Hans Turck GmbH & Co.KG • Postfach • D-45466 Mülheim an der Ruhr • Telefon 02 08/49 52-0 • Telefax 02 08/49 52-264
Subject to change without notice • © Hans Turck GmbH & Co.KG 2002 • Edition: • 15.04.2004
Subject to change without notice • © Hans Turck GmbH & Co.KG 2002 • Edition:
Hans Turck GmbH & Co.KG • Postfach • D-45466 Mülheim an der Ruhr • Telefon 02 08/49 52-0 • Telefax 02 08/49 52-264
Inductive sensor
Bi5-G18SK-AZ3X
●threaded barrel, M18 x 1
●chrome-plated brass
●2-wire AC, 20...250 VAC
●2-wire DC, 10...300 VDC
●normally open
●terminal chamber
Wiring diagram
Function principles
Inductive proximity switches are designed
for wear-free non-contact detection of me-
tal objects. For this they use a high-fre-
quency electro-magnetic AC field that
interacts with the target. With inductive
sensors, this field is generated by an LC re-
sonant circuit with a ferrite core coil.
4
3
Type Bi5-G18SK-AZ3X
Ident-No. 43310
Rated operating distance Sn 5 mm
Mounting mode flush
Hysteresis (switching distance) 3... 15 %
Min. repeat accuracy ≤ 2 %
Temperature drift ≤ ± 10 %
Operating temperature -25 ...+ 70 °C
Rated operational voltage (AC) UB20... 250 VAC
Rated operational voltage (DC) UB10... 300 VDC
Rated operational current (AC) Ie≤ 400 mA
Rated operational current (DC) Ie≤ 300 mA
Line frequency 50... 60 Hz
Max. OFF-state current ≤ 1,7 mA
Max. switching frequency ≤ 0,02 kHz
Rated insulation voltage ≤ 1,5 kV
Surge Current ≤ 8 A (≤ 10 ms max. 5 Hz)
Output function 2-wire, normally open
Max. voltage drop at Ie≤ 6 V
Min. operational current Im≥ 3 mA
Housing style threaded barrel; M18 x 1
Dimensions 87 mm
Housing material metal, CuZn, chrome-plated
Active face plastic, PA12-GF30
Max. fixing torque of coupling nut 25 Nm
Wiring terminal chamber
Clamping ability ≤ 2,5 mm2
External diameter cabel 4,5... 8 mm
Vibration resistance 55 Hz (1 mm)
Shock resistance 30 x g (11 ms)
Degree of protection IP67
Switching status indication LED red
Included with sensor cable gland, 2x plastic seals
LED
M18 x 1
17
Pg 9
24/4
55
87
50
29