Specifications are subject to change without notice (14.07.2003) 1
AC Solid State Relay
Zero switching
Low-cost triac type
Rated operational current: 10 and 25 AACrms
Non-repetitive voltage: Up to 650 Vp
Rated operational voltage: 230 VACrms
Input ranges: 3 to 32 VDC
Insulation: OPTO (input-output) 4000 VACrms
Fast-on version available
Product Description Ordering Key
Solid State Relays
Type Selection
Switching mode Rated opera- Rated operational Control voltage Non-rep. voltage Output
tional voltage current
A: Zero switching 24: 230 VACrms 10: 10 AACrms -D: 3 to 32 VDC 06: 650 VpT: Triac
25: 25 AACrms TF: Triac/Fast-on
terminals
Solid State Relay
Switching mode
Rated operational voltage
Rated operational current
Control voltage
Non-rep. peak voltage
Output
Selection Guide
Rated operational Non-rep. voltage Terminal Control voltage Rated operational current
voltage type 10 AACrms 25 AACrms
230 VACrms 650 VpRivet terminals 3 to 32 VDC RA 2410 -D 06T RA 2425 -D 06T
230 VACrms 650 VpFast-on terminals 3 to 32 VDC RA 2410 -D 06TF RA 2425 -D 06TF
General Specifications
Operational voltage range 24 to 280 VACrms
Non-rep. peak voltage 650 Vp
Operational frequency range 45 to 65 Hz
Power factor 0.5 @ 230 VACrms
Approvals CSA, UL
CE-marking Yes
Insulation
Rated insulation voltage
Input to output 4000 VACrms
Output to case 4000 VACrms
Insulation resistance
Input to output 1010 W
Output to case 1010 W
Insulation capacitance
Input to output 8 pF
Output to case 25 pF
Industrial, 1-Phase ZS
Types RA 24.. -D 06 T, RA 24.. -D 06 TF
RA 24 10 -D 06 T
The triac version of the zero
switching relay is an inexpen-
sive solution for resistive
loads. The zero switching re-
lay switches ON when the AC
sine curve just crosses zero,
and switches OFF when the
current crosses zero.
2Specifications are subject to change without notice (14.07.2003)
RA 24.. -D 06 T, RA 24.. -D 06 TF
RA 24 .. -D 06T/TF
Control voltage range 3 to 32 VDC
Pick-up voltage 3 V
Drop-out voltage 1 V
Reverse voltage 32 VDC
Input impedance 1.5 k
Response time pick-up 1/2 cycle
Response time drop-out 1/2 cycle
Output Specifications
RA 2410 -D 06 T/F RA 2425 -D 06 T/F
Rated operational current AC 51 10 Arms 25 Arms
Minimum operational current 20 mArms 20 mArms
Rep. overload current t=1 s 30 Ap50 Ap
Non-rep. surge current t=20 ms 90 Ap200 Ap
Off-state leakage current
@ rated voltage and frequency 5 mArms 5 mArms
I2t for fusing t=1-10 ms 40 A2s200 A2s
Critical dI/dt 10 A/µs 10 A/µs
On-state voltage drop
@ rated current 1.6 Vrms 1.6 Vrms
Critical dV/dt commutating 10 V/µs 10 V/µs
Critical dV/dt off-state 250 V/µs 250 V/µs
Thermal Specifications
RA 2410 -D 06 T/TF RA 2425 -D 06 T/TF
Operating temperature
-20° to +70°C (-4° to +158°F) -20° to +70°C (-4° to +158°F)
Storage temperature
-40° to +100°C (-40° to +212°F) -40° to +100°C (-40° to +212°F)
Junction temperature 125°C (257°F) 125°C (257°F)
Rth junction to case 2.5 K/W 1.8 K/W
Rth junction to ambient 12.5 K/W 12.5 K/W
Control
input
Functional Diagram
Mains input/load output
Load output/mains input
Wiring Diagram
Input Specifications
Control
input Line/load
Weight Approx. 110 g
Housing material Noryl GFN 1, black
Base plate Aluminium
Potting compound Polyurethane
Relay
Mounting screws M5
Mounting torque 1.5 Nm
Control terminal
Mounting screws/Fast-on M3 x 6/6.3 x 0.8 mm
Mounting torque 0.5 Nm
Power terminal
Mounting screws/Fast-on M5 x 6/6.3 x 0.8 mm
Mounting torque 2.4 Nm
Housing Specifications
Specifications are subject to change without notice (14.07.2003) 3
RA 2410 .. 06 T, RA 24.. -D 06 TF
RA 24 10 .. .. T/F
6.5 5.6 4.7 3.9 3 2.1 12
7.8 6.8 5.8 4.8 3.8 2.8 10
9.2 8 6.9 5.7 4.6 3.4 9
10.8 9.5 8.1 6.8 5.4 4.1 7
- 11.4 9.8 8.2 6.5 4.9 6
- - 12.2 10.2 8.1 6.1 5
- - - - 10.5 7.9 4
- - - - - 10.9 3
------2
------1
20 30 40 50 60 70
10
9
8
7
6
5
4
3
2
1
TA
Thermal resistance
[K/W] Power dissipa-
tion [W]
Load
current [A]
RA 24 25 .. .. T/F
1.4 1.1 0.77 0.45 - - 32
1.9 1.5 1.2 0.79 0.43 - 28
2.5 2.1 1.6 1.2 0.81 0.39 24
3.3 2.8 2.3 1.8 1.3 0.8 20
4.3 3.7 3.1 2.5 2 1.4 17
5.8 5.1 4.4 3.6 2.8 2.2 14
7.6 6.7 5.7 4.8 3.8 2.9 11
10.5 9.2 7.9 6.6 5.3 4 8
- 14.4 12.3 10.3 8.2 6.2 5
- - - - 17.1 12.8 3
20 30 40 50 60 70 TA
Ambient temp. [°C]
25
23
20
18
15
13
10
8
5
3
Load
current [A] Thermal resistance
[K/W] Power dissipa-
tion [W]
Dimensions
** = ±0.4 mm
*** = ±0.5 mm
**
**
***
*** ***
***
Ambient temp. [°C]
Accessories
Protection cover
Heatsinks
DIN rail adapter
Varistors
Fuses
Terminals RA 24.. -D 06 TF
Control terminal (Fast-on) 6.3 x 0.8 mm
Power terminal (Fast-on) 6.3 x 0.8 mm
For further information refer
to "General Accessories".
Heatsink Dimensions (load current versus ambient temperature)
Heatsink Selection
Carlo Gavazzi Heatsink
(see Accessories)
No heatsink required
RHS 100 Assy
RHS 301 Assy
RHS 301 F Assy
Consult your distributor
Thermal resistance
Rth s-a > 12.5 K/W
3.0 K/W
0.8 K/W
0.25 K/W
< 0.25 K/W
Compare the value found in the current versus temperature
chart with the standard heatsink values and select the heat-
sink with the next lower value.
RA Triac with FAST-ON
Terminals RA Triac
** = ±0.4 mm
*** = ±0.5 mm
**
**
***
*** ***
***