Electromagnetic Compatibility) standards are as
follows: EMS (Electromagnetic Susceptibility): EN 61000-6-2, EMI
(Electromagnetic Interference): EN 61000-6-4, and EN 61000-6-4
Radiated emission: 10-m regulations
Low Voltage Directives
Always ensure that devices operating at voltages of AC 50 to 1,000 V
and DC 75 to 1,500 V meet the required safety standards. The
applicable directive is EN60950-1.
Conformance to EC Directives
This product complies with EC Directives. To ensure that the machine
or device in which the this product is used complies with EC
Directives, the product must be installed as follows:
This product must be installed within a control panel.
You must use reinforced insulation or double insulation for the
direct power supply equipment connected to this product.
Models of this product that comply with EC Directives also conform
to the Common Emission Standard. Radiated emission
characteristics (10-m regulations), in particular, may vary
depending on the configuration of the control panel used, other
devices connected to the control panel, wiring, and other
conditions. Therefore, even when using a model of this product
that complies with EC Directives, you must confirm and ensure the
compliance to EC Directives of the entire machine or equipment.
This is a Class A product (for industrial environments). In a
residential environment, it may cause radio interference. If radio
interference occurs, the user may be required to take appropriate
measures.
Precautions for Correct Use
Do not stackDo not mount on floor with
front side down
To mount UPS on floor with its top side away
from you, ensure that its top side is not in
contact with wall.
Ambient
temperature 6-Month Inspection 3-Month Inspection
55°C Up to 1 year from the
date of purchase
1 year from the date
of purchase and
afterward
50°C Up to 1.5 years from
the date of purchase
1.5 years from the
date of purchase and
afterward
40°C Up to 3 year from the
date of purchase
3 years from the date
of purchase and
afterward
25°C Up to 6 year from the
date of purchase
6 years from the date
of purchase and
afterward
Conformance to EC Directives
S8BA-LF
18
Conformance to UL
This product must be installed within a control panel with an
internal heater or other unit to protect against the formation of
condensation.
Gaps in the door to the control panel must be completely filled or
covered with gaskets or other material.
For use as a UL compliant device, the specifications for S8BA-
24D24D480LF become as follows:
Maximum input current: 20 A
Rated output current/capacity: 16.7 A/400 W
For use in Pollution Degree 2 Environment.
Surrounding Air Temperature, 55°C.
Make sure to connect the device with Class 2 output to the USB
port.
FCC CAUTION
Changes or modifications not expressly approved by the party
responsible for compliance could void the user’s authority to operate
the equipment.
This equipment has been tested and found to comply with the limits
for a Class A digital device, pursuant to part 15 of the FCC Rules.
These limits are designed to provide reasonable protection against
harmful interference when the equipment is operated in a
commercial environment.
This equipment generates, uses, and can radiate radio frequency
energy and, if not installed and used in accordance with the
instruction manual, may cause harmful interference to radio
communications.
Operation of this equipment in a residential area is likely to cause
harmful interference in which case the user will be required to
correct the interference at his own expense.
Conformance to UL
Conformance to FCC
Conformance to KC
19
Uninterruptible Power Supply (UPS) Separated battery type
S8BA-SBF
DC-DC type small UPS mounts on a
DIN rail to provide an ideal
countermeasure for momentary
power losses and power failures in
industrial computers (IPC) and
controllers.
System reliability greatly improved because 24VDC power
supply is backed up for a certain period of time in the event
of voltage drop or power failure.
Compactness, weight reduction, and long battery life
realized thanks to the adoption of a lithium-ion battery.
Push-in terminal block adopted for the power input and
output I/F.
Shutdown in conjunction with the industrial purpose
computer (IPC) or controller realized by the USB/RS-
232C/I/O port installed in the UPS.
Two types of batteries are selectable for the 480W, allowing the ideal backup time to be realized
A wide lineup culminating in the 960W makes it possible to provide long-lasting backup for every type of industrial
controller
Model Number Structure
Model Number Legend * Use the following format to place an order.
The control unit and battery unit are separate, and the battery unit is sold separately.
Control unit part
Battery unit part
!Refer to Safety Precautions on page 33.
2 31
Series name
S8BA-
@@@@@@@@@SBF
1.
Input voltage specification
2.Output voltage 3.Capacity
Code Input voltage
specification Code Output voltage Code Capacity
24D 24 VDC 24D 24 VDC 480 480 W
960 960 W
1.Battery type 3.Terminal block shape
Code Type Code Terminal block
shape
SSeparated
battery type 480 480 W
960 960 W
21
Series name
S8BA-
@@@@L
S8BA-SBF
20
Ordering Information
Main body
Uninterruptible Power Supply (UPS) / Control Unit Part
Note: The control unit (960 W) and the battery unit (480 W) cannot be connected.
Battery unit part
Note: The control unit (960 W) and the battery unit (480 W) cannot be connected.
Communication cable
Input voltage Output voltage Output current/capacity Model number
24 VDC 24 VDC 20 A/480 W S8BA-24D24D480SBF
40 A/960 W S8BA-24D24D960SBF
Rated voltage Rated capacity Weight Model UPS Model : Required units
25.2 VDC 3900 mAh 1.5 kg S8BA-S480L S8BA-24D24D480SBF
25.2 VDC 7800 mAh 2.5 kg S8BA-S960L S8BA-24D24D960SBF
Specifications Type Length Model number
For RS-232C port RJ45/Dsub9Pin 2 m S8BW-C01
For CONTACT port RJ45/Discrete wire S8BW-C02
S8BA-SBF
21
Ratings, Characteristics, and Functions
Description Capacity 480 W 960 W
DC input
Rated input voltage 24 VDC
Input voltage range 23 to 28 VDC
Input
maximum
current
for rated input voltage
for rated loads connected 21.5 A 43.5 A
Input terminal Push-in terminal block
Input protection Fuse (cannot be replaced by the customer)
Input protection capacity 30 A 60 A
DC output
Rated
current for rated output voltage 20 A 40 A
Switching time Uninterrupted
Output
voltage
Normal operation Input voltage through output
Backup operation 21 to 28 V (the voltage cannot be adjusted)
Output terminal Push-in terminal block
Overload
protection
Warning display
UPS output will
continue through
bypass [during normal
operation]
UPS output will continue
through battery [during
backup operation]
101% or more
Output stopped by
overload protection
Stop output [during
normal operation]
The internal power
supply to the UPS will
stop after 10 sec. [during
backup operation]
111% or more
Warning display
cancellation (During
normal operation, during
backup operation)
93% or more
Battery unit
Type Lithium-ion battery
Rated voltage 25.2 VDC
Rated capacity 3900 mAh 7800 mAh
Battery life expectancy *1 10 years (25°C), 6.7 years (35°C), 3.7 years (45°C), 1.9 years (55°C)
Replacement by user Yes (Hot swapping)
Battery Life Counter Function Yes
Charging time 8 hours (90%) *3
Backup time (25°C, initial
characteristics)
6 min. (constant power rated load)
The backup time can be set from the mode selection / backup operation time selection switch, or the
shutdown software.
Environme
nt
Operating environment temperature /
humidity 0 to +55°C / 10 to 90%RH with no condensation
Storage environment temperature /
humidity 20 to +55°C / 10 to 90%RH with no condensation
Vibration resistance
JIS C 60068-2-6 compliant
5 to 8.4 Hz amplitude: 3.5 mm, 8.4 to 150 Hz
acceleration rate: 9.8 m/s2 X, Y, and Z directions: 100 min.
(Sweep time: 10 min.×Sweep count 10 times=Total: 100 min.)
Shock resistance JIS C 60068-2-27 compliant: 147 m/s2 X, Y, and Z directions three times
Structure
Dimensions (W×H×D mm) *2 44 × 124 × 111.4 (UPS control unit 20 A)
80 × 124 × 111.4 (battery unit 20 A)
52 × 124 × 111.4 (UPS control unit 40 A)
150 × 124 × 111.4 (battery unit 40 A)
Weight Weight of control unit Approx. 0.6 kg Approx. 0.7 kg
Weight of battery unit Approx. 1.5 kg Approx. 2.5 kg
Cooling method Natural cooling
Dielectric
breakdown
voltage
Withstand voltage DC external terminals to casing: 510 V AC, 1 minute, leakage current 5 mA max.
Insulation resistance DC external terminals to casing: 20 MΩ or more. (500 V DC)
Standard
compliance
Safety standard UL508 / CE / C22.2 No. 107.1-01
EMI Radiation disturbance
field strength EN61000-6-4 / FCC / ICES / RCM / KC / EAC
Internal power consumption
(normal *4 / maximum *5) 7 W / 29 W 15 W / 58 W
Serial
communica
tion
RS-232C (Interface terminal)
Yes (RJ45)
USB (Interface terminal)
I/O signal (Interface terminal) Yes (RJ45)
Accessories USB cable (2.2 m) (included with control unit)
Battery connection cable (included with battery unit)
S8BA-SBF
22
*1. Guideline for a standard installation. Not a guaranteed value.
*2. Unit dimensions excluding the DIN rail stopper.
*3. When using in an environment at a high temperature, charging may be paused by charging temperature protection, then the charging time will
be longer than specified time.
*4. Conditions: With rated loads connected, at a rated input voltage, and at a full battery charge.
*5. Conditions: With rated loads connected, at a rated input voltage and at maximum battery charging current.
Accessory functions Remote ON/OFF signal logic setting; Battery life counter setting; Maximum backup time setting; Startup
battery level setting; Backup stop (BS) signal delay time setting; and Backup (BU) signal delay time setting
Description Capacity 480 W 960 W
S8BA-SBF
23
Nomenclature
Front view
S8BA-24D24D480SBF S8BA-S480L
S8BA-24D24D960SBF S8BA-S960L
(1)
(2)
(3)
(4)
(5)
(7)
(8)
(6)
Positive terminal
[DC ON] LED
[BATT] LED
[ALERT] LED
Negative terminal (3)
(6)
No. Name No. Name
(1) DC input terminal block (5) CONTACT port
(2) DC output terminal block (6) Battery communication port
(3) Battery connection terminal block (7) Mode selection / Backup time setting switch
(4) LED indicators (8) RS232C / USB port
[DC ON] LED
[BATT] LED
[ALERT] LED
Positive terminal
Negative terminal
(1)
(4)
(2)
(3)
(5)
(7)
(8)
(6)
(3)
(6)
No. Name No. Name
(1) DC input terminal block (5) CONTACT port
(2) DC output terminal block (6) Battery communication port
(3) Battery connection terminal block (7) Mode selection / Backup time setting switch
(4) LED indicators (8) RS232C / USB port
S8BA-SBF
24
Rear view
S8BA-24D24D480SBF S8BA-S480L
S8BA-24D24D960SBF S8BA-S960L
(9)
(9)
No. Name
(9) DIN rail hook
(9)
(9)
No. Name
(9) DIN rail hook
S8BA-SBF
25
Connections
Block Diagrams
S8BA-24D24D@@@SBF
Note: 1. In normal operation, 24 VDC is output as-is for charging the battery and from the input power supply.
If the 24 VDC from the input power supply becomes lower, the operation automatically switches to backup operation, and 24 VDC is
output from the battery.
Input and output voltage time chart when shifting to backup operation
Connecting a cable to the input terminal block and the output terminal block
For details about the connectable sizes and recommended cable sizes, see the following table.
20 A 40 A
Connectable sizes Cable
Solid wire 0.2 to 10 mm2
0.75 to 16.0 mm2
Stranded wire 0.2 to 6 mm2
AWG AWG 8 to 24 AWG 6 to 18
Stripped cable length 8 to 10 mm 18 mm
Recommended sizes
Solid wire /
Stranded wire 2.0 mm28.0 to 14.0 mm2
AWG AWG 12 AWG 6 to 8
Temperature rating for recommended cable 90°C
24 VDC
Control unit
Battery unit
Input
24 VDC
Normal operation: OFF
Backup operation: ON
Output
Battery
Normal operation
Backup operation
FET
Normal operation: ON
Backup operation: OFF
FET
Charge
Normal operation: ON
Backup operation: OFF
FET
powerfailureorinputvoltagedrop
28V
21V
24VDC
22VDC
Outputvoltage
Inputvoltage
18VDC
DCvoltage
S8BA-SBF
26
I/O signal functions
Type of output signals
Type of input signals
*BS signal delay time
It is possible to set the period of time from when a BS signal is received until the output of the UPS is stopped. The output of the UPS can be
stopped by inputting the voltage signal (High).
I/O signal port (RJ45 connector)
Contact signal ratings
Signal Description
Backup signal output (BU) Stays ON during backup operation at a power failure.
Low battery level signal output (BL) Goes ON when the battery becomes weak during backup operation at a power failure.
Trouble signal output (TR) Goes ON when an internal failure of the UPS occurs or when the battery life counter expires.
Battery replacement signal output (WB) Goes ON when the test determines that battery replacement is necessary due to deterioration
or when the battery life counter goes off-scale. (The battery life counter goes on counting during
the input power is being supplied.)
Signal Description
Input of the UPS stop signal (BS) When the BS signal is ON (High), the output of the UPS is stopped after the time period specified
in advance has elapsed.*
Remote ON/OFF signal
Remote ON/OFF signals can be used to start and stop the UPS, by using either an externally
connected contact or the ON/OFF status of the open collector circuit. When signal is OFF, the
UPS will be turned on. When signal is ON, the UPS will be turned off.
In the factory settings, the UPS stops operation when this is short-circuited.
You must connect the unit to the input power supply to be able to use this function.
Outlook of the connector Pin number Cable color Item
1 White/orange Backup signal output (BU)
2 Orange Remote ON/OFF input (-)
3 White/green Trouble signal output (TR)
4 Blue COMMON (COM)
5 White/blue Battery LOW signal output (BL)
6 Green Backup stop signal input (BS)
7 White/brown Battery Replacement Signal output (WB)
8 Brown Remote ON/OFF input (+)
Signal Description
Signal output (BL, TR, BU, WB)
Applicable voltage: 50 VDC or less
Maximum current: 500 mA
BU signal min. response time: 10 ms
Remote ON/OFF
Voltage between terminals: 3.3 VDC
Current when closed: 10 mA max.
Min. signal response time: When stopped 100 ms
When restarting 300 ms
UPS Stop Signal input (BS)
Input voltage: HIGH (ON) 8 to 24 VDC
LOW (OFF) 0.5 VDC or less
Input current: 250 mA
Min. signal response time: When stopped 100 ms
When restarting 300 ms
Pinnumber1Pinnumber8
S8BA-SBF
27
Contact signal circuit
Precautions when selecting switch mode power supplies
When selecting switch mode power supplies, install devices with a capacity larger than the total of the UPS internal power consumption and internal
power consumption of connected devices to the input side of the UPS. When these conditions are met, usage will be possible with no problems
even if the rated capacity of the UPS is larger than the rated capacity of the switching power supply.
Switch mode power supply capacity > (UPS internal power consumption + Internal power consumption of connected devices)
(Ex.)
Signal output (BU, TR, BL, WB) Remote ON/OFF
UPS Stop Signal input (BS)
Switch mode power supply
(Capacity: 92 W or more) >
(
UPS
(Internal power consumption: 29 W) +Industrial-purpose computers (IPC)/controllers, etc.
(Internal power consumption: 70 W, DC input)
)
S8BA
(Capacity: 480 W)
BL
TR
BU
WB
BS
COM
100 Ω
3.3 V
220 Ω
Remote ON/OFF (+)
Remote ON/OFF (–)
S8BA-SBF
28
Engineering Data
Estimated backup time
The backup time varies depending on the capacity of connected devices.
After calculating the total capacity of connected devices, refer to the graph of the backup time to obtain an estimation of the initial value of the
backup time. (This is also applied to checking the battery.)
1. Convert the total capacity (power consumption) of the connected devices to watts (W).
For the indication of connected devices, check your computer and the rear of the display.
The indicator can show values in two different ways: amperes (A), and watts (W).
Example 1: 24 VDC, 145 W
Example 2: 24 VDC, 1.8 A
For devices that use the A indication, convert the capacity into W.
Example 2: 1.8 (A) = 1.8 × 24 (W) = 43.2 (W)
2. Add the values converted into W to obtain the total capacity of the connected devices.
3. Calculate the initial value of the backup time for the total capacity of the connected devices from the graph below.
Graph of backup time (graph of initial values for products that have not been used at 25°C). The backup time becomes shorter than the graph
(table) below when temperature is lower.
The smaller the capacity of connected devices becomes, the longer the backup time becomes.
Note: These backup times are for reference only. Times may vary according to battery life and external environmental conditions (temperature,
etc).
Indication Value
A W = A × 24
Model Capacity (Watt)
30 60 90 120 180 240 300 360 420 480 540 600 660 720 780 840 900 960
480W
(S8BA-24D24D480SBF
+
S8BA-S480L)
134 63 41 29 19 15 11 9 8 6 --- --- --- --- --- --- --- ---
480W
(S8BA-24D24D480SBF
+
S8BA-S960L)
290 138 94 66 43 30 24 20 16 14 --- --- --- --- --- --- --- ---
960W
(S8BA-24D24D960SBF
+
S8BA-S960L)
2901389466433024201614131211109876
0
40
80
120
160
200
240
280
320
0 60 120 180 240 300 360 420 480 540 600 660 720 780 840 900 960 1020
S8BA-24D24D960SBF
+
S8BA-S960L
S8BA-24D24D480SBF
+
S8BA-S960L
S8BA-24D24D480SBF
+
S8BA-S480L
Backup time (Minutes)
Capacity (W)
S8BA-SBF
29
Derating curve
Backup operation sequence in the event of power failure/voltage drop (instantaneous voltage drop)
When the input power supply recovers while the battery level is sufficiently high
*For details, refer to I/O signal functions on page 26.
When the input power supply recovers while the battery level is Low
*For details, refer to I/O signal functions on page 26.
Standard mounting (15 mm or more space
between the left and right) Contact mounting (Less than 15 mm
space between the left and right)
0 10 20 30 40 50 60
100
80
60
40
20
0
Ambient temperature (°C)
Load rate (%)
0 10 20 30 40 50 60
100
80
60
40
20
0
Ambient temperature (°C)
Load rate (%)
Durling power failure
Input power supply
Battery restorage
Output from UPS
UPS
operating
mode
BU signal (OUT)
BL signal (OUT)
BS signal (IN)
Normal operation
Backup operation
ON
ON
OFF
OFF
OFF
OFF
High
Low
Empty
OFF
ON
ON
ON
ON
ON
OFF
OFF
OFF
OFF
High
Low
Empty
OFF
ON
ON
ON
Durling power failure
Input power supply
Output from UPS
UPS
operating
mode
BU signal (OUT)
BL signal (OUT)
BS signal (IN)
Normal operation
Backup operation
Battery restorage
S8BA-SBF
30
When the input power supply does not recover until the battery becomes empty
*For details, refer to I/O signal functions on page 26.
Overcurrent protection curve
480 W/960 W
Durling power failure
Input power supply
Output from UPS
UPS
operating
mode
Normal operation
Backup operation
BU signal (OUT)
BL signal (OUT)
BS signal (IN)
Battery restorage
ON
ON
OFF
OFF
OFF
OFF
High
Low
Empty
OFF
ON
ON
ON
0
20
40
60
80
100
0 20 40 60 80 100 120
111%
Load ratio (%)
Output voltage (%)
S8BA-SBF
31
Dimensions (Unit: mm)
Control unit
Battery unit
S8BA-24D24D480SBF
124
9.5
31
99.4
44 111.4
S8BA-24D24D960SBF
9.5
52
124
111.4
31
99.4
111.4 9.5
30.7
80
124
99.4
S8BA-S480L
111.4 9.5
150
124
30.7
99.4
S8BA-S960L
S8BA-SBF
32
DIN Rail (Order Separately)
Mounting Rail (Material: Aluminum)
PFP-100N
PFP-50N
Mounting Rail (Material: Aluminum)
PFP-100N2
End Plate
PFP-M
Note: 1. If there is a possibility that the Unit will be subject to vibration or shock, use a steel DIN Rail. Otherwise, metallic filings may result from
aluminum abrasion.
2. If the Unit may be subjected to sliding to either side, attach an End Plate (model PFP-M) on each side of the Unit.
Power management solutions
The following software is available as a free download from our website.
Name Description Conditions Interface
Power Attendant
Lite
You can execute computer shutdown and UPS auto stop
when an input power problem occurs (power failure, etc.).
You can use a computer that has "Power Attendant Lite"
installed to send a script over the network to devices that do
not have shutdown software installed to log in to each device
and execute a device shutdown command.
You can automatically start and stop computers and the
UPS according to a preset schedule.
Windows 10 / 8.1 / 8 / 7
Windows Server 2016
Windows Server 2012 R2 / 201208
Windows Storage Server 2008
Windows Storage Server 2016
Windows Storage Server 2012 R2 / 2012
Windows Storage Server 2008 R2 / 2008
RS232C
USB
Simple Shutdown
Software
You can execute computer shutdown and UPS auto stop
when an input power problem occurs (power failure, etc.).
You can modify and recompile the source code to
incorporate a UPS management function into your Windows/
Linux system.
Supports Windows and Linux
<For Windows>
Windows 10 / 8.1 / 8 / 7
Windows Server 2012 R2 / 2012
Windows Server 2008 R2 / 2008
Windows Server 2003R2 / 2003
Windows Vista / XP
Windows 10 IoT Enterprise LTSB
Windows Embedded Standard 7
<For Linux>
Red Hat Enterprise Linux Ver.7.x
CentOS Ver.7.x
RS232C
USB
Setting Utility
This software is used to configure UPS settings.
(Setting item examples)
Function for sending commands
Function for saving settings to a backup file
Function for restoring settings from a backup file
Function for reading UPS settings
Function for returning UPS settings to default settings
Windows 10 / 8.1 / 8 / 7
Windows Server 2012 R2 / 2012
Windows Server 2008 R2 / 2008
Windows Server 2003R2 / 2003
Windows Vista / XP
Windows 10 IoT Enterprise LTSB
Windows Embedded Standard 7
RS232C
USB
4.5
15 25 25
10 10
1,000 (500) *
25 25 15(5) *
35±0.3
7.3±0.15
27±0.15
1
* Values in parentheses are for the PFP-50N.
4.5
15 25 25
10 10
1,000
25 25 15 1 1.5
29.2242735±0.3
16
1.3
4.8
35.5 35.3
1.8
1.8
10
6.2
1
50
11.5
10
M4 spring washer
M4×8 pan-
head screw
S8BA-SBF
33
Safety Precautions
Warning Indications
Meaning of Product Safety Symbols
(for use of this product)
Provide safety measures outside the UPS to ensure
safety in the entire system even if the UPS is damaged
or an abnormality occurs due to an external factor. Not
doing so may result in serious accidents due to
incorrect operation.
(Wiring)
Do not short between the connector terminals.
Doing so may result in electric shock.
The battery unit's protection board may be damaged
due to a short-circuit.
Connect each connection cable to the correct
connected device.
Connect the terminal of each connection cable to the connector
port with correct polarity.
Be sure to follow the connection procedure described in User's
Manual (NUD-D18006A)
(When replacing the battery unit)
Dispose of or collect (recycle) the battery unit according
to your own rules set for that purpose or as instructed by
laws and regulations.
Do not dispose of it in fire. Otherwise, it could explode.
(for installation and connection)
Pay attention to the weight and balance when carrying
the unit, and install it in a solid and stable location.
Do not drop the battery unit and do not expose it to
strong impact. Dropping the unit may result in injury or
fire.
If you drop the unit, have it inspected and repaired. For
repairs, contact our sales personnel.
Keep plastic package bags out of reach of children.
Children may suffocate if they place their heads into
plastic bags.
Be sure to connect the input power supply of the unit to a
DC power supply device having a rated voltage (24
VDC), or a battery power feed system.
The input voltage ranges for the UPS are as shown
below. Check that the output voltage of the DC power
supply device connected to the input terminal of the UPS is within
any of the voltage ranges below.
Voltage range: 23 to 28 V DC
Connecting to a DC or AC power supply device with a different
voltage may result in malfunction in or damage to the UPS, or
cause a fire.
When an abnormality (unusual sound or smell) occurs,
turn OFF the unit’s ‚”Power‚” switch to stop the output,
and stop the supply of commercial power.
To make an emergency stop, move the rotary switch to
"BATT REP", and when the LED changes from a fast blink to a slow
blink, shut off the input power.
When performing maintenance on the connected devices, follow
the above instructions to ensure safety.
When installing the input cable, make sure to perform the
connection as specified.
Make sure to stop the primary power supply before
connecting the unit to the input power supply terminal.
When connecting a cable to the terminal block, use a
cable that complies with the input current specification
of the UPS. Failure to do so may result in electric
shock or ground fault.
Do not disassemble, repair, or modify the unit.
Doing so may cause an electric shock or a fire.
Do not install the unit in other than specified orientations.
Dropping or toppling the unit may cause injury.
If you install the unit in an orientation other than
specified, the internal temperature may rise,
eventually damaging the UPS or deteriorating the battery.
Warning
Indicates a potentially hazardous
situation that, if not avoided, could
result in serious injury or death.
Additionally there may be significant
property damage.
Caution
Indicates a potentially hazardous
situation that, if not avoided, could
result in minor or moderate injury or
property damage.
Precautions for
Safe Use
Supplementary comments on what to
do or avoid doing, to use the product
safely.
Precautions for
Correct Use
Supplementary comments on what to
do or avoid doing, to prevent failure to
operate, malfunction or undesirable
effect on product performance.
General inhibition
Notice prohibiting an unspecified general action.
General instruction
Notice instructing an unspecified general action.
Do-not-disassemble prohibition
Notice prohibiting disassembly because
disassembling the device may cause such an
accident as an electric shock.
Prohibition of use in locations subject to water
such as a bathroom and shower room
Notice prohibiting installation of the device in
locations subject to water, because if a device not
made water-proof is used in such locations, injury
may occur due to an electric leak.
Do-not-touch prohibition
Indicates the possibility of injuries by touching
the specific portion of the device under specific
conditions, prohibiting touching of the device.
Explosion alert
Notice alerting the user to the possibility of
explosion under certain conditions.
Warning
Caution
廢電池請回收
S8BA-SBF
34
Do not use the unit at a location where the operating
environment temperature is more than 55°C
The battery deteriorates rapidly. It may result in fire.
If the battery's resin separator is damaged, the battery
may be short-circuited inside, and may cause an
abnormal heating, smoke, rupture or fire.
Doing so may cause a failure or malfunction of the unit.
Do not exceed the ranges specified for environmental
conditions during use/storage.
Do not install or store the unit in the places listed below.
Do not store in places where the humidity is lower than
10% or higher than 90%.
Do not use the unit in places where the ambient
temperature is lower than 0°C or higher than 55°C.
(With no condensation)
Do not use in places where the humidity is lower than
10% or higher than 90%.
Do not install/store the unit in closed places such as
cabinets with no clearance, places where there is
flammable or corrosive gas, places with large amounts
of dust, places exposed to direct sunlight, places
exposed to shock or vibration, salty or wet places, or
outdoors.
Installation or storing the unit in such a place may
cause a fire.
When you use plug strip and other plugs to connect
additional devices, do not connect devices that exceed
the current capacity of the available plugs.
The current protection of the unit may operate, which
may stop the output.
The cable heats up, which may cause a fire.
Do not use a cable with damaged insulation.
Do not pinch or sharply bend the cable.
Do not fold or knot the cable.
Doing so may cause the cable to be damaged or
heated, which may cause an electric shock or a fire.
If the cable is damaged, stop using the unit and have the cable
repaired.
For repair, contact our sales personnel.
Do not connect any devices other than rated voltage is 24
VDC.
The rated output voltage of this unit is 24 VDC.
Overvoltage or overcurrent may damage the
connected devices.
The output voltage range is 22 to 30 VDC.
All of the included accessories are designed to be used
with the unit. Do not use the accessories with other
devices.
Doing so may compromise the safety of devices.
When this product is used in compliance with CE
marking, please use under 2 m communication cable.
Do not block the air vents (upper and lower).
Doing so will cause the internal temperature to rise,
which may cause the unit to fail and the battery to
deteriorate.
During installation, leave a space of 50 mm or more
above the top and below the bottom.
Do not connect the RS232C/USB port or the CONTACT
port to a LAN device using a LAN cable.
Connection to a LAN device may result in malfunction
in or damage to the UPS or the LAN device.
Do not run this unit in parallel.
Operating this unit in parallel may cause a failure or
malfunction.
(for use)
Do not allow the unit to come in contact with water.
Doing so may cause an electric shock or a fire.
Doing so may cause an abnormal heating, smoke,
rupture, or fire on the battery.
If the unit comes in contact with water, immediately
stop using it and have it inspected and repaired. To
make an emergency stop, turn the rotary switch to
"BATT REP" and turn off the input power after the LED
changes from fast blinking to slow blinking.
For repair, contact our sales personnel.
When the battery unit is dead, replace it immediately or
stop using the unit.
Continuing the use of it may cause fire or electric
shock due to liquid leaks.
*The values in the table are the expected life under
standard use conditions and are not guaranteed.
Occasionally, wipe off dust on the input terminal block
and the output terminal block with a dry cloth.
Accumulated dust may cause a fire.
Before wiping off dust, stop all connected devices and
the unit, and stop the supply of commercial power.
The unit will stop after 30 seconds of setting the mode selection/
backup operation time selection switch to "0.5".
Do not use the unit in a closed place and do not cover the
unit.
Doing so may cause abnormal heating or a fire.
If you notice something unusual such as abnormal sound
or smell, discoloration, deformation, and heating, turn
OFF the unit's power and stop the supply from the input
power supply.
To make an emergency stop, move the rotary switch to
"BATT REP", and when the LED changes from a fast
blink to a slow blink, shut off the input power.
Using the unit under such conditions may cause an
abnormal heating, rupture or fire.
If you notice such a condition, stop using the unit and
contact our sales personnel for inspection and repairs.
If fluid leaks from the interior, do not touch the fluid.
Doing so may cause blindness or burns.
If the fluid contacts your eyes or skin, wash it out with
lots of clean water and consult your doctor. The fluid
may damage your eye if your eye is left untreated.
Do not place any objects on the unit, and do not drop
heavy objects onto the unit.
Doing so may cause distortion/damage to the case or
a failure of the internal circuit, which may cause a fire.
Ambient temperature Expected life
25°C 10 years
35°C 6.7 years
45°C 3.7 years
55°C 1.9 years
S8BA-SBF
35
The unit is equipped with an output circuit that can supply
power to the connected devices even if the unit stops due
to a failure or mis-operation of the internal circuit function.
If you want to stop the output, stop the source of the “input
power supply”.
Output is continuing even when all indicators of the
front panel are off.
When charging the battery, if the battery cannot be
charged completely even after the predetermined
charging time, turn OFF the "Power" switch of the unit to
stop charging the battery.
The unit will stop after 30 seconds of setting the mode
selection/backup operation time selection switch to "0.5".
Otherwise, it may cause an abnormal heating, smoke, rupture or
fire on the battery.
(for maintenance)
When performing maintenance of the connected
equipment, turn OFF the unit's power and stop the supply
from the input power supply.
The unit will stop after 30 seconds of setting the mode
selection/backup operation time selection switch to "0.5".
Even if the input power supply is stopped in the
operating state, the power supply output of the unit will not stop,
and power will be supplied from the battery.
Do not disassemble, repair, or modify the unit.
Doing so may cause an electric shock or a fire.
If fluid leaks from the interior, do not touch the fluid.
Doing so may cause blindness or burns.
If the fluid contacts your eyes or skin, wash it out with
lots of clean water and consult your doctor.
Do not throw the unit into fire.
Since the battery is incorporated in the unit, the
insulator may melt, the gas exhaust valve or protection
mechanism may be damaged, or the electrolyte may
catch fire, and it may result eventually in an abnormal
heating, smoke, rupture or fire.
Do not insert metal objects into the input terminal block
and the output terminal block of the UPS.
Doing so may result in electric shock.
Do not insert metal objects into the battery connectors.
Do not short between the connector terminals.
Doing so may result in electric shock.
The battery unit's protection board may be damaged
due to a short-circuit.
(for battery replacement)
Do not use other than the designated battery unit.
Not doing so may cause a fire.
Product model: S8BA-S480L, S8BA-S960L
Do not replace the battery unit in a place where there is
flammable gas.
Spark may occur when connecting the battery unit,
which may cause an explosion or fire.
If fluid leaks from the battery unit, do not touch the fluid.
Doing so may cause blindness or burns.
If the fluid contacts your eyes or skin, wash it out with
lots of clean water and consult your doctor.
Do not disassemble or modify the battery unit.
A safety mechanism and protection mechanism to
prevent danger are embedded into the battery unit. If
these are damaged, it may cause the battery to emit
heat, smoke, explode, or catch fire.
Do not drop the battery unit and do not expose it to strong
impact.
Dropping the unit may result in injury or fire.
Doing so may cause a leakage, abnormal heating,
smoke, rupture or fire on the battery unit. And, if the
battery unit's protection mechanism is broken, the
battery may be charged at an abnormal current or
voltage, an abnormal chemical reaction may occur
inside the battery, and it may result eventually in an
abnormal heating, smoke, rupture or fire.
Do not short the battery unit with metal objects.
Doing so could cause an electric shock, fire or burn.
Some electrical energy still remains inside the spent
battery unit.
Do not dispose of battery units in a fire.
The insulator inside the battery unit may melt, the gas
exhaust valve or protection mechanism may be
damaged, or the electrolyte may catch fire, and it may
result eventually in abnormal heating, smoke, rupture
or fire.
S8BA-SBF
36
Before using
The battery has not been charged at the time of purchase. Be sure
to charge it before use.
Connect this unit to the input power supply to charge the battery
unit.
When moving the unit from a cold place to a warm place, leave it for
several hours before using it.
If the unit is promptly turned ON after being moved to a warmer
place, condensation may form inside the unit and cause it to fail.
Take measures for handling unforeseen accidents, such as data
backup and system redundancy.
The output may stop when there is failure in this unit.
Connecting
Do not short the unit output lines together, and do not short the battery
connection cable (to ground).
The unit may fail.
In the event you transfer or sell this unit to a third party, please include
all of the documentation that came with the unit. This is to ensure that
the unit is used in line with the conditions described in the included
documentation.
Using
Before stopping the commercial power to the unit, turn OFF the
“Power” switch of the unit.
The unit will stop after 30 seconds of setting the mode selection/
backup operation time selection switch to "0.5".
The unit enters Battery Mode when input power supply is stopped.
If the frequency of backup operation becomes high, the battery life
may be significantly reduced.
Do not use for an application that frequently requires Battery Mode.
The battery unit will deteriorate and fail to maintain the specified
backup time.
If you want the UPS to stand by in a UPS startup state, set 3 months
or less for the input power supply stop period.
The UPS startup state means the state of waiting for startup
triggered by a remote ON/OFF or BS signal.
If the UPS is left unused in the above state for 3 months or longer,
the battery goes into overdischarge state, and the backup time
may become shorter or the battery may become unusable.
Storing
Storing the battery in UPS for a long term, store at an environment
less than 25°C and recharge 15 to 30 minutes the battery within 1
year.
The battery self-discharges even when it not being used, and it
goes into overdischarge state if it is left for a long period of time.
The backup time may become shorter or the battery may become
unusable.
We recommend keeping the temperature 25°C or less when
storing the unit for long periods of time.
Turn OFF the unit’s power when storing it.
Do not install or store the unit in a place exposed to direct sunlight.
The rise of temperature may cause the battery unit to deteriorate
rapidly and become unusable.
Correct Installation Method
For installation, to improve the long time reliability of the UPS, pay
much attention to heat dissipation. Ensure convection of air around
the UPS main body, and use the UPS in an operating condition
below the derating curve.
During machining work for mounting, make sure that no metal
scrap goes into the product.
The heat dissipation of the UPS may become worse depending on
how the UPS is mounted; in rare cases, internal components may
deteriorate and get damaged. Use the UPS in an operating
condition based on the derating curve for each mounting direction.
Standard mounting
Note: 1. This UPS can be mounted with the sides in close contact.
Up to 3 units can be mounted in close contact.
Follow the derating curve during mounting with the sides in
close contact.
2. When you install devices other than the UPS on the left or
the right of the UPS, leave a space of at least 15 mm.
Face-up mounting
Precautions for Safe Use
Leave 50 mm of space between the upper and lower.
Leave 50 mm of space between the upper and lower.
S8BA-SBF
37
Incorrect Installation Method
Mounting to the DIN Track
Battery unit Replacement
The UPS supports hot swapping. Battery unit replacement is possible
both when the power is turned OFF (while the power output is OFF)
and when the power is turned ON (while the power output is ON).
When replacing the battery unit, set the unit to "BATT REP"
(Battery unit replacement mode) using the mode selection / backup
operation time selection switch.
(Perform a reset with the “input power supply” ON.)
When you replace the battery, the battery life counter automatically
resets.
If you replace the battery unit without activating the battery unit
replacement mode, the battery life may not be detected accurately
because the battery life counter is not reset.
Do not replace the battery unit while the UPS is operating in
backup mode. Output will stop.
For details on the precautions for maintenance, refer to (for
maintenance) on page 35 and (for battery replacement) on page
35.
If an input power supply error such as a power failure occurs when
replacing the battery unit while in operation, backup cannot be
performed and output stops.
The battery unit used in the unit has a limited lifespan. The life
varies depending on your use environment and backup frequency.
The nearer the end of the life is, the more rapidly deterioration
proceeds.
The battery unit deteriorates even if it is stored. The higher the
temperature is, the shorter the life becomes.
Do not short between the terminals.
Doing so may result in electric shock.
The protection board inside the battery unit may be damaged due
to a short-circuit.
Connect each connection cable to the correct connected device.
Connect the terminal of each connection cable to the connector
port with correct polarity.
Be sure to follow the above connection procedure.
Battery check schedule and frequency
Applicable directives
EMC Directives
Low Voltage Directives
Principles regarding conformance
OMRON electronic devices that comply with EC Directives also
conform to the related EMC standards so that they can be more easily
built into other devices or the overall machine. The actual products
have been checked for conformity to EMC standards*.
Whether the products conform to the standards in the system used by
the customer, however, must be checked by the customer. EMC-
related performance of the OMRON devices that comply with EC
Directives will vary depending on the configuration, wiring, and other
conditions of the equipment or control panel on which the OMRON
devices are installed. The customer must, therefore, perform the final
check to confirm that devices and the overall machine conform to
EMC standards.
*Applicable EMC (Electromagnetic Compatibility) standards are as
follows: EMS (Electromagnetic Susceptibility): EN 61000-6-2, EMI
(Electromagnetic Interference): EN 61000-6-4, and EN 61000-6-4
Radiated emission: 10-m regulations
Low Voltage Directives
Always ensure that devices operating at voltages of AC 50 to 1,000 V
and DC 75 to 1,500 V meet the required safety standards. The
applicable directive is EN60950-1.
Precautions for Correct Use
Bottom mounting
Mount UPS upside down
DIN rail is placed vertically
Reverse the left/right positions
of the battery unit and control unit
Stack the units
Average ambi-
ent temperature 6-month check 3-month check
55°C For the first year
after starting use
When 1 year or
more have passed
after starting use
50°C For the first 1.5
years after starting
use
When 1.5 years or
more have passed
after starting use
45°C For the first 3 years
after starting use
When 3 years or
more have passed
after starting use
40°C For the first 5 years
after starting use
When 5 years or
more have passed
after starting use
25°C For the first 6 years
after starting use
When 6 years or
more have passed
after starting use
Conformance to EC Directives
S8BA-SBF
38
Conformance to EC Directives
This product complies with EC Directives. To ensure that the machine
or device in which the this product is used complies with EC
Directives, the product must be installed as follows:
This product must be installed within a control panel.
You must use reinforced insulation or double insulation for the
direct power supply equipment connected to this product.
Models of this product that comply with EC Directives also conform
to the Common Emission Standard. Radiated emission
characteristics (10-m regulations), in particular, may vary
depending on the configuration of the control panel used, other
devices connected to the control panel, wiring, and other
conditions. Therefore, even when using a model of this product
that complies with EC Directives, you must confirm and ensure the
compliance to EC Directives of the entire machine or equipment.
This is a Class A product (for industrial environments). In a
residential environment, it may cause radio interference. If radio
interference occurs, the user may be required to take appropriate
measures.
Conformance to UL
This product must be installed within a control panel with an
internal heater or other unit to protect against the formation of
condensation.
Gaps in the door to the control panel must be completely filled or
covered with gaskets or other material.
FCC CAUTION
Changes or modifications not expressly approved by the party
responsible for compliance could void the user’s authority to operate
the equipment.
This equipment has been tested and found to comply with the limits
for a Class A digital device, pursuant to part 15 of the FCC Rules.
These limits are designed to provide reasonable protection against
harmful interference when the equipment is operated in a
commercial environment.
This equipment generates, uses, and can radiate radio frequency
energy and, if not installed and used in accordance with the
instruction manual, may cause harmful interference to radio
communications.
Operation of this equipment in a residential area is likely to cause
harmful interference in which case the user will be required to
correct the interference at his own expense.
Conformance to UL
Conformance to FCC
Terms and Conditions Agreement
Read and understand this catalog.
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have
any questions or comments.
Warranties.
(a) Exclusive Warranty. Omron’s exclusive warranty is that the Products will be free from defects in materials and workmanship
for a period of twelve months from the date of sale by Omron (or such other period expressed in writing
by Omron). Omron disclaims all other warranties, express or implied.
(b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, ABOUT
NON-INFRINGEMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE
PRODUCTS. BUYER ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE PRODUCTS WILL
SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE.
Omron further disclaims all warranties and responsibility of any type for claims or expenses based on infringement by the Products
or otherwise of any intellectual property right. (c) Buyer Remedy. Omron’s sole obligation hereunder shall be, at Omron’s election,
to (i) replace (in the form originally shipped with Buyer responsible for labor charges for removal or replacement thereof) the
non-complying Product, (ii) repair the non-complying Product, or (iii) repay or credit Buyer an amount equal to the purchase price
of the non-complying Product; provided that in no event shall Omron be responsible for warranty, repair, indemnity or any other
claims or expenses regarding the Products unless Omron’s analysis confirms that the Products were properly handled, stored,
installed and maintained and not subject to contamination, abuse, misuse or inappropriate modification. Return of any Products by
Buyer must be approved in writing by Omron before shipment. Omron Companies shall not be liable for the suitability or
unsuitability or the results from the use of Products in combination with any electrical or electronic components, circuits, system
assemblies or any other materials or substances or environments. Any advice, recommendations or information given orally or in
writing, are not to be construed as an amendment or addition to the above warranty.
See http://www.omron.com/global/ or contact your Omron representative for published information.
Limitation on Liability; Etc.
OMRON COMPANIES SHALL NOT BE LIABLE FOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES,
LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS,
WHETHER SUCH CLAIM IS BASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY.
Further, in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted.
Suitability of Use.
Omron Companies shall not be responsible for conformity with any standards, codes or regulations which apply to the
combination of the Product in the Buyer’s application or use of the Product. At Buyer’s request, Omron will provide applicable
third party certification documents identifying ratings and limitations of use which apply to the Product. This information by itself is
not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine, system,
or other application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product with
respect to Buyer’s application, product or system. Buyer shall take application responsibility in all cases.
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY OR IN LARGE
QUANTITIES WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS,
AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE
OVERALL EQUIPMENT OR SYSTEM.
Programmable Products.
Omron Companies shall not be responsible for the user’s programming of a programmable Product, or any consequence thereof.
Performance Data.
Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining
suitability and does not constitute a warranty. It may represent the result of Omron’s test conditions, and the user must correlate it
to actual application requirements. Actual performance is subject to the Omron’s Warranty and Limitations of Liability.
Change in Specifications.
Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our practice
to change part numbers when published ratings or features are changed, or when significant construction changes are made.
However, some specifications of the Product may be changed without any notice. When in doubt, special part numbers may be
assigned to fix or establish key specifications for your application. Please consult with your Omron’s representative at any time to
confirm actual specifications of purchased Product.
Errors and Omissions.
Information presented by Omron Companies has been checked and is believed to be accurate; however, no responsibility is
assumed for clerical, typographical or proofreading errors or omissions.
Authorized Distributor:
In the interest of product improvement,
specifications are subject to change without notice.
Cat. No. U701-E1-03 0418 (0515)
© OMRON Corporation 2015-2018 All Rights Reserved.
OMRON Corporation Industrial Automation Company
OMRON ELECTRONICS LLC
2895 Greenspoint Parkway, Suite 200
Hoffman Estates, IL 60169 U.S.A.
Tel: (1) 847-843-7900/Fax: (1) 847-843-7787
Regional Headquarters
OMRON EUROPE B.V.
Wegalaan 67-69, 2132 JD Hoofddorp
The Netherlands
Tel: (31)2356-81-300/Fax: (31)2356-81-388
Contact: www.ia.omron.com
Kyoto, JAPAN
OMRON ASIA PACIFIC PTE. LTD.
No. 438A Alexandra Road # 05-05/08 (Lobby 2),
Alexandra Technopark,
Singapore 119967
Tel: (65) 6835-3011/Fax: (65) 6835-2711
OMRON (CHINA) CO., LTD.
Room 2211, Bank of China Tower,
200 Yin Cheng Zhong Road,
PuDong New Area, Shanghai, 200120, China
Tel: (86) 21-5037-2222/Fax: (86) 21-5037-2200
· Windows is a registered trademark of Microsoft Corporation in the USA and other countries.
· Linux is a trademark or registered trademark of Linus Torvalds in the USA and other countries.
· Other company names and product names mentioned in this document are the trademarks or registered trademarks of their respective companies.
CSM_4_5_1018